Room Temperature Controller 230/10 (4) A~ with NC contact and On/Off button
0392 ..
Contents
Operating instructions Room temperature controller 230/10 (4) A~ with NC
contact and On/Off switch
3
Installation of the room temperature controller
Area of application
The room temperature controller is used to control the temperature in closed rooms, such as apart­ments, schools, lecture halls, workshops etc.
Installation site
• Install the room temperature controller on an inte­rior wall and, if possible, directly across from the heat source.
• Comply with the recommended installation height of approx. 1.5 m above the floor.
• The permissible relative humidity may not exceed the max. of 95 %. Avoid condensation.
• Avoid exterior walls and draughts from windows and doors.
4
• Ensure that the normal convective air of the room can reach the room temperature controller unim­peded. For this reason, the controller is not to be mounted within shelf walls or behind curtains or similar coverings.
• Heat from other sources negatively influences con­troller precision. For this reason, avoid direct sun­light and objects which emit heat (televisions, heaters, lamps, chimney, heating pipes etc.).
• Dimmers also generate heat! If the room temperature controller is used in con­junction with a dimmer, the distance between the two should be as great as possible. If aligned verti­cally, the room temperature controller should be installed below the dimmer.