Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
Kp-300
Operator Control Panel
The Kp-300 has all the controls that are needed to run any motion base or other
Smart Brick system. It mounts in 5-1/4” of standard 19” rack space. Operator controls
include buttons for starting and stopping the Hydraulic Power Unit (HPU), pausing and
then continuing a paused show, for ʻloggingʼ occupied seats, and for selecting and playing up to eight different shows.
Because many of the functions of the Kp-300 are safety related, the Kp-300 has no
CPU of any kind. With no microcontroller, there is no possibility of a software crash.
Kp-300 Manual / September 4, 2012 4:29 PM / page 1 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
TheKp-300istypicallyprogrammedin‘Software-only’or‘HardwarelessRealTime’mode.IfyouareusingtheUSB-DMX-512forprogrammingyourKp-300throughtheDMX-512 inputs, please refer to thePC•MACs ‘Unlimited’ mode.
ThefullPC•MACsmanualcanbedownloadedfromourweb site at:
http://www.gilderfluke.com
Kp-300 Manual / September 4, 2012 4:29 PM / page 6 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
This isnʼt a blank page either
Kp-300 Manual / September 4, 2012 4:29 PM / page 7 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
KP-300 Expansion • Gilderfluke & Company, Burbank, California
Relay Outputs
1/4 J6 Outputs
Inputs
J6 Inputs
3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7
2.0 2.1 2.2 2.3 2.4 2.5 2.6 2.7
1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
2019181716151413121110987654321
65432165432107
Kp-300 Typical Block Diagram for a Hydraulic Motion Base
HPU
Door, Ramp,
Seat Belt and
other 'Safety'
Switches
HPU error signals
(Oil low, overtemp,
filter dirty, etc.)
HPU Run Output
HPU Run/Stop
Status Signals
Kp-300
Kp-300 Expansion(s)
(if needed)
Pb-DMX with
3.5 Amp
Relays
Audio/Video
Playback
Light Dimmers
RGB LED
Lamp Fixtures
Br-ANA or
DAC-Quad
EFB-Quad(s)
or PID-Quad(s)
Valves, Cylinders
and position
sensors
Moving Head
Light Fixtures
Smog
Machines
Moving head
Light Fixtures
Br-MiniBrick8
Strobe Lights
Fans
other DMX-512
compatible
equipment
Br-Brain4
(typically)
Network
(DMX-512)
Four or
sixteen
0-10 VDC
commands
Kp-300 Manual / September 4, 2012 4:29 PM / page 8 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
Kp-300 Overview
The Kp-300 features fifteen safety inputs, plus an onboard E-Stop Button and
Keyswitch that can be used to lock the system. All the safety inputs are ʻfail safeʼ (they
want to see a closure on them and will be triggered by any wire break). With the one exception of the E-Stop Button and Keyswitch on the Kp-300, each safety input can be individually set to force the system to:
Enter an E-Stop condition
Pause the show
Turn the HPU off (if there is one)
The E-Stop Button and Keyswitch on the Kp-300 always force an E-Stop condition.
More safety inputs can be added if needed using the Kp-300 Expansion.
Safety inputs that trigger an E-Stop condition normally include only critical sensors.
An example of these would be a low hydraulic fluid level sensor. If the motion base is
running low on oil, this would trigger an immediate E-Stop, and as long as the oil level
remained low, the Kp-300 would not let you start the HPU. All E-Stops turn the HPU off.
The show always has to be started over from the beginning after an E-Stop.
A pause input is used for less critical sensors. An example of this is where a seat belt
was opened by a rider. The show would instantly be paused and could only be continued by the operator when the condition that caused the pause had been cleared. Alternatively, if after the pause was triggered the operator deemed it necessary to evacuate
the attraction, he could call up a show that parks the motion base or just E-Stop it to
bring it home.
Door sensors are actually a point where a pause is generally safer to use than a full
E-Stop. If a door is opened, instead of returning to home position the motion base will
just freeze. This is less likely to take a leg off someone who is trying to step through the
door.
Two bypass busses are available from the motion profile program. These are used to
temporarily disable inputs that might otherwise cause an error condition to be flagged.
An example of their use is on the door sensors. During the motion base ʻflightʼ, a door
sensor should trigger an error condition (either a pause or E-Stop), but during the Load/
Unload times it should not. For this reason this input would be bypassed during Load/
Unload times by one of the two bypass busses.
Seat belt logging allows any input which has been wired to a seat belt to be ignored
once it has been logged as an unoccupied seat. The seat belt logging can be done from
Kp-300 Manual / September 4, 2012 4:29 PM / page 9 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
the Kp-300, remotely via a switch closure, or automatically as part of the motion profile
program.
Each safety input as well as the built in E-Stop Button and Keyswitch have indicator
LEDs that show their current status.
a) A green light means that the input is ʻOKʼ.
b) A yellow light means that the input has been logged as ʻtemporarily unusedʼ.
Typically this is used in an installation that has switches to monitor the seat
belts. Before starting the ride, any inputs from unoccupied seats would be
ʻloggedʼ so that they wonʼt cause an error condition.
c) If an input opens and triggers an error condition, then a red LED will flash
next to that input to flag it as the one that caused the failure. This allows you
to catch short lived error conditions like a HPU level sensor or pressure
switch kicking an E-stop for just an instant.
A solid state counter records the number of show cycles that are run. Shows that are
run with the HPU off or while the system is E-Stopped are not counted. The show cycle
count is retained even during power outages.
With the addition of a three slot card cage (which mounts on the back of the Kp-300),
a Smart Brick Brain, Analog or other Smart Brick (depending on the type of motion base
you are running) and a Z-Brick, the Kp-300 becomes a complete motion base control
system. When ordered in this way, the small LCD that normally is mounted on the front
of a Br-Brain4 is replaced by a large format LCD display on the front of the Kp-300.
Since the entire system is networked, you can put components wherever you like.
Dimmers and the controllers for your ʻ4Dʼ effects can be right in the cabin. The video
playback can be mounted near to the projector or video screen. Just a single shielded
twisted pair of wire connects the DMX-512 to control everything. This can be used to
minimize the number of bulky multi conductor cables that need to be run, especially
those that need to be run in a location that will require continuous flexing. All of this
makes the initial connections, as well as adding new features in the future as simple as
tapping into the existing cable.
Customized front panel artwork is available on the Kp-300. These can be custom
branded, or labeled for specific show names and error inputs. Please contact the
Gilderfluke & Company factory for details on generating custom Kp-300 labels.
Kp-300 Manual / September 4, 2012 4:29 PM / page 10 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
Kp-300 Panel Indicators
There are sixty-one LED indicators and one or two LCD displays on the front of the
Kp-300. They are used as follows:
A) Error Input Logged LEDs
(One yellow LED for each Error Input)
!(Fifteen LEDs total)
These are lit to show that an input has been logged as inactive for the
current show. Once an input which is open (green LED is not on) has been
logged, it will be ignored until it is logged as active again. This feature is
typically used to log seat belt inputs. A seat which is unoccupied will be
logged so that it canʼt cause an E-Stop or Pause if it changes state during
the show.
Seat belts can be logged at any time that the Show Pause Reset Input
from the Smart Brick System is active. When this input is active, the safety
inputs can be logged by either pressing the Log Belts button or activating the
Remote Log Belts Input by pressing Remote Log Belts Button(s) attached to
it. If you want to automatically log belts from the motion profile, just set the
Remote Log Belts Input for Internal Power and attach the two wires for this
input together so it is always active. Whenever the Show Pause Reset Input
is programmed active, the inputs that are set to be logged will automatically
be logged.
Input logging actually takes place at the instant that the Log Belts Button,
Log Belts Remote Input, or Show Pause Reset Input are released. The LED
next to the Log Belts Button will light whenever the seat belts are being
logged.
B) Error Input Status LEDs
(One green LED for each Error Input, plus one for the E-Stop Button/
Keyswitch)
!(Sixteen LEDs total)
These are lit to show that an input is in its ʻsafeʼ condition. If any one of
these inputs is off and that input hasnʼt been logged as an unoccupied seat
(yellow LED IS on), then it is not safe to start the show.
Kp-300 Manual / September 4, 2012 4:29 PM / page 11 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
All the inputs are configured to ʻfail safeʼ, which is to say that an error is
triggered by an open circuit on an input. This is true even for the Kp-300ʼs E-
Stop Button and Keyswitch. These are wired in series and trigger an E-Stop
if this connection is opened at any point.
C) Error Input Events LEDs
(One red LED for each Error Input, plus one for the E-Stop Button/Keyswitch)
!(Sixteen LEDs total)
These LEDs flash on the input(s) that triggered an error condition. They
allow you to find which input caused the error, even if it only existed for an
instant.
An example of this featureʼs use is in events like a HPU filter dirty sensor
which has been configured to trigger an E-Stop event. The dirty filter sensor
on the HPU is typically a differential pressure switch which measures the
pressure across the filter. If this pressure gets too high, then the switch
opens to indicate a clogged filter and triggers the E-Stop condition. The thing
that makes this hard to catch is that the E-Stop turns off the HPU, so the differential pressure immediately drops back into zero (the ʻOKʼ region, as far
as the switch is concerned), turning back on the green Error Input Status
LED for the input. To further complicate things, because the HPU potentially
turned off right in the middle of a show, the ʻlow pressureʼ error input (if there
is one) will turn off its green Error Input Status LED because the pressure
just went to zero. Under these circumstances the only Error Input Event LED
that will be flashing will be the original ʻDirty Filterʼ one that initiated the EStop in the first place. All the other Error Input Event LEDs will be off.
Once these LEDs are turned on by an E-Stop event, they can only be
cleared when the operator starts the next show. They will keep flashing until
the next show is started. If they were triggered by a Show Pause event, they
will stop flashing but remain lit after the error condition is cleared and the
show is ʻresumedʼ. They will be cleared when there is another E-Stop/Show
Pause event or the next show is started by the operator.
D) Log Belts LED
(One yellow LED)
This LED turns on when the error inputs are are being logged as temporarily unused. Seat belts can be logged at any time that the Show Pause
Reset Input from the Smart Brick System is active. When this input is active,
Kp-300 Manual / September 4, 2012 4:29 PM / page 12 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
the safety inputs can be logged by either pressing the Log Belts Button or
activating the Remote Log Belts Input by pressing Remote Log Belts But-
ton(s) attached to it. If you want to automatically log belts from the motion
profile, just set the Remote Log Belts Input for Internal Power and attach the
two wires for this input together so it is always active. Whenever the Show
Pause Reset Input is programmed active, the inputs that are set to be
logged will automatically be logged.
Input logging actually takes place at the instant that the Log Belts Button,
Log Belts Remote Input, or Show Pause Reset Input are released.
E) Show Start Button LEDs
(One green LED for each Show Start Button)
!(Eight LEDs total)
These LEDs are controlled directly by the motion control profile stored in
the Smart Brick System. This allows the LEDs to be programmed on, off or
flashing as desired at any point in time. They are programmed to indicate
which shows are available to the operator, or to indicate which show is already running. We typically program them in a chase pattern, lighting only
the valid show selections. Once a show has started, we typically program all
but the selected Show Start Button LEDs off, and flash the selected show
LED a few times before turning it on through the rest of the show. If any
other show selection is valid while another show is running, we then flash it
discretely throughout the show that is running.
Whenever a Show Start Button LED is programed to indicate that a Show
Start Button is valid, it is also necessary to actually enable the correspond-
ing Show Start Button Enable Input output from the Smart Brick System to
make the Show Start Buttons active. If this is not done, then the Show Start
Buttons will remain inactive.
F) Show Cycle Counter LED
(One green LED)
This LED lights to show that the show cycle counter has been commanded to advance by the motion control profile stored in the Smart Brick
System. The count on the LCD counter will advance by one if the Kp-300 is
not currently in any type of E-Stop condition and the HPU is running, as indicated by 24 vdc being received on the HPU Running Input.
Kp-300 Manual / September 4, 2012 4:29 PM / page 13 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
The Show Cycle Count Advance Input pulse is typically programmed to
take place towards the end of the motion base program. This lets a show
which is aborted for any reason not be counted.
The LCD module that displays the current show cycle count permanently
stores the count each time it is advanced. The count will be retained even if
power is removed from the Kp-300. Please contact the Gilderfluke & Co. factory if you need a resettable cycle counter.
G) E-Stop Buss LED
(One red LED)
This LED lights to show that the Kp-300 currently has an unresolved EStop condition. The beginning of any E-Stop event stops the HPU (if there is
one), disables the Blocking Valve output and triggers the Smart Brick Sys-
tem to play the E-Stop Show through the Blue ʻE-Stopʼ Input to the Smart
Brick Brain. Calling up the E-Stop show sets the ʻE-Stop Show Runningʼ
output from the Smart Brick System (this must be programmed into the motion profile of the E-Stop show). This resets the first of the two E-Stop
latches on the Kp-300. At this point you can start the HPU and any shows
that have been enabled in the motion control profile of the E-Stop Show.
If this LED is ON, you should not run the show unless you just want to
see the video and sound, without any motion. If a show is started while there
is still an unresolved E-Stop condition, the Kp-300 can be configured to:
a) Lock out the ʻBlocking Valveʼ output until another show is started
with the E-Stop Buss LED off. This is the safer of the two options, because the motion base will not start moving until a show
is started cleanly.
b) Lock out the ʻBlocking Valveʼ output until the E-Stop condition is
cleared. This can allow the motion base to spring into movement
if the E-Stop condition is resolved half way through the show.
If you want to disallow shows to be run at all if there is an E-Stop condition present, you can configure one of the two bypass busses to momentar-
ily (for just one frame) bypass all the possible E-Stop error inputs at the very
beginning of all shows1. At the end of the bypass buss pulse, any error conditions that remain will trigger the E-Stop to keep even the video and audio
1
This technique is flexible enough that you can even leave it out of any maintenance shows that you want to be able to run without
motion
Kp-300 Manual / September 4, 2012 4:29 PM / page 14 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
from running. This technique should be used in applications that donʼt use
the Blocking Valve Output. Typical of these are most electric motion base in-
stallations.
H) Show Pause Buss LED
(One red LED)
This LED lights to show that the Kp-300 currently has an unresolved
Show Pause condition. If this LED is ON, you should not run the show.
When the Show Pause Reset Input from the Smart Brick System goes
away2, the Kp-300 will be paused. The condition that caused the Show
Pause will then have to be cleared before the current show can be resumed.
Alternatively, the operator can bail out by pressing the E-Stop or running another show that simply gets the operator back to the Load/Unload shows
without triggering an E-Stop.
I) HPU Stop Buss LED
(One red LED)
This LED lights to show that the Kp-300 currently has an unresolved HPU
Stop condition. If this LED is ON, you should not run the show. The Kp-300
will keep the operators from starting the HPU until this condition is resolved.
The error conditions that are typically used to trigger a HPU Stop Buss event
are those which might cause damage to the HPU, Motion base or their riders. Typical of these are ʻHPU Oil Level Lowʼ or ʻHPU Over Temperatureʼ
sensors.
It is not unusual for operators to try to override this type of safety feature.
For this reason, many HPU applications use a number of techniques to lock
out the show if the HPU is turned on locally:
a) The primary technique is to run the HPUʼs 24 vdc ʻHPU Stoppedʼ
and ʻHPU Runningʼ outputs through the ʻAutoʼ position of the
HPU ʻHand/Off/Manualʼ switch on the way to the Kp-300. By doing this, both the HPU LEDs on the Kp-300 will be off unless the
HPU is in the ʻAutoʼ mode. This has the added advantage of giving the operators a remote indication of the position of the HPUʼs
ʻHand/Off/Manualʼ switch.
b) The ʻAutoʼ position of the HPUʼs ʻHand/Off/Manualʼ switches on
2
Usually at the start any of the Main shows. It is normally programmed as active during the E-Stop and Load/Unload shows
Kp-300 Manual / September 4, 2012 4:29 PM / page 15 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
the HPUs wired into one of the error inputs of the Kp-300. This
input is configured to keep the motion base from running if the
HPU ʻHand/Off/Manualʼ switch is in anything but the ʻAutoʼ position.
c) The Blocking Valve Output from the Kp-300 can be run through
the ʻAutoʼ position of the HPU ʻHand/Off/Manualʼ switch. Unless
the HPU is started by the Kp-300, this too will prevent the motion
base from moving. This will only work on hydraulic motion bases
that use a blocking valve.
J) Blocking Valve LED
(One green LED)
This LED lights to show that the motion control profile stored in the Smart
Brick System has enabled the Blocking Valve to allow the motion base to
move. If the Kp-300 is still in an E-Stop condition or the HPU is not running
(as indicated by 24 vdc being received on the HPU Running Input), this LED
will simply flash and the Blocking Valve output will not be activated. If a show
is started while there is still an unresolved E-Stop condition, the Kp-300 can
be configured to:
a) Lock out the ʻBlocking Valveʼ output until another show is started
with the E-Stop Buss LED off. This is the safer of the two options, because the motion base will not start moving until a show
is started cleanly.
b) Lock out the ʻBlocking Valveʼ output until the E-Stop condition is
cleared. This can allow the motion base to spring into movement
if the E-Stop condition is resolved half way through the show.
K) Bypass Buss #1 LED
L) Bypass Buss #2 LED
(Two green LEDs)
These LEDs lights to show that the motion control profile has been programmed to bypass some or all the Safety inputs which have been configured to create an E-Stop or Show Pause. Typical examples of the use of the
bypass buss are:
a) HPU Startup/Shutdown: If the HPU is started and stopped as
part of the motion profile, there will usually be a time just after it
Kp-300 Manual / September 4, 2012 4:29 PM / page 16 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
is started and a time after it is stopped where any HPU pressure
sensors inputs will need to be bypassed. Do this by programming the Bypass Buss you are using and Remote HPU Start In-
put to be active at the beginning of the show. The Bypass Buss
needs to be active for the time it takes for the HPU to build up
pressure. If the pressure doesnʼt come up during the time allotted, the Kp-300 will automatically trigger an error condition (either E-Stop or Show Pause, as configured).
#If the HPU is to be turned off at the end of the show, then the
Bypass Buss which is being used would be programmed active
along with a pulse on the Remote HPU Stop Input. This allows
the HPU to be stopped without triggering an error condition. If
configured to trigger an E-Stop, the Bypass Buss will also need
to be programmed active during the E-Stop and Load/Unload
shows so that the HPUʼs low pressure wonʼt trigger an error during these shows when the HPU is off.
b) Door Sensors: If the door or floor mat sensors inputs are set to
trigger an E-Stop, they will need to be bypassed during the EStop and Load Unload shows. This is because although you
want these inputs to trigger an error while the motion base is in
flight, you donʼt want this to trigger an E-Stop when the doors are
opened for the passengers to be loaded and unloaded.
c) Electric Motion Bases and other Installations that donʼt use
the Kp-300 Blocking Valve Output: If you donʼ t want to allow
shows to be run if there is an E-Stop condition present, you can
configure one of the two bypass busses to momentarily (for just
one frame) bypass all the possible error inputs at the very start
of all shows3. At the end of the Bypass Buss pulse, any error
conditions that remain will trigger the E-Stop. This technique
should be used in applications that donʼt use the Blocking Valve
Output. Typical of these are most electric motion base installa-
tions.
If you are using the Seat Belt Logging features of the Kp-300, be sure you
donʼt configure the Kp-300 to bypass any inputs that are to be logged during
the time during which they need to be logged. Bypassing an input will con-
3
This technique is flexible enough that you can even leave it out of any maintenance shows that you want to be able to run without
motion.
Kp-300 Manual / September 4, 2012 4:29 PM / page 17 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
vince the Kp-300 that the inputs are in the ʻsafeʼ position, and so they will not
be logged as ʻunoccupiedʼ.
The Show Pause functions are usually disabled during the E-Stop and
Load/Unload shows by the Show Pause Reset Input from the Smart Brick
System. Inputs that trigger a Show Pause are never needed during the EStop and Load/Unload shows anyway, so there is no need to bypass them
separately during these shows.
M)E-Stop Show Running LED
One green LED
This LED lights to show that the motion control profile is running the EStop Show. The E-Stop Show Running output is normally only programmed
active during the E-Stop Show, and is used reset one of the Kp-300ʼs onboard latches to allow the HPU to be started and the E-Stop conditions to be
cleared.
N) Remote HPU Start LED
O) Remote HPU Stop LED
(Two green LEDs)
These LEDs light to show that the motion control profile on the Smart
Brick System has had the commands to start or stop the HPU embedded in
it. This is an optional feature. If you donʼt want the HPU to be started and
stopped automatically, just donʼt use them.
These outputs parallel the HPU Start Button and HPU Stop Button that
are on the front of the Kp-300. If the HPU is being forced off by a HPU Stop
Buss error, the Remote HPU Start Input can NOT override the error.
Any of the ʻstopʼ inputs take precedence over any of the ʻstartʼ inputs. You
can use an active Remote HPU Stop Input in the motion profile stored on the
Smart Brick System to keep the operator or Remote HPU Start Input from
starting the HPU.
P) Show Pause Reset LED
(One green LED)
This LED lights to show that the motion control profile on the Smart Brick
System has the Show Pause Reset Input command programmed to reset or
Kp-300 Manual / September 4, 2012 4:29 PM / page 18 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
disable the Kp-300 Show Pause functions. This is normally programmed active only during the E-Stop and Load/Unload shows.
Seat belts can be logged at any time that the Show Pause Reset Input
from the Smart Brick System is active. When this input is active, the safety
inputs can be logged by either pressing the Log Belts button or activating the
Remote Log Belts Input by pressing Remote Log Belts Button(s) attached to
it. If you want to automatically log belts from the motion profile, just set the
Remote Log Belts Input for Internal Power and attach the two wires for this
input together so it is always active. Whenever the Show Pause Reset Input
is programmed active, the inputs that are set to be logged will automatically
be logged.
Input logging actually takes place at the instant that the Log Belts Button,
Remote Log Belts Input, or Show Pause Reset Input are released. The LED
next to the Log Belts Button will light whenever the seat belts are being
logged.
Q) HPU Running LED
(One green LED)
This LED lights to show that the Hydraulic Power Unit (HPU) is running.
This LED is turned on only when a 24 vdc signal is applied to the HPU Run-
ning Input. This signal normally comes from the HPU. If there is no HPU in
the system, this input can be permanently attached to a 24 vdc or the HPU
Run Output.
Unless this signal is received by the Kp-300, the Blocking Valve Output
will never turn on and the Show Cycle Counter will not advance.
To help keep shows from being run when the HPU has been started by its
local Hand/Off/Auto switch, the HPU Stopped Input and HPU Running Input
signals are often routed through the ʻAutoʼ position on the switch. If the
switch isnʼt in the ʻAutoʼ position, the HPU Stopped LED and HPU Running
LED wonʼt light and the Blocking valve wonʼt be enabled.
R) HPU Stopped LED
(One red LED)
This LED lights to show that the Hydraulic Power Unit (HPU) is not running. This LED is turned on only when a 24 vdc signal is applied to the HPU
Kp-300 Manual / September 4, 2012 4:29 PM / page 19 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
Stopped Input. Unlike the HPU Running Input, this input is not used for any
other purpose than lighting this LED.
To help keep shows from being run when the HPU has been started by its
local Hand/Off/Auto switch, the HPU Stopped Input and HPU Running Input
signals are often routed through the ʻAutoʼ position on the switch. If the
switch isnʼt in the ʻAutoʼ position, the HPU Stopped LED and HPU Running
LED wonʼt light and the Blocking valve wonʼt be enabled.
S) Show Continue LED
(One green LED)
This LED lights to show that the Motion profile on the Smart Brick System
has been programmed with the Show Pause Reset Input inactive and that
the current show has not been paused.
When a show is paused, the Kp-300 sends a signal to the Smart Brick
Brain through its Green ʻPauseʼ Output. The Smart Brick Brain input must be
configured to pause the currently running show on a closure on this input4.
When a show is 'continued', the signal is dropped on the Green ʻPauseʼ
Output to the Smart Brick Brain. This input must be configured to continue
the currently running show on an opening on this input.
Once a show has been paused, the only two ways to 'continue' a show
are to:
a) Send an active signal from the Smart Brick System to the Kp-
300ʼs Show Pause Reset Input.
b) Once the condition that caused the Show Pause has been re-
moved, the operator can press the Show Continue button.
T) Show Pause LED
(One red LED)
This LED lights to show that the Motion profile on the Smart Brick System
has been programmed with the Show Pause Reset Input inactive and that
the current show has been paused by the operator pressing the Show
Pause Button or an error condition.
When a show is paused, the Kp-300 sends a signal to the Smart Brick
Brain through its Green ʻPauseʼ Output. The Smart Brick Brain input must be
4
In some applications, you may want to call up a different show using this input, instead of pausing the current show.
Kp-300 Manual / September 4, 2012 4:29 PM / page 20 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
configured to pause the currently running show on a closure on this input5.
When a show is 'continued', the signal is dropped on the Green ʻPauseʼ
Output to the Smart Brick Brain. This input must be configured to continue
the currently running show on an opening on this input.
Once a show has been paused, the only two ways to 'continue' a show
are to:
a) Send an active signal from the Smart Brick System to the Kp-
300ʼs Show Pause Reset Input.
b) Once the condition that caused the Show Pause has been re-
moved, the operator can press the Show Continue button.
U) DMX-512 Receive LED (v3.0+ Only)
(One red LED, Located on back of Kp-300)
To support the DMX-512 input, the v3.0+ Kp-300 adds an LED that
flashes on each update via the DMX-512.
The Kp-300 requires DMX-512 that includes GilderChecksums.
If receiving DMX-512 without valid checksums, the DMX-512 Receive
LED on the back of the Kp-300 will not flash and only the Show Start Button
LEDs will follow the incoming the DMX-512. The signals like the Show Start
Button Enable Inputs, blocking valve enable, and automatic HPU start/stop
will not work if the GilderChecksums are invalid.
5
In some applications, you may want to call up a different show using this input, instead of pausing the current show.
Kp-300 Manual / September 4, 2012 4:29 PM / page 21 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
Kp-300 Operator Controls
The Kp-300 has just a small number of operator controls. Most of these have LEDs
that can be lit under program control, or indicate their current status.
A) E-Stop Button/Keyswitch
These two switches are wired in series. Opening either one will cause an
E-Stop and HPU Stop event on the Kp-300. The beginning of any E-Stop
event stops the HPU (if there is one), disables the Blocking Valve output and
triggers the Smart Brick System to play the E-Stop Show through the Blue
ʻE-Stopʼ Input to the Smart Brick Brain. Calling up the E-Stop show sets the
ʻE-Stop Show Runningʼ output from the Smart Brick System (this must be
programmed into the motion profile of the E-Stop show). This resets the first
of the two E-Stop latches on the Kp-300. At this point you can start the HPU
and any shows that have been enabled in the motion control profile of the EStop Show.
The E-Stop switch has a red mushroom-style cap. Once pushed, the button latches in the E-Stopped position. To release the cap, it is rotated clockwise. The E-Stop button has a spare set SPDT set of contacts available for
your use. Users of Moog electric motion bases can use this switch closure
for the hardware E-Stop input they require.
The Keyswitch is typically used to lock unauthorized users from starting
the HPU or running shows with motion. The Keyswitch can be turned to one
of two positions. The key can be removed in either of these two positions.
The show can be run without motion while the keyswitch is turned off or
the E-Stop button has been pushed in. If you want to disallow shows to be
run at all if there is an E-Stop condition present, you can use the DipSwitch
#3, DipSwitch #4 or DipSwitch #5 to disallow running shows if there is an er-
ror condition.
B) Log Belts Button
Seat belts can be logged at any time that the Show Pause Reset Input
from the Smart Brick System is active. When this input is active, the safety
inputs can be logged by either pressing the Log Belts button or activating the
Remote Log Belts Input by pressing Remote Log Belts Button(s) attached to
it. If you want to automatically log belts from the motion profile, just set the
Remote Log Belts Input for Internal Power and attach the two wires for this
Kp-300 Manual / September 4, 2012 4:29 PM / page 22 of 75
Gilderfluke & Co.• 205 South Flower Street • Burbank, California 91502 • 818/840-9484 • 800/776-5972 • fax 818/840-9485
input together so it is always active. Whenever the Show Pause Reset Input
is programmed active, the inputs that are set to be logged will automatically
be logged.
Input logging actually takes place at the instant that the Log Belts Button,
Remote Log Belts Input, or Show Pause Reset Input are released. The LED
next to the Log Belts Button will light whenever the seat belts are being
logged.
C) Show Start Buttons
(Eight Buttons)
The Kp-300 has been designed to support up to eight shows which can
be directly accessed. If more shows are needed, these Show Start Buttons
can be bypassed with a Kp-100 or Kp-200 to allow access to the Smart Brick
Systemʼs 255 show capacity.
Which shows are available to the user (which of these eight Show Start
Buttons are enabled), is controlled as a function of the motion profile running
on the Smart Brick System. Enabling a Show Start Buttons just requires set-
ting the appropriate Show Start Button Enable Inputs in the motion profile.
Any or all of the Show Start Buttons can be enabled/disabled at any time.
The Show Start Button LEDs next to these buttons are also controlled as
part of the motion profile. This allows the Show Start Button LEDs to be pro-
grammed on, off or flashing as desired at any point in time.
Typically the Show Start Buttons are programmed as active during the E-
Stop and Load/Unload shows. During the main shows, typically none of
them are enabled. If any are enabled, then the user can jump directly out of
the currently running show and into the one(s) that have been enabled. This
is sometimes used to enable a ʻparkʼ show that brings the motion base home
without having to do anything as drastic as an E-Stop. Any show that is enabled while another show is running will be enabled even during a show
pause. Make sure that if you are using this technique, that the show that is
jumped into has the Show Pause Reset Input set for at least a few frames at
the beginning. Otherwise the new show will begin running, but the Show
Pause functions of the Kp-300 wonʼt be reset (the Show Pause LED will remain lit, and the next Show Pause event will be ignored). At the end of the
pulse on the Show Pause Reset Input, the Kp-300 will check for an outstanding Show Pause condition. If one still persists, then the new show will
be paused.
Kp-300 Manual / September 4, 2012 4:29 PM / page 23 of 75
Loading...
+ 52 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.