Giant Factories UG50-65(-59), UG50-65, UG50-59 Owner's Manual Installation And Operating Instructions

ISO 9001
ENREGISTRÉ
ISO 9001
REGISTRED
(EQUIPPED WITH FVIR TECHNOLOGY)
OWNER’S MANUAL
INSTALLATION AND OPERATING INSTRUCTIONS
UG50-65(-59) Model
This water heater IS NOT design certified for installation in a manufactured (mobile) home or for installation outdoors.
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.
DO NOT store or use gasoline or other flammable vapours and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
•DO NOT try to light any appliance.
•DO NOT touch any electrical switch,
DO NOT use any phone in your building.
•From a neighbour’s phone, immediately call your gas supplier. Follow the gas
supplier’s instructions.
•If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by
a qualified installer, service agency, or the gas supplier.
IMPORTANT
READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION. PROPER INSTALLATION WILL PROVIDE SAFE AND EFFICIENT SERVICE, AND AVOID NEEDLESS EXPENSE NOT COVERED BY THE WARRANTY. READ THE PRODUCT WARRANTY CONTAINED IN THIS MANUAL AND REMEMBER TO FILL OUT AND RETURN TO THE MANUFACTURER ALL RELEVANT WARRANTY CARDS AND CERTIFICATES. SHOULD YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR LOCAL DEALER OR REFER TO THE GETTING SERVICE FOR YOUR WATER HEATER SECTION OF THIS MANUAL.
SAVE THIS MANUAL FOR FUTURE REFERENCES.
For your records, write the model and serial number here:
Model # ________________________________
Serial # _________________________________
54000012
© 2012 Giant Factories Inc. Printed in Canada GI-IM015En-1112
TABLE OF CONTENTS
Safety Information ............. 3
Installation Instructions
Location ................ 4
Minimum Clearances .......... 4
Combustion and Ventilation Air Supply .. 4 Requirements for Unconfined Spaces ... 5
Requirements for Confined Spaces .... 5
Louvers and Grilles ........... 6
Corrosive Atmospheres ......... 6
Venting ................. 7
Through-the-Wall Venting Installation ... 7 Through-the-Roof Venting Installation ... 8 Condensation in the Venting System ... 8
Installation of the venting system ..... 8
Water Piping .............. 8
Temperature & Pressure-Relief Valve .. 10 Pressure Build-up in a Water System .. 11
Filling the Water Heater ........ 11
Gas Connections ........... 11
Installation Instructions for Water Heaters Approved for Space Heating and Potable Water Heating . 12
.......... 4
Wiring ................ 12
Installation Checklist .......... 14
Operating Instructions
Lighting the Water Heater ....... 15
Water Temperature Regulation ..... 16
Out of Fuel .............. 17
General Maintenance
Housekeeping ............. 17
Safety System ............. 17
Condensation ............. 17
Burner Ignitor Assembly ........ 18
Water Heater Tank ........... 18
Temperature and Pressure-Relief Valve . 18
Venting System Inspection ....... 18
Anode rods .............. 18
Draining the Water Heater ....... 18
Vacation ................ 19
Getting Service for your Water Heater .. 19
Replacement Parts Troubleshooting Guide Warranty
................. 24
.......... 15
........... 17
............ 20
.......... 21
FVIR technology equipped with a flammable vapour sensor and the flame arrestor
This water heater is equipped with new FVIR technology. Activation of the FVIR technology occurs when flammable vapours are drawn into the water heater. If the flammable vapour sensor detects the presence of flammable vapours when the water heater is operating, the gas control will switch to lock out mode and the water heater will shut down. If the water heater is not operating when the flammable vapours are detected, the control will switch to lock out mode and prevent the water heater from lighting. If the flammable vapours enter the combustion chamber and ignite, the flame arrestor will prevent these combustible vapours from igniting outside of the water heater.
If flammable vapours are detected:
•DO NOT try to light any appliance. • DO NOT touch any electrical switch, DO NOT use any phone in your building. •From a neighbour’s phone, immediately call your gas supplier. Follow the gas supplier’s instructions. •Ifyoucannotreachyourgassupplier,callthefiredepartment.
After the flammable vapours have been evacuated, contact a qualified service technician or the gas supplier to have the water heater inspected immediately. Replacement of an FVIR technology equipped water
heater due to a flammable vapour shutdown is not covered under the terms of the Standard Basic Limited Warranty.
2
SAFETY INFORMATION
WARNING
Your safety and the safety of others is extremely important during the installation, opera­tion, and servicing of this water heater. Many safety-related messages have been provided in this manual and on your water heater. Always read and obey all safety messages. These messages will point out the potential hazard, tell you how to reduce the risk of injury, and tell you what will happen if the instructions are not followed.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others. All safety messages will follow the safety alert symbol and either the word “DANGER” or “WARNING”.
Serious injury or death can occur if you do not
DANGER
WARNING
follow the instructions immediately.
Serious injury or death can occur if you do not follow the instructions.
DO NOT use this water heater if any part has been under water. Immediately call a qualified service technician to inspect the water heater and to replace any part of the
control system and any gas control which has been under water. Failure to follow this instruction can result in property damage, personal injury, or death.
3
INSTALLATION INSTRUCTIONS
IMPORTANT
These instructions have been written as a guide for the proper installation and operation of your water heater, and the manufacturer of this water heater will not accept any liability where these instructions have not been fol­lowed. However, for your safety and to avoid damage caused by improper installation, this water heater must be installed by a Certified Licensed Professional, and meet all local codes or, in the absence of local codes, CAN/ CSA B149.1, Natural Gas and Propane Gas Installation Code, in Canada, and/or the National Fuel Gas Code, ANSI Z223.1/NFPA 54, in the United States.
Before proceeding with the installation instructions:
1)
Inspect the water heater and its component parts for possible damage. DO NOT install or attempt to
repair any damaged component parts. If you detect any damage, contact the dealer where the water heater was purchased or the manufacturer listed on the warranty card.
Verify that the type of gas being supplied corresponds to that which is marked on the rating plate and gas
2)
control valve of the water heater.
Location
This water heater should be located close enough to the outside wall so that it is within the venting requirements listed in these installation instructions and as close as possible to the main use of hot water. This location must not be subject to freezing temperatures. The water heater should be positioned, so that there is easy access to the burner, gas control valve, and drain valve. It must be located close to a suitable free-flow­ing floor drain. Where a floor drain is not adjacent to the water heater, a suitable drain pan must be installed under the water heater (see Figure 10). This drain pan should be at least four (4) inches (10.2 cm) larger than the diameter of the water heater, and at least one (1) inch (2.5 cm) deep, providing access to the drain valve. This pan must not restrict the flow of ventilation and combustion air. This pan must be piped to a suit­able drain to prevent damage to property in the event of a water leak from the piping, the relief valve, or the water heater.
Sooner or later, all water heaters leak. The manufacturer, based on national building codes, has given the necessary instructions to prevent damage to the building. Under no circumstances is the manufacturer to be held liable for any water damage, in connection with this water heater.
This water heater is approved for installation on either a combustible or non-combustible floor. However, should this water heater be installed directly on carpeting, the carpeting must be protected by a wood or metal panel beneath the water heater. This panel must extend at least three (3) inches (7.6 cm) beyond the width and depth of the water heater. Should the water heater be installed in an alcove or closet, the entire floor area must be covered by the panel.
Minimum Clearances
The minimum clearances from combustible material for this water heater are: Two (2) inches (5.1 cm) from the sides and rear, four (4) inches (10.2 cm) from the front, and eighteen (18) inches (45.7 cm) from the top (see Figure 1).
Figure 1
18''
2'' min.
2'' min.
2'' min.
4'' min.
Combustion and Ventilation Air Supply
In order for the water heater to operate properly, it must be supplied with an uninterrupted flow of clean combustion and ventilation air. The area around the water heater must always be kept clear and the com­bustion air intake holes at the bottom of the water heater must never be blocked. An inadequate supply of air to the water heater will produce a bright yellow burner flame causing sooting in the combustion cham­ber, on the burner, and in the flue tube. This can result in damage to the water heater and serious bodily injury, if not corrected.
min.
4
INSTALLATION INSTRUCTIONS
Confined Space
Inlet air duct
18''
24''
Combustion and ventilation air requirements are deter­mined by where the water heater is to be located. Water heaters are installed in either open (unconfined) spaces or smaller (confined) spaces, such as closets or small rooms.
Requirements for Unconfined Spaces
An unconfined space is an area with at least 50 cubic feet for each 1,000 BTUH (4.8 m
3
/kW) of the total input rating for all gas appliances installed in that space. Water heaters installed in unconfined spaces do not usually require outdoor air to function properly. However, in buildings with tight construction (heavy insulation, vapour barriers, weather stripping, etc.), and particularly in modern buildings, additional fresh air may need to be provided. For instructions on obtaining additional air supply, see the requirements below for confined spaces.
Requirements for Confined Spaces
A confined space is an area where the volume is less than 50 cubic feet for each 1,000 BTUH (4.8 m3/kW) of the total input rating for all gas appliances installed in that space. Water heaters installed in confined spaces require additional air. This can be provided in two ways:
In Canada (refer to CAN/CSA B149.1)
All Air From Inside the Building (see Figure 2):
1)
The confined space shall be provided with
one opening of one (1) square inch per 1,000 BTUH (22.0 cm2/kW) communicating directly with one or more rooms of sufficient volume, so that the com­bined volume of all spaces meets the criteria for an unconfined space for all the appliances installed in that confined space.
Figure 2
within two (2) feet horizontally from the burner level of the appliance having the largest input.
Figure 3
Confined Space
Inlet air duct
18''
24''
In U.S.A. (refer to ANSI Z223.1/NFPA 54)
1) All Air From Inside the Building (see Figure 4):
The confined space shall be provided with two per-
manent openings communicating directly with one or more rooms of sufficient volume, so that the combined volume of all spaces meets the criteria for an uncon­fined space. The total input rating of all gas appliances installed in the combined space shall be considered in making this determination.
Each opening shall have a minimum free area of one (1) square inch per 1,000 BTUH (22.0 cm2/kW) total input rating of all gas appliances in the confined space, but not less than 100 square inches (645,16 cm2). One opening shall commence within six (6) inches (15.2 cm) of the top and one within six (6) inches (15.2 cm) of the bottom of the enclosure.
2) All Air From Outdoors: The confined space shall be provided with two perma-
nent openings, one commencing within six (6) inches (15.2 cm) of the top and one commencing within six (6) inches (15.2 cm) from the bottom of the enclosure. The openings shall communicate directly or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
of the
All Air From Outdoors: (see Figure 3):
2)
An air-supply shall be provided with one opening that
communicates directly with the outdoors by means of a duct. This duct shall be sized according to CAN/CSA B149.1 and terminate within one (1) foot above and
Confined Space
Permanent Opening
-------------­1 square inches /
1,000 BTUH
Figure 4
5
INSTALLATION INSTRUCTIONS
A) When communicating directly with the outdoors,
each opening shall have a minimum free area of one (1) square inch per 4,000 BTUH (5.5 cm2/kW) of the total input rating of all gas appliances in the enclosure (see Figure 5).
B) When communicating with the outdoors through
vertical ducts, each opening shall have a minimum free area of one (1) square inch per 4,000 BTUH (5.5 cm2/kW) of the total input rating of all gas appli­ances in the enclosure (see Figure 6).
C) When communicating with the outdoors through
horizontal ducts, each opening shall have a mini­mum free area of one (1) square inch per 2,000 BTUH (11.0 cm2/kW) of the total input rating of all gas appliances in the enclosure (see Figure 7).
When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. The minimum short side dimension of rectangular air ducts shall not be less than three (3) inches (7.62 cm).
Louvers and Grilles
In calculating free area for ventilation and com­bustion air supply openings, consideration must be given to the blocking effect of louvers, grilles, or screens protecting the openings. Screens must not be smaller than 1/4 inch (6.4 mm) mesh. If the free area through a particular design of louver or grille is known, it should be used in calculating the size of opening required to provide the free area speci­fied. If the design and free area is not known, it may be assumed that wood louvers and grilles will allow 20-25% free area and metal louvers and grilles will allow 60-75% free area. Louvers and grilles must be installed in the open position or interconnect­ed with the water heater so that they are opened automatically during water heater operation.
Figure 5
Figure 6
Figure 7
Corrosive Atmospheres
If this water heater is to be installed in a beauty shop, barber shop, photo processing lab, dry cleaning establishment, a building with an indoor pool, or near a chemical storage area, it is imperative that the combustion and ventilation air be drawn from outside these areas. These particular environments contain products such as aerosol sprays, detergents, bleaches, cleaning solvents, refrige rants, and other volatile compounds that, in addition to being highly flammable, become highly corrosive acid compounds when burned. Exposure to such compounds can be hazardous and lead to premature product failure.
Should the water heater fail, due to exposure to such a corrosive atmosphere, the warranty is void.
6
INSTALLATION INSTRUCTIONS
Venting
When installing the venting system, make sure to follow all local codes or, in the absence of local codes, CAN/CSA B149.1, Natural Gas and Propane Gas Installation Code, in Canada, and/ or the National Fuel Gas Code, ANSI Z223.1/ NFPA 54, in the United States. Never operate the water heater unless it is properly ventilated to the outdoors and has adequate air supply for proper operation. Failure to properly install the venting system could result in property damage, personal injury, or death.
Before installing the vent piping, make sure that the vent system layout has been properly planned. Verify that the location of the water heater respects all clearances from combustible material, all venting requirements (see Table 1), and that the vent terminal will be installed as specified by all local codes or, in the absence of local codes, CAN/CSA B149.1, Natural Gas and Propane Installation Code, in Canada, and/or the National Fuel Gas Code, ANSI Z223.1/NFPA 54, in the United States (see Figure 9).
According to the CAN/CSA-B149, Natural Gas and Propane Installation Code, plastic vent systems installed in Canada must be certified to the STANDARD FOR TYPE BH GAS VENTING SYSTEMS, ULC S636. Components of the certified vent system must not be interchanged with other vent systems or unlisted pipe/ fittings. Plastic components and specified primers and glues of the certified vent system must be from a single vent system manufacturer and not intermixed with other vent system manufacturer’s vent system parts unless those are certified to be used with this system. Plastic vent systems shall also be installed such that the first three (3) feet (91 cm) of pipe from the water heater outlet is readily accessible for visual inspection.
Through-the-Wall Venting Installation
Cut or drill a hole through the exterior wall, slightly larger than the diameter of the vent pipe selected. The larger hole will allow for final alignment with the water heater. Extend a section of pipe through the hole to the outside and attach the terminating elbow to the exterior end of the pipe. Connect and secure all piping and elbows from the power venter to the wall. Make sure that all horizontal runs have a minimum rise of 1/4 inch per foot (21 mm/m) of run (see Figure 8).
This water heater is equipped with a power venter that evacuates the products of combustion to the outdoors. All models are shipped from the factory with the power venter already installed.
Figure 8
3'' min.
18'' min.
2" min.
This water heater must be vented directly to the out­doors, either horizontally through the wall or vertically through the roof. The venting must not be attached to an existing chimney, or in common with any other appli­ance, and must not be insulated. Only three (3) inch (7.6
18'' min.
1/4"/foot (21mm/m)
cm) schedule 40 PVC or CPVC, pipe and fittings may be used to vent this water heater. The pipe and all the fittings must be permanently joined using the appro­priate primer and solvent-based cement. Horizontal runs of vent pipe must be supported every three (3) feet (91 cm) and vertical runs of vent pipe must be supported every five (5) feet (1.5 m).
Table 1
UG50-65(-59)
PIPE VENT DIAMETER 3 inch Maximum length plus one 45o or 90o termination elbow 50.0 feet (15.2 m)
Minimum length plus one 90o elbow and plus one 45o termination elbow 2.5 feet (0.8 m) One 45o radius elbow is equivalent, in straight pipe, to 4.0 feet (1.2 m) One 90o radius elbow is equivalent, in straight pipe, to 7.0 feet (2.1 m)
MAXIMUM EQUIVALENT LENGTH OF PIPE — DO NOT EXCEED MAXIMUM LENGTH OF PIPE
7
INSTALLATION INSTRUCTIONS
When the installation is completed, the vent terminal must be a minimum of two (2) inches (5.1 cm) from the exterior surface of the wall (see Figure 8). Make sure that all piping is properly braced. If the venting will pass through an enclosed area, make sure to leave at least one (1) inch (2.5 cm) clearance around the piping for air circulation.
Through-the-Roof Venting Installation
Cut or drill a hole through the roof and ceiling, slightly larger than the diameter of the vent pipe selected. The larger hole will allow for final alignment with the water heater. Construct the vent terminal assembly. Extend a section of pipe through the hole in the roof to the outside and attach the terminal assembly to the exterior end of the pipe. Connect and secure all piping and elbows from the power venter to the roof. Make
1
sure that all horizontal runs have a minimum rise of inch per foot (21 mm/m) of run (see Figure 8). When the installation is completed, the vent terminal must be a minimum of eighteen (18) inches (45.7 cm) from the exterior surface of the roof (see Figure 8). Make sure that all piping is properly braced. If the venting will pass through an enclosed area, make sure to leave at least one (1) inch (2.5 cm) clearance around the piping for air circulation.
Condensation in the Venting System
In some installations, condensation will form in the horizontal runs of vent piping. To prevent condensa­tion from flowing back into the power venter, install a condensate trap just past the first elbow of the vent piping system. Make sure that the condensate remov­al tube flows to a suitable free-flowing drain.
Installation of the venting system
ALWAYS read and obey all safety messag-
es printed on the primer, cleaner, and cement containers. Primer, cleaner, and cements are extremely flammable. DO NOT store these prod­ucts near heat, sparks, or flames. They are harmful or fatal if swallowed. Their vapours are also harmful. They may irritate eyes and can be absorbed through the skin. Failure to follow these instructions can result in property damage, per­sonal injury, or death.
1) Adjust the vent pipe length to properly fit the vent sys­tem adaptor on the blower assembly outlet.
2) Cut pipe ends squarely, removing all burrs and dirt.
3) Dry fit the pipe/fitting to be connected to make sure they fit properly.
4) Clean the pipe/fitting with the proper primer or cleaner.
/4
5) Apply a thin coat of cement to the fitting, avoiding pud­dling inside.
6) Apply a liberal coat of cement to the vent pipe, leaving no voids.
7) QUICKLY assemble parts while cement is fluid! If you wait too long, re-coat pipe/fitting.
8) Push the vent pipe completely into the PVC coupling, turning as it goes until it bottoms out.
9) Hold pipe and fitting together for 30 seconds. Then carefully clean off any excess material with a cloth. Allow connections a sufficient time to cure before dis­turbing.
10) Loosen the upper hose clamp on the rubber transi­tion fitting and fully insert the CPVC pipe of the vent system adaptor (1.25” deep). Do not apply cement to the rubber transition fitting.
11) Tighten the upper hose clamp to ensure the vent pipe is firmly secured and gas tight.
12) Make sure that the lower hose clamp is firmly seated, secured and gas tight. Gently move the vent pipe side to side and vertically to ensure that it is securely in place and that there is no slippage.
When the installation is complete, visually inspect the venting system to make sure that all joints are prop­erly connected and all instructions have been followed. Failure to properly install the venting system could result in property damage, personal injury, or death.
Water Piping
Refer to Figure 10 for a typical installation. Use of this layout should provide a trouble-free installation for the life of the water heater. Before making the plumbing connections, locate the COLD water inlet and the HOT water outlet. These fittings are both 3/4” N.P.T. male thread. Make sure that the dip-tube is installed in the cold water inlet. Install a shut-off valve close to the water heater in the cold water line. It is recommended that unions be installed in the cold and hot water lines so that the water heater can be easily disconnected, if servicing is required.
When assembling the hot and cold piping, use a good food grade of pipe joint compound, and ensure all fittings are tight. It is imperative that open flame is not applied to the inlet and outlet fittings, as heat will damage or destroy the plastic-lined fittings. This will
result in premature failure of the fittings, which is not covered by the warranty.
8
Loading...
+ 16 hidden pages