This water heater IS NOT design certified for
installation in a manufactured (mobile) home or
for installation outdoors.
If the information in these instructions is not
followed exactly, a fire or explosion may
result causing property damage, personal
injury or death.
DO NOT store or use gasoline or other
flammable vapours and liquids in the vicinity of
this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• DO NOT try to light any appliance.
• DO NOT touch any electrical switch.
• DO NOT use any phone in your building.
• From a neighbour’s phone, immediately
call your gas supplier. Follow the gas
supplier’s instructions.
• If you cannot reach your gas supplier, call the
fire department.
Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
IMPORTANT
READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION. PROPER
INSTALLATION WILL PROVIDE SAFE AND EFFICIENT SERVICE AND AVOID NEEDLESS EXPENSE NOT
COVERED BY THE WARRANTY. READ THE PRODUCT WARRANTY CONTAINED IN THIS MANUAL AND
REMEMBER TO FILL OUT AND RETURN TO THE MANUFACTURER ALL RELEVANT WARRANTY CARDS
AND CERTIFICATES. SHOULD YOU HAVE ANY QUESTIONS, PLEASE CONTACT YOUR LOCAL DEALER OR
REFER TO THE
SAVE THIS MANUAL FOR FUTURE REFERENCES.
GETTING SERVICE FOR YOUR WATER HEATERSECTION OF THIS MANUAL.
For your records, write the model and serial number here:
Temperature and Pressure-Relief Valve .. 9
Pressure Build-up in a Water System ... 10
Filling the Water Heater .......... 12
Gas Connections ............. 12
Installation Instructions for
Water Heaters Approved for Space Heating
and Potable Water Heating ....... 13
Wiring .................. 14
Installation Checklist ........... 15
Operating Instructions ........... 16
Lighting the Water Heater ......... 16
Water Temperature Regulation ...... 17
Out of Fuel ............... 18
General Maintenance ........... 18
Housekeeping . . . . . . . . . . . . . . 18
Safety System .............. 18
Condensation .............. 18
Burner Ignitor Assembly .......... 19
Water Heater Tank ............ 19
Temperature and Pressure-Relief Valve... 19
Venting System Inspection......... 19
Anode .................. 19
Draining the Water Heater ......... 19
Vacation ................. 20
Getting Service for your Water Heater ... 20
Replacement Parts ............. 21
Troubleshooting Guide ........... 22
Warranty .................. 26
FVIR technology equipped with a flammable vapour sensor and the flame arrestor.
WARNING
!!
Flammable Vapour Sensor
Do not remove the protective cover. Do not spray water or leak detector
products on this sensor. Do not expose this sensor to bleach or other liquid
cleaning products. Avoid humid environments and freezing temperatures.
If the sensor detects the presence of flammable vapour, the gas control will
switch to lock out mode and the water heater will shut down. Do not try and
restart the water heater. Have the water heater inspected immediately by a
qualified service technician or the gas supplier.
This water heater is equipped with FVIR technology. Activation of the FVIR technology occurs when flammable
vapours are drawn into the water heater. If the flammable vapour sensor detects the presence of flammable vapours
when the water heater is operating, the gas control will switch to lock out mode and the water heater will shut down.
If the water heater is not operating when the flammable vapours are detected, the control will switch to lock out mode
and prevent the water heater from lighting. If the flammable vapours enter the combustion chamber and ignite, the
flame arrestor will prevent these combustible vapours from igniting outside of the water heater.
If flammable vapours are detected:
•DO NOT try to light any appliance.
• DO NOT touch any electrical switch. DO NOT use any phone in your building.
•
From a neighbour’s phone, immediately call your gas supplier.
After the flammable vapours have been evacuated, contact a qualified service technician or the gas supplier to have
the water heater inspected immediately.
to a flammable vapour shutdown is not covered under the terms of the Standard Basic Limited
Warranty.
Replacement of an FVIR technology equipped water heater due
2
Page 3
SAFETY INFORMATION
WARNING
WARNING
Your safety and the safety of others is extremely important during the installation, operation
and servicing of this water heater. Many safety-related messages have been provided in
this manual and on your water heater. Always read and abide by all safety messages. These
messages will point out the potential hazard, tell you how to reduce the risk of injury and tell
you what will happen if the instructions are not followed.
This is the safety alert symbol. This symbol alerts you to potential hazards
that can kill or hurt you and others. All safety messages will follow the safety
alert symbol and either the word “DANGER” or “WARNING”.
DANGER
WARNING
Serious injury or death can occur if you do not
follow the instructions immediately.
Serious injury or death can occur if you do not follow
the instructions.
DO NOT use this water heater if any part has been under water. Immediately call a
qualified service technician to inspect the water heater and to replace any part of the
control system and any gas control which has been under water. Failure to follow this
instruction can result in property damage, personal injury or death.
3
Page 4
INSTALLATION INSTRUCTIONS
IMPORTANT
These instructions have been written as a guide for the proper installation and operation of your water heater
and the manufacturer of this water heater will not accept any liability where these instructions have not been followed. However, for your safety and to avoid damage caused by improper installation, this water heater must be
installed by a Certified Licensed Professional and meet all local codes or, in the absence of local codes, CAN/
CSA B149.1, Natural Gas and Propane Gas Installation Code, in Canada and/or the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, in the United States.
Before proceeding with the installation instructions:
1) Inspect the water heater and its component parts for possible damage. DO NOT install or attempt to
repair any damaged component parts. If you detect any damage, contact the dealer where the water
heater was purchased or the manufacturer listed on the warranty card.
2) Verify that the type of gas being supplied corresponds to what is marked on the rating plate and gas
control valve of the water heater.
Altitude
This water heater is approved for altitudes up to 5,000 feet
(1,524 m).
Location
This water heater should be located close enough to the
outside wall so that it is within the venting requirements
listed in these installation instructions and as close as
possible to the main use of hot water. This location must
not be subject to freezing temperatures. The water
heater should be positioned, so that there is easy
access to the burner, gas control valve and drain valve.
It must be located close to a suitable free-flowing floor
drain. Where a floor drain is not adjacent to the water
heater, a suitable drain pan must be installed under the
water heater (see Figure 12). This drain pan should be
at least four (4) inches (10.2 cm) larger than the diameter
of the water heater and at least one (1) inch (2.5 cm)
deep, providing access to the drain valve. This pan
must not restrict the flow of ventilation and combustion
air. This pan must be piped to a suitable drain to prevent damage to property in the event of a water leak
from the piping, the relief valve or the water heater.
Minimum Clearances
The minimum clearances from combustible material
for this water heater are: Two (2) inches (5.1 cm) from
the sides and rear, four (4) inches (10.2 cm) from the
front and eighteen (18) inches (45.7 cm) from the top
(see Figure 1).
Figure 1
18''
min.
2'' min.
4'' min.
2'' min.
2'' min.
Sooner or later, all water heaters leak. The
manufacturer, based on national building codes,
has given the necessary instructions to prevent
damage to the building. Under no circumstances
is the manufacturer to be held liable for any water
damage in connection with this water heater.
This water heater is approved for installation on either a
combustible or non-combustible floor. However, should
this water heater be installed directly on carpeting, the
carpeting must be protected by a wood or metal panel
beneath the water heater. This panel must extend at
least three (3) inches (7.6 cm) beyond the width and
depth of the water heater. Should the water heater be
installed in an alcove or closet, the entire floor area must
be covered by the panel.
Combustion and Ventilation Air Supply
In order for the water heater to operate properly, it must
be supplied with an uninterrupted flow of clean combustion and ventilation air. The area around the water
heater must always be kept clear and the combustion
air intake holes at the bottom of the water heater must
never be blocked. An inadequate supply of air to the
water heater will produce a bright yellow burner flame
causing sooting in the combustion chamber, on the
burner and in the flue tube. This can result in damage to the water heater and serious bodily injury, if not
corrected.
Combustion and ventilation air requirements
are determined by where the water heater is to be
located. Water heaters are installed in either open
4
Page 5
INSTALLATION INSTRUCTIONS
Confined Space
Inlet air duct
18''
24''
(unconfined) spaces or smaller (confined) spaces,
such as closets or small rooms.
Requirements for Unconfined Spaces
An unconfined space is an area with at least 50 cubic
feet for each 1,000 BTUH (4.8 m3/kW) of the total
input rating for all gas appliances installed in that
space. Water heaters installed in unconfined spaces
do not usually require outdoor air to function properly.
However, in buildings with tight construction (heavy
insulation, vapour barriers, weather stripping, etc.) and
particularly in modern buildings, additional fresh air
may need to be provided. For instructions on obtaining
additional air supply, see the requirements below for
confined spaces.
Requirements for Confined Spaces
A confined space is an area where the volume is less
than 50 cubic feet for each 1,000 BTUH (4.8 m3/kW)
of
the total input rating for all gas appliances installed in
that space. Water heaters installed in confined spaces
require additional air. This can be provided in two
ways:
In Canada (refer to CAN/CSA B149.1)
1) All Air From Inside the Building (see Figure 2):
The confined space shall be provided with
one opening of one (1) square inch per 1,000 BTUH
(22.0 cm2/kW) communicating directly with one or
more rooms of sufficient volume, so that the combined volume of all spaces meets the criteria for an
unconfined space for all the appliances installed in
that confined space.
Figure 2
1 foot above and within 2 feet horizontally from
the burner level of the appliance having the
largest input.
Figure 3
Confined Space
Inlet air duct
18''
24''
In U.S.A. (refer to ANSI Z223.1/NFPA 54)
1) All Air From Inside the Building (see Figure 4):
The confined space shall be provided with two
permanent openings communicating directly with
one or more rooms of sufficient volume, so that
the combined volume of all spaces meets the
criteria for an unconfined space. The total input
rating of all gas appliances installed in the
combined space shall be considered in making this
determination.
Each opening shall have a minimum free area of
one (1) square inch per 1,000 BTUH (22.0 cm2/
kW) of the total input rating of all gas appliances in
the confined space, but not less than 100 square
inches (645.16 cm2). One opening shall commence
within 6 inches (15.2 cm) of the top and one within 6
inches (15.2 cm) of the bottom of the enclosure.
Confined Space
2) All Air From Outdoors: (see Figure 3):
An air-supply shall be provided with one open-
ing that communicates directly with the outdoors
by means of a duct. This duct shall be sized
according to CAN/CSA B149.1 and terminate within
Permanent
Opening
-------------1 square inches /
1000 BTUH
2) All Air From Outdoors:
The confined space shall be provided with two
permanent openings, one commencing within six
Figure 4
5
Page 6
INSTALLATION INSTRUCTIONS
(6) inches (15.2 cm) of the top and one commencing
within six (6) inches (15.2 cm) from the bottom of the
enclosure. The openings shall communicate directly
or by ducts, with the outdoors or spaces (crawl or
attic) that freely communicate with the outdoors.
A) When communicating directly with the outdoors,
each opening shall have a minimum free area of
one (1) square inch per 4,000 BTUH (5.5 cm2/kW)
of the total input rating of all gas appliances in the
enclosure (see Figure 5).
B) When communicating with the outdoors through
vertical ducts, each opening shall have a minimum
free area of one (1) square inch per 4,000 BTUH (5.5
cm2/kW) of the total input rating of all gas appliances
in the enclosure (see Figure 6).
C) When communicating with the outdoors through
horizontal ducts, each opening shall have a minimum free area of one (1) square inch per 2,000
BTUH (11.0 cm2/kW) of the total input rating of
all gas appliances in the enclosure (see Figure 7).
Figure 5
Figure 6
When ducts are used, they shall be of the same
cross-sectional area as the free area of the openings
to which they connect. The minimum short side dimension of rectangular air ducts shall not be less than
three (3) inches (7.62 cm).
Louvers and Grilles
In calculating free area for ventilation and combustion air supply openings, consideration must be
given to the blocking effect of louvers, grilles or
screens protecting the openings. Screens must not
be smaller than 1/4 inch (6.4 mm) mesh. If the free
area through a particular design of louver or grille
is known, it should be used in calculating the size
of opening required to provide the free area specified. If the design and free area is not known, it may
be assumed that wood louvers and grilles will allow
20-25% free area and metal louvers and grilles will
allow 60-75% free area. Louvers and grilles must
be installed in the open position or interconnected with the water heater so that they are opened
automatically during water heater operation.
Figure 7
Corrosive Atmospheres
If this water heater is to be installed in a beauty
shop, barber shop, photo processing lab, dry cleaning
establishment, a building with an indoor pool or
near a chemical storage area, it is imperative that
the combustion and ventilation air be drawn from outside these areas. These particular environments
contain products such as aerosol sprays, detergents,
bleaches, cleaning solvents, refrige rants and other
volatile compounds that, in addition to being highly flammable, become highly corrosive acid compounds when
burned. Exposure to such compounds can be hazardous and lead to premature product failure.
6
Page 7
INSTALLATION INSTRUCTIONS
WARNING
DANGER
Should the water heater fail, due to exposure to
such a corrosive atmosphere, the warranty is void.
Venting
When installing the venting system, make sure to
follow all local codes or, in the absence of local
codes, CAN/CSA B149.1, Natural Gas and
Propane Gas Installation Code, in Canada and/
or the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, in the United States. Never operate the
water heater unless it is properly ventilated to the
outdoors and has adequate air supply for proper
operation. Failure to properly install the venting
system could result in property damage, personal
injury or death.
Before installing the vent piping, make sure that the
vent system layout has been properly planned. Verify
that the location of the water heater respects all
clearances from combustible material, all venting
requirements (see Table 1) and that the vent terminal
will be installed as specified by all local codes or, in the
absence of local codes, CAN/CSA B149.1, Natural Gas
and Propane Installation Code, in Canada and/or the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, in the
United States (see Figure 11).
According to the CAN/CSA-B149, Natural Gas and
Propane Installation Code, plastic vent systems
installed in Canada must be certified to the STANDARD
FOR TYPE BH GAS VENTING SYSTEMS, ULC S636.
Components of the certified vent system must not be
interchanged with other vent systems or unlisted pipe/
fittings. Plastic components and specified primers and
glues of the certified vent system must be from a single
vent system manufacturer and not intermixed with
other vent system manufacturer’s vent system parts
unless those are certified to be used with this system.
Plastic vent systems shall also be installed such that
the first three (3) feet (91 cm) of pipe from the water
heater outlet is readily accessible for visual inspection.
Termination screen
A restrictor screen (see Figure 9) is provided with the
following Energy Star models (see Table 2). The two
(2) inch (5.1 cm) restrictor screen must be installed and
glued, and the wire mesh shall be removed from the
vent termination elbow when total equivalent length is
thirty (30) feet (9.1 m) or less of two inch vent pipe, otherwise a standard wire mesh screen shall be installed.
When using three (3) inch vent pipe a standard wire
mesh must be installed in all cases (see Table 3).
Figure 8
This water heater is equipped with a power venter
that evacuates the products of combustion to the
outdoors. All models are shipped from the factory
with the power venter already installed.
This water heater must be vented directly to the outdoors, either horizontally through the wall or vertically
through the roof. The venting must not be attached
to an existing chimney or in common with any other
appliance and must not be insulated. Only two (2)
inch (5.1 cm) or three (3) inch (7.6 cm) schedule 40
PVC or CPVC pipe and fittings may be used to
vent this water heater. The pipe and all the fittings
must be permanently joined using the appropriate
primer and solvent-based cement. Horizontal runs
of vent pipe must be supported every three (3)
feet (91 cm) and vertical runs of vent pipe must be
supported every five (5) feet (1.5 m).
Table 1
PV1 Models only UG40, UG50 and UG60
VENT PIPE DIAMETER 2 inches 3 inches
Maximum equivalent length*
Minimum equivalent length*
One 45˚ elbow is equivalent, in straight pipe, to
One 90˚ elbow is equivalent, in straight pipe, to
* Note: Outdoor termination elbow not to be counted when determining total length.
MAXIMUM EQUIVALENT LENGTH OF VENT PIPE - DO NOT EXCEED
50,0 feet (15,2 m)
7,5 feet (2,3 m)
3,0 feet (0,9 m)
5,0 feet (1,5 m)
140,0 feet (42,7 m)
9,5 feet (2,9 m)
4,0 feet (1,2 m)
7,0 feet (2,1 m)
7
Page 8
INSTALLATION INSTRUCTIONS
WARNING
Through-the-Wall Venting Installation
Cut or drill a hole through the exterior wall, slightly
larger than the diameter of the vent pipe selected.
The larger hole will allow for final alignment with the
water heater. Extend a section of the pipe through
the hole to the outside and attach the terminating
elbow to the exterior end of the pipe. Connect and
Figure 9
Table 2
Natural GasPropane Gas
UG40-40LFPV1-N2UUG40-38LFPV1-P2U
UG50-40LFPV1-N2UUG50-38LFPV1-P2U
UG60-40MFPV1-N2UUG60-38MFPV1-P2U
secure all piping and elbows from the power venter
to the wall. Make sure that all horizontal runs have a
minimum rise of
Figure 8). When the installation is completed, the vent
terminal must be at two (2) inches (5.1 cm) from the
exterior surface of the wall (see Figure 8). Make sure
that all piping is properly braced. If the venting will pass
through an enclosed area, make sure to leave at least
one (1) inch (2.5 cm) clearance around the piping for
air circulation.
Through-the-Roof Venting Installation
Cut or drill a hole through the roof and ceiling, slightly
larger than the diameter of the vent pipe selected. The
larger hole will allow for the final alignment with the
water heater. Construct the vent terminal assembly.
Extend a section of pipe through the hole in the roof
to the outside and attach the terminal assembly to the
exterior end of the pipe. Connect and secure all piping
and elbows from the power venter to the roof. Make
sure that all horizontal runs have a minimum rise of
inch per foot (21 mm/m) of run (see Figure 8).
1
/4 inch per foot (21 mm/m) of run (see
1
/4
When the installation is completed, the vent terminal
must be a minimum of eighteen (18) inches (45.7 cm)
from the exterior surface of the roof (see Figure 8).
Make sure that all piping is properly braced. If the venting will pass through an enclosed area, make sure to
leave at least one (1) inch (2.5 cm) clearance around
the piping for air circulation.
Condensation in the Venting System
In some installations, condensation will form in the
horizontal runs of vent piping. To prevent condensation from flowing back into the power venter, install a
condensate trap to the drain outlet of the rubber
transition fitting. Make sure that the condensate removal tube flows to a suitable free-flowing drain.
CPVC Adaptor
A CPVC vent system adaptor should be installed when
using PVC pipes for venting this water heater (see Figure 10). The vent system adaptor consists of a
PVC coupling glued to a CPVC pipe. The CPVC pipe
must be inserted into the rubber transition fitting on the
outlet of the blower assembly (see Figure 10).
INSTALLATION
The PVC coupling on the vent system adaptor must be
attached to the PVC vent system using the proper primer,
cleaner and cement.
ALWAYS read and abide by all safety messages
printed on the primer, cleaner and cement containers. Primer, cleaner and cements are extremely
flammable. DO NOT store these products near
heat, sparks or flames. They are harmful or fatal if
swallowed. Their vapours are also harmful. They
may irritate eyes and can be absorbed through the
skin. Failure to follow these instructions can result
in property damage, personal injury or death.
1) Adjust the vent pipe length to properly fit the vent
system adaptor on the blower assembly outlet.
2) Cut pipe ends squarely, removing all burrs and dirt.
3) Dry fit the pipe/fitting to be connected to make sure
they fit properly.
4) Clean the pipe/fitting with the proper primer or cleaner.
Table 3
VENT DIAMETER
2” (5.1 cm)
VENT DIAMETER
3” (7.6 cm)
TERMINATION
45˚ ELBOW
TERMINATION
45˚ ELBOW
0’ - 30’ 30’ - 50’
0’ - 30’ 30’ - 140’
8
Page 9
WARNING
INSTALLATION INSTRUCTIONS
WARNING
5) Apply a thin coat of cement to the fitting, avoiding
puddling inside.
6) Apply a liberal coat of cement to the vent pipe, leaving no voids.
7) QUICKLY assemble parts while cement is fluid! If
you wait too long, re-coat pipe/fitting.
8) Push the vent pipe completely into the PVC coupling,
turning as it goes until it bottoms out.
9) Hold pipe and fitting together for 30 seconds. Then carefully clean off any excess material with a cloth. Allow
connections a sufficient time to cure before disturbing.
10) Loosen the upper hose clamp on the rubber transition
fitting and fully insert the CPVC pipe of the vent system adaptor (1” [2.5 cm] deep). Do not apply cement
to the rubber transition fitting.
11) Tighten the upper hose clamp to ensure the vent
pipe is firmly secured and gas tight.
12) Make sure that the lower hose clamp is firmly seated,
secured and gas tight. Gently move the vent pipe
side to side and vertically to ensure that it is securely
in place and that there is no slippage.
Note: If you are using CPVC pipes for the venting system, the use of the vent system adaptor is not necessary.
When the installation is complete, visually inspect the
venting system to make sure that all joints are properly connected and all instructions have been followed.
Failure to properly install the venting system could
result in property damage, personal injury or death.
Water Piping
Refer to Figure 11 for a typical installation. Use of this
layout should provide a trouble-free installation for the life
of the water heater. Before making the plumbing connections, locate the COLD water inlet and the HOT water
outlet. These fittings are both 3/4” N.P.T. male thread.
Make sure that the dip-tube is installed in the cold water
inlet. Install a shut-off valve close to the water heater in
the cold water line. It is recommended that unions be
installed in the cold and hot water lines so that the water
heater can be easily disconnected, if servicing is required.
When assembling the hot and cold piping, use a good
food grade of pipe joint compound and ensure all fittings are tight. It is imperative that open flame is not
applied to the inlet and outlet fittings, as heat will
damage or destroy the plastic-lined fittings. This will
result in premature failure of the fittings, which
is not covered by the warranty.
Temperature and Pressure-Relief Valve
DO NOT plug the temperature and pressurerelief valve or its discharge line. DO NOT remove
the relief valve. Make sure the relief valve is
properly sized for the water heater. If the relief valve
continuously discharges water, call a qualified
service technician to correct the problem. Failure
to follow these instructions can result in property
damage, personal injury or death.
Figure 10
Vent System Adaptor
Drain Outlet
Blower Assembly Outlet
Connection to a 2 inch vent system Connection to a 3 inch vent system
The blower assembly must always have the two (2) inch rubber transition fitting. A reducing coupling
2” X 3” is necessary for a three (3) inch venting system. This coupling must be installed as close as
possible after the rubber transition fitting and in every case, before the first elbow.
Rubber
transition tting
Vent System Adaptor
Drain Outlet
Blower Assembly Outlet
Rubber
transition tting
9
Page 10
INSTALLATION INSTRUCTIONS
Figure 11
26
21
20
19
18
17
27
22
1
2
25
24
23
Minimum Slope
1/4”/foot (21mm/m)
3
7
8
9
10
11
4
5
1) Vent pipe
2) Power vent assembly
3) Union
4) Cold water
manual shut-off valve
5) Cold water inlet
6) Expansion tank
7) Temperature
and pressure-relief valve
8) Overflow tube
9) Drain valve
10) Combustion
air intake holes
11) Drain pan
6
12) Free-flowing floor drain
13) Sight glass
14) Resettable Thermal Switch
15) Outer access door
16) Inner access door
17) Flammable vapour sensor
18) Cap
19) Drip leg (Sediment trap)
20) Gas supply
manual shut-off valve
21) Union
22) Gas control valve
23) Rating plate
24) Dip-tube
25) 12’ Power cord (3,86 m)
26) Hot water outlet
27) Union
28) Flame sensor
29) Ignitor
30) Burner orifice
31) Burner
28
31
16
12
15
14
13
To protect from excessive pressure and/or temperature, the manufacturer has installed a temperature and
pressure-relief valve that meets the requirements of
the Standard for Relief Valves and Automatic Gas
Shut-Off Devices for Hot Water Supply Systems,
CSA 4.4, in Canada and ANSI Z21.22, in the United
States. This relief valve has a maximum set pressure that does not exceed the hydrostatic working
pressure of the water heater (150 psi = 1,035 kPa) and
a BTU/h rating equal to or greater than the input rating,
as shown on the water heater rating plate. It should never
be plugged or removed from the opening marked for it on
the water heater.
If this relief valve should need to be replaced, use only
a new temperature and pressure-relief valve. Never
install an old or existing relief valve, as it may be
damaged or inadequate for the working requirements of
the new water heater. This new relief valve must meet
all local codes or, at a minimum, the requirements listed
above. Never install any other type of valve between the
relief valve and the water heater.
29
30
A discharge line must be installed into the relief valve.
The discharge line:
When the water heater operates, the heated water
expands creating a pressure build-up. This is a
natural function and is one of the reasons for installing a
temperature and pressure-relief valve. If the cold water
E)Clearance to service regulator vent outlet..3 feet (91 cm)6 feet (1,82 m)
F)Clearance to each side of center line extended above
meter/regulator assembly.
G) Clearance to non-mechanical air supply inlet to building or
the combustion air inlet to any other appliance..
H)Clearance to a mechanical air supply inlet.
I)Clearance above paved sidewalk or paved driveway
located on public property.
•
Clearance under veranda, porch, deck or balcony.**
•
Clearance to permanently closed window.*
Vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 2 feet (61 cm) from
•
the center line of the terminal.*
Clearance to unventilated soffit.*
•
Canadian InstallationsU.S.A. Installations)
12 inches (30 cm)
**
*
3 feet (91 cm) within a
height 15 feet (4.57 m)
above the meter/regulator
assembly
12 inches (30 cm)
6 feet (1.82 m)
7 feet (2.13 m)7 feet (2.13 m)
12 inches (30 cm)Shall not
3 feet (91 cm) within a
height 15 feet (4.57 m)
above the meter/regulator
* * *
3 feet (91 cm)
assembly
* * *
* * * *
Clearance in accordance with local installation codes and the requirements of the gas supplier.
*
For Canadian and U.S.A. installations, the vent shall not terminate above a paved driveway that is located between two single family dwellings and serves both
dwellings.
** The veranda, porch or deck is fully open on a minimum of two sides beneath the floor.
***The vent terminal must terminate at least four (4) feet (1.22m) below, four (4) feet (1.22m) horizontally from or one (1) foot (30 cm) above any door, window
and gravity air inlet to the building.
**** The vent terminal must terminate at least three (3) feet (91cm) above any forced air inlet duct located within ten (10) feet (3.05m).
11
Page 12
INSTALLATION INSTRUCTIONS
WARNING
WARNING
WARNING
WARNING
supply line has a built-in water meter, check valve or
pressure-reducing valve, a suitable expansion tank
must be installed to prevent pressure build-up or water
hammer effect. Otherwise, the warranty is void (see Figure 11). An indication of pressure build-up is frequent discharges of water from the relief valve. If the
relief valve discharges water on a continuous basis,
it may indicate a malfunction of the relief valve and a
qualified service technician must be called to have the
system checked and the problem corrected.
Filling the Water Heater
NEVER operate the water heater unless it is
completely filled with water.
this instruction can result in premature failure of the water heater that is not covered by
the warranty.
Check that all of the water piping connections have
been made. To fill the water heater:
1) Make sure that the water heater drain valve is
closed by inserting a flat head screwdriver into the
slot on the head of the drain valve and turning the
knob clockwise
2) Open the cold water supply manual shut-off valve.
This valve must remain open, as long as the water
heater is in use. NEVER operate the water heater with
the cold water supply manual shut-off valve closed.
3) To make sure the water heater is completely full of
water, open all of the hot water faucets in the house
to let the air out of the water heater and plumbing
system. Leave the faucets open until a constant
flow of water is obtained.
4) Check all of the plumbing connections to make
sure there are no leaks.
Gas Connections
DO NOT attempt to use this water heater with
any gas other than the type of gas shown on
the water heater rating plate. Failure to follow
this instruction can result in property damage, personal injury or death.
The gas piping must be installed as indicated in
Figure 11. For the correct size of piping for this water
heater, consult CAN/CSA B149.1, National Gas and
Propane Installation Codes (in Canada) and/or the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
.
Failure to follow
in the United States. Only new piping with cleanly
cut threads may be used, together with a suitable
sealing compound that is approved for natural and
propane gases. It is mandatory that a readily accessible
manual shut-off valve be installed in the gas supply
line. The gas supply manual shut-off valve must be
close to the water heater. A drip leg (sediment trap)
must be installed in the gas line ahead of the gas control valve to prevent dirt from entering it. A union must
be installed between the gas control valve and the gas
supply manual shut-off valve for easy maintenance of
the water heater.
NEVER use an open flame to test for gas leaks.
A fire or explosion could occur resulting in property
damage, personal injury or death.
The water heater and its gas connection must
be leak tested before placing the appliance into operation. To leak test the system:
1) Turn on the manual gas shut-off valve near the
water heater.
2) Use a soapy water solution to test all connections
and fittings for leaks. Bubbles indicate a gas leak.
3) Correct all leaks.
Make sure that the inlet pressure to the water heater
1
does not exceed
propane gases. Pressures in excess of
can damage the gas control valve, resulting in a fire or
explosion from leaking gas. For purposes of adjustment,
the minimum inlet pressure is indicated on the water
heater rating plate.
If any pressure testing of the gas line is undertaken
at test pressures in excess of
water heater and its gas supply manual shut-off
valve must be disconnected from the gas supply
piping system and the end of the pipe sealed with a
female cap. If the testing is to be undertaken at a test
pressure less than
manual shut-off valve must be closed.
U.L. and CSA recognized fuel gas and Carbon
Monoxide (Co) detectors are recommended in
all applications and should be installed using the
manufacturer’s instructions and local codes, rules
or regulations.
/2 psi (3.5 kPa) for both natural and
1
/2 psi (3.5 kPa)
1
/2 psi (3.5 kPa), the
1
/2 psi (3.5 kPa), the gas supply
12
Page 13
INSTALLATION INSTRUCTIONS
Installation Instructions for Water Heaters
Approved for Space Heating and
Potable Water Heating (see Figure 13)
When using a water heater for space and potable water heating, the instructions provided in this
manual and with the air-handling unit must be respected and, in particular, the following:
1) All piping and components that are used in the
system must be of a nonferrous type suitable for
potable water. This also applies to any sealant
used.
2) When used as a dual purpose water heater, it must
not be connected to any system that has been previously used for non-potable water heating. This includes
any piping because, in all probability, existing piping
would have been, in the past, treated with chemicals
for cleaning or sealing the system.
3) If this water heater is to be used for space heating,
make sure that all safety codes are respected.
Pay special attention to safety valve pressure and
expansion tanks.
4) Do not use toxic chemicals to clean the potable
water heating system.
5) Where water temperature in excess of 140
o
C) is required for a space heating application, a
(60
o
F
mixing valve must be installed in the potable side of
the system. This will temper the water and reduce
the risk of scalding.
6) If the incoming water line to the heater is
equipped with a check valve, water meter or
pressure-reducing valve, an expansion tank
must be installed in the system. This will prevent
weeping from the water heater relief valve and premature failure of the heater due to expansion of the
water during the heating cycle.
7) Before acquisition of a water heater for space
heating application, it is necessary to have
the area of intended use sized by a qualified
technician. This will ensure that an adequate water
heating capacity will be available for both heating
and potable water supply and that the application
will meet all local codes and public utility requirements.
Note: It is good practice to oversize the water heater,
to ensure that all of the potential hot water requirements are available.
Figure 13
Hot water
to house
Water heater
Cold water supply
to water heater
Check Valve
Circulation Pump
Air handler
13
Page 14
INSTALLATION INSTRUCTIONS
WARNING
Wiring
This water heater uses an external electrical source
for power. It must be electrically grounded in accordance with all local codes or, in the absence of local
codes, CSA C22.1 Canadian Electrical Code, in
Canada and/or the National Electrical Code, ANSI/
NFPA 70, in the United States. Failure to properly
ground this water heater can result in property damage, personal injury or death.
Wiring Diagram
for Models UG40, UG50, UG60
Figure 14
Blower Unit
High Limit Switch
Yellow
Before lighting your water heater, check that all of the
wires have been installed correctly (see Figure 14).
Make sure that none of the wires are grounded, have
split or are broken. Verify that all wiring connections
are properly secured, as there is a possibility that they
have become loose during transportation. If any of the
original wiring needs replacing, use only 18AWGtype or greater wire that is approved for 221oF (105oC).
Before lighting or re-lighting your
water heater, make sure that you
have read and understood all of the
instructions and warnings in this manual and on your water heater. If you
have any questions about lighting
your water heater, immediately contact a qualified
installer, service agency or the gas supplier.
• Gasoline or other flammable vapours and
liquids have been stored in the vicinity of the
water heater.
Failure to follow these instructions can result in
property damage, personal injury or death.
16
Page 17
OPERATING INSTRUCTIONS
CLIGNOTANT
TEMPÉRATURE
APPROXIMATIVE
˚F (˚C)
70 (21)
(Vacances)
110 (43)
115 (46)
120 (49)
125 (52)
130 (54)
135 (57)
140 (60)
145 (63)
150 (66)
160 (71)
TEMPS
NÉCESSAIREPOUR CAUSERUNE BRÛLURE
S/O
5 minutes
30 secondes
5 secondes
1,5 seconde
moins d'une
seconde
AFFICHAGE
WARNING
Water Temperature Regulation
The higher the setting, the greater the risk of
scalding. Hot water can cause third degree burns
o
in under one (1) second at 160
F (71oC), in five (5)
seconds at 140oF (60oC) and in thirty (30)
seconds at 130oF (54oC). In households where
there are children, physically challenged individuals
or elderly persons, mixing valves for point of use
are necessary as means of reducing the scalding
potential of hot water.
The gas control valve is factory-adjusted to its lowest temperature, approximately 70
o
F (21oC). When
the water heater is plugged in for the first time, the
gas control valve will start to heat the water to this
temperature. To avoid any unintentional changes in
the water temperature settings, the gas control valve
has a tamper resistant feature included for changing
the temperature setting. If you want to change this
setting for either cooler or warmer water, the following
steps are necessary:
2. If this is the first time that the control has been
used, the leftmost
green indicator will be
illuminated, indicating
the water temperature
setting of approximately
70°F (21°C). If the control
has been in operation
for some time, the water
temperature setting may
indicate a diffe rent temperature. See Figure 15 for an explanation of
what each of the temperature indicators mean.
To decrease the temperature, press and release
the COOLER button once. The temperature indicators will now display the new temperature
setting. Press and release the COOLER button until
you have reached the desired setting.
HOLDING DOWN THE BUTTON WILL NOT
CONTINUE TO LOWER THE SETTING. The
button must be pressed and released for each temperature change desired.
Figure 15
DISPLAY
FLASHING
1) “Wake up” the temperature indicators by holding
down both the COOLER and HOTTER temperature adjustment buttons at the same time for one
second (see Lighting Instructions). One or two
of the temperature indicators will light up. These
indicators will only remain on for 30 seconds, if
no further buttons are pressed. After 30 seconds,
the control will go back to “Sleep” mode and both
buttons will again have to be pressed to see the
water temperature setting. Release both of the
temperature adjustment buttons.
APPROXIMATE
TEMPERATURE
˚F (˚C)
70 (21)
(Vacation)
110 (43)
115 (46)
120 (49)
125 (52)
130 (54)
135 (57)
140 (60)
145 (63)
150 (66)
160 (71)
APPROXIMATE
TIME TO
CAUSE INJURY
N/A
5 Minutes
30 Seconds
5 Seconds
1.5 Seconds
Under 1 Second
To increase the temperature, press and release
the HOTTER button once. The temperature
indicators will now display the new temperature
setting. Press and release the HOTTER button until you have reached the desired setting.
HOLDING DOWN THE BUTTON WILL NOT
CONTINUE TO RAISE THE SETTING. The
button must be pressed and released for each
temperature change desired.
To maximize the efficiency of this water heater and
reduce the risk of scalding, it is recommended that
the gas control valve be set at the setting below the
large triangle
(«m»)
, which represents approximately
120°F (49°C).
3. When you have completed setting the control, wait 30 seconds to see that the temperature
indicators go off and the control enters “Sleep”
mode. ALL OF THE TEMPERATURE
INDICATORS WILL BE OFF DURING NORMAL
OPERATION. If at any time you see the indicators
on, there may be a system error and you should consult the Troubleshooting Guide of this document or
contact a trained service professional.
When hot water is drawn from the tank in frequent
short bursts, a condition known as “stacking” is
created. “Stacking” is the result of increased cycling of
the burner and can produce very hot water temperatures
at the hot water outlet. Always remember to check the
hot water coming out of any faucet with your hand before
use. This will reduce the risk of scalding-related injury.
17
Page 18
WARNING
WARNING
GENERAL MAINTENANCE
The gas control valve pictured in this manual
is equipped with a single-use type automatic high
temperature cutoff. Should the temperature of the
water exceed 193
cutoff will automatically shut off the gas supply to the
water heater. If this situation occurs, the gas control
valve must be replaced immediately by a qualified
service technician.
Should overheating occur or the gas supply fail
to shut off, close the gas supply manual shut-off
valve. Failure to follow this instruction can result in
property damage, personal injury or death.
Out of Fuel
If your water heater should run out of gas, proceed
as follows:
1) Unplug the power cord from the wall socket.
2) Close the gas supply manual shut-off valve.
3) Once the gas supply has been re-established,
proceed to the Lighting Instructions.
Housekeeping
Keep the area around the water heater clean and free of
dust, lint and dirt. Verify the combustion air intake holes,
at the bottom of the water heater, at least once every six
(6) months and vacuum up any dirt, as required. Make
sure that all of the minimum clearances to combustible
materials are being maintained.
DO NOT store or use gasoline or other flammable
vapours and liquids around the water heater.
DO NOT block or, in any way, restrict the flow of
fresh air through the combustion air intake holes at
the bottom of the water heater.
DO NOT put or store any objects on the top of the
water heater.
Failure to follow these instructions can result in
property damage, personal injury or death.
Safety System
This water heater is equipped with a safety system
that will shut it down in the event of a flammable
vapour incident. It is a safety feature that may prevent property damage, personal injury or death.
The safety system is comprised of two parts, a flammable vapour (FV) sensor and the flame arrestor.
The FV sensor is located on the front left bottom of
the exterior casing of the water heater. The FV sensor is protected from shock and contaminants by a
robust plastic cover. The function of the FV sensor is
to detect the presence of flammable vapours before
o
F (90oC), the high temperature
they enter the combustion chamber and ignite. If
the FV sensor detects the presence of flammable
vapours while the water heater is operating, the gas
control will switch to lock out mode and the water
heater will shut down. If the water heater is not operating when the flammable vapours are detected, the
control will switch to lock out mode and prevent the
water heater from lighting.
It is unlikely that there will ever be a flammable
vapour ignition in the combustion chamber as the
flammable vapours will have been detected by the
FV sensor. However, if flammable vapours manage
to enter the combustion chamber during main burner
operation and ignite, the flame arrestor technology
will prevent ignition of the vapours outside the
combustion chamber.
After a flammable vapour incident has occurred
and the flammable vapours have dissipated, the FV
sensor is designed to automatically reset itself. The
Intelli-Vent gas control, however, will have gone into
lock out mode and will need to be manually reset. A
qualified service technician must be called to determine if flammable vapours entered the combustion
chamber and ignited. In most instances, there will
not have been ignition of flammable vapours inside
the combustion chamber because the FV sensor
will have detected these vapours and shut down
the water heater. In this case, the Intelli-Vent
control can be reset and the water heater may
resume normal operation. On the other hand, if the
flammable vapours ignited inside the combustion
chamber, the water heater may need to be replaced.
The technician will be able to determine whether or
not the water heater needs to be replaced based on
the amount of flammable vapours that entered the
combustion chamber and the damage to the water
heater from the resulting fire.
Condensation
As moisture from the products of combustion comes
into contact with the cold surface of the inner tank, it
may condense. This situation will usually occur:
1) When the water heater is filled with cold water for
the first time.
2) If the water heater has been undersized.
3) When large amounts of hot water are drawn from
the water heater in a short period of time and the
refill water is very cold.
Due to the high-efficiency rating of this gas-fired
water heater, it may produce more condensation
than older models. Condensation forming on the
flue tube will drop on the burner making a “sizzling”
sound. This condition is not uncommon and must
never be misinterpreted as a leaking tank. It will disappear once the water becomes heated.
18
®
gas
Page 19
GENERAL MAINTENANCE
WARNING
Because of the large amounts of water that can
condense, it is very important that a drain pan be
installed under the water heater (refer to Figure
11). Under no circumstances is the manufacturer to be held liable for any water damage, in
connection with this water heater. If the problem
does not go away and water continues to drip after the
water heater has heated up, check all of the plumbing
connections to make sure they are not leaking.
Burner Ignitor Assembly
Every three (3) months, check the burner and ignitor
assembly. Remove the outer access door and look
through the sight glass to examine the flames. A soft
blue flame indicates proper gas combustion. A yellow
tipped flame indicates poor combustion. With a vacuum
cleaner, remove any dust, lint and dirt accumulation
on or around the combustion chamber and in the
combustion air intake holes.
Water Heater Tank
Drain a pail of water through the drain valve at least
once a year. This will remove excess sediment
from the bottom of the tank. This sediment, if allowed
to
accumulate, will reduce the efficiency and the life of
the tank.
can be obtained from the manufacturer.
The life expectancy of the water heater is reduced
where a water softener is introduced to fight hard
water, because the sodium salts added by a softener make this water extremely conductive. In these
conditions, the anode is consumed more rapidly and
should be verified every year.
In certain water conditions, the anode will react with
the water, producing discoloured or smelly water.
The most common complaint is hot water that smells
like rotten eggs. This phenomenon is the result of the
reaction between the anode and hydrogen sulfide
gas dissolved in the water, which occurs frequently in
well systems. This problem can usually be eliminated
or reduced by changing the anode to a type more
suitable for these conditions (aluminum anode) and
by chlorinating the water heater and plumbing system. If the problem persists, special filtration equipment may be required. Under no circumstances is
the anode to be removed from the water heater on a
permanent basis. Removal of the anode will lead
to premature failure of the water heater and
void the warranty.
Temperature and Pressure-Relief Valve
Manually operate the temperature and pressure-relief
valve at least once a year, standing clear of the outlet
to avoid being burned. Lift and release the operating
lever on the valve to make it operate freely. If, after
manually operating the valve, it fails to completely
reset itself and continues to discharge water, replace
it with a new one.
Venting System Inspection
The venting system must be thoroughly inspected
once a year. Check the area where the water heater
is located to make sure that there is enough clean
combustion and ventilation air. Remove any possible
obstructions that would prevent proper air circulation
and venting. Check the venting system to make sure
that all of the connections are securely fastened and
that all of the joints are properly sealed. If any part of
the venting system is damaged, it must be replaced
by a qualified service technician.
Anode
This water heater is equipped with an anode that
is designed to prolong the life of the glass-lined
tank. The anode is slowly consumed, protecting the
glass-lined tank from corrosion. The anode should
be checked every two (2) years. If more than half
of the anode has been consumed, it should be
replaced. Instructions on how to change the anode
Hydrogen gas can be produced in a hot water system that has not been used for a long period of time
(generally two [2] weeks or more). HYDROGEN GAS IS EXTREMELY FLAMMABLE. It is highly
recommended to open the hot water faucet in the
kitchen for several minutes before you use any
electrical appliances connected to the hot water
system, such as a dishwasher or washing machine.
If hydrogen gas is present, there will be an unusual
sound, such as air escaping through the pipe, as
the hot water faucet is opened. DO NOT smoke
or introduce an open flame near the faucet when it
is opened.
Draining the Water Heater
To completely drain the water heater:
1) Unplug the power cord from the wall socket.
2) Close the gas supply manual shut-off valve.
3) Close the cold water supply manual shut-off valve.
4) Connect one end of a garden hose to the water
heater drain valve and put the other next to a freeflowing drain.
5) Open the drain valve by inserting a flat head
screwdriver into the slot on the head of the drain valve
and turning the knob counterclockwise .
6) Open a hot water faucet to allow air into the system.
19
Page 20
GENERAL MAINTENANCE
Vacation
If you are planning a vacation or other prolonged
absence, it is highly recommended to shut off the
gas supply and the cold water supply to the water
heater. This will save energy, protect against property
damage in the event the water heater leaks and
prevent the build-up of hydrogen gas. If the water
heater and piping are exposed to freezing temperatures, they should both be drained.
Remember to check the water heater thoroughly
after it has been shut off for an extended period of
time before putting it back in operation. Make sure
that the water heater is completely full of water and
that the cold water supply manual shut-off valve is
open, before lighting the burner.
Getting Service for your Water Heater
If you are experiencing problems with your water
heater, follow these three easy steps:
1) Consult the Troubleshooting Guide contained
in this manual (see Page 22). It lists the
most common problems experienced with your
gas-fired water heater. The solutions you find
listed may provide a quick and simple solution
to your problem and save you time and money.
2) If the solution listed in the Troubleshooting Guide
does not solve the problem or if your particular problem is not listed in the guide, contact the installer of
the water heater or the local gas utility.
3) If you still cannot solve the problem, contact the
manufacturer’s Customer Service Department
by e-mail at gemco@gemcoinc.com or by
phone at 1-800-363-9354. To help serve you in
a quick and efficient manner, always have the
following information ready:
a) Model number.
b) Serial number.
c) Date of installation.
d) Where the water heater was purchased.
e) Complete address where the water heater
is installed.
f) A description of the problem.
20
Page 21
15
17
18
17
16
Complete blower assemblyfor model UG50-65(-59)
REPLACEMENT PARTS
Complete
blower assembly
for PV1 model
UG40/UG50/UG60
Disconnect the electrical power before servicing the water heater. Service should only be performed by a
qualified service technician. Failure to follow these instructions can result in personal injury or death.
CONDITION (code#) CAUSE REMEDY
An open earth ground circuit to the igni-
1
tion.
A wiring error or a high resistance to earth
2
ground.
1) Check that the earth ground conductor is properly connected at the fuse box or breaker panel
and the water heater.
2) Check that the grounding conductors on the water heater are properly connected and secure.
1) Check for proper connection of the line neutral and line hot wires.
2) Check that the water heater is securely connected to earth ground.
The pressure switch remained closed
3
longer than 5 seconds after the call for
heat began.
The pressure switch remained open
4
longer than 5 seconds after the power
venter was energized.
(see note at the bottom of the page)
The self diagnostic test has detected an
5
error in the hot surface ignitor circuit..
The maximum number of ignition retries
6
or recycles has been reached and the
system is in lockout .
The gas valve driver circuit.1) Turn off the power to the water heater for 10 seconds and then back on.
7
The internal microcomputer.1) Turn off the power to the water heater for 10 seconds and then back on.
8
The internal circuit..1) Turn off the power to the water heater for 10 seconds and then back on
9
Flame signal sensed out of proper
10
sequence.
1) The pressure switch wiring is incorrect.
2) The pressure switch is defective and must be replaced.
1) The pressure switch wiring is incorrect.
2) The pressure switch tubing is not connected correctly.
3) There are obstructions or restrictions in the water heater air intake or exhaust flue.
1) Check the wiring is correct and secure.
2) Disconnect the ignitor connector and measure the ignitor resistance with
an accurate ohmmeter between pins 1 and 2. Resistance should be
between 11.5 and 18.8 ohms. If the reading is incorrect, replace the hot surface ignitor.
3) If the above checks are good, replace the gas control valve.
1) Check if the gas supply is off or too low to operate.
2) Check the flame sensor rod to see that it is located properly and free from contamination.
Reposition the flame sensor rod or lightly clean it with an abrasive cloth.
3) The hot surface ignitor may not be positioned correctly. Reposition as necessary.
4) Check that the hot surface ignitor and flame sensor rod are wired correctly and in good working condition.
5) Low voltage to the water heater. Check and repair.
2) If the above step did not clear the error, replace the gas control valve.
2) If the above step did not clear the error, replace the gas control valve.
2) If the above step did not clear the error, replace the gas control valve.
1) Replace the gas control valve..
The high temperature thermal cut-off is
11
open.
One of the temperature adjust buttons is
12
stuck closed.
The water temperature sensor is either
13
open or short-circuited.
The self-diagnostic test found a problem
14
with the flammable vapour sensor.
The control detected the presence of
15
flammable vapours near the appliance
and entered lockout.
Note: Since the high limit switch on the blower is in series with the pressure switch, the problem could be that the high limit switch tripped.
1) Replace the gas control valve..
1) Make sure that there are no objects leaning against the front of the control.
2) Lightly press and release each of the buttons once.
3) If the above actions do not clear the error, the control will continue to regulate the water
temperature at the last setting, but you will not be able to change settings unless you replace
the gas control valve.
1) Check that all of the wiring is correct and that there are no open or shorted circuits.
2) If no wiring problems are found, the gas control valve must be replaced.
1) Check that all wiring is correct and that there are no open or shorted circuits.
2) If no wiring problems are found, the flammable vapour sensor must be replaced.
1) Identify the source of the flammable vapours and remove it from the area surrounding the
water heater
2) Contact a qualified service technician or the gas supplier to have the water heater inspected
immediately.
22
Page 23
TROUBLESHOOTING GUIDE
CONDITIONCAUSEREMEDY
The burner will not ignite.No gas.Check with gas utility company.
Dirt in gas line.Notify utility company. Install drip leg in gas line.
Combustion air intake holes blocked.With a vacuum cleaner, remove dirt, dust and lint.
Main burner line clogged.Clean. Check for source of trouble and correct.
Defective flame sensor.Replace with new flame sensor.
Defective gas control valve.Replace with new gas control valve.
Gas control valve set too low.Turn temperature dial to desired temperature.
Heater installed in a confined area.Provide fresh air ventilation.
The burner flame floats and
lifts off ports.
Vacuum switch located in the
blower assembly remain open.
The burner flame is yellow
and lazy.
The burner flame is too high.Insufficient secondary air.Provide fresh air ventilation.
The flame burns at the orifice.Low gas pressure.Check with gas utility company.
High operating costs.Gas control valve set too high.Turn temperature dial to desired temperature.
Insufficient hot water.Low gas pressure.Check with gas utility company.
Slow hot water recovery.Insufficient secondary air.Provide fresh air ventilation.
High gas pressure.Check with gas utility company.
Orifice too large.Replace with correct orifice.
Flue clogged.Clean. Check for source of trouble and correct.
Combustion air intake holes blocked.With a vacuum cleaner, remove dirt, dust and lint.
Heater installed in a confined area.Provide fresh air ventilation.
Cold drafts (downdraft).Locate source and correct.
One of the potential causes is excessive
dirt, dust and other debris accumulation
on the flame arrestor and on the blower
impeller.
Insufficient secondary air.Provide fresh air ventilation.
Flue clogged.Clean. Check for source of trouble and correct.
Combustion air intake holes blocked.With a vacuum cleaner, remove dirt, dust and lint.
Main burner line clogged.Clean. Check for source of trouble and correct.
Heater installed in a confined area.Provide fresh air ventilation.
Orifice too large.Replace with correct orifice.
Defective gas control valve.Replace with new gas control valve.
Defective gas control valve.Replace with new gas control valve.
Sediment or lime in tank.Drain. Check to see if water treatment is necessary.
Water heater is undersized.Install size of water heater that meets demand.
Wrong piping connections.Correct piping, dip tube must be in cold inlet.
Leaking faucets.Repair faucets.
Gas leaks.Check with gas utility company. Repair at once.
Wasted hot water.Advise consumer.
Long runs or exposed piping.Insulate piping.
Hot water piping on outside wall.Insulate piping.
Wrong piping connections.Correct piping, dip tube must be in cold inlet.
Sediment or lime in tank.Drain. Check to see if water treatment is necessary.
Water heater is undersized.Install the size of water heater that meets the demand.
Gas control valve set too low.Turn temperature knob to desired temperature.
Leaking faucets.Repair faucets.
Wasted hot water.Advise consumer.
Long runs or exposed piping.Insulate piping.
Hot water piping on outside wall.Insulate piping.
Low gas pressure.Check with gas utility company.
Gas control valve set too low.Turn temperature dial to desired temperature.
Improper calibration.Replace gas control valve.
Flue clogged.Clean. Check for source of trouble and correct.
Water heater is undersized.Install size of water heater that meets demand.
Wrong piping connection.Correct piping, dip tube must be in cold inlet.
Wasted hot water.Advise consumer.
Clean the flame arrestor in the combustion chamber
using a stiff brush, compressed air and/or a vacuum
cleaner. In no circumstances, the blower assembly
should be removed for cleaning or replaced without contacting the manufacturer.
23
Page 24
TROUBLESHOOTING GUIDE
CONDITIONCAUSEREMEDY
Leaking water.Poorly sealed, hot or cold water connec-
tions, gas control valve threads, relief
valve or drain valve.
Leakage from plumbing system or other
appliances.
Condensation.Refer to Condensation.
Water drips from the relief
valve.
The gas control valve fails
to shut-off.
Condensation.Water heater filled for the first time.Let water heater warm up. Problem should go away. If it
Combustion odours.Insufficient secondary air.Provide fresh air ventilation.
Smoking and carbon formation
(sooting).
Smelly water.High sulfate or mineral content in water.Change magnesium anode to an aluminum anode and
The access door temperature
high limit switch is tripping.
Heater stacking.Lower gas control valve setting.
Excessive water pressure.Install a pressure-reducing valve.
Thermal expansion in a closed water sys-
tem.
Improperly seated valve.Check relief valve works properly and replace, if neces-
Defective gas control valve.Replace with new gas control valve.
Improper calibration.Replace gas control valve.
Heavy draws of hot water with Let water heater warm up. Problem should go away.
very cold refill water.If it persists, check all plumbing connections for leaks.
Water heater is undersized.Install size of water heater that meets demand.
Heater installed in a confined area.Provide fresh air ventilation.
Flue clogged.Clean. Check for source of trouble and correct.
Insufficient secondary air.Provide fresh air ventilation.
Low gas pressure.Check with gas utility company.
Burner flame yellow, lazy.Refer to The burner flame is yellow and lazy.
Flue clogged.Clean. Check for source of trouble and correct.
Defective gas control valve.Replace with new gas control valve.
Heater installed in a confined area.Provide fresh air ventilation.
Not enough draft from the venting
system.
Not enough fresh air for the combustion.Supply make-up air. Refer to installation instructions pro-
Ambiant air temperature is too high.Reduce ambiant air temperature.
Excessive dirt, dust or other debris accu-
mulation on the flame arrestor.
Tighten threaded connections.
Inspect plumbing system and other appliances.
Install an expansion tank.
sary.
persists, check all plumbing connections for leaks.
bleach tank.
Check for any obstruction in the chimney. Ensure that the
chimney is sized and installed according to installation
instructions provided in this manual.
vided in this manual.
Clean the flame arrestor in the combustion chamber using
a stiff brush, compressed air and/or a vacuum cleaner.