The Signet 3519 Flow Wet-Tap Valve provides a fast method of removing the sensor
from the pipe under speci ed operating pressures. The PVC and stainless steel
design of the Wet-Tap makes it resistant to corrosion and chemical attack by acids,
alkalies, salt, and a number of other harsh chemicals.
The Signet 3519 Wet-Tap Valve mounts directly onto standard Signet installation
ttings. The 3519 Wet-Tap consists of a ange and support plate that threads onto the
pipe tting insert, and a PVC ball valve through which an extended length sensor is
inserted into the pipe�
NOTE: The ball valve union ends are glued and not accessible for servicing
Dimensions
Total minimum clearance
for sensor insertion and
removal:
Operating Instructions
Pipe SizeClearance
Inch
1/2 to 415 to 10073729
5 to 8125 to 20076230
10 and up250 and up81332
Metric
DN (mm)mm Inch
English
• English
• Deutsch
• Français
• Español
H-Dimensions
The plastic sensor insert in the
Weldolet tting MUST be removed
before the welding process. When
reinstalled, it is important that the
insert be threaded to the proper
height ("H" dimension).
Refer to your local Georg Fischer Sales ofce for the most
current warranty statement.
All warranty and non-warranty repairs being returned must
include a fully completed Service Form and goods must be
returned to your local GF Sales ofce or distributor.
Product returned without a Service Form may not be
warranty replaced or repaired.
Signet products with limited shelf-life (e.g. pH, ORP, chlorine
electrodes, calibration solutions; e.g. pH buffers, turbidity
standards or other solutions) are warranted out of box but not
warranted against any damage, due to process or application
failures (e.g. high temperature,
mishandling (e.g. broken glass,
chemical poisoning, dry-out) or
damaged membrane, freezing
and/or extreme temperatures).
Product Registration
Thank you for purchasing the Signet line of Georg Fischer
measurement products.
If you would like to register your product(s), you can now
register online in one of the following ways:
• Visit our website www.gfsignet.com.
Under Service and Support click on
Product Registration Form
• If this is a pdf manual (digital copy), click here
Manufactured under ISO 9001 for Quality, ISO 14001 for
Environmental Management and OHSAS 18001 for Occupational
Health and Safety.
CE
RoHS Compliant
China RoHS(Go to www.gfsignet.com for details)
120
Fluid Conditions
Pressure/Temperature Ratings:
• 7 bar max. @ 20 °C
(100 psi max. @ 68 °F)
• 1.4 bar max. @ 66 °C
(20 psi max. @ 150 °F)
8.3
110
7.6
100
6.9
90
6.2
80
5.5
70
4.8
60
4.1
50
3.4
40
2.8
30
2.1
20
1.4
10
.7
0
-2002040 6080
°C
3519 Wet-Tap
Safety Information
1. The 3519 Flow Wet-Tap Valve may only be installed into, and
removed from, non-pressurized systems (0 psig).
2. The pressure must be reduced to 172.37 kPa (25 psi) when
removing or installing the sensor and must maintain
172.37 kPa (25 psi) or lower while the sensor is removed.
3. Stay clear of sensor stroke area and safety cable during
sensor removal.
4. Conrm chemical compatibility before use.
5. Do not exceed maximum temperature/pressure specications.
6. Wear safety goggles or faceshield during installation/service.
7. Do not alter product construction.
Failure to follow safety precautions may result in severe
personal injury!
2
Caution / Warning / Danger
Indicates a potential hazard. Failure to follow all warnings
may lead to equipment damage, injury, or death
Personal Protective Equipment (PPE)
Always utilize the most appropriate PPE during
installation and service of Signet products.
Pressurized System Warning
Sensor may be under pressure, take caution to vent
system prior to installation or removal. Failure to do so
may result in equipment damage and/or serious injury.
Hand Tighten Only
Overtightening may permanently damage product threads
and lead to failure of the retaining nut.
Do Not Use Tools
Use of tool(s) may damage product beyond repair and
potentially void product warranty.
Signet 3519 Flow Wet-Tap Valve
Signet Fittings
TypeDescription
Plastic tees• 0.5 in. to 4 in. versions
• PVC or CPVC
PVC Glue-on
Saddles
PVC Clamp-on
Saddles
Iron Strap-on
saddles
Carbon Steel &
Stainless Steel
Threaded Tees
Carbon steel & Stainless
Steel Weld-on Weldolets
Metric PVC-U
Saddle
Metric Union
Fitting
Consult the Signet Measurement and instrumentation Catalog for a
complete listing of installation ttings.
• 10 in. and 12 in. only
• Cut 2.5 in. hole in pipe
• Weld in place using solvent
cement
• 2 in. to 4 in., cut 1.5 inch hole
in pipe
• 6 in. to 8 in., cut 2.25 in. hole
in pipe
• 2 in. to 4 in., cut 1.5 inch hole
in pipe
• Over 4 inch, cut 2.25 inch hole
in pipe
• Special order 14 in. to 36 in.
• 0.5 in. to 2 in. versions
• 2 in. to 4 in., cut 1.5 inch hole
in pipe
• Over 4 inch, cut 2.25 inch hole
in pipe
• See installation section
for details
• For pipes DN 65mm to 200 mm
• Requires a 38 mm diam. hole in
the pipe
• For pipes from
DN 15 mm to 50 mm
PP or PVDF
Page 3
black conduit
cap
capuchon de
conduit noir
PROCESS PIPE
(TOP VIEW)
direction of flow
sensor bale
TUYAU DU FLUIDEDE L'OPÉRATION (VUE DU DESSUS)
Sens de l'ècoulement
Anse du capteur
clamps
safety
cable
Hex
bolts
(6 ea.)
OPEN
Colliers deretenue
câble de sécurité
OUVERT
Boulonshex. (6)
P3 sensor = 197 mm (7.75 inches)
P4 sensor = 229 mm (9 inches)
P5 sensor = 305 mm (12 inches)
SENSOR
STROKE AREA
Capteur P3 = 197 mm (7,75 pouces)Capteur P4 = 229 mm (9 pouces)Capteur P5 = 305 mm (12 pouces)
ZONE DE COURSE
DU CAPTEUR
O-rings
brackets
CLOSED
Supports
Joints toriques
FERMÉ
Wet-Tap Valve Installation
Flow Sensor Insertion
The Signet 3519 Flow Wet-Tap Assembly attaches directly
to Signet installation ttings to enable ow sensor removal
without system shutdown. It consists of a ange and support
plate which thread onto the pipe tting insert, and a PVC
ball valve through which an extended length ow sensor is
inserted into the pipe�
CAUTION: The 3519 Flow Wet-Tap Valve may
only be installed into, and removed from,
non-pressurized systems -0.22 bar (0 psig).
Procedure
1� Remove six hex nuts and bolts from the Wet-Tap ange.
Separate the support plate from the main assembly. Be
sure that the Viton O-ring is properly seated in the support
plate groove�
2. Apply sealant to the pipe tting insert threads to prevent
leaks.To eliminate any leakage, the valve can be sealed
to the tting using one of these two methods:
1. Use a silicone RTV such as “GE Sealants and
Adhesives Silicone II”.
2. Use a PVC cement such as Christy’s “Red Hot Blue
Glue” (for PVC ttings) or a similar PVC pipe cement.
NOTE: This will permanently bond the valve to the
installation tting and the fast drying period will not
allow for errors in the installation process.
3� Screw support plate onto pipe tting insert (O-ring side
facing up). It must be threaded completely down until the
notches at the top of the pipe tting insert are exposed.
4. Mount the main Wet-Tap Assembly on the support plate.
Make certain the alignment keys on the ange mate with
the notches on the pipe tting insert.
5� Loosen support plate (holding the main Wet-Tap
Assembly in place) until it resists slightly. Loosen an
additional ¼-turn to seat O-ring.
6� Replace the six hex nuts and bolts to secure the Wet-Tap
Assembly in place. Adjust the support plate position as
necessary to align screws.
7� Check the pressure relief plug on Wet-Tap Assembly. It
must be closed nger tight to prevent leaks.
8� Close ball valve by turning the handle to the fully closed
position (parallel with pipe).
1-1/4 X 11-1/2 in.
NPSM thread
Valve handle
(shown in
open position)
Viton O-ring
Support plate
Align notch and key
under wet tap flange
parallel with pipe.
Key
Pressure
relief plug
Allen bolts
and hex nuts
Sealant
1� Lubricate O-rings with a non-petroleum based, viscous
lubricant (grease) compatible with the system.
2. Carefully insert the sensor into the 3519 valve assembly
until the rst two O-rings seat inside the bore (Figure 1).
• Do not damage the rotor on closed ball valve.
3� Using the clamps, attach the sensor safety cable to the
3519 assembly brackets (hand tighten only).
4. Pull the ow sensor upward to remove slack in the safety
cables (Figure 2).
WARNING: Safety cables are factory installed
at precise length� DO NOT attempt to service or
replace safety cables.
System pressure must be 172.37 kPa (25 psi) or
less prior to sensor insertion or removal.
5� Open the ball valve (Figure 2).
6� Using a twisting motion, push the ow sensor into the
3519 assembly.
• Turn the sensor so the arrows on the black conduit cap
point in the direction of ow.
• When properly aligned, the sensor bale will be parallel
with the pipe (Figure 3).
Figure 1
Figure 2
Figure 3
3
Signet 3519 Flow Wet-Tap Valve
Page 4
sensor
bale
sensor
cap
tab
black
conduit
cap
capuchon
du capteur
capuchon
de conduit noir
notch
Anse du
capteur
Languette
Encoche
Flow Sensor Insertion continued
Hand tighten only!
7� Align the tabs under the sensor cap with the notches on the tting insert and tighten the
sensor cap (Figure 4).
HAND TIGHTEN ONLY.
DO NOT use any tools that may damage plastic parts.
Flow Sensor Removal
WARNING: System pressure must be 172.37 kPa (25 psi) or less prior to ow
sensor insertion or removal. Stay clear of sensor stroke area and safety
cable during sensor removal.
Check the six (6) Hex bolts (Figure 2) prior to unscrewing the sensor cap.
If bolts are loose, tighten securely before proceeding.
1� Unscrew the sensor cap. (DO NOT use any tools that may damage plastic parts.)
2. Carefully pull the ow sensor upward with a twisting motion until the safety lanyards are fully extended (Figure 2).
3� Close the ball valve (Figure 1).
4. Loosen the relief plug to depressurize the sensor area.
5� Disconnect the sensor safety cable clamps from the 3519 assembly brackets.
6� The sensor can now be safely removed.
Figure 4
Ordering Information
Part NumberCodeDescription
3-3519159 000 757PVC Wet-Tap valve (sensor not included)
P51530-P3198 840 310Polypro extended length paddlewheel sensor (0.5 in. to 4 in.)
P51530-P4198 840 311Polypro extended length paddlewheel sensor (5 in. to 8 in.)
P51530-P5198 840 312Polypro extended length paddlewheel sensor (10 in. to 36 in.)
3-2536-P3159 000 758Polypro extended length low ow paddlewheel sensor (0.5 in. to 4 in.)
3-2536-P4159 000 759Polypro extended length low ow paddlewheel sensor (5 in. to 8 in.)
3-2536-P5159 000 760Polypro extended length low ow paddlewheel sensor (10 in. to 36 in.)