Material No. 132916 • Rev. 01-2009 • Drawing No. 35207-9-0955
GEZE SecuLogic Emergency Exit System
TZ320 Door Control Unit
Installation And Commissioning Instructions
With Connection Diagram
GB
Document information
Document information
Document identification
Title: Installation And Commissioning Instructions With Connection Diagram GEZE SecuLogic Emergency
Exit System
TZ320 Door Control Unit
Material number: 132916
Revision state:01-2009
7.4Service menu - service terminal ST220 ..........................................................................82
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
3
In this document
1In this document
This instruction describes the installation and commissioning as well as the connection of
GEZE door control unit.
1.1Product description
The GEZE door control unit is an integral part of SecuLogic escape route system and
serves for the control and monitor of electric interlocked emergency exits.
Furthermore, it offers a wide range of gateways to other products as well as systems.
Revolving door drive systems as well as motor locks, signalling device, e. t. c. can be
connected. Also, signal messages on superordinate factory master control systems or the
central visualisation can be forwarded via PC or tableau.
Intelligent functions can be realised between the door control units via the GEZE bus
system, e.
alarm systems.
g. sluice functions or the switching on and forwarding of fire alarm and burglar
1.2Other documents
Data sheets with technical data are included in the delivery of the components
respectively. You will find these data sheets and other documents in the internet by visiting
the website www.geze.de/SecuLogic.
1.3Symbols and markings
Some information in this document are highlighted as follows:
Instructions
Requirements:As a prerequisite, there are conditions that must be fulfilled so that the subsequent action
steps can be carried out.
Here is something to do. This symbol indicates an instruction that contains only an
action step or action steps in warning notices, in which there is no particular sequence.
1. Multiple step instructions are marked by successive numbers.
Results of an action are marked by this arrow.
Important information
Text marked like this informs about special features.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
4
In this document
EltVTR
Safety instructions
You will find basic safety instructions in a separate section (see page 7).
Section related safety instructions are marked as follows:
DANGER
A note on safety refers to dangers, their causes and consequences.
Here are measures to avoid danger.
Section related safety instructions are divided into four danger levels, which are identified
by the signal word:
Signal wordMeaning
DANGERWarns against an imminent danger that leads to death or fatal injuries if it is
not avoided
WARNINGWarns against danger that can lead to death or fatal injuries if it is not avoided
CAUTIONWarns against danger that can lead to fairly serious or mild injuries
NOTEWarns against material damages
Standards conformity
Marking to show that the product does not comply with the specified standard,
here "guidelines on electric locking systems of doors in the escape routes"
(EltVTR)
1.4Abbreviations
In this documentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungAnschlussplanAnhang
AbbreviationSpecification
TZ320Door control unit in bus technique
TZ322Door control unit in the bus technique without emergency button
TZ323Door control unit in the bus technique, rotated 180°
TZ320BDoor control unit with illuminated emergency exit shield
TZ320SDoor control unit with key-operated push button (connection via ribbon cable)
TZ320NDoor control unit with integrated mains supply circuit
TZ320BSNDoor control unit with illuminated emergency exit shield, key-operated push
button and integrated mains supply circuit
TZ320BSDoor control unit with illuminated emergency exit shield and key-operated
push button
TZ320SNDoor control unit with key-operated push button and integrated mains supply
circuit
APOn-wall
UPIn-wall
BMAFire alarm system
GMAHazard alarm system
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
5
In this document
AbbreviationSpecification
RWASmoke and heat venting system
GLTBuilding control
EMABurglar alarm system
ZSUTime-switch
KZFShort-term release
NOPotential-free closer contact (normal open)
NCPotential-free opener contact (normal closed)
NTMains supply circuit
SLE220Signal light
SLH220Alarm horn
BLE220Flashing light
SHB220Signal horn with flashing light
SCT320Key-operated push button, single-pole reverse push button (two closers)
SCT221Key-operated push button, single-pole push button (closer), expandable to
single-pole reverse push button (two closers)
SCT222Key-operated push button with LED display, single-pole reverse push button
(two closers)
MLSMotor lock
HLSHandle lock
TST320TZ control unit
NSA220Emergency button
KL220Terminal box
FTÖEmergency exit opener
FSFalling lock
MA500Holding magnet
TE220Tableau unit
VAT220Visualisation software
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
6
Safety and liability
2Safety and liability
The GEZE door control unit was designed according to the state-of-the-art technology and
the accepted safety-related rules. However, there might be danger during installation and
use. Therefore, pay attention to the following instructions.
2.1Basic safety instructions
The installation, commissioning and repairs must be carried out exclusively by an
electrician or an expert authorised by GEZE
Use only GEZE original parts for repair work
GEZE assumes no liability for damages resulting from unauthorised changes to the
system
Primary safety measures take place on site
The standards VDE 0100 and VDE 0815 must be observed during cable routeing
In order to avoid unauthorised inspections, do not leave the key in the key-operated
push button
An expert must check the doors with electric locking mechanism in the escape routes
once a year. The expert is to issue a certificate on the in-service inspection, which the
operator of the building supervisory board has to show on demand. Within the scope of
a maintenance contract, the checking can be carried out by a GEZE service technician
or a professional organisation authorised by GEZE.
Furthermore, GEZE recommends that the operator inspects the escape route system
monthly for identifiable damages and defects. Such damages and defects, if available,
must be repaired immediately by a GEZE service technician or a professional
organisation authorised by GEZE.
Intended use
The GEZE door control unit is designed to control and monitor electric-locked emergency
exits. External products may only be integrated after consulting GEZE.
Contrary to the intended use
Zu diesem DokumentSafety and liabilityInstallation und MontageInbetriebnahmeBedienungAnschlussplanAnhang
The connection of products which were not expressly approved for use by GEZE is
contrary to the intended purpose.
2.2Target group and qualification
The installation, assembly, commissioning and repairs must be carried out only by a
trained electrician or an expert authorised by GEZE.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
7
Installation and assembly
1
7
6
2
3
5
4
3Installation and assembly
DANGER
Danger of electrocution
The installation and assembly must be carried out exclusively by an electrician or an
expert authorised by GEZE
Check that the cables are disconnected before the installation.
3.1Requirements
Cable laying available in accordance with GEZE cable diagram
Circuit breakers as the primary cutting off plate cylinder on the mains-side
Compliance with the standards VDE 0100 and VDE 0815 for the cable routeing
Sabotage secured cable routeing according to VDE 0833 (on-wall cables in the steel
tube)
For the type of in-wall plug sockets installed near the door (base range 62.5 mm) with an
installation height top of floor of 850
emergency button
mm up to a maximum of 1200 mm for the
3.2Install in-wall door control unit
These instructions describe the installation of an in-wall door control unit using the
example of TZ320BSN, as recommended by GEZE.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
8
Installation and assembly
1. Pass the power lead and ribbon cables through the in-wall plug socket.
2. Connect cable to the terminal strips in accordance with the connection diagram.
62,5
60
71
Zu diesem DokumentSicherheit und VerantwortungInstallation and assemblyInbetriebnahmeBedienungAnschlussplanAnhang
850 - 1200
71
3. Connect and secure the mains supply circuit.
4. Connect the door control system with the key-operated push button and the keyoperated push button with the emergency exit shield using the ribbon cable.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
9
Installation and assembly
A
B
C
D
C
B
D
A
5. Plug the terminal strips to the circuit board of the door control system.
6. Set jumper in accordance with the connection diagram (see page 44).
7. Install the door control unit.
8. Check the functional capability.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
10
Installation and assembly
3.3Install the on-wall door control unit
These instructions describe the installation of an on-wall door control unit using the
example of TZ320BSN, as recommended by GEZE.
1
2
[1]TZ320BSN door control unit
[2]TZ323BSN door control unit
[3]Terminal strips
1. Open the housing.
Zu diesem DokumentSicherheit und VerantwortungInstallation and assemblyInbetriebnahmeBedienungAnschlussplanAnhang
3
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
11
Installation and assembly
850 - 1200
2. Install the wall bracket close to the door (height of the emergency button: 850 mm 1200
mm top of floor).
3. Unscrew the covering of the mains supply.
4. Connect the 230-V circuit to the luster terminal of the mains supply circuit and screw
the covering.
5. Connect cable to the terminal strips in accordance with the connection diagram (see
page 44).
6. Plug the terminal strips to the circuit board of the door control system.
7. Set jumper in accordance with the connection diagram.
8. Secure loose cabling with cable clips.
9. Hook up the housing and bolt.
10.Insert the covering of the emergency button.
11.Check the functional capability.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
12
Installation and assembly
3.4Change the lock cylinder
The lock cylinder must meet the following standards:
Profile half cylinder 40 mm (30/10)
8-fold adjustable
1. Set the system on the service mode if it is in operation.
2. Dismantle the housing from the wall bracket.
3. Unscrew the key-operated push button
4. Unscrew the cylinder head screw and dismantle the lock cylinder.
Zu diesem DokumentSicherheit und VerantwortungInstallation and assemblyInbetriebnahmeBedienungAnschlussplanAnhang
5. Change the lock cylinder.
6. Insert a new lock cylinder and fasten with cylinder head screw.
7. Install the door control unit in the inverse order.
8. Check the functional capability.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
13
Commissioning
1
2
3
4Commissioning
4.1Requirement
Before the first commissioning of doors with electric locking mechanisms in the escape
routes, correlation with verification of suitability is to be confirmed by means of a certificate
issued by the manufacturer. Likewise, an expert is to establish if the electric locking
mechanism is installed properly and if it is operational
4.2Service mode
The service mode must be engaged in order to set different parameters on the door control
unit.
4.2.1Switch on the service mode
Requirements:There is no alarm.
The burglar alarm system is disconnected.
(see page 77).
1. Insert the key into the lock of the key-operated push button.
2. Turn the key left and hold for approximately ten seconds.
LED 2 flashes green. LEDs 1 and 3 do not flash.
4.2.2Switch off the service mode
Do not make adjustment nor go to the service menu for three minutes
Select end of service mode.
Door control unit is in normal state again.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
14
Commissioning
ON
X
21
4.3Connect the service terminal ST220 with the door control
unit
The service terminal is connected with the door control unit via an infrared interface.
[1]Service terminal ST220
[2]Infrared interface on TZ320
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageCommissioningBedienungAnschlussplanAnhang
Service terminal ST220
Button DescriptionFunction
ON buttonSwitch-on
ESC button
UP button
DOWN
button
RETURN
button
Go back one menu level,
without taking on a new value
Go one line upward
or increase the numerical value
Go one line downward
or reduce the numerical value
Select
or take on a new value
1. Before covering the control unit, hold the service terminal and press the ON button for
approximately one second.
The service terminal is switched on.
2. Press the ESC button.
The first level of the service menu is displayed.
4.4Switch off the service terminal
Do not press any button for two minutes.
The service terminal is switched off.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
In the service menu system setup > clock/date select the corresponding menu
item and set the values.
The adjusted value is displayed on the upper display row of the service terminal.
If several door control units are connected with each other via the bus, the adjusted
data of all connected door control units are transferred.
4.5.2Set language
For the service menu, the following languages are available in the service terminal:
German (default setting)
English
In the service menu, select system setup > language > choice and set the
language.
The service menu is displayed in the selected language.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
16
Commissioning
4.6Door control unit settings
4.6.1Set short-term unlock
Menu "TZ parameter > short-term unlock"
Menu itemSubmenuChoice
DurationChange value0s - infinite (10s)
Abort–Yes
Post trigger–
Duration: Duration of the short-term unlock
Abort: Exiting the short-term unlock by closing the door
Post trigger: Extending the short-term unlock through renewed short-term unlock
If Abort is set on No, the duration of the short-term unlock must not be set on
infinite.
(Default setting)
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageCommissioningBedienungAnschlussplanAnhang
No
(Yes)
In the service menu, set TZ parameter > short-term unlock and make
adjustments for corresponding menu items.
The selected value is displayed on the upper display row of the service terminal.
In order to avoid an inadvertent continuous unlocking in highly frequented doors,
use an external control device for the short-term release.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
Pre-alarm: An acoustic signal that starts after a short-term release time elapses if the
door was not closed. The pre-alarm time ends if the door is closed. If the door is not
closed, the alarm is triggered off if the set time elapses
Alarm: An acoustic signal on the door control unit for the duration of the set alarm time.
Thereafter, there is a two-minute break before the alarm rings out again
Buzzer: Volume and sound of the alarm types
1. In the service menu, set TZ parameter > alarm setup.
2. Set times for pre-alarm and alarm.
3. Set buzzer for alarm, pre-alarm and sabotage.
The selected value is displayed on the upper display row of the service terminal.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
18
Commissioning
4.6.3Set inputs
Activities
The inputs of the door control units and terminal boxs can be set on the following activities:
ActivitySpecification
High-activeThe input is active if the input is closed (closer). 24 V is pending in the input
Low-activeThe input is active if the input is open (opener). 0 V is pending in the input
DisabledThe input is inactive
Set activity for the door control unit
Pay attention to the stepping sequence if an input is adjusted from high-active
to low-active or vice versa.
1. Set input on disabled.
2. Connect wires.
3. Set input on low-active or high-active.
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageCommissioningBedienungAnschlussplanAnhang
1. In the service menu, set TZ parameter > custom inputs.
2. For the corresponding input numbers, choose TZ input 1-3 >
activity TZ1-3 > choice and select activity (default setting: high-active).
The selected value is displayed on the upper display row of the service terminal.
Set activity for the terminal box
1. In the service menu, select system environment > KL > custom inputs.
2. For the corresponding input number, choose KL input 1-4 > activity KL1-4 >
choice and select activity (default setting: high-active).
The selected value is displayed on the upper display row of the service terminal.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
19
Commissioning
Configurations
The inputs of the door control units and terminal boxs can be set on the following
configurations:
ConfigurationSpecificationInterpretation
Sabotage ext.The signal message sabotage is triggered off,
sabotage alarm follows
UnlockThe system goes to the state unlockedFlank
LockThe system goes to the state lockedFlank
Short-term unlockThe system goes to the state short-term
unlocked
Burglar alarm
system
Time-switchThe signal message time-switch is activeLevel
Fire alarm system The signal message fire alarm system is activeLevel
Motor lockInput for lock with the motor lock for door control
HandleInput for handle contacts for triggering the pre-
Public holidayTime-switch is switched off in an active inputLevel
The signal message burglar alarm system is active Level
unit control or acknowledgement of alarms
alarm when the handle is actuated
Level
Flank
Level
Level
Level: A permanent signal is active
Flank: An impulse is active
Set configuration for the door control unit
1. In the service menu, set TZ parameter > custom inputs.
2. For the corresponding input number, choose TZ input 1-3 > configuration TZ1-3 > choice and select configuration.
The selected value is displayed on the upper display row of the service terminal.
Set configuration for the terminal box
1. In the service menu, select system environment > KL > custom inputs.
2. For the corresponding input numbers, choose KL input 1-4 >configuration KL1-4 > choice and select configuration.
The selected value is displayed on the upper display row of the service terminal.
4.6.4Set outputs
Contacts
The outputs of the door control units and terminal boxs can be set on the following
contacts:
ContactParameterSpecification
CloserNOContact closes
OpenerNCContact opens
Disabled–The output is not controlled
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
20
Commissioning
Set contact for the door control unit
1. In the service menu, set TZ parameter > custom outputs.
2. For the corresponding output number, choose TZ output 1-2 > contact TZ1-2 > choice and select contact (default setting: closer).
The selected value is displayed on the upper display row of the service terminal.
Set contact for the terminal box
1. In the service menu, select system environment > KL > custom outputs.
2. For the corresponding output number, choose KL output 1-6 > contact KL1-6 > choice and select contact (default setting: closer).
The selected value is displayed on the upper display row of the service terminal.
Configurations
The outputs of TZ320 door control unit as well as the outputs 1 + 2 of KL220 terminal box
are two-pole outputs. The outputs 3
set on
closer, the terminals have the function described in the connection diagram. The
terminals with lower numbers are the close contacts
higher numbers are the open contacts
If these outputs are adjusted to opener, the function of the terminals changes. NO
becomes NC and NC becomes NO.
- 6 of KL220 are change-over contacts. If the output is
NO respectively and the terminals with
NC.
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageCommissioningBedienungAnschlussplanAnhang
For example: Output 4 of KL220
Setting closer30 = NO 31 = COM 32 = NC
Setting opener30 = NC 31 = COM 32 = NO
The outputs of the door control units and terminal boxs can be set on the following
configurations:
ConfigurationParameterSpecification
Door stateCloser NOContact closed, if the door is closed
Opener NCContact closed, if the door is open
OM controlCloser NOContact closed, if the door control unit is unlocked
(permanent unlock not in short-term release)
Opener NCContact closed, if the door control unit is not unlocked
Drive controlCloser NOContact closes for 3 seconds, if short-term release was
actuated (also if the system unlocks).
Contact closed during release or emergency unlock,
until the alarm stops
Opener NCLike NO, however, contact opens
AlarmCloser NOContact closes in the event of all alarms except pre-
alarm
Opener NCContact opens in the event of all alarms except pre-
alarm
ReleaseCloser NOContact closes when the emergency button on TZ320 is
actuated and during indirect release
Opener NCContact opens when the emergency button on TZ320 is
actuated and during indirect release
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
21
Commissioning
ConfigurationParameterSpecification
Release directCloser NOContact closes when the emergency button on TZ320 is
actuated
Opener NCContact opens when the emergency button on TZ320 is
actuated
Release indirectCloser NOContact closes during indirect release
Opener NCContact opens during indirect release
Door alarmCloser NOContact closes when the door hold-open time is over
stepped, the pre-alarm has elapsed or the door is
broken up
Opener NCContact opens when the door hold-open time is over
stepped, the pre-alarm has elapsed or the door is
broken up
Sabotage alarmCloser NOContact closes, if an input sabotage is active or
sabotage contact on TZ320, KL220, SCT320 or TT220
is actuated
Opener NCLike NO, however, contact opens
Pre-alarmCloser NOContact closes for the set time when the door hold-open
time is over stepped
Opener NCContact opens for the set time when the door hold-open
time is over stepped
System faultCloser NOContact closes during system fault
Opener NCContact opens during system fault
Traffic light red
(only in an active
sluice function)
Traffic light green
(only in an active
sluice function)
Door-o. op.cur.Closer NOContact closes for 3 seconds, if short-term release was
LockedCloser NOContact is closed, if the system is locked
Emergency buttonCloser NOContact is closed, as long as the emergency button on
Short-term unlockCloser NOContact is closed, if the system is short-term unlocked
Closer NOContact is closed, if the door above the sluice is locked
Opener NCContact is closed, if the door above the sluice is not
locked
Closer NOContact is closed, if the door above the sluice is not
locked
Opener NCContact is closed, if the door above the sluice is locked
actuated (also if the system unlocks).
Opener NCLike NO, however, contact opens
Opener NCContact is closed, if the system is unlocked or short-
term unlocked
TZ320 is actuated
Opener NCContact is opened, as long as the emergency button on
TZ320 is actuated
Opener NCContact is opened, if the system is short-term unlocked
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
22
Commissioning
ConfigurationParameterSpecification
Collective alarmCloser NOContact closes, if alarm is triggered off in one door
control unit on the bus line (apart from pre-alarm)
Opener NCContact opens, if alarm is triggered off in one door
control unit on the bus line (apart from pre-alarm)
Coll. lockedCloser NOContact closes, if all door control units on the bus line
are locked
Opener NCContact opens, if all door control units on the bus line
are locked
Coll. closedCloser NOContact closes, if all door control units on the bus line
are closed
Opener NCContact opens, if all door control units on the bus line
are closed
Set configuration for the door control unit
1. In the service menu, set TZ parameter > custom outputs.
2. For the corresponding output number, choose TZ output 1-2 > configuration TZ1-2 > choice and select configuration.
The selected value is displayed on the upper display row of the service terminal.
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageCommissioningBedienungAnschlussplanAnhang
Set configuration for the terminal box
1. In the service menu, select system environment > KL > custom outputs.
2. For the corresponding output numbers, choose KL output 1-6 >configuration KL1-6 > choice and select configuration.
The selected value is displayed on the upper display row of the service terminal.
4.7Components settings
4.7.1KL220 terminal box
One KL220 terminal box connected to TZ320 is automatically recognised and switched on.
It can be switched off again via the service menu.
Switch on the terminal box
In the service menu,select system environment > KL > available > choice
> available.
The selected value is displayed on the upper display row of the service terminal.
Switch off the terminal box
In the service menu,select system environment > KL > available > choice
> unavailable.
The selected value is displayed on the upper display row of the service terminal. All
components connected to the terminal box are without functions and are no longer
active.
Set inputs/outputs
The setting of the inputs/outputs conforms with the setting of the door control unit (see
page 19).
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
23
Commissioning
4.7.2TT220 door control unit
One TT220 door control unit connected to TZ320 is automatically recognised and switched
on. The door control unit can be switched off again via the service menu.
Switch on the door control unit
In the service menu, select system environment > TT > choice > available.
The selected value is displayed on the upper display row of the service terminal.
Switch off the door control unit
In the service menu, select system environment > TT > choice >
unavailable.
The selected value is displayed on the upper display row of the service terminal.
4.7.3Set sabotage contacts
Menu "system environment > sabotage contacts"
Menu itemSubmenuChoice
TZChoiceActive
Key-operated push buttonChoiceActive
KLChoiceActive
TTChoice
(Default setting)
Inactive
(Active)
Inactive
(Inactive)
Inactive
(Active)
1. In the service menu, select system environment > sabotage contacts.
2. Select components and set.
The selected value is displayed on the upper display row of the service terminal.
4.7.4Set inverse door drive
If a revolving door drive system GEZE TSA160NT is connected inversely, the inverse door
drive must be set on available. The drive system undertakes the control of the
emergency exit opener.
In the service menu, select system environment > inverse door drive >
available (default setting: unavailable).
The selected value is displayed on the upper display row of the service terminal.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
24
Commissioning
4.7.5Set time-switch
Set internal time-switch
Menu "time-switch"
Menu itemSubmenuSubmenuSubmenuChoice
Time-switch1-3Clock startHourChange value 0 - 23 (0)
Clock start: Time, on which the time-switch is active
Clock stop: Time, on which the time-switch is inactive
Days: Days, on which the set times apply
(Default setting)
MinuteChange value 0 - 59 (0)
Clock stopHourChange value 0 - 23 (0)
MinuteChange value 0 - 59 (0)
DaysMonday - SundayChoiceActive
Inactive
(Inactive)
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageCommissioningBedienungAnschlussplanAnhang
1. In the service menu, select system environment > time-switch.
2. Select the start time, end time and effective days for the desired time-switch1-3.
The selected value is displayed on the upper display row of the service terminal.
Set time-switch interruptible
ChoiceSpecification
OnIf the time-switch signal is active, the door control unit can be locked via the
internal key-operated push button, the VAT220, the TE220 or the adjustable
inputs. If the system in an active time-switch signal is unlocked again via the
key-operated push button, the door control unit returns to the time-switch
mode
OffIf the time-switch is active, the door control unit can no longer be locked
(exception: burglar alarm system is active)
In the service menu, set TZ parameter > time-switch interruptible >
choice select (default setting: on).
The selected value is displayed on the upper display row of the service terminal.
Time-switch interruptible on public holidays
In order to be able to interrupt the time-switch during public holidays, an input must be set
on public holiday and a switch connected to this.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
25
Commissioning
4.8Bus settings
The bus function is a pre-requisite for connection to other TZ320 door control units, to the
tableau unit TE220, to the visual display software VAT220SN or to an OPC interface
OPC220.
4.8.1Assign bus address
A bus address can only be assigned once within a bus line. Bus addresses already
assigned are skipped in the service menu.
If the bus addresses are assigned before the bus connection is engaged, the bus
addresses can be assigned several times. Then, there is a fault report.
In the service menu, choose bus configuration > bus address > change
value and select bus address.
The selected value is displayed on the upper display row of the service terminal.
4.8.2Switch on the bus function
Assign a bus address in the service menu.
The connection to other door control units etc. is established.
4.8.3Check bus function
Re-assign an assigned bus address in the service menu.
Possible: no bus connection is available
Impossible: Bus connection is functional
4.8.4Switch off the bus function
In the service menu, set the bus address on the value 0.
The connection to other door control units etc. is disconnected.
4.8.5Set bus functions
Signals of a burglar alarm system, time-switch or fire alarm system can be given to the bus
via a door control unit and several door control units can be controlled simultaneously. To
this end, it is enough to switch on the signals once on a door control unit or terminal box in
the bus system. The signals are displayed on the bus system from there.
Burglar alarm system (EMA)
If the burglar alarm system signal is active on a door control unit, it is locked primarily. In
an active burglar alarm system, the doors can no longer be unlocked via a push button,
switch, tableau etc. By actuating the local emergency button as well as a burglar alarm
system signal, the door is released and emergency unlocked respectively.
Fire alarm system (BMA)
If the fire alarm system on the door control unit is active, it is unlocked primarily and a local
alarm is triggered off (acoustic via integrated buzzer and optical via integrated LED). The
system remains unlocked until the signal is no longer available and the alarm was reset onsite on TE220 or on the VAT via the key-operated push button.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
26
Commissioning
Time-switch (ZSU)
In the door control unit, a weekly time-switch is integrated, with which up to three times can
be stored. In addition, external time-switches can be connected to the door control unit or
the terminal box. For the setting of the time-switch
Arrange functions
Five groups can be formed in all three functions. A group can be formed per door control
unit and be shown on the bus. The bus signal is given to the bus on the door control unit,
on which the master bus function is selected in the group. In the same group, all door
control units that should react to the signal must be set on bus function on.
If several groups are formed, the signals must be entered in different door control units/
terminal boxs.
Menu "bus configuration"
Menu itemSubmenuSubmenuChoice
Burglar alarm
system
Fire alarm
system
Time-switchGroup1-5Choice
Group1-5ChoiceBus function off
Group1-5Choice
(see page 25).
(Default setting)
Bus function on
Master Bus function
(Bus function off)
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageCommissioningBedienungAnschlussplanAnhang
Bus function off: The bus signal is inactive (only local interpretation)
Bus function on: The bus signal is active on this door control unit
Master Bus function: The adjacent signal is displayed as bus signal on the bus system and
active on all door control units that are set in the same group on
In the service menu, select bus configuration and select group number and value
for corresponding function.
The selected value is displayed on the upper display row of the service terminal.
If the master function is assigned twice in a group, there is a system fault as a
result of multiple allocation.
4.8.6Set emergency unlock
On the door control unit, it can be set if it reacts to a signal when the emergency button is
activated on the tableau unit TE220 or the VAT220SN.
In the service menu select and set bus configuration > emergency unlock.
The selected value is displayed on the upper display row of the service terminal.
bus function on
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
27
Commissioning
4.8.7Set sluice
The necessary control electronics for the sluice function is already integrated into the
TZ320 door control units. Two types of sluices can be set up:
Active sluice: In the active sluice, all doors set as active sluice in the initial state are locked
and closed. Only one door can be short-term unlocked in a sluice group.
If one of these doors is short-term unlocked, it simultaneously sends a signal to all other
doors in the sluice group and, consequently, prevents the short-term unlock of the
remaining doors that are still locked.
If one door is continuously unlocked, the sluice function is automatically switched off on
this door. The sluice function is switched on again by locking the door.
Passive sluice: In the passive sluice, all doors set as passive sluice in the initial state are
unlocked, but closed.
If one of these doors is opened, i. e. the door leaf moves, the door sends a signal to all
other doors in the sluice group. The remaining doors are then locked and opening is
prevented, e.
In passive sluices, two or more doors opening simultaneously cannot be prevented.
Active and passive sluice mixed: In this configuration, when opening the door with passive
setting, the control devices of the door with active setting is locked. In actuating the control
devices of the door with active setting, the door with passive setting is unlocked.
g. via short-term unlock.
Select/deactivate sluice type
In the service menu bus configuration > sluice > sluice type > choice,
select the desired type.
The selected value is displayed on the upper display row of the service terminal.
The doors must be locked during the first commissioning of the sluice.
An immediate inspection by activating the emergency button is possible at all
times. The emergency button is effective only for the corresponding door.
Group sluices
Ten sluice groups with 63 members can be formed within a bus line respectively.
In the service menu select and set bus configuration > sluice >
allocation > group1-10 > choice (default setting: not assigned).
The selected value is displayed on the upper display row of the service terminal.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
28
Operation
1
2
3
5Operation
1
2
3
[1]Emergency exit shield
[2]Key-operated push button
[3]Control unit with emergency button
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeOperationAnschlussplanAnhang
Abb. 1 LEDs of TZ320 door control unit
No. DisplayColourMeaning
1RedLocked
Red flashing (every second)Sluice allocated
Red flashing (every 2 seconds)Locked via burglar alarm system
GreenUnlocked
Green flashing (every second)Short-term release
Green flashing (every 2 seconds)Unlocked via time-switch
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
29
Operation
1
2
3
1
2
3
5.1Control TZ320 door control unit via key-operated push
button
Unlock door
When unlocking, the interlocking elements are disconnected by an authorised person. The
door can be opened.
1. Insert the key into the lock of the key-operated push button.
2. Turn the key left and hold approximately for a second.
LED 1 flashes green. The door is unlocked.
One sluice function engaged on this door is switched off when unlocking.
Lock door
When locking, the interlocking elements are engaged by an authorised person. The door
cannot be opened.
Requirements:The door is closed or else the pre-alarm is triggered off.
1. Insert the key into the lock of the key-operated push button.
2. Turn the key right and hold approximately for a second.
LEDs1 and 2 flash red. The door is locked.
One sluice function switched off for this door is engaged again when locking.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
30
Operation
1
2
3
1
2
3
Unlock door temporary (short-term release)
During the short-term release, the door is unlocked for a variable time (release time) by an
authorised person. The door is unlocked again after the lapse of the release time.
If the door is not closed after the lapse of the set release time, the pre-alarm is triggered
off
If the door is closed before the lapse of the release time, the door is locked again (abort)
If a new short-term release is triggered during the release time, the release time starts
over again (post trigger)
1. Insert the key into the lock of the key-operated push button.
2. Turn the key right and hold approximately for a second.
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeOperationAnschlussplanAnhang
LED 1 flashes green. The door is unlocked for the set release time from 0 seconds to
infinite (see page 17).
5.2Open the doors and trigger off the alarm in case of an
emergency
By actuating the emergency button, the interlocking elements on the corresponding door
are switched off (direct release).
If a connected fire alarm system or the like is triggered off, the interlocking elements are
automatically switched off (emergency unlock).
Press emergency button
LED 1 flashes green and LED 3 flashes yellow. The door is unlocked.
Alarm is triggered off.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
31
Operation
5.3Cancel alarm
The alarm remains pending on the door control unit until the cause of the alarm is
eliminated and the alarm on the door control unit was acknowledged. The cause of the
alarm can be read out with the aid of the service terminal
5.3.1Reset emergency button
After the emergency case is resolved, the emergency button must be reset.
1. Remove the covering of the emergency button.
2. Turn the emergency button right.
The emergency button returns to the normal state.
3. Insert covering.
4. Acknowledge alarm.
5.3.2Acknowledge alarm
Requirements:The cause of the alarm is eliminated and acknowledge alarm is displayed in the service
terminal.
The door is closed and the emergency button is reset.
(see page 35).
Insert the key into the lock of the key-operated push button.
In order to acknowledge the alarm and to lock the door, turn the key right and hold
approximately for a second.
In order to acknowledge the alarm and to unlock the door, turn the key left and hold
approximately for a second.
The alarms emergency unlock, door alarm and sabotage alarm can also be acknowledged
via the functions
corresponding mode of operation.
In addition, the door alarm can be acknowledged via the outputs short-term unlock.
lock and unlock on TE220 and VAT220. The door state changes in the
A sabotage alarm can only be acknowledged 30 seconds after the cause of the
alarm is acknowledged.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
32
Operation
5.4Read out the alarm memory via the service terminal
Relevant alarm and fault reports are saved in the alarm memory of the door control unit
and can be read out with the service terminal.
1. Activate service mode and connect service terminal with the door control unit.
2. In the service menu, select diagnosis > alarm memory> display list. The last 20 relevant alarm and fault reports are displayed with date, time and cause.
Alarm signals
Memory entryDescription
INITInit
SKBreakdown of safety circuit
Mains supply circuit-TZDirect release
Mains supply circuit-TTIndirect release TT
IDIRIndirect release
NEBUSEmergency unlock
SB-TZSabotage door control unit
SB-SCTSabotage key-operated push button
SB-TTSabotage TT
SB-KLSabotage KL
SB-PESabotage PE
DOORDoor alarm
INVALInvalid
Fault reports
Memory entryDescription
INITInit
KL485Communication terminal box
TT485Communication door control unit
MAINSMains return
CLOCKClock
EEPROMEEPROM
INVALInvalid
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeOperationAnschlussplanAnhang
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
33
Operation
5.5Read out fault report
Faults in the system are indicated via the flashing of LED 3.
1. Connect the service terminal with the door control unit.
The fault report is shown on the display of the service terminal.
2. Find out the cause of malfunction and correct the fault with the aid of the following
table.
Fault reportCause of malfunctionFault correction
Locking mechanismLocked signal message despite
unavailability of power supply
24V_EXT is missing Locking device is defective, no
external voltage supply
KL communicationConnection with terminal box is
faulty
TT communicationConnection with door control unit
is faulty
Bus signal is
unavailable
Duplicate bus
address
Assembly variantDoor control unit (assembly
2 M. in a fire alarm
system group
2 M. in a burglar
alarm system group
2 M. in a time-switch
group
Invalid clock/dateInvalid values for the date and
EEPROM errorEEPROM cannot be read out Change the door control unit
Transmission of CAN messages
is defective
Multiple allocation of address in
the bus system
variant) incompatible with the
software version
Two active masters in a fire alarm
system group
Two active masters in a burglar
alarm system group
Two active masters in a timeswitch group
time
Check the contact of the
interlocking element and
change if it is defective
Check external voltage supply
Change locking device
Switch off the terminal box via
the service menu
Re-establish connection to the
terminal box
Change terminal box
Switch off the door control unit
via the service menu
Re-establish connection to the
door control unit
Change door control unit
Check CAN connection
Change CAN address
Change the door control unit
Switch off master group of a
door control unit
Switch off master group of a
door control unit
Switch off master group of a
door control unit
Correct data in the service
menu
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
34
Operation
5.6Read out alarm signal
Misuse of the system or emergency situations are indicated via an alarm tone and flashing
of LED
1. Connect the service terminal with the door control unit.
The alarm signal is shown on the display of the service terminal.
2. Find out the cause of the alarm and cancel the alarm with the aid of the following table.
3. In order to switch off the service terminal, do not press any button on the service
3.
terminal for two minutes.
Alarm signalCause of alarmCancel alarm
Door alarm
Door is not closedClosed signal message is
missing
Door is not lockedLocked signal message is
missing
Sabotage alarm
Sabotage contact TZSabotage contact of the door
control unit is not closed
Sabotage contact
SBC
Sabotage contact KLSabotage contact of the terminal
Sabotage contact TTSabotage contact of the door
Sabotage contact
EXT
Sabotage time
runs
Emergency unlock
via busEmergency unlock via tableau,
via fire alarm
system (bus)
via fire alarm
system (local)
Indirect release
Mains supply
circuit TT pressed
Sabotage contact of the keyoperated push button is not
closed
box is not closed
control unit is not closed
External sabotage contact is
active
Sabotage time unexpired Acknowledge alarm after the
VAT etc.
Emergency unlock via fire alarm
system-bus-function
Emergency unlock via the fire
alarm system connected locally
Indirect release via door control
unit
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeOperationAnschlussplanAnhang
Close door
Check door contact
Check the interlocking
element
1. Close contact
2. Acknowledge alarm after the
lapse of the sabotage time
Check sabotage message
lapse of the sabotage time
Pull the emergency button
on the tableau
Switch off the emergency
button on the VAT
Check the fire alarm system
and switch off the
emergency unlock signal
Check the input of the
corresponding door control
unit
Check the fire alarm system
and switch off the
emergency unlock signal
Check the input of the
corresponding door control
unit
Reset the emergency button
on the door control unit
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
35
Operation
Alarm signalCause of alarmCancel alarm
Direct release
Mains supply
circuit TZ pressed
SK omitted
Program memoryProgram memory is invalid
Mains supply
circuit opener
omitted
Feedback signal of
the internal
emergency button
is unavailable
Relay1 sticksRelay 1 in the safety circuit
Relay2 sticks
Acknowledge
alarm
Direct release via internal
emergency button
Reset the emergency button
on the door control unit
Change the door control unit
(CRC test)
Opener contact of the internal
emergency button is omitted
1. Press reset button
2. Correct error
3. Check emergency button
Change the door control unit
Feedback signal of the internal
emergency button is unavailable
Press internal emergency
button
Change the door control unit
Change the door control unit
sticks
Bridge circuit on FTÖ331U
was not removed
FTÖ332 was connected
without RP220
Short-circuit in the feeder of
the interlocking element
Resolve the cause of the alarm Acknowledge alarm via the
Remove bridge circuit on
FTÖ331
Check the feeder of the
interlocking element for
short-circuit
Connect FTÖ332 with
RP220
key-operated push button
5.7Power failure
The escape route system GEZE SecuLogic saves the active preset mode of operation in a
non-volatile memory (EEPROM), so that it also becomes active after a power failure.
Components (KL, TT etc.) that are not switched off are automatically recognised.
Mode of operation before
power failure
LockedLocked
Locked via burglar alarm
system
Permanent unlockingPermanent unlocking
Short-term releaseLocked
Unlocked via time-switchCorresponding signal "unlock via time-switch"
Diagnosis/ServiceService
Mode of operation after power failure
Corresponding signal "lock via burglar alarm system"
Signal active: locked via burglar alarm system
Signal inactive: locked
Signal active: unlocked via time-switch
Signal inactive: locked
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
36
Operation
5.8Reset door control unit to default setting
Via service terminal
1. Activate service mode and connect service terminal with the door control unit.
2. In the service menu, select system setup > default settings > choice > reset.
The door control unit settings are reset to default settings.
Via reset button
1. Remove the covering of the emergency button.
2. Press reset button (see page 41) for approximately ten seconds.
The door control unit settings are reset to default settings.
3. Insert covering.
5.9Display software version
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeOperationAnschlussplanAnhang
1. Activate service mode and connect service terminal with the door control unit.
2. In the service menu, select diagnosis > version > display.
The software version of the door control unit is displayed.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
37
Operation
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
38
Terminal connection diagram
6Terminal connection diagram
6.1Contents
Door control units ........................................................................................................41
TZ320 door control unit, TZ320N (KL, jumper, locking devices)
Instructions for the terminal connection diagram
Door control unit TZ320BS, TZ320BSN
Door control unit TZ320, TZ320N
Door control unit TZ320B, TZ320BN
Door control unit TZ320S, TZ320SN
GEZE bus ......................................................................................................................48
GEZE bus with TZ320 (all specifications)
GEZE bus with TE220, VATSN220 and TZ320
Pay attention to the overall power input when connecting external devices.
Power output for external devices via standard power supply unit:
In-wall variant (NET220): 24 V DC / max. 350 mA
On-wall variant (NT19.2-24): 24 V DC / max. 650 mA
Power output for external devices via external mains supply circuit (Net24-5, logo):
1,3
A
Power output for external devices (terminal boxs): 24 V DC / max. 600 mA
47002
New
abbreviation
is according
IEC 757
to DIN
ColourUntil now,
abbreviation
is according
47002
to DIN
New
abbreviation
is according
IEC 757
to DIN
Consumer loadConsumption in
mA (approximate)
TZ320 door control unit
(all variants)
Control unit TST320100Signal light SLE
KL220 terminal box80Flashing light
TT220 door control unit80Signal horn with
Holding magnet MA500250Alarm horn SLH220 16
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
130Numerical code
Consumer loadConsumption in
mA (approximate)
50
lock CTI
85
220
90
BLE220
110
flashing light
40
Terminal connection diagram
Door
LED
Buzzer
Emergency push button
LED
1
2
3
4
J1
J2
1
2
Interface
programming
Alarm LEDs
Bolt
LED
Sabotage
contact
Reset
button
Interface
Service terminal
F1
X102
X104 (red)
X108 (blue)
X107 (green)
X106 (orange)
J3
1 3 46 45 42 41 2
21211
22 21 1 2 51 50
X105 (BK)
217151453 52 982265
1234
12
12
Consumer loadConsumption in
Emergency exit opener
FTÖ331
Emergency exit opener
FTÖ332
Relay circuit board RP22010Master tableau
Emergency button NSA320/
NOT220
Motor lock MLS80
Handle lock HLS210Smoke switch RS519
6.5Door control units
Consumer loadConsumption in
mA (approximate)
160Key-operated push
button with LED
SCT220
105Tableau unit TE220
MTA220
30Slave tableau
MTA220
Emergency tableau
(short-term 250)
NTA220
mA (approximate)
30
30
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
30
30
6.5.1TZ320 door control unit, TZ320N (KL, jumper, locking devices)
Jumper
JumperPositionSpecification
J1, J2No indirect release,
internal voltage supply of the safety circuit (delivery
status: bridge circuit set on terminal X107 between
+ 8)
7
Indirect release,
external voltage supply of the safety circuit connected
to terminal 7
CAN load resistance not set
+ 8 of terminal box X107
1234
J3CAN load resistance set (delivery status)
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
41
Terminal connection diagram
Terminal connections
Plug and screw terminals max. cable cross section: 1 mm²
Clamping fieldTerminalFunction (default setting)
X102–Ribbon cable plug connector for GEZE key-operated
push button without illumination
X104
red clamping field
X105
black clamping field
X106
orange clamping field
X107
green clamping field
X108
blue clamping field
1GND supply unit
324-V-DC supply unit
46CAN-H, GEZE-bus-communication
45CAN-L, GEZE-bus-communication
42RS485-A, communication with KL220, TAN220
41RS485-B, communication with KL220, TAN220
224 V DC
12Key-operated push button - lock, short-term release,
acknowledge alarm
11Key-operated push button - unlock, acknowledge alarm
5Interlocking element, +, 24 V DC
6Interlocking element, -, GND
14Feedback signal: Door locked
15Feedback signal: Door closed
224 V DC
224 V DC
9Adjustable input 1 (short-term unlock)
52Adjustable input 2 (short-term unlock)
53Adjustable input 3 (fire alarm system)
224 V DC
1GND
7Indirect releaseTo the connection of
8Indirect release
224 V DC
22COM, adjustable output 1(Alarm, closer)
21NO/NC, adjustable output 1
1GND
224 V DC
51COM, adjustable output 2(Door-o. op.cur.,
50NO/NC, adjustable output 2
external emergency
button
max. 1 A, 30 V DC
closer)
max. 1 A, 30 V DC
Locking device
DescriptionValueSpecification
F11,5 A, SMF 125 V,
swift
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
24 V external
42
Terminal connection diagram
Operating controls/indicators
Bolt-LED
Door-LED
Alarm-LED
Emergency button-LED
Buzzer (100 dB in approx. 50 cm distance)
6.5.2Instructions for the terminal connection diagram
The instructions apply for the following connection diagram of TZ320 in different
specifications.
If no interlocking element is connected (door supervision), there are the following
possibilities:
Use door control unit without emergency button
Connect door control unit with emergency button to terminal box X106 as
follows:
Set between terminals 5 and 6 10-K resistance
Set between terminals 5 and 14 bridge circuit or connect external locked-
signal
Connect to terminals 2 and 15 door contact or set bridge circuit
Rest against terminals 5 and 6 in the unlocked state 12 V (measurement contrary
to GND).
1) The mains fuse takes place on site.
2) GEZE mains supply circuit in TZ320N UP = NET220. 500 mA max. 350 mA for peripherals
GEZE power supply unit in TZ320N AP = NT19.2-24. 750 mA max. 650 mA for peripherals
Divide the primary and secondary sites spatially.
3) In TZ320, the mains supply circuit is installed outside the door control unit.
4) TZ320N UP: Protection class II (do not connect protective conductor)
TZ320N AP: Protection class I with protective conductor test in accordance with VDE0100
5) Bridge circuit set in the original condition.
During an indirect release, remove bridge circuit and change jumper positions J1 and J2.
6) Default setting:
The contact closes in the event of an alarm.
The contact is open in the event of power failure.
Pay attention to the overall power input.
7) In the on-wall variant, the luster terminal is located on the mounting plate.
8) The contact is closed in a closed door.
9) Set bridge circuit when connecting a GEZE alarm horn or siren.
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
43
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
Input 1 (Short-term unlock)
9
2
24 V DC
Input 3 (fire alarm system)
53
52
Input 2 (Short-term unlock)
X108 (blue terminal strip)
24 V DC
2
NO/ (NC) output 1 (alarm)
21
22
COM output 1 (max. 30 V, 1 A)
24 V DC
2
1
GND
NO/ (NC) output 2
50
51
COM output 2 (max. 30 V, 1 A)
X104 (red terminal strip)
GND supply unit
1
CAN-H (GEZE-bus)
46
3
24-V-DC supply unit
RS485-A
42
45
CAN-L (GEZE-bus)
41
RS485-B
X107 (green terminal strip)
24 V DC
2
Indirect release
7
1
GND
8
Indirect release
Mains supply circuit
Luster terminal
X102
Plug connector for GEZE
Key-operated push button
BK/RD
RD
BN
BU
6 A
2)
1)
BN
BU
L1
N
GN/YE
PE
4)
5)
+
-
NO
COM
NC
1
2
8
7
6
MA500
Door contact
FTÖ331U
+
-
NO
COM
NC
5
14
6
2
Interlocking element connection
Caution:
Disconnect red bridge circuit (1-7) in FTÖ 331U.
Short-term release via
push button, key-operated push button,
access control ...
Ribbon cable
SLE220
Signal light
+
-
SLH220
Alarm siren
+
-
OR
Illuminated shield
for emergency button
GEZE key-operated push button
TST320
6)
7)
without illumination
Connection to
TST320 X102
Connection to
Key-operated push button
without illumination
Connection to
Key-operated push button
without TST320 X102
AKRR
RR
5
4
3
NO
COM
NC
15
OR
8)
9)
To other TZ (option)
To KL220 (option)
5051221222
X108
1
X108
(blue)
8712
X107
X107
(green)
5614152295253
X106
X106
(orange)
414245463
X104
1
X104
(red)
X102
X102
1
J1
J2
2
3
4
J1 J2
F1
F1
Terminal connection diagram
6.5.3Door control unit TZ320BS³, TZ320BSN
For instructions regarding the connection diagram see page 43.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
44
Terminal connection diagram
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
Input 1 (Short-term unlock)
9
2
24 V DC
Input 3 (fire alarm system)
53
52
Input 2 (Short-term unlock)
X104 (red terminal strip)
GND supply unit
CAN-H (GEZE-bus)
46
3
24-V-DC supply unit
RS485-A
42
45
CAN-L (GEZE-bus)
41
RS485-B
Mains supply circuit
Luster terminal
BK/RD
RD
BN
BU
6 A
2)
1)
BN
BU
L1
N
GN/YE
PE
4)
+
-
NO
COM
NC
2
8
7
6
MA500
Door contact
FTÖ331U
+
-
NO
COM
NC
5
14
6
2
Short-term release via
push button, key-operated push button,
access control ...
TST320
7)
X108 (blue terminal strip)
24 V DC
2
21
22
24 V DC
2
GND
50
51
X107 (green terminal strip)
24 V DC
2
Indirect release
7
1
GND
8
Indirect release
X105 (black terminal strip)
24 V DC
2
SCT unlock, acknowledge
11
12
SCT lock, short-term release, acknowledge
5)
SCT320 external key-operated push button
COM
2
Left closed
11
12
Right closed
SLE220
Signal light
+
-
SLH220
Alarm siren
+
-
OR
(Option)
(Option)
AKRR
RR
5
4
3
NO
COM
NC
15
OR
NO/ (NC) output 1 (alarm)
COM output 1 (max. 30, V 1 A)
NO/ (NC) output 2
COM output 2 (max. 30, V 1 A)
6)
Caution:
Disconnect red bridge circuit (1-7) in FTÖ 331U.
8)
9)
Interlocking element connection
To other TZ (option)
To KL220 (option)
1
1
1
5051221222
X108
1
X108
(blue)
8712
X107
X107
(green)
5614152295253
X106
X106
(orange)
21211
X105
X105
(black)
414245463
X104
1
X104
(red)
X102
X102
1
J1
J2
2
3
4
J1 J2
F1
F1
6.5.4Door control unit TZ320, TZ320N
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
For instructions regarding the connection diagram see page 43.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
45
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
Input 1 (Short-term unlock)
9
2
24 V DC
Input 3 (fire alarm system)
53
52
Input 2 (Short-term unlock)
X104 (red terminal strip)
GND supply unit
CAN-H (GEZE-bus)
46
3
24-V-DC supply unit
RS485-A
42
45
CAN-L (GEZE-bus)
41
RS485-B
Mains supply circuit
Luster terminal
X102
Plug connector for GEZE
Key-operated push button
BK/RD
RD
BN
BU
6 A
2)
1)
BN
BU
L1
N
GN/YE
PE
4)
+
-
NO
COM
NC
2
8
7
6
MA500
Door contact
FTÖ331U
+
-
NO
COM
NC
5
14
6
2
Short-term release via
push button, key-operated push button,
access control ...
Ribbon cable
Illuminated shield
for emergency button
TST320
7)
without illumination
Connection to
TST320 X102
X108 (blue terminal strip)
24 V DC
2
21
22
24 V DC
2
GND
50
51
X107 (green terminal strip)
24 V DC
2
Indirect release
7
1
GND
8
Indirect release
X105 (black terminal strip)
24 V DC
2
SCT unlock, acknowledge
11
12
SCT lock, short-term release, acknowledge
5)
SLE220
Signal light
+
-
SLH220
Alarm siren
+
-
OR
(Option)
(Option)
AKRR
RR
5
4
3
NO
COM
NC
15
OR
NO/ (NC) output 1 (alarm)
COM output 1 (max. 30 V, 1 A)
NO/ (NC) output 2
COM output 2 (max. 30 V, 1 A)
6)
Caution: Disconnect red bridge circuit (1-7)
in FTÖ 331U.
8)
9)
Interlocking element connection
SCT320 external key-operated push button
COM
2
Left closed
11
12
Right closed
To other TZ (option)
To KL220 (option)
1
1
1
5051221222
X108
1
X108
(blue)
8712
X107
X107
(green)
5614152295253
X106
X106
(orange)
21211
X105
X105
(black)
414245463
X104
1
X104
(red)
X102
X102
1
J1
J2
2
3
4
J1 J2
F1
F1
6.5.5Door control unit TZ320B, TZ320BN
Terminal connection diagram
For instructions regarding the connection diagram see page 43.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
46
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
Input 1 (Short-term unlock)
9
2
24 V DC
Input 3 (fire alarm system)
53
52
Input 2 (Short-term unlock)
X108 (blue terminal strip)
24 V DC
2
21
22
24 V DC
2
GND
50
51
X104 (red terminal strip)
GND supply unit
CAN-H (GEZE-bus)
46
3
24-V-DC supply unit
RS485-A
42
45
CAN-L (GEZE-bus)
41
RS485-B
X107 (green terminal strip)
24 V DC
2
Indirect release
7
1
GND
8
Indirect release
Mains supply circuit
Luster terminal
X102
Plug connector for GEZE
Key-operated push button
BK/RD
RD
BN
BU
6 A
2)
1)
BN
BU
L1
N
GN/YE
PE
4)
5)
+
-
NO
COM
NC
2
8
7
6
MA500
Door contact
FTÖ331U
5
4
3
+
-
NO
COM
NC
NO
COM
NC
5
14
6
15
2
Interlocking element connection
Short-term release via
push button, key-operated push button,
access control ...
Ribbon cable
SLE220
Signal light
+
-
SLH220
Alarm siren
+
-
OR
GEZE key-operated push button
TST320
7)
OR
without Illumination
Connection to
TST320 X102
(Option)
(Option)
AKRR
RR
NO/ (NC) output 1 (alarm)
COM output 1
NO/ (NC) output 2
COM output 2
6)
Caution: Disconnect red bridge circuit (1-7)
in FTÖ 331U.
8)
9)
To other TZ (option)
To KL220 (option)
1
1
1
5051221222
X108
1
X108
(blue)
8712
X107
X107
(green)
5614152295253
X106
X106
(orange)
414245463
X104
1
X104
(red)
X102
X102
1
J1
J2
2
3
4
J1 J2
F1
F1
Terminal connection diagram
6.5.6 Door control unit TZ320S, TZ320SN
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
For instructions regarding the connection diagram see page 43.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
47
Terminal connection diagram
6.6GEZE bus
X104
X104
(red)
1
414245463
J3
1
J3
6.6.1GEZE bus with TZ320 (all specifications)
2
12
J3
TZ320
CAN 1
CAN-L (GEZE bus)
4546
X104 (red terminal strip)
J3
1)
2)
CAN-H (GEZE bus)
12
TZ320
CAN 2
CAN-L (GEZE bus)
CAN-H (GEZE bus)
4546
12
J3
TZ320
CAN 3
CAN-L (GEZE bus)
CAN-H (GEZE bus)
4546
*)*)*)*)*)
J3
12
TZ320
CAN 4
4546
CAN-L (GEZE bus)
CAN-H (GEZE bus)
J3
12
TZ320
CAN 5
4546
CAN-L (GEZE bus)
CAN-H (GEZE bus)
J3
12
TZ320
CAN 6
4546
CAN-L (GEZE bus)
CAN-H (GEZE bus)
*) On site terminal block
On site 2-fold luster terminal
1)
J3
TZ320
CAN 40
4546
12
CAN-L (GEZE bus)
CAN-H (GEZE bus)
1) Jumper setting "1-2" in jumper 3 of TST320 = load resistance set (original condition).
Set the jumper "outwards" if the door control unit is not the last member in the BUS system.
2) CAN 1-63 = CAN-bus-address. This must be set differently for each door control unit. The setting
of the CAN address takes place via the service terminal ST220.
Maximum length per BUS line = 900 m
Maximum number of members per BUS line = 63
The load resistance must be set in the first and last members in the BUS assembly
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
48
Terminal connection diagram
X104 (red terminal strip)
Dongle VAT220SN
BN
WH
Dongle VAT220SN
CAN-H (GEZE bus)
CAN-L (GEZE bus)
4546
CAN-H (GEZE bus)
46
45
CAN-L (GEZE bus)
VAT220SN / building system
Tableau TE220
X1
CAN-H (GEZE bus)
CAN-L (GEZE bus)
4546
CAN-H (GEZE bus)
CAN-L (GEZE bus)
4546
CAN-H (GEZE bus)
CAN-L (GEZE bus)
4546
CAN-H (GEZE bus)
CAN-L (GEZE bus)
4546
CAN-H (GEZE bus)
CAN-L (GEZE bus)
4546
CAN-H (GEZE bus)
CAN-L (GEZE bus)
4546
TZ320
CAN 1
TZ320
CAN 2
TZ320
CAN 3
TZ320
CAN 4
TZ320
CAN 5
TZ320
CAN 6
TZ320
CAN 40
J3
12
12
J3
12
J3
12
J3
12
J3
12
J3
12
J3
12
J1
MTA220
3
3)
4)
1)
1)
2)
5)
*)*)*)*)*)*)
*) On site terminal block
On site 2-fold luster terminal
6.6.2GEZE bus with TE220, VATSN220 and TZ320
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
1) Jumper setting "1-2" in jumper 3 of TST320 = load resistance set (original condition).
Set the jumper "outwards" if the door control unit is not the last member in the BUS system.
2) CAN 1-63 = CAN-bus-address. This must be set differently for each door control unit. The setting
of the CAN address takes place via the service terminal ST220.
3) On delivery, a 120-ohm load resistance is fixed on the dongle of VAT220SN.
Remove the load resistance if VAT is not the last member in the BUS system.
4) Jumper setting "1-2" in the master tableau MTA220 of the tableau unit TE220 = load resistance is
not set.
Set the jumper on "2-3" if the tableau is the last member in the BUS system.
5) Use the emergency button of TE220 for unlocking the door control units only.
Maximum length per BUS line = 900 m
Maximum number of members per BUS line = 63
Maximum number of TE220 per BUS line = 5
Maximum number of VAT220SN per BUS line = 2
The load resistance must be set in the first and last members in the BUS assembly
The arrangement of the members can be arbitrary. The tableau and VAT220SN can be
arranged at any desired location in the BUS system
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
49
Terminal connection diagram
(green terminal strip)
indirect release
indirect release
78
indirect release
indirect release
indirect release
indirect release
indirect release
indirect release
+-
ext.
Mains supply circuit
1)
*)
787878
TZ320, door 2TZ320, door 3TZ320, door xx
X107
X107X107X107
TZ320, door 1
J1, J2
1234
Set jumper 1 and 2 in all TZs on external voltage supply.
2)
2)
2)
2)
2)
1
2
(NC)
1
2
Switching element with
1 opener contact
max.250V/1,2W
X1 (-)
Element with LED
X2 (+)
RD
BK
RD
BK
NOT220, emergency button
*)*)*)
Circuit 1
Circuit 2
6.7Safety circuit (indirect release)
The safety circuit is a separate loop for security-relevant (indirect) release of several door
control units in connection with a central emergency button.
1) Use the mains supply circuits NET220 No. 087243 and NT19.2-24 No. 089862 only.
Voltage supply of the safety circuit from TZ320 is prohibited.
2) Condense the wires in the connection room.
Maximum length of the safety circuit = 400 m
Current drain for the safety circuit per TZ320 approx. 20 mA
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
50
Terminal connection diagram
6.8Interlocking elements
In several interlocking elements, connect the spooling in parallel and the feedback
signals in array.
5614152295253
X106
6.8.1Holding magnet MA500 (1-flanked doors)
TST320
X106 (orange terminal strip)
Locking mechanism +
Locking mechanism -
Door locked
24 V DC
Door closed
24 V DC
X106
(orange)
5
6
14
2
15
2
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
MA500
+
-
NO
COM
NC
Door contact
6.8.2Holding magnet MA500 (2-flanked doors)
TST320
X106 (orange terminal strip)
Locking mechanism +
Locking mechanism -
Door locked
24 V DC
Door closed
5
6
14
2
15
AB
MA500
Door contact
+
-
NC
COM
NO
Contact closed,
if the door is closed
MA500
A
B
Door contact
Contact closed,
if the door is closed
+
-
NC
COM
NO
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
51
Terminal connection diagram
1
TST320
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
2
24 V DC
2
8
7
6
FTÖ331U
5
4
3
+
-
NO
COM
NC
NO
COM
NC
Caution: Disconnect red bridge circuit (1-7)
AKRR
RR
TST320
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
2
8
7
6
FTÖ331U
5
4
3
+
-
NO
COM
NC
NO
COM
NC
Caution: Disconnect red bridge circuit (1-7) in
both FTÖs.
AKRR
RR
2
8
7
6
FTÖ331U
5
4
3
+
-
NO
COM
NC
NO
COM
NC
AKRR
RR
A
B
A
B
11
TST320
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
2
24 V DC
5
6
3
2
FTÖ331
right DIN
RD
GN
BU
+
-
NO
COM
NC
NO
COM
NC
2
4
5
6
FTÖ331
left DIN
RD
GN
BU
+
-
NO
COM
NC
NO
COM
NC
5
14
6
15
2
AKRR
RR
1
1
6.8.3Emergency exit opener TYP331U DIN right/left (1-flanked doors)
6.8.4Emergency exit opener TYP331U DIN right/left (2-flanked doors)
6.8.5Emergency exit opener TYP331 DIN right/left (1-flanked doors)
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
52
Terminal connection diagram
TST320
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
2
4
5
6
RD
GN
BU
+
-
NO
COM
NC
NO
COM
NC
AKRR
RR
+
-
NO
COM
NC
NO
COM
NC
AKRR
RR
FTÖ331
left DIN
FTÖ331
left DIN
2
4
5
RD
GN
BU
6
A
B
A
B
1
1
TST320
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
2
24 V DC
2
4
5
6
FTÖ332
3
+
-
NO
COM
NC
AKRR
RR
Relay circuit board RP220, No. 102355
51
NO
55
52
COM
53
54
NC
1
+
-
6.8.6Emergency exit opener TYP331 DIN right (2-flanked doors)
TST320
X106 (orange terminal strip)
Locking mechanism +
Locking mechanism -
Door locked
24 V DC
Door closed
FTÖ331
right DIN
5
6
14
2
15
5
6
3
2
RD
GN
BU
+
-
NO
COM
NC
NO
COM
NC
AKRR
RR
FTÖ331
right DIN
A
B
A
B
6.8.7Emergency exit opener TYP331 DIN left (2-flanked doors)
5
6
3
2
11
RD
GN
BU
+
-
NO
COM
NC
NO
COM
NC
AKRR
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
54
Terminal connection diagram
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
Input 1 (Short-term unlock)
9
2
24 V DC
+
-
NO
COM
NC
1
2
8
7
6
MA500
Door contact
FTÖ331U
+
-
NO
COM
NC
5
14
6
2
Caution: Disconnect red bridge circuit (1-7)
in FTÖ 331U!
TST320
24 V DC
2
indirect release
7
1
indirect release
8
AKRR
RR
5
4
3
NO
COM
NC
15
OR
1234
J1, J2
X107 (green terminal strip)
2)
GND
3)
3)
Switching element with
1 Opener contact
Element with LED
RD
BK
BK
NOT220, emergency button
Circuit 1
Circuit 2
max.250V/1,2W
X2 (+)X1 (-)
(NC)
2
112
6.9Emergency button
For the safety of indirect release, run two cables between the external emergency
buttons.
J1 J2
J1
1
2
1234
3
4
J2
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
X108
(blue)
5051221222
5614152295253
X106
(orange)
X107
(green)
X107
X108
1
8712
X106
6.9.1External emergency button NOT220
Variant with an emergency button
1) Only emergency buttons authorised by GEZE must be used.
2) Set jumper 1-2 of TST320 on external voltage supply.
3) Condense the wires in the connection room.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
55
Terminal connection diagram
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
Input 1 (Short-term unlock)
9
2
24 V DC
+
-
NO
COM
NC
1
2
8
7
6
MA500
Door contact
FTÖ331U
+
-
NO
COM
NC
5
14
6
2
Caution: Disconnect red bridge circuit (1-7)
in FTÖ 331U
TST320
AKRR
RR
5
4
3
NO
COM
NC
15
OR
1234
J1, J2
2)
24 V DC
2
indirect release
7
1
indirect release
8
X107 (green terminal strip)
GND
3)
3)
Switching element with
1 opener contact
Element with LED
RD
BK
BK
NOT220, emergency button
Circuit 1
Circuit 4
max.250V/1,2W
X2 (+)X1 (-)
(NC)
21
1
2
3)
Switching element with
1 opener contact
Element with LED
NOT220, emergency button
max.250V/1,2W
X2 (+)X1 (-)
(NC)
21
1
2
Circuit 2
Circuit 3
BK
RD
BK
Variant with two emergency buttons
1) Only emergency buttons authorised by GEZE must be used.
2) Set jumper 1-2 of TST320 on external voltage supply.
3) Condense the wires in the connection room.
If other emergency buttons are connected, connect lamps in parallel and the opener
contacts in array.
6.9.2Unlocking via fire alarm, hazard alarm and smoke and heat venting
systems
An on-site emergency button is necessary.
2
9
52
53
Burglar alarm system
Hazard alarm system
Smoke and heat venting system
NC
COM
56
TZ320
X106 (orange terminal strip)
24 V DC
Input 1 (Short-term unlock)
Input 2 (Short-term unlock)
Input 3 (fire alarm system)
Set input 3 of TZ320 on:
Fire alarm system (default setting)
Low-active (opener)
Before connection, set input on "disabled" or else alarm is triggered off.
Set the input on "high-active" if a closer contact for unlocking is available on the fire alarm,
hazard alarm and smoke and heat venting systems.
If input 3 is allocated, entries 1 and 2 of the door control unit as well as entries 1 to 4 of
KL220 can also be used for this function.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
Terminal connection diagram
SCT220
COM
L
Left closed
2
Right closed
X106 (orange terminal strip)
Input 1 (Short-term unlock)
9
2
24 V DC
Input 3 (fire alarm system)
53
52
Input 2 (Short-term unlock)
TZ320
1
6.10Key-operated push button
5614152295253
X106
6.10.1Key-operated push button SCT220
X106
(orange)
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
SCT220 No. 94169, UP Jung ST550 (outlet)
SCT220 No. 94170, UP Jung LS990 stainless steel
324-V-DC supply unit
41RS485-B, communication with TST320
42RS485-A, communication with TST320
224 V DC
16Adjustable input 1 (burglar alarm system)
17Adjustable input 2 (time-switch)
224 V DC
18Adjustable input 3 (unlock)
19Adjustable input 4 (lock)
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
61
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
Input 1 (Short-term unlock)
9
2
24 V DC
Input 3 (fire alarm system)
53
52
Input 2 (Short-term unlock)
X108 (blue terminal strip)
24 V DC
2
NC output 1 (alarm)
21
22
COM output 1
24 V DC
2
GND
NO/ (NC) output 2
50
51
COM output 2
X104 (red terminal strip)
GND supply unit
CAN-H (GEZE-bus)
46
3
24-V-DC supply unit
RS485-A
42
45
CAN-L (GEZE-bus)
41
RS485-B
X107 (green terminal strip)
24 V DC
2
Indirect release
7
1
GND
8
Indirect release
X102
Plug connector for GEZE
Key-operated push button
5)
+
-
NO
COM
NC
2
8
7
6
MA500
Door contact
FTÖ331U
+
-
NO
COM
NC
5
14
6
2
Caution: Disconnect red bridge circuit (1-7)
in FTÖ 331U
Short-term release via
push button, key-operated push button,
access control ...
SLE220
Signal light
+
-
SLH220
Alarm siren
+
-
OR
Illuminated shield
for emergency button
GEZE key-operated push button
TST320
6)
without Illumination
Connection to
TST320 X102
Connection to
Key-operated push button
without Illumination
Connection to
Key-operated push button
without TST320 X102
5
4
3
NO
COM
NC
15
OR
X1.1
GND supply unit
RS485-B
41
3
24-V-DC supply unit
24 V DC
2
42
RS485-A
16
Input 1 (burglar alarm system)
Ter m in a l
BK/RD
RD
6 A
1)
BN
BU
L1
N
Input 2 (time-switch)
17
Output 3 (unlock)
18
2
24 V DC
19
Output 4 (lock)
X2.1
GND
NO-output 1
23
2
24 V DC
25
24
COM-output 1
26
27
29
28
X3.1
24 V DC
2
30
GND
32
31
33
34
36
35
37
(OM drive)
(Closer)
NO-output 2
COM-output 2
(Drive control)
(Closer)
NO-output 3
COM-output 3
(Locked)
(Closer)
NC-output 3
38
NO-output 4
COM-output 4
(Door state)
(Closer)
NC-output 4
NO-output 5
COM-output 5
(Sabotage)
(Closer)
NC-output 5
NO-output 6
COM-output 6
(System fault)
(Closer)
NC-output 6
TZ320BS
Mains supply circuit
2)
BN
BU
KL220, KL
Burglar alarm system (option)
Unlock (option)
9)
8)
(Option)
To other TZ (option)
To other TZ (option)
1
1
1
1
1
1
3736353433323130 1
X3.1
382
29282726252423 2 1
X2.1
X2.1
X1.1
34142216218
19
17
1
X1.1
F1
F1
Res
Res
X3.1
Ausgang: 24V= 0.8A
Typ: NT19.2-24-Netzteil
Netz: 230V~50Hz 0,25A
Umg.-Temp.: -10 T 50
Mat.Nr.: 089862
230V AC
BU/BN
24V DC
RD/BK
5051221222
X108
1
X108
(blue)
8712
X107
X107
(green)
5614152295253
X106
X106
(orange)
21211
X105
X105
(black)
414245463
X104
1
X104
(red)
X102
X102
J3
2
1
J3
F1
F1
Terminal connection diagram
6.12.2KL220 terminal box
The KL220 terminal box can be installed in order to expand the system by four inputs and
six outputs.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
62
Terminal connection diagram
1) The mains fuse takes place on site.
2) GEZE mains supply circuit NT19.2-24. 600 mA max. for periphery protection class II
The voltage supply of TZ320 must take place via the mains supply circuit of KL220.
5) Bridge circuit set in the original condition.
During an indirect release, remove bridge circuit and change jumper positions J1 and J2.
6) Default setting:
The contact closes in the event of an alarm.
The contact is open in the event of power failure.
Pay attention to the overall power input.
8) The contact is closed in a closed door.
9) Set bridge circuit when connecting a GEZE alarm horn or siren.
All outputs and inputs of the door control unit and terminal box are freely adjustable via
the service terminal
All outputs can be allocated with the same functions
In addition, each output can be set as "closer contact", "opener contact" or "disabled"
(closer = default setting)
All inputs can be allocated with the same functions
In addition, each input can be set as "high-active (= closer)", "low-active (= opener) or
"disabled"
"High-active" = The input connects as soon as the input is closed (default setting).
"Low-active" = The input connects as soon as the input is opened
"Disabled" = The output or input are without function
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
63
Terminal connection diagram
X106 (orange terminal strip)
Input 1 (Short-term unlock)
9
2
24 V DC
Input 3 (handle)
53
52
Input 2 (Short-term unlock)
X108 (blue terminal strip)
24 V DC
2
NC output 1 (OM drive)
21
22
COM output 1
24 V DC
2
GND
NO output 2 (door-o. op.cur.)
50
51
COM output 2
TST320
black wire
Solenoid -
COM motor lock
red/blue wire
grey/pink wire
NO motor lock
COM handle
green wire
blue wire
NO handle
Option 3
Connecting cable lock
1)
Solenoid +
red wire
Option 2
Option 1
1
6.13Locks
In addition, pay attention to the installation and operating instructions of the motor
and handle locks (No. 103672).
X102
F1
X104
(red)
X107
(green)
J3
6.13.1Handle lock HLS
X107
X104
1
F1
8712
J3
1
2
X106
414245463
X102
X105
21211
X108
X105
(black)
X108
1
(blue)
5051221222
5614152295253
X106
(orange)
TST320 on HLS (voltage supply from TST320)
1) The voltage supply of HLS takes place via the control system TST320.
Pay attention to the maximum power input of TST320.
Options:
1: Connect output 2 of TST320 to the magnet inductor (black wire) if the door control
unit is in "continuous unlock" and the HLS should be "coupled".
For this function, set output 1 on "OM drive".
2: The output "motor lock" (red/blue + grey/pink wires) of HLS can be connected to an
adjustable output of TST320 (terminals 2 + 52 or 53).
Mode of operation: A short-term release is triggered on the door control unit when the
cylinder is activated using the key.
3: The output "handle" (green + blue wire) of HLS can be connected to an adjustable
output of TST320 (terminals 2 + 52 or 53).
Mode of operation: "Pre-alarm" is triggered off when the handle is activated in locked
door control unit.
For this function, set the input of TST on "handle".
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
64
Terminal connection diagram
TST320 on HLS (voltage supply from separate mains supply circuit)
TST320
X108 (blue terminal strip)
24 V DC
COM output 1
NC output 1 (OM drive)
GND
24 V DC
COM output 2
NO output 2 (Short-term unlock)
X106 (orange terminal strip)
24 V DC
Input 1 (Short-term unlock)
Input 2 (Short-term unlock)
Input 3 (handle)
NT 6.3.24, mains supply circuit
RD
+
BK/RD
-
2
22
Option 1
21
1
2
51
50
2
9
52
53
Connecting cable lock
L
N
black wire
red wire
Option 2
red/blue wire
grey/pink wire
Option 3
green wire
blue wire
1)
Solenoid -
Solenoid +
COM motor lock
NO motor lock
COM handle
NO handle
1) The voltage supply of HLS takes place via the detached mains supply circuit NT6.3-24 (no.
109637).
Options:
1: Connect output 2 of TST320 to the magnet inductor (red wire) if the HLS should be in
"coupled" and the door control unit is in "permanent unlock".
For this function, set output 1 on "OM drive".
2: The output "motor lock" (red/blue + grey/pink wire) of HLS can be connected to an
adjustable input of TST320 (terminals 2 + 52 or 53).
Mode of operation: A short-term release is triggered on the door control unit when the
cylinder is activated using the key.
3: The output "handle" (green + blue wire) of HLS can be connected to an adjustable
input of TST320 (terminals 2 + 52 or 53).
Mode of operation: "Pre-alarm" is triggered off when the handle is activated in a locked
door control unit.
For this function, set the input of TST on "handle".
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
In order to couple the lock for the duration of the short-term release time set on the
door control unit, set output 2 of TST320 on "short-term unlock".
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
65
Terminal connection diagram
TST320 on HLS (control via the motor lock)
TST320
X104 (red terminal strip)
GND supply unit
24-V-DC supply unit
CAN-H (GEZE-bus)
X106 (orange terminal strip)
Locking mechanism +
Locking mechanism -
Door locked
24 V DC
Door closed
24 V DC
Input 1 (Short-term unlock)
Input 2 (motor lock)
Input 3 (handle)
1
3
46
5
6
14
2
15
2
9
52
53
BK/RD
RD
2)
Mains supply circuit
BN
BU
4)
Luster terminal
MA500
+
-
NO
COM
NC
8)
Door contact
Connecting cable lock
7)
1)
6 A
BN
BU
GN/YE
5
6
14
2
OR
15
L1
N
PE
FTÖ331U
+
2
-
8
NO
7
AKRR
COM
6
NC
5
NO
4
RR
COM
3
NC
Caution: Disconnect red bridge circuit (1-7)
in FTÖ 331U.
COM motor lock
NO motor lock
COM handle
NO handle
Solenoid -
Solenoid +
X108 (blue terminal strip)
24 V DC
COM output 1
NC output 1 (OM drive)
GND
24 V DC
COM output 2
NO output 2 (Short-term unlock)
X107 (green terminal strip)
24 V DC
GND
Indirect release
Indirect release
red/blue wire
grey/pink wire
Option 2
2
22
Option 1
21
1
2
51
50
2
1
7
8
5)
green wire
blue wire
black wire
red wire
For instructions regarding the connection diagram see page 43.
In order to couple the lock for the duration of the short-term release time set on the
door control unit, set output 2 of TST320 on "short-term unlock".
With the variant, key-operated push button on the door control unit is not necessary.
Changeover of the mode of operation (unlock/lock/short-term unlock) takes place via the
motor lock.
(Details from the state "unlock". In the case of an unlocked system, it is, first of all, locked.)
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
66
Terminal connection diagram
Options:
1: Connect output 1 of TST320 to the magnet inductor (red wire) if the HLS should be in
"coupled" and the door control unit is in "permanent unlock".
For this function, set output 1 on "OM drive".
2: The output "handle" (green + blue wire) of HLS can be connected to an adjustable
input of TST320 (terminals 2 + 52 or 53).
Mode of operation: "Pre-alarm" is triggered off when the handle is activated in a locked
door control unit.
For this function, set the input of TST on "handle".
6.13.2Motor lock MLS
TST320 on MST210
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
TST320
X108 (blue terminal strip)
24 V DC
COM output 1
NC output 1 (OM drive)
GND
24 V DC
COM output 2
NO output 2 (door-o. op.cur.)
X106 (orange terminal strip)
24 V DC
Input 1 (Short-term unlock)
Input 2 (Short-term unlock)
Input 3 (handle)
NT 6.3.24, mains supply circuit
RD
BK/RD
2
22
Option 1
21
1
2
51
50
2
9
52
53
1)
MST210, motor control system
OR
X7
X6
X8 Option 2
X2
+
-
1
3
2
5
2
4
24
25
Option 3
17
16
1)
L
N
GND in
24-V-DC supply unit
24 V DC
Release
24 V DC
Day / night
COM motor lock
NO motor lock
COM handle
NO handle
1) Voltage supply of MST210 from the separate mains supply circuit NT6.3-24 No. 109637 or from
the control system TST320.
Pay attention to the maximum power input of TST320.
Options:
1: Connect output 2 of TST320 to the input "day/night" of MST210 if the door control unit
is in "permanent unlock" and the motor lock must be on the mode of operation "day".
For this function, set output 1 on "OM drive".
2: The output "motor lock" (terminals 24 + 25) of MST210 can be connected to an
adjustable input of TST320 (terminals 2 + 52 or 53).
Mode of operation: A short-term release is triggered on the door control unit when the
cylinder is activated using the key.
3: The output "handle" (terminals 16 + 17) of MST210 can be connected to an adjustable
input of TST320 (terminals 2 + 52 or 53).
Mode of operation: "Pre-alarm" is triggered off when the handle is activated in a locked
door control unit.
For this function, set the input of TST on "handle".
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
67
Terminal connection diagram
MST210, motor lock control system
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
Input 1 (Short-term unlock)
9
2
24 V DC
Input 3 (handle)
53
52
Input 2 (motor lock)
X104 (red terminal strip)
GND supply unit
CAN-H (GEZE-bus)
46
3
24-V-DC supply unit
Mains supply circuit
Luster terminal
BK/RD
RD
BN
BU
6 A
2)
1)
BN
BU
L1
N
GN/YE
PE
4)
+
-
NO
COM
NC
2
8
7
6
MA500
Door contact
FTÖ331U
+
-
NO
COM
NC
5
14
6
2
TST320
7)
X107 (green terminal strip)
24 V DC
2
Indirect release
7
1
GND
8
Indirect release
5)
AKRR
RR
5
4
3
NO
COM
NC
15
OR
Caution: Disconnect red bridge circuit (1-7)
in FTÖ 331U
8)
X108 (blue terminal strip)
24 V DC
2
NC output 1 (OM drive)
21
22
COM output 1
24 V DC
2
GND
NO output 2 (door-o. op.cur.)
50
51
COM output 2
X7
GND in
3
24-V-DC supply unit
X6
24 V DC
2
5
Release
24 V DC
2
4
Day / night
Option 1
X8
COM motor lock
24
25
NO motor lock
X2
COM handle
17
16
NO handle
Option 2
1
1
1
1
TST320 on MST210 (control via the motor lock)
For instructions regarding the connection diagram see page 43.
With the variant, key-operated push button on the door control unit is not necessary.
Changeover of the mode of operation (unlock/lock/short-term unlock) takes place via the
motor lock.
(Details from the state "unlock". In the case of an unlocked system, it is, first of all, locked.)
Options:
1: Connect output 2 of TST320 to the input "day/night" of MST210 if the door control unit
is in "permanent unlock" and the motor lock must be on the mode of operation "day".
For this function, set output 1 on "OM drive".
2: The output "handle" (terminals 16 + 17) of MST210 can be connected to an adjustable
input of TST320 (terminals 2 + 52 or 53).
Mode of operation: "Pre-alarm" is triggered off when the handle is activated in a locked
door control unit.
For this function, set the input of TST on "handle".
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
68
Terminal connection diagram
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
Input 1 (Short-term unlock)
9
2
24 V DC
Input 3 (fire alarm system)
53
52
Input 2 (Short-term unlock)
X104 (red terminal strip)
GND supply unit
1
3
24-V-DC supply unit
Mains supply circuit
Luster terminal
BK/RD
RD
BN
BU
6 A
1)
BN
BU
L1
N
GN/YE
PE
1
2
8
7
6
FTÖ331U
NO
COM
NC
5
6
Caution: Disconnect red bridge circuit (1-7)
in FTÖ 331U
Short-term release via
push button, key-operated push button,
access control ...
X108 (blue terminal strip)
24 V DC
2
21
22
24 V DC
2
1
GND
50
51
X107 (green terminal strip)
24 V DC
2
Indirect release
7
1
GND
8
Indirect release
5)
(Option)
AKRR
RR
5
4
3
NO
COM
NC
NO output 1 (OM drive)
COM output 1
NO output 2 (drive control)
COM output 2
3)
X102
Plug connector for GEZE
Key-operated push button
ribbon cable
GEZE key-operated push button
TST320
without Illumination
Connection to
TST320 X102
KB
24 V DC
2
20
Contact sensor authorised
PS-GF
DO Permanent opening
9
8
AUT Automatic
2
24 V DC
2)
4)
TZ320SN, TZ
DCU5, control system TSA160NT
6)
5051221222
X108
1
X108
(blue)
8712
X107
X107
(green)
5614152295253
X106
X106
(orange)
414245463
X104
1
X104
(red)
1
J1
J2
2
3
4
J1 J2
F1
F1
6.14Revolving door drive system
6.14.1Revolving door drive system TSA160NT
Furthermore, pay attention to the connection diagram DCU5 to TSA160NT, Mat.No. 120062.
TSA160NT on TZ320
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
69
Terminal connection diagram
1) The mains fuse takes place on site.
2) In 2-flanked, connect the door drive systems to the control system of the operation flank.
3) Set output 1 on "door drive system mode of operation".
4) Set output 2 on "door drive system control".
5) Bridge circuit set in the original condition.
Remove the bridge circuit during an indirect release.
6) Disconnect the internal program switch.
Mode of operation:
RWS locked
The revolving door drive system is in the mode of operation "night".
The drive system is controlled by actuating the short-term release on the TZ320.
The door closes and the door control unit locks after the lapse of the hold-open time set
on the drive system.
On the drive system, set the short-term unlock time of TZ320 longer than the hold-open
time.
RWS unlocked
The drive system is in the mode of operation "automatic".
The control devices connected to the drive system are active.
No program switch may be connected to the drive system because the door control unit
takes over the control of the modes of operation.
From software version DCU5 V2.1 and hardware version DCU500 Rev. B, the program
switches DPS and TPS can be connected to the drive system.
In connecting the program switch DPS or TPS, connect output 1 of the door control unit
(OM drive) to the adjustable input PE1 or PE2.
On the DCU5, set the input PE on "night".
On TZ320, set output 1 on "opener".
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
70
X106 (orange terminal strip)
Locking mechanism +
5
Door locked
14
6
Locking mechanism -
Door closed
15
2
24 V DC
Input 1 (Short-term unlock)
9
2
24 V DC
Input 3 (fire alarm system)
53
52
Input 2 (short-term unlock)
X104 (red terminal strip)
GND supply unit
3
1
24-V-DC supply unit
Mains supply circuit
Luster terminal
BK/RD
RD
BN
BU
6 A
1)
BN
BU
L1
N
GN/YE
PE
2
1
8
7
6
FTÖ331U
NO
COM
NC
5
6
Caution: Disconnect red bridge circuit (1-7)
in FTÖ 331U
X108 (blue terminal strip)
24 V DC
2
21
22
24 V DC
2
1
GND
50
51
X107 (green terminal strip)
24 V DC
2
Indirect release
7
1
GND
8
Indirect release
5)
AKRR
RR
5
4
3
NO
COM
NC
NO output 1 (OM drive)
COM Output 1
NO Output 2 (drive control)
COM Output 2
3)
X102
Plug connector for GEZE
Key-operated push button
ribbon cable
GEZE key-operated push button
TST320
without Illumination
Connection to
TST320 X102
KB
24 V DC
2
20
Contact sensor authorised
PS-GF
DO Permanent opening
9
8
AUT Automatic
2
24 V DC
2)
4)
TZ320SN, TZ
DCU5, control system TSA160NT
6) 15)
Burglar alarm system / hazard alarm system /
smoke and heat venting system
NC
COM
TOE
TOEA
31
32
TOEB
+ 24V in
2
- GND in
Mains shut-off circuit board Nr. 067581
Reset
2
1
1
Reset
14)
11)
12)
2)
2)
13)
5051221222
X108
1
X108
(blue)
8712
X107
X107
(green)
5614152295253
X106
X106
(orange)
414245463
X104
1
X104
(red)
X102
X102
1
J1
J2
2
3
4
J1 J2
F1
F1
Terminal connection diagram
TSA160NT inverse on TZ320
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
1) The mains fuse takes place on site.
2) In 2-flanked, connect the door drive systems to the control system of the operation flank.
3) Output 1 = "door drive system mode of operation".
4) Output 2 = "door drive system control".
5) Bridge circuit set in the original condition.
Remove the bridge circuit in the event of an indirect release.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
71
Terminal connection diagram
X2.1
GND
NO Output 1
23
2
1
24 V DC
25
24
COM output 1
26
27
29
28
X3.1
GND supply unit
2
30
24 V DC supply unit
32
31
33
34
36
35
37
(OM drive)
(Closer)
NO Output 2
COM output 2
(Drive control)
(Closer)
NO Output 3
COM output 3
(Locked)
(Closer)
NC output 3
38
NO output 4
COM output 4
(Door state)
(Closer)
NC output 4
NO output 5
COM output 5
(Sabotage)
(Closer)
NC output 5
NO output 6
COM output 6
(System fault)
(Closer)
NC output 6
PS-GS
AUT Automatic
8
2
24 V DC
KB
24 V DC
2
20
Contact sensor authorised
PS-GS
AUT Automatic
8
2
24 V DC
KB
24 V DC
2
20
Contact sensor authorised
KL220 KL
OR
1
DCU5, control system
DCU5, control system
6) Disconnect the internal program switch.
No external program switch may be connected to the drive system.
10)In combining RWS with inverse drive system, the inverse drive system takes over the control of
the emergency exit opener.
In 2-flanked Connect the drive systems of the emergency exit openers to the corresponding drive
system respectively.
11)Bridge the reset input.
12)Parameter "TZ setting" - "inverse door drive" = "available"
13)Output 3 = "fire alarm system" and "low-active"
When setting, the following sequence must be take into consideration:
1. Set input on "disabled".
2. Connect opener contact.
3. Set input on "low-active".
14)On the drive system, set parameter "9" (door opener) on the value "02" (standby current door
opener) or "05" (standby current with tension compression before opening).
15)On the drive system, set parameter "16" (type of drive system) on the value "01" (TSA160NT
inverse).
Voltage supply of the mains shut-off circuit board takes place via terminals 5 + 6 of
TST320. The emergency exit opener is also supplied via terminals 5 + 6. For control by
means of the drive system, supply via the "output TOE" of the drive system is
uninterrupted.
In actuating the emergency button, the F-shut-off circuit board is switched off and the
emergency exit opener is disconnected from the mains. The door opens via spring tension.
Optionally, it can be set on the drive system if the drive system should keep the door shut
in a closed position (parameter 17, solenoid valve).
TSA160NT on KL220 terminal box
Use outputs 1 - 6 of terminal box if there are insufficient outputs on TST320 for TSA
connection. The setting of the outputs is identical with the settings of the door control unit.
Use the terminals COM and NO in outputs with change-over relay (outputs 4, 5 and 6).
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
72
Terminal connection diagram
Drive system disconnection in a locking system
TSA160NT
End position push button
locking position
DCU5
PE1
5)
2 24 V DC
51 PE1
5) If "locking position" is used for the end position push button, set parameter "12" (input PE1) on
"01" ("locking position").
Without end position push button, set parameter "12" on "00" (default setting).
The safety sensor beads are active for 10 seconds after the door had started the closing
operation if the door control unit is actuated in a locked state (drive system in the mode of
operation "night").
Shutdown the drive system in a closed position in order to avoid further unintended
activations and in order not to trigger off the alarm state. The auxiliary limit switch unit No.
071154 is necessary for this function.
Permanent opening via an internal program switch
DCU5, control system TSA160NT
2)
Switch position "0"
Switch position "2"
Switch position "1"
DO permanent opening
AUT Automatic
24 V DC
24 V DC
Contact sensor authorised
TST320, TZ320
X108 (blue terminal strip)
24 V DC
COM output 1
NO output 1 (OM drive)
GND
24 V DC
COM output 2
NO output 2 (drive control)
Internal program switch
WH
BN
GN
2)
PS-GF
2
3)
4)
22
21
1
2
51
50
9
8
2
KB
2
20
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
2) In 2-flanked, connect the door drive systems to the control system of the operation flank.
3) Set output 1 on "door drive system mode of operation".
4) Set output 2 on "door drive system control".
Use the internal program switch (in connection with RWS disconnected) or a digital
program switch in order to adjust the mode of operation "permanent opening" on the drive
system.
Mode of operation:
RWS locked
Drive system in the mode of operation "night"
Program switch without function
RWS unlocked
Internal program switch on position "1" = drive system "permanent opening"
Internal program switch on position "2" = drive system "automatic"
Internal program switch on position "0" = drive system "night"
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
73
Terminal connection diagram
Locking mechanism +
5
6
Door locked
14
Locking mechanism -
Door closed
15
2
24 V DC
Input 1 (Short-term unlock)
9
2
24 V DC
Input 3 (fire alarm system)
53
52
Input 2 (Short-term unlock)
X104 (red terminal strip)
GEZE key-operated push button
GND supply unit
3
1
24-V-DC supply unit
Mains supply circuit
Luster terminal
BK/RD
RD
BN
BU
6 A
1)
BN
BU
L1
N
GN/YE
PE
2
1
8
7
6
FTÖ331U
NO
COM
NC
5
6
Caution: Disconnect red bridge circuit (1-7)
in FTÖ 331U
Short-term release via
push button, key-operated push button,
access control ...
X108 (blue terminal strip)
24 V DC
2
21
22
24 V DC
2
1
GND
50
51
X107 (green terminal strip)
24 V DC
2
Indirect release
7
1
GND
8
Indirect release
5)
(Option)
AKRR
RR
5
4
3
NO
COM
NC
NO output 1 (OM drive)
COM output 1
NO output 2 (drive control)
COM output 2
3)
X102
Plug connector for GEZE
Key-operated push button
ribbon cable
TST320
without Illumination
Connection to
TST320 X102
KB
24 V DC
2
20
Contact sensor authorised
PS
DO permanent opening
9
8
AUT Automatic
6
NA night
2)
4)
TZ320SN, TZ
2
24 V DC
6)
DCU2, control system Slimdrive EMD
X106 (orange terminal strip)
5051221222
X108
1
X108
(blue)
8712
X107
X107
(green)
5614152295253
X106
X106
(orange)
414245463
X104
1
X104
(red)
1
J1
J2
2
3
4
J1 J2
F1
F1
6.14.2Revolving door drive system Slimedrive EMD
Furthermore, pay attention to the connection diagram DCU2 to Slimdrive EMD,
Mat.-No. 107579.
Slimdrive EMD on TZ320
1) The mains fuse takes place on site.
2) In 2-flanked, connect the door drive systems to the control system of the operation flank.
3) Set output 1 on "door drive system mode of operation".
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
74
Terminal connection diagram
X2.1
GND
NO Output 1
23
2
1
24 V DC
25
24
COM Output 1
26
27
29
28
X3.1
GND supply unit
2
1
30
24-V-DC supply unit
32
31
33
34
36
35
37
(OM drive)
(Closer)
NO Output 2
COM Output 2
(Drive control)
(Closer)
NO Output 3
COM Output 3
(Locked)
(Closer)
NC Output 3
38
NO Output 4
COM Output 4
(Door state)
(Closer)
NC Output 4
NO Output 5
COM Output 5
(Sabotage)
(Closer)
NC Output 5
NO Output 6
COM Output 6
(System fault)
(Closer)
NC Output 6
DCU2
PS
AUT Automatic
8
2
24 V DC
KB
24 V DC
2
20
Contact sensor authorised
DCU2
PS
AUT Automatic
8
2
24 V DC
KB
24 V DC
2
20
Contact sensor authorised
KL220 KL
OR
4) Set output 2 on "door drive system control".
5) Bridge circuit set in the original condition.
Remove the bridge circuit in the event of an indirect release.
6) Disconnect the internal program switch.
Mode of operation:
RWS locked
The revolving door drive system is in the mode of operation "night".
The drive system is controlled by actuating the short-term release on the TZ320.
The door closes and the door control unit locks after the lapse of the hold-open time set
on the drive system.
On the drive system, set the short-term unlock time of TZ320 longer than the hold-open
time.
RWS unlocked
The drive system is in the mode of operation "automatic".
The control devices connected to the drive system are active.
The program switches DPS and TPS can be connected to the drive system (see page 76).
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungTerminal connection diagram
Slimdrive EMD on KL220 terminal box
Use outputs 1 - 6 of the terminal box if there are insufficient outputs on TST320 for the
connection of EMD. The setting of the outputs is identical with the settings of the door
control unit.
Use the terminals COM and NO for outputs with change-over relay (outputs 4, 5 and 6).
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
75
Terminal connection diagram
KB
24 V DC
2
20
Contact sensor authorised
PS
DO Permanent opening
9
8
AUT Automatic
6
NA Night
2)
DCU2, control system Slimdrive EMD
2
24 V DC
X108 (blue terminal strip)
24 V DC
2
21
22
24 V DC
2
1
GND
50
51
NC output 1 (OM drive)
COM output 1
NO output 2 (drive control)
COM output 2
6)
4)
TST320, TZ320
Display program switch DPS and button program switch TPS on DCU2
2) In 2-flanked, connect the door drive systems to the control system of the operation flank.
4) Set output 2 on "door drive system control".
6) Set output 1 on "door drive system mode of operation" and "opener".
Only the button program switch (TPS) and the display program switch (DPS) can be
connected to the drive system.
The DPS is not functional if the door control unit is locked.
The mode of operation set on the DPS applies if the door control unit is unlocked.
1. Connect output 1 of TZ320 to the terminal "night" of EMD.
2. Set output relay 1 on "opener".
Permanent opening via an internal program switch
,
DCU2, control system Slimdrive EMD
2)
Switch position "0"
Switch position "2"
Switch position "1"
DO Permanent opening
AUT Automatic
NA Night
24 V DC
24 V DC
Contact sensor authorised
TST320, TZ320
X108 (blue terminal strip)
24 V DC
COM Output 1
NO output 1 (OM drive)
GND
24 V DC
COM Output 2
NO Output 2 (drive control)
Internal program switch
WH
BN
GN
2)
PS
2
3)
4)
22
21
1
2
51
50
9
8
6
2
KB
2
20
2) In 2-flanked, connect the door drive systems to the control system of the operation flank.
3) Set output 1 on "door drive system mode of operation" and "closer".
4) Set output 2 on "door drive system control".
Use the internal program switch (in connection with RWS disconnected) or a digital
program switch in order to adjust the mode of operation "permanent opening" on the drive
system.
Mode of operation:
RWS locked
Drive system in the mode of operation "night"
Program switch without function
RWS unlocked
Internal program switch on position "1" = drive system "permanent opening"
Internal program switch on position "2" = drive system "automatic"
Internal program switch on position "0" = drive system "night"
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
76
Annex
7Annex
7.1Checklist for commissioning
Electric power supply is in order
Top edge of all push buttons between 850 mm and 1200 mm from top of
floor
Appropriate marking for all emergency buttons
Cable laying according to DIN VDE 0833, sabotage protected
All screws of the magnetic fixing are tightened
Rubber buffer on the screws of the durance striker plate is in order
All cables are connected, idle cables are insulated
Hazard alarm system connection, release is functional
Jumper for indirect release is properly plugged (J1, J2)
Illumination in the emergency button flashes
The function "emergency button" is in order
The function "main emergency button" is in order
Sabotage contacts are functional
Unlock via the key-operated push button is functional
Lock via the key-operated push button is functional
Automatic locking mechanism via the burglar alarm system is functional
Feedback signal from the solenoid and/or door opener is functional
Auxiliary door contacts are functional
LED wing open/closed is functional
LED door locked/unlocked is functional
LED alarm/fault is functional
Bus is functional, jumper is properly plugged (J3)
Relay "door control unit" is functional (depending on the programming)
Relay "terminal box" is functional (depending on the programming)
Sluice function is in order
Solenoids are functional, lock door opener
The period "pre-alarm" is in order
The period "short-term release" is in order
The period "alarm" is in order
The buzzer is functional (depending on the programming)
All access possibilities are in order (access control etc.)
The emergency exit is in order
Outer key-operated push button is in order
External alarm device / external alarm device combination is functional
Emergency-power supply USV is functional
Tableau unit is functional, visualisation is in order
Signal messages on the superordinate building control
Correct cable laying in indirect release
YesNoUnavailable
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungAnschlussplanAnnex
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
77
Annex
7.2Glossary
Direct release (according to EltVTR)
Security-relevant interruption of electric power supply to the electric locking mechanism via
an opener contact by actuating the emergency button.
Indirect release (according to EltVTR)
Security-relevant interruption of electric power supply to the electric locking mechanism if
further switching operation, which then interrupts the electric power supply to the electric
locking mechanism, is triggered via an opener contact by actuating the emergency button.
Unlock (according to EltVTR):
No security-relevant interruption of electric power supply to the electric locking
mechanism, e.
Emergency unlock (according to EltVTR):
No security-relevant interruption of electric power supply to the electric locking
mechanism, e.
g. via a key-operated push button.
g. via a hazard alarm system (GMA) or a similar automatic tripping device.
Pre-alarm:
An acoustic signal, which should point out to the user that the timeout has started, is
released if the release time is exceeded during an inspection. The duration of the prealarm is adjustable within the range of 0 sec. – 10 min. The door is automatically closed
and the pre-alarm is reset if the door is closed during a pending pre-alarm.
Door alarm:
Likewise, the so- called door alarm is triggered off if the pre-alarm time is exceeded. It can
be reset via the integrated key-operated push button or all inputs "short-term unlock" as
well as via the tableau TE220 or the visualisation VAT220SN. If the door is closed during a
pending door alarm, it is locked and can only be unlocked again when the alarm has been
reset (except for the actuation of the emergency button). Door alarm is also triggered off
after a "break-in through the door" if the door is opened by force without previous release.
Abort of the short-term release:
During abort, the door locks ahead of time if the door is closed and the release time is
unexpired. Consequently, accessibility for unauthorised person can be prevented after
somebody had passed through the door.
The setting abort can be disabled via the service menu. Then, the door always remains
unlocked for the duration of the preset time. The release time can be aborted by
reactivation via the key-operated push button.
Post trigger of the short-term release:
The release time restarts if a short-term release is triggered again during the release time.
The setting post trigger can be disabled via the service menu. In a running release
time, the system locks again if a short-term release is triggered once again with the internal
key-operated push button or a programmable input.
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
78
Annex
7.3Data sheets
7.3.1TZ320UP door control unit
Technical data
Device designationTZ320UP door control unit (standard variant)
TZ322UP door control unit (without emergency button)
FunctionMonitoring and control of an escape route door
Dimensions55 x 55 x 47(B x H x T)
B x H: Helmet
T: Distance top edge bearing ring to fitted terminals
InstallationIn UP-Dose, 60 mm, base range 62.5 mm
Operating voltage24 V DC (±10%)
Separate power input100 mA in 24 V DC (without peripherals)
Overall power input1 A / 24 V (dependent on the mains supply circuit in use)
Protection classII according to EN 60 950 (in installed state)
Range of applicationDry rooms
Climate conditions-10 to 50 °C
Guidelines"Guidelines on electric locking systems of doors in escape routes
(EltVTR) - version December 1997"
Packaging contentsControl unit, connection terminals and spare fuse
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungAnschlussplanAnnex
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
79
Annex
7.3.2TZ320AP door control unit
Technical data
Device designationTZ320AP door control unit (standard variant)
TZ322AP door control unit (without emergency button)
TZ323AP door control unit (standard variant, rotated 180°)
TZ325AP door control unit (without emergency button, rotated
180°)
VariantsBSN: with illuminated emergency exit shield, key-operated push
button and mains supply circuit
BN: with illuminated emergency exit shield and mains supply circuit
SN: with key-operated push button and mains supply circuit
N: with mains supply circuit
BS: with illuminated emergency exit shield and key-operated push
button
B: with illuminated emergency exit shield
S: Key-operated push button
FunctionMonitoring and control of an escape route door
Dimensions197 x 72 x 88(B x H x T)
InstallationWall mounting
Operating voltageVariants with mains supply circuit: 230 V 50Hz
Variants without mains supply circuit: 24 V DC (±10%)
Separate power input100 mA in 24 V DC (without peripherals)
Overall power inputVariants with mains supply circuit: 800 mA
Variants without mains supply circuit: max. 1A (dependent on the
mains supply circuit in use)
Protection classVariants with mains supply circuit: I according to EN 60 950
Variants without mains supply circuit: II according to EN 60 950
Range of applicationDry rooms
Climate conditions-10 to 50 °C
Guidelines"Guidelines on electric locking systems of doors in escape routes
(EltVTR) - version December 1997"
Packaging contentsMounting plate, pre-assembled housing, mounting accessories,
connection terminals and spare fuse
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
Emergency exit shield FWS320UP B (illuminated)
FunctionEmergency exit shield
Dimensions55 x 55 x 16(B x H x T)
B x H: Emergency exit shield
T: Distance top edge bearing ring to the fitted ribbon cable
InstallationIn UP-Dose, 60 mm, base range 62.5 mm
Operating voltage24 V DC (±10 %) (only illuminated variant)
Power inputMax. 30 mA / 24 V (only illuminated variant)
Protection classII according to EN 60 950 (in installed state; only illuminated
variant)
Range of applicationDry rooms
Climate conditions-10 to 50 °C
Packaging contentsEmergency exit shield module, green frame, ribbon cable (only
illuminated variant)
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungAnschlussplanAnnex
white-aluminium
FunctionKey-operated push button with sabotage monitoring
Dimensions55 x 55 x 41(B x H x T)
B x H: Covering
T: Distance top edge bearing ring to the fitted terminal
InstallationIn UP-Dose, 60 mm, base range 62.5 mm
Operating voltage24 V DC (±10 %)
Power inputMax. 1 A / 24 V (only illuminated variant
Protection classII according to EN 60 950 (in installed state)
Range of applicationDry rooms
Climate conditions-10 to 50 °C
Packaging contentsKey-operated push button module, connection terminal and spare
fuse
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
81
7.4Service menu - service terminal ST220
1. Menu level2. Menu level3. Menu level4. Menu level5. Menu level6. Menu levelChoice (default setting)
TZ parameterShort-term
unlock
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
Custom outputsTZ output1Configuration TZ1ChoiceDoor state
Contact TZ1ChoiceOpener
83
Handle
Public holiday
(Short-term unlock)
Low-active
Disabled
(High-active)
OM control
Drive control
Alarm
Release
Release direct
Release indirect
Door alarm
Sabotage alarm
Pre-alarm
System fault
Traffic light red
Traffic light green
Door-o. op.cur.
Locked
Emergency button
Short-term unlock
Collective alarm
Coll. locked
Coll. closed
(Alarm)
Closer
Disabled
(Closer)
Annex
Zu diesem DokumentSicherheit und VerantwortungInstallation und MontageInbetriebnahmeBedienungAnschlussplanAnnex
1. Menu level2. Menu level3. Menu level4. Menu level5. Menu level6. Menu levelChoice (default setting)
TZ output2Configuration TZ2ChoiceDoor-o. op.cur.
Contact TZ2Choice(Closer)
System
environment
Installation And Commissioning Instructions With Connection Diagram GEZE Door Control Unit
In accordance with the defined liability of the manufacturer for this
products in the Product Liability Act,
attention should be paid to the information contained in this brochure
(product information, intended use,
incorrect use, product performance,
product maintenance, duties to
supply information and instructions).
Non-observance exonerates the
manufacturer from his liability.
GEZE representative:
Der
Maßstab
unseres
Handelns
Material No. 132916 • Rev. 01-2009 • Drawing No. 35207-9-0955• Printed in Germany • Subject to change without prior notice