GEZE SECULOGIC T 320 Series, SECULOGIC T 320 UP, SECULOGIC T 320 AP Installation And Commissioning Instructions With Connection Diagram

GEZE SECULOGIC T 320
Emergency Exit System Terminal
EN
Installation And Commissioning
1
Content
1 In this document ...................................................................................................................................................3
1.1 Product description ......................................................................................................................................................................................3
1.2 Other documents ..........................................................................................................................................................................................3
1.3 Symbols and signs .........................................................................................................................................................................................3
2 Safety and liability ................................................................................................................................................4
2.1 Basic safety instructions .............................................................................................................................................................................4
2.2 Product liability ..............................................................................................................................................................................................4
3 Installation and assembly ...................................................................................................................................5
3.1 Requirements ..................................................................................................................................................................................................5
3.2 Install the terminal ........................................................................................................................................................................................5
4 Commissioning ......................................................................................................................................................5
4.1 Requirement ...................................................................................................................................................................................................5
4.2 Service mode ..................................................................................................................................................................................................5
4.3 Settings ............................................................................................................................................................................................................6
4.4 Terminal T 320 settings ................................................................................................................................................................................6
4.5 Description of basic functions ..................................................................................................................................................................7
SECULOGIC T 320
5 Operation .................................................................................................................................................................8
5.1 Control the terminal T 320 via key-operated push button ............................................................................................................8
5.2 Open the doors and trigger the alarm in an emergency ...............................................................................................................9
5.3 Cancel alarm ....................................................................................................................................................................................................9
5.4 Read out fault report (via TZ 320) ......................................................................................................................................................... 10
5.5 Read out alarm signal (via TZ 320)........................................................................................................................................................ 10
5.6 Correct fault .................................................................................................................................................................................................. 10
6 Connection diagram ..........................................................................................................................................11
6.1 Door control unit (terminals) ...................................................................................................................................................................11
6.2 Terminal T 320 ...............................................................................................................................................................................................12
6.3 Connection of external key-operated push button to T 320 ......................................................................................................13
7 Technical Data ......................................................................................................................................................14
7.1 Terminal T 320 UP ........................................................................................................................................................................................14
7.2 Terminal T 320 AP ........................................................................................................................................................................................15
2
SECULOGIC T 320
1 In this document
This instruction describes the installation, commissioning and connection of the GEZE Terminal T 320.
1.1 Product description
The GEZE terminal is part of the SecuLogic escape route system and secures and monitors electrically locked doors in bidirectional emergency routes. Doors along emergency routes are reliably safeguarded against unauthorised access in both emergency directions by the GEZE door control unit with Terminal T 320. Simultaneously, entry in emergency situations is ensured at all times via the integrated emergency button.
1.2 Other documents
Data sheets with technical data are included in delivery of the corresponding components. You will nd these data sheets and other documents as well as the detailed installation and commissioning instructions with connection diagram for the door control unit TZ 320 No. 131537 on the internet at www.geze.de/SecuLogic.
1.3 Symbols and signs
Warning notices
In these instructions warning notices are used to warn you about damage to person and property.
XX
Please always read and observe these warning notices.
XX
Follow all measures designated with the warning symbol and warning word.
Warning symbol
Warning word Meaning
WARNING
In this document
Danger for persons. Non-observance may lead to serious injury or death.
Further symbols and signs
In order to clarify the correct meaning, important information and technical information is highlighted.
Symbol Meaning
XX
"Important information"
"Additional information"
Symbol that indicates an action: You are required to do something here. Note the correct order where there is more than one step.
3
Safety and liability
2 Safety and liability
The GEZE terminal was designed according to state-of-the-art technology and recognised, safety-related regulations. However, there might be danger during installation and use. Therefore, pay attention to the following instructions.
2.1 Basic safety instructions
XX
Installation, commissioning and repairs may only be carried out by experts authorised by GEZE.
XX
Use only GEZE original parts for repair work.
XX
GEZE assumes no liability for damages resulting from unauthorised changes to the system.
XX
Primary safety measures take place on site.
XX
The standards VDE 0100 and VDE 0815 must be observed during cable routing.
XX
An expert must check the doors with electric locking mechanism in the escape routes once a year. The expert is to issue a certicate on the in-service inspection, which the operator has to show on demand to the building supervisory board. Inspection can be carried out by a GEZE service technician or a professional organisation authorised by GEZE.
XX
Furthermore, GEZE recommends that the operator inspects the escape route system monthly for externally identiable damages and defects. Such damages and defects, if existing, must be repaired immediately by a GEZE service technician or a professional organisation authorised by GEZE.
Intended Use
The GEZE door control unit is designed to control and monitor electrically locked emergency routes. External products may only be integrated after consulting GEZE.
SECULOGIC T 320
Contrary to intended use
The connection of products which were not expressly approved for use by GEZE is contrary to the intended purpose.
2.2 Product liability
à In accordance with the manufacturer's dened liability for its products in the Product Liability Act,
attention should be paid to the information contained here and in corresponding installation instructions and connection diagrams for the product (product information, intended use, incorrect use, product performance, product maintenance, obligations to supply information and instructions). Non-observance releases the manufacturer from its liability.
à Only experts authorised by GEZE may carry out installation, functional inspection and maintenance.
GEZE assumes no liability for damages resulting from unauthorised changes to the system.
à GEZE assumes no liability for combining with devices from other manufacturers. Use only GEZE original parts
for repair work and maintenance.
4
SECULOGIC T 320
3 Installation and assembly
WARNING!
Danger of electric shock.
XX
Installation may only be carried out by an expert authorised by GEZE.
XX
Check that the cables are disconnected before installation.
3.1 Requirements
à Cable routing is in accordance with GEZE cable diagram à Automatic circuit breakers as primary disconnection on the mains-side à Compliance with the VDE 0100 and VDE 0815 standards for the cable routing à Sabotage secured cable routing according to VDE 0833 (on-wall cables in the steel tube) à For in-wall plug socket variant installed near the door (depth 62.5 mm) with an installation height top of oor
of 850 mm to a maximum of 1200 mm for the emergency button
3.2 Install the terminal
Installation of the T 320 terminal is identical to installation for the door control unit TZ 320. Consult the installation instructions from the Installation and Commissioning Instructions No. 131537 or the Brief Instructions No. 139926. When using a T 320 terminal a TZ 320 is always required. The TZ 320 assumes control of the system.
Installation and assembly
4 Commissioning
4.1 Requirement
Before the rst commissioning of doors with electric locking mechanisms in the escape routes, correlation with verication of suitability is to be conrmed by means of a certicate issued by the manufacturer. An expert must also ensure that the electric locking mechanism is installed properly and operational (see checklist for commissioning in the TZ 320 instructions or in the inspection book). The door control unit TZ 320 must be in operation, and the connection between the door control unit and terminal must be set up according to the connection diagram (page 12). All settings for the terminal are implemented via the door control unit TZ 320.
4.2 Service mode
The service mode must be activated at the door control unit TZ 320 in order to set parameters on the terminal.
4.2.1 Switch on the service mode
Requirement:
à There is no alarm. à The burglar alarm system is disabled.
XX
Turn the key left and hold for approximately ten seconds.
à The right LED lights up green, the left and lower LEDs are o.
4.2.2 Switch o the service mode
XX
Do not make adjustments or select 'end of service mode' in the service menu for three minutes.
à The door control unit and terminal are in normal state again.
5
Commissioning
4.2.3 Connect the service terminal ST 220 with the door control unit
The service terminal is connected with the door control unit via an infrared interface.
SECULOGIC T 320
3
XX
Before covering the control unit, hold the service terminal and press the ON button for approximately one second.
à The service terminal is switched on.
XX
Press the ESC button.
à The rst level of the service menu is displayed.
4.3 Settings
All settings can only be implemented with the service terminal ST 220 via the TZ 320.
4.4 Terminal T 320 settings
A terminal connected to TZ 320 is automatically recognised and switched on. The terminal can be switched o via the service menu.
4.4.1 Switch on terminal
1 Service terminal ST 220
2 Infrared interface to TZ 320
3 ESC button
XX
In the service menu, select system environment > terminal > terminal available.
à The upper display line of the service terminal shows the selected value.
4.4.2 Switch o terminal
XX
In the service menu, select system environment > terminal > terminal unavailable.
à The upper display line of the service terminal shows the selected value.
4.4.3 Set sabotage contact
XX
In the service menu, select system environment > sabotage contacts.
XX
To evaluate sabotage contacts, select TT > sabotage contact TT active : yes.
XX
To not evaluate sabotage contacts, select TT > sabotage contact TT active : no.
4.4.4 Short-term unlock and alarm setup
The settings for short-term unlock and alarm setup for the terminal are implemented by the door control unit.
6
SECULOGIC T 320
4.5 Description of basic functions
4.5.1 Short-term unlock
Short -term unlock is the authorised, time-limited release of the emergency route locking device. During the short -term unlock time the door can be passed through without triggering an alarm. It is triggered via the inter­nal key-operated push button or an external control device connected to the 'short-term unlock' input.
4.5.2 Abort with short-term unlock
With continuous short-term the door locks ahead of time when the door is closed before expiry of the short -term unlock time. This prevents accessibility for unauthorised persons after somebody has passed through the door.
4.5.3 After-trigger with short-term unlock
The unlock time restarts if a short-term unlock is triggered again during the release time.
4.5.4 Pre-alarm
If the release time is exceeded during passing through, an acoustic signal is output which informs the user that the short -term unlock time has been exceeded. If the door is closed during a pending pre-alarm it is automati­cally locked and the pre-alarm is reset.
Commissioning
4.5.5 Door alarm
The door alarm is triggered if the pre-alarm time is exceeded. The door alarm must be reset via the internal key switch or via a short-term release. If the door is closed during a pending door alarm, it is locked and can only be unlocked again when the alarm has been reset (except with actuation of the emergency button or with emergency unlock). The door alarm is also triggered with a 'door break-in'.
4.5.6 Unlocked
The current supply to the interlocking element is permanently interrupted. The door can be passed through without triggering an alarm.
4.5.7 Locked
The interlocking element is fed with current via the door control unit. The emergency route locking device is 'active' and passing through for unauthorised persons is only possible via the emergency button (alarm is triggered).
4.5.8 Emergency unlock
The TZ 320 can be emergency unlocked via the re alarm system or hazard alarm system (burglar alarm system/ hazard alarm system/smoke and heat venting system). This is a non security-relevant interruption of current supply to the interlocking element.
4.5.9 Direct release (according to EltVTR)
Security-relevant interruption of electric power supply to the electric locking mechanism via an opening contact by actuating the emergency button.
4.5.10 Indirect release (according to EltVTR)
Security-relevant interruption of electric power supply to the electric locking mechanism if a further switching op­eration is triggered upon activating the emergency button via the opening contact which then interrupts power supply to the electric locking mechanism.
7
Operation
5 Operation
SECULOGIC T 320
1 'Locking' LED
2 'Door state' LED
3 'Alarm' LED
4 Emergency button
No. Display
1
2
3
Colour Meaning
Red Locked Red ashing (every second) Sluice allocated Red ashing (every 2 seconds) Locked via burglar alarm system Red ashing (3 seconds on, 1 second o) Locked level Green Unlocked Green ashing (every second) Short-term unlock Green ashing (every 2 seconds) Unlocked via time-switch Green ashing (3 seconds on, 1 second o) Passive sluice Red Door closed Green Door open Yellow Alarm Yellow ashing (every second) Pre-alarm Yellow ashing (every second) Fault
5.1 Control the terminal T 320 via key-operated push button
Unlock door
When unlocking, the interlocking elements are disconnected by an authorised person. The door can be opened.
XX
Turn the key left and hold for approximately one second.
à LED 1 ashes green. The door is unlocked.
Note
The 'Unlock' function can be disabled via the service menu:
system environment > SCT conguration > unlock by SCT activate : yes/no.
Lock door
When locking, the interlocking elements are engaged by an authorised person. The door cannot be opened.
XX
Turn the key to the right.
à LEDs 1 and 2 light up red. The door is locked.
Unlock door temporarily (short-term unlock)
During the short-term unlock the door is unlocked for a settable time by an authorised person. The door is unlocked again after expiry of the unlock time.
à If the door is not closed after expiry of the unlock time, the pre-alarm is triggered à If the door is closed before expiry of the unlock time, the door is locked again (abort) à If a new short-term release is triggered during the unlock time, the unlock time starts over again (post trigger)
XX
Turn the key to the right.
à LED 1 ashes green.
8
SECULOGIC T 320
5.2 Open the doors and trigger the alarm in an emergency
By actuating the emergency button, the interlocking elements on the corresponding door are switched o (indirect release via TZ 320).
XX
Press emergency button. à LED 1 lights up green and LED 3 lights up yellow. The door is unlocked. à The alarm is triggered.
5.3 Cancel alarm
The alarm remains active at the door control unit until the cause of the alarm is eliminated and the alarm on the door control unit or terminal is acknowledged.
5.3.1 Reset emergency button
After the emergency situation has been eliminated the emergency button must be reset.
XX
Remove the cover of the emergency button.
XX
Turn the emergency button to the right. à The emergency button returns to normal state.
XX
Replace cover.
XX
Acknowledge alarm.
Operation
5.3.2 Acknowledge alarm
Precondition:
à The cause of the alarm is eliminated. à Reset alarm is displayed in the service terminal.
Acknowledge alarm and lock door
Acknowledge alarm and unlock door
The non security-relevant alarms emergency unlock, door alarm and sabotage alarm can also be acknowledged via the Lock and Unlock functions on the TE 220 and VAT 220. The door alarm can also be acknowledged via the short-term unlock input of the TZ 320 or KL 220.
XX
Turn the key to the right.
XX
Turn the key left and hold for approximately one second.
A sabotage alarm can only be acknowledged 30 seconds after the cause of the alarm has been eliminated. For the duration of the sabotage time the TZ 320 and T 320 are primarily locked. Release via the emergency button is possible.
If the alarm cannot be acknowledged by pressing the key-operated push button the a new alarm is possibly pending.
XX
Check which alarm/fault is pending with the service terminal and correct with the following tables.
9
Operation
5.4 Read out fault report (via TZ 320)
Faults in the system are indicated via ashing of LED 3.
XX
Connect the service terminal with the door control unit.
à The fault report is shown on the display of the service terminal.
XX
Find out the cause of malfunction and correct the fault with the aid of the following table. The table only contains faults that can be caused by the Terminal T 320. Please refer to the TZ 320 user manual for further fault reports.
Fault report Cause Remedy TT communication Connection with door control unit is faulty
5.5 Read out alarm signal (via TZ 320)
Misuse of the system or emergency situations is indicated via alarm tones and lighting up of LED 3.
XX
Connect the service terminal to the door control unit and press the ESC button.
à The alarm signal is shown on the display of the service terminal.
XX
Establish the cause of the alarm and cancel the alarm with the aid of the following table. The table only contains alarm signals that can be caused by the Terminal T 320. Please refer to the TZ 320 user manual for further alarm signals.
Alarm signal Cause Remedy Sabotage alarm
sabotage contact TT Sabotage contact of the terminal is not
closed
sabotage time runs Sabotage time unexpired
Indirect release
EB TT pushed Indirect release via terminal
fuse failure Fuse F1 is defective
J1, J2 jumper for indirect release to TZ 320 falsely set
Acknowledge alarm Cause of the alarm eliminated
SECULOGIC T 320
XX
Switch o the terminal via the service menu
XX
Establish connection to the terminal
XX
Change the terminal
XX
Close contact
XX
Acknowledge alarm after expiry of the sabotage time
XX
Acknowledge alarm after expiry of the sabotage time
XX
Reset the emergency button on the terminal
XX
Change the fuse
XX
Conrm the emergency button of the T 320
XX
Reset the emergency button of the T 320
XX
Acknowledge alarm via the key-operated push button
5.6 Correct fault
Fault Cause Remedy Emergency button T 320
without function, no alarm signal available
By actuating the key­operated push button of the T 320 / TZ 320, all LEDs and the emergency button lighting go out
All LEDs are o despite power supply
10
J1J2 jumper for indirect release to TZ 320 falsely set
Ribbon cable incorrectly connected between SCT 320 and TZ 320 / T 320
F1 locking device of the TZ 320 is defective
XX
Disconnect power supply to system
XX
Set jumpers J1 and J2 to external power supply
XX
Connect power supply
à Alarm signal for indirect release is
displayed
XX
Conrm the emergency button of the T 320 and reset
XX
Acknowledge alarm
XX
Connect ribbon cable correctly
XX
Change the F1 fuse (GEZE Id-No. 138362, VE 10)
SECULOGIC T 320
6 Connection diagram
Door
Buzzer
state LED
Locking LED
Sabotage contact
Emergency button LED
Alarm LEDs
6.1 Door control unit (terminals)
Terminal connections
Plug and screw terminals, max. cable cross section: 1 mm²
Clamping eld Terminal Function (default setting) X100 1 GND supply
3 24 V DC supply unit 7 Indirect release + 24 V DC 8 Indirect release - GND 41 R5485-B, communication with door control unit TZ 320 42 R5485-A, communication with door control unit TZ 320
X103 Ribbon cable plug connector for GEZE key-operated push button
Programming interface
11
Connection diagram
Door control unit
6.2 Terminal T 320
Here connected to a TZ 320 SN.
SECULOGIC T 320
GEZE Key-operated push button
X104 (red terminal strip)
GND supply
24 V DC supply
X107 (green terminal strip)
24 V DC
GND
indirect release
indirect release
Connection to TST 320 X 102
Plug connector for GEZE key-operated push button or illumination
GEZE ribbon cable
Power supply unit
Important! Set jumper 1-2 of TZ 320 to external voltage supply.
2)
3)
Luster terminal
4)
Door terminal
1)
GEZE ribbon cable
GND supply
24 V DC supply
Indirect release +
Indirect release -
Connection to GEZE SCT 320
GEZE Key-operated push button SCT 320
Plug connector for GEZE key-operated push button or illumination
X106 (orange terminal strip)
Locking mechanism +
Locking mechanism -
Door locked
24 V DC
Door closed
24 V DC
Input 1 (short-term unlock)
Input 2 (short-term unlock)
Input 3 (Fire alarm system)
Instructions for the connection diagram
1) The mains fuse is implemented on-site.
2) GEZE power supply unit with TZ 320N UP = NET220. 500 mA max. 350 mA for periphery GEZE power supply unit with TZ 320N AP = NT19.2-24. 750 mA max. 650 mA for periphery Spatially separate the primary and secondary sides.
3) TZ 320N UP: Protection class II (do not connect protective conductor) TZ 320N AP: Protection class I with protective conductor test in accordance with VDE0100
4) In the on-wall variant, the luster terminal is located on the mounting plate.
5) The contact is closed in a closed door.
Door contact
or
5)
Short-term unlock via push button, key-operated push button, access control...
Caution! Disconnect red bridge (1-7) in FTÖ 331U.
12
SECULOGIC T 320
Simplied diagram of connection between the TZ 320 and T 320
Connection diagram
Sequence of terminals modied
TZ 320 Door control unit
X104 (red terminal strip)
X107 (green terminal strip)
GND 24 V DC Indirect release Indirect release
T 320 Door terminal
GND supply 24 V DC supply
Indirect release + Indirect release -
Important! Set jumper 1-2 of TZ 320 to external voltage supply.
6.3 Connection of external key-operated push button to T 320
Connection of the key switch to the T 320 is only possible via ribbon cable. If other key switches are to be connected the ribbon cable must be divided. 3 wires are required for the connection. The red wire and both adjacent wires. The other 3 wires have no function and must be insulated.
Key-operated push button
red wire of ribbon cable
COM unlock lock
13
Technical Data
7 Technical Data
7.1 Terminal T 320 UP
Terminal T 320 UP Function Monitoring and control of a door in bidirectional emergency routes
Dimensions 55 x 55 x 37 mm (W x H x D)
Installation in ush-mounted socket, ø 60 mm, depth 62.5 mm Operating voltage 24 V DC (± 10 %) Current consumption 100 mA at 24 V DC Protection class II according to EN 60950 (in installed state) Application In interior spaces with up to 85% air humidity (non-condensing) Operating temperature -10 to +50 °C Guidelines Guideline for electric locking systems of doors in escape routes (EltVTR) - version
Package content Control unit Indicators Locking LED, door state LED, alarm LED, buzzer
SECULOGIC T 320
(with a door control unit TZ 320)
W x H: Helmet T: Distance of top edge of bearing ring to rear edge of terminal
December 1997
Buzzer 75 DB (at approx. distance of 50 cm)
14
SECULOGIC T 320
7.2 Terminal T 320 AP
Terminal T 320 AP Variants T 320 green
Function Monitoring and control of a door in bidirectional emergency routes
Dimensions 77 x 197 x 88 mm (W x H x D) Installation Wall mounting Operating voltage 24 V DC (± 10 %) Current consumption 100 mA at 24 V DC Protection class II according to EN 60950 Application In interior spaces with up to 85% air humidity (non-condensing) Operating temperature -10 to +50 °C Guidelines Guideline for electric locking systems of doors in escape routes (EltVTR) - version
Package content Mounting plate
Indicators Locking LED, door state LED, alarm LED, buzzer
Technical Data
T 320 white-aluminium
(with a door control unit TZ 320)
December 1997
Pre-assembled housing Mounting accessories
Buzzer 75 DB (at approx. distance of 50 cm)
15
Germany
GEZE Sonderkonstruktionen GmbH Planken 1 97944 Boxberg-Schweigern Tel. +49 (0) 7930-9294 -0 Fax +49 (0) 7930-9294 -10 E-Mail: sk .de@geze.com
Germany
GEZE GmbH Niederlassung Nord/Ost Bühringstraße 8 13086 Berlin (Weissensee) Tel. +49 (0) 30-47 89 90-0 Fax +49 (0) 30- 47 89 90-17 E-Mail: berlin.de@geze.com
Germany
GEZE GmbH Niederlassung West Nordsternstraße 65 45329 Essen Tel. +49 (0) 201-83082-0 Fax +49 (0) 201-83082-20 E-Mail: essen.de@geze.com
Germany
GEZE GmbH Niederlassung Mit te Adenauerallee 2 61440 Oberursel (b. Frankfurt) Tel. +49 (0) 6171-63610-0 Fax +49 (0) 6171-63610-1 E-Mail: frankfurt.de@geze.com
Germany
GEZE GmbH Niederlassung Süd Breitwiesenstraße 8 71229 Leonberg Tel. +49 (0) 7152-203-594 Fax +49 (0) 7152-203-438 E-Mail: leonberg.de@geze.com
Germany
GEZE Service GmbH Reinhold-Vöster-Straße 25 71229 Leonberg Tel. +49 (0) 7152-9233-0 Fax +49 (0) 7152-9233-60 E-Mail: service -info.de@geze.com
Germany
GEZE Service GmbH Niederlassung Berlin Bühringstraße 8 13086 Berlin (Weissensee) Tel. +49 (0) 30-470217-30 Fax +49 (0) 30- 470217-33 E-Mail: service -info.de@geze.com
Austria
GEZE Austria GmbH Wiener Bundesstrasse 85 5300 Hallwang b. Salzburg Tel. +43-(0)662- 663142 Fax +43-(0)662-663142-15 E-Mail: austria.at@geze.com
Baltic States
GEZE GmbH Baltic States oce Dzelzavas iela 120 S 1021 Riga Tel. +371 (0) 67 89 60 35 Fax +371 (0) 67 89 60 36 E-Mail: oce-latvia@geze.com
GEZE GmbH
P.O.Box 1363 Reinhold-Vöster-Straße 21–29 71229 Leonberg Germany
Benelux
GEZE Benelux B.V. Leemkuil 1 Industrieterrein K apelbeemd 5626 EA Eindhoven Tel. +31-(0)40-26290-80 Fax +31-(0)40-26 290-85 E-Mail: benelux.nl@geze.com
Bulgaria
GEZE Bulgaria - Trade Representative Oce 61 Pirinski Prohod, entrance „B“, 4th oor, oce 5, 1680 Soa Tel. +359 (0) 24 70 43 73 Fax +359 (0) 24 70 62 62 E-Mail: oce-bulgaria@geze.com
China
GEZE Industries (Tianjin) Co., Ltd. Shuangchenzhong Road Beichen Economic Development Area (BEDA) Tianjin 300400, P.R. China Tel. +86(0)22-26973995-0 Fax +86(0)22-26972702 E-Mail: Sales-info@geze.com.cn
China
GEZE Industries (Tianjin) Co., Ltd. Branch Oce Shanghai Unit 25N, Cross Region Plaza No. 899, Ling Ling Road, XuHui District 200030 Shanghai, P.R. China Tel. +86 (0)21-523 40 960 Fax +86 (0)21-644 72 007 E-Mail: chinasales@geze.com.cn
China
GEZE Industries (Tianjin) Co., Ltd. Branch Oce Guangzhou Room 17C3 Everbright Bank Building, No.689 Tian He Bei Road 510630 Guangzhou, P.R. China Tel. +86(0)20-38731842 Fax +86(0)20-38731834 E-Mail: chinasales@geze.com.cn
China
GEZE Industries (Tianjin) Co., Ltd. Branch Oce Beijing Room 1001, Tower D Sanlitun SOHO No. 8, Gongti North Road, Chaoyang District, 100027 Beijing, P.R.China Tel. +86-(0)10-5935 9300 Fax +86-(0)10-5935 9322 E-Mail: chinasales@geze.com.cn
China
GEZE Industries (Tianjin) Co., Ltd. Branch Oce Singapore 21, Bukit Batok Crescent, No. 23-75, Wcega Tower, Singapore 658065 Tel. +65-6846 1338 Fax +65-6846 9353 E-Mail: gezesea@geze.com.sg
France
GEZE France S. A.R.L. ZAC de l’Orme Rond RN 19 77170 Servon Tel. +33-(0)1-606260-70 Fax +33-(0)1-606260-71 E-Mail: france.fr@geze.com
Hungary
GEZE Hungary Kf t. Bartók Béla út 105-113. Budapest H -1115 Tel. +36 (1) 481 4670 Fax +36 (1) 481 4671 E-Mail: oce-hungary@geze.com
Iberia
GEZE Iberia S.R.L. Pol. Ind. El Pla C/Comerc, 2-22, Nave 12 08980 Sant Feliu de Llobregat (Barcelona) Tel. +34 9-02 19 40 36 Fax +34 9-02 19 40 35 E-Mail: info@geze.es
India
GEZE India Private Ltd. MF2 & 3, Guindy Industrial Estate Ekkattuthangal Chennai - 600 097 Tamilnadu Tel. +91 (0) 44 30 61 69 00 Fax +91 (0) 44 30 61 69 01 E-Mail: oce-india@geze.com
Italy
GEZE Italia Srl Via Giotto, 4 20040 Cambiago (MI) Tel. +3902950695-11 Fax +3902950695-33 E-Mail: italia.it@geze.com
Italy
GEZE Engineering Roma Srl Via Lucrezia Romana, 91 00178 Roma Tel. +3906-7265311 Fax +3906-72653136 E-Mail: roma@geze.biz
Kazakhstan
GEZE Central Asia 050061, Almaty, Kasak hstan Rayimbek ave. 348, A, oce 310 Tel. +7 (0) 72 72 44 78 03 Fax +7 (0) 72 72 44 78 03 E-Mail: oce-kazakhstan@geze.com
Poland
GEZE Polska Sp.z o.o. ul. Annopol 21 03-236 Warszawa Tel. +48 (0)22 440 4 4 40 Fax +48 (0)22 440 4 400 E-Mail: geze.pl@geze.com
Romania
GEZE Romania S.R.L. IRIDE Business Park Building nr. 10, level 2 Str. Dimitrie Pompei nr. 9–9a RO-020335 Bucharest, sector 2 Tel. +40 (0) 316 201 257 Fax +40 (0) 316 201 258 E-Mail: oce-romania@geze.com
Russia n Federation
GEZE GmbH Representative Oce Russia Kolodesnij pereulok3, str. 25 Oce Nr. 5201-5203 107076 Moskau Tel. +7 (0) 49 55 89 90 52 Fax +7 (0) 49 55 89 90 51 E-Mail: oce-russia@geze.com
Scandinavia
GEZE Scandinavia AB Mallslingan 10 Box 7060 18711 Täby, Sweden Tel. +46(0)8-7323-400 Fax +46(0)8-7323-499 E-Mail: sverige.se@geze.com
Tel.: 0049 7152 203-0 Fax: 0049 7152 203-310
www.geze.com 143250-00
Scandinavia
GEZE Nor way Industriveien 34 B 2072 Dal Tel. +47(0)639-57200 Fax +47(0)639-57173 E-Mail: norge.se@geze.com
Scandinavia
GEZE Finland Postbox 20 15871 Hollola Tel. +358(0)10 -4005100 Fax +358(0)10 -4005120 E-Mail: nland.se@geze.com
Scandinavia
GEZE Denmark Mårkær vej 13 J-K 2630 Taastrup Tel. +45(0)46-323324 Fax +45(0)46-323326 E-Mail: danmark.se@geze.com
South Af rica
DCLSA Distributors (Pty.) Ltd. 118 Richards Drive, Midrand, Halfway House Ext. 111 P.O. Box 7934 Midrand 1685 Tel. +27(0)113158286 Fax +27(0)113158261 E-Mail: info@dclsa.co.za
Switzerland
GEZE Schweiz AG Bodenackerstrasse 79 4657 Dulliken Tel. +41-(0)62-2855400 Fax +41-(0)62-2855401 E-Mail: schweiz.ch@geze.com
Turkey
GEZE GmbH Türkiye - İstanbul İrtibat Bürosu Ataşehir Bulvarı, Ata 2/3 Plaza Kat: 9 D: 84 Ataşehir Kadıköy / İstanbul Tel. + 90 (0) 21 64 55 43 15 Fax + 90 (0) 21 64 55 82 15 E-Mail: oce-turkey@geze.com
Ukraine
Repräsentanz GEZE Ukraine TOV ul. Viskoznaya, 17, building 93- B, oce 12 02094 Kiev Tel. +38 (0) 44 501 22 25 Fax +38 (0) 44 499 77 25 E-Mail: oce-ukraine@geze.com
United Arab Emirates/GCC
GEZE Middle East P.O. Box 17903 Jebel Ali Free Zone Dubai Tel. +971(0)4-8833112 Fax +971(0)4-8833240 E-Mail: geze@emirates.net.ae
United K ingdom
GEZE UK Ltd. Blenheim Way Fradley Park Licheld Staordshire WS13 8SY Tel. +44(0)1543443000 Fax +44(0)1543443001 E-Mail: info.uk@geze.com
Loading...