GEZE SecuLogic RWS TZ 300, SecuLogic RWS TZ 320 Komfort, SecuLogic RWS TZ 320 Standard System Documentation

BEWEGUNG MIT SYSTEM
GEZE SAFETY TECHNOLOGY
System documentation
EN
GEZE SecuLogic RWS
Escape route system
2
Contents
DOOR TECHNOLOGY
AUTOMATIC DOOR SYSTE MS
RWA AND WINDOW TECHNOLOGY
SAFET Y TECHNOLOGY
GLASS SYST EMS
Foreword
Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Terms and de nitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cable speci cation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Safety and responsibility . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Systems
System overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
GEZE SecuLogic System TZ 300 SN . . . . . . . . . . . . . . . . . . . . 8
GEZE SecuLogic System TZ 320 Standard . . . . . . . . . . . . . . . . 9
GEZE SecuLogic System TZ 320 Komfort . . . . . . . . . . . . . . . 10
GEZE SecuLogic System TZ 320, 1-box solution . . . . . . . . . . . 11
GEZE SecuLogic Vernetzt . . . . . . . . . . . . . . . . . . . . . . . . . 12
GEZE special system for children’s nurseries . . . . . . . . . . . . . 14
GEZE special system for bi-directional emergency exit route . . 15
GEZE special system for areas without local emergency
push button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
GEZE special system for
air locks on emergency exit routes . . . . . . . . . . . . . . . . . . . 17
System components
GEZE Door Control Unit TZ 300 SN . . . . . . . . . . . . . . . . . . . 18
GEZE Door Control Unit TZ 320 . . . . . . . . . . . . . . . . . . . . . 19
GEZE Terminal Box KL 220 . . . . . . . . . . . . . . . . . . . . . . . . 20
GEZE Control Panel TE 220/TTE 220 . . . . . . . . . . . . . . . . . . 21
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Annex
Dimensional drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Cable diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Certi cates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
EltVTR directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
3
GEZE System Documentation RWS Foreword
Foreword
Safety comes  rst
In public buildings, escape routes and respective control systems are a must. They are an inherent part of building planning and pertain to  re and personal protection.
What must a high-quality escape route system do to save lives? It must be absolutely reliable. But beyond this functionality, which is regulated by stringent legal restraints, the quality of an escape route system is also demonstrated in many further aspects.
With the GEZE SecuLogic escape route system we provide answers to the most important requirements a modern system solution has to ful ll.
Reliable, certi ed safety
GEZE SecuLogic escape route systems meet the requirements of the EltVTR guideline, the “Guideline governing electrical locking systems on doors in escape routes” issued by the Deutsche Institut für Bautechnik (German Institute for Building Technology).
Cutting-edge technology for more functions
Modular bus technology, wireless parameter setting using infrared technology, simple and fast installation and a comprehensive range of services account for the quality and safety of the GEZE SecuLogic escape route system.
Systems grow – and the GEZE SecuLogic escape route system does too
Components such as  re or hazard alarm systems, access control, emer­gency exit openers or motor locks can be integrated in the GEZE Secu­Logic escape route system at any time. This is guaranteed by the terminal box KL 220, the control panel TE 220/ TTE 220 and the control software VAT 220 SN (virtual display and operat­ing panel).
A question of design too
The  ush-mounted version of the door control unit TZ 320 can be integrated in the 55-size switch ranges of brand manufacturers such as Berker, Feller, Gira, Jung and Merten.
If things really do get serious
All elements must be easily recognisable and operable with a single movement. GEZE SecuLogic escape route system has put this into practice: A large-surface emergency push button, illuminated emergency sign and clear acoustic and optical signals are always reliable helpers in an emergency. The size of the emergency push button makes its operation “barrier-free”, i.e. it is also easy for people with restricted mobility, children and older people to use in an emergency.
Because as we already mentioned: Safety comes  rst – and goes hand in hand with design and convenience at GEZE.
ZuKo
BMA
GEZE MLS
FTÖ
FTÖ
FTÖ
4
GEZE System Documentation RWS Foreword
c
Aborting the short-term release:
When this is aborted, the door is locked prematurely when it is closed and the short-term release has not expired. This prevents the door being accessible for unauthorised people after someone has passed through it. The abortion setting can be deactivated via the service menu. In this case, the door remains unlocked for the duration of the time set. The release time can be ended prematurely by actuating the key switch again.
c
Direct release (in accordance with EltVTR)
Safety-related interruption of power supply to the electrical locking system by means of an opener contact when the emergency push button is actuated.
c
Unlocking (in accordance with EltVTR):
Non-safety-related interruption of the power supply to the electrical locking system e.g. through a key switch.
c
Indirect release (in accordance with EltVTR):
Safety-related interruption of the power supply to the electrical locking system if a further switching process is triggered by the opener contact of the emergency push button, with this new process interrupting the power supply to the electrical locking system.
c
After-triggering the short-term release:
If a new short-term release is triggered during the release time, the release time begins again. The after-triggering setting can be deactivated via the service menu. If a new short-term release is triggered during the release time by means of the internal key switch or a programmable input, the system locks again.
c
Emergency unlocking (in accordance with EltVTR):
Non safety-related interruption of the power supply to the electrical locking system e.g. through a hazard alarm system (GMA) or similar automatic triggering device.
c
Pre-alarm:
If the release time is exceeded during passage, an acoustic signal is sounded which informs the user that the time has been exceeded. If the door is closed during a pre-alarm, it is automatically locked and the pre-alarm is reset.
c
Door alarm:
If the pre-alarm time is also exceeded, the so-called door alarm is triggered. This can be reset via the integrated key switch or all inputs “short-term release” as well as via the control panel TE220 or the visualisation VAT 220 SN. If the door is closed during a door alarm, the door will be locked and can only be unlocked again once the alarm has been reset (except if the emergency push button is pressed). A door alarm will also be given if the door is “broken open”, in other words when the door is opened by force or without prior release.
Terms and de nitions
5
GEZE System Documentation RWS Foreword
AP Surface-mounted version
BLE 220 Flashlight
BMA Fire alarm system
EMA Burglar alarm system
FS Latch lock
FTÖ Emergency exit opener
FWS Emergency exit route sign
GLT Building management system
GMA Hazard alarm system
IQ Lock C Contact lock
IQ Lock EL Motor lock
IQ Lock EM Lever lock
IQ Lock M Motor lock
KL 220 Terminal box
KZF Short-term release
MA 500 Holding magnet
NC Potential-free opener contact (normal closed)
NO Potential-free closer contact (normal open)
NOT 320 Emergency push button
NT Power supply
OK Upper edge
RWA Smoke and heat extraction system
SCT 221 Key switch, one-pole switch (closer)
SCT 222 Key switch with LED display, one-pole reversible switch (two closers)
SCT 320 Key switch, one-pole reversible switch (two closers)
SHB 220 Signal horn with  ashlight
SLE 220 Signal light
SLH 220 Signal horn
TE 220 Control panel
TZ 320 Door control unit using bus technology
TZ 322 Door control unit using bus technology without emergency push button
TZ 323 Door control unit using bus technology, turned through 180°
... B Door control unit with illuminated emergency exit route sign
... S Door control unit with key switch (connection via ribbon cable)
... N Door control unit with integrated power supply
... BSN Door control unit with illuminated emergency exit route sign, key switch and integrated power supply
... BS Door control unit with illuminated emergency exit route sign and key switch
... SN Door control unit with key switch and integrated power supply
UK Lower edge
UP Flush-mounted version
USV Uninterruptible power supply
VAT 220 SN Visualisation software
ZSU Timer
ZuKo Access control
Abbreviations
Example for the name of the door control unit:
Door control unit with illuminated emergency exit route sign with key switch Description TZ 320 B S = TZ 320 BS
6
GEZE System Documentation RWS Foreword
The GEZE SecuLogic RWS was designed according to the latest technical standards and recognised safety-related regulations. Nevertheless, hazards can still occur during installation and application. For this reason, please note the following instructions:
c
Basic safety instructions
– Start-up and maintenance may only be carried out by a quali ed electrician or an expert trained by GEZE. – Only genuine GEZE spare parts or accessories approved by GEZE may be used. – Unauthorised modi cations to the system exclude GEZE’s liability for any resulting damage. – Primary protective measures are to be carried out on side. – Respective national standards must be heeded when laying cables.
c
Proper use
The GEZE SecuLogic RWS system has been designed for the control and monitoring of electrically locked emergency exit routes. External products may only be used after consultation with GEZE.
c
Improper use
The connection of products which have not been expressly approved for use by GEZE constitutes improper use.
Safety and responsibility
How to lay cables safely
Here are a few tips to help you lay the required cables safely and precisely:
c
Interference-free
Do not lay the data cable parallel to high-voltage cables (electromagnetic interference)!
c
The right cable
Shielded cable with twisted pairs of conductors.
Peripherals
• J-Y(ST)Y 2x2x0.6
• J-Y(ST)Y 4x2x0.6
Mains cable
• NYM-J 3x1.5
Bus cabling
• J-Y(ST)Y 2x2x0.8
• J-Y(ST)Y 4x2x0.8
c
Structure or networking
Do not route the bus line in a star shape, but rather in series.
Cable speci cation
7
GEZE System Documentation RWS System overview
System overview
Application
TZ 300 TZ 320 Standard TZ 320 Komfort
Local operation
Short-term release (KZF) (20 sec)
Short-term release (KZF) (1 sec - in nity)
Abortion of KZF with door closed
After-triggering of KZF
Pre-alarm (60 sec)
Pre-alarm (1 sec - 10 min)
Alarm 10 sec - 2 min / permanent alarm
- / • • / • • / •
Permanent unlocking
Release via emergency push button
Connection possibilities
Emergency exit opener type 331
UP 2x AP 3x
UP 2x AP 3x
UP 3x AP 3x
Holding magnet MA 500
UP 1x AP 2x
UP 1x AP 2x
UP 2x AP 2x
Emergency unlocking for hazard alarm system
Indirect release
Central emergency push button via safety circuit
External key switch
External emergency push button
Terminal T 320 (bi-directional emergency exit route)
Access control (short-term release)
Latch (short-term release)
Timer (unlocking) external
Timer (unlocking) internal
Burglar alarm system (locking has priority)
Programmable inputs
0 3 7
Programmable outputs
0 2 8
Flashlight/siren/alarm message
•*
Motor lock
•*
Lever lock
•*
Swing door drive
•**
Signal light control
•**
Additional door opener access control
•*
Output of di erent system states
•*
Control panel TE 220/TTE 220
Visualisation software VAT 220 SN
Other
Setting times / parameters using the key switch
• / – • / –
Infrared interface for diagnosis, readout of the alarm memory, setting parameters via Service terminal ST 220
Alarm memory
Integrated air lock control
Network function for BMA, ZSU, EMA
* Function can be realised via 2 outputs for which parameters can be freely set. There are 2 outputs available on the TZ 320. If more outputs are required, the TZ 320 Komfort with terminal box must be used. ** 2 outputs are required for this function.
8
GEZE System Documentation RWS GEZE SecuLogic System TZ 300 SN
TZ 300 SN UP
TS 5000
FTÖ
TZ 300 SN AP
TS 5000TS 5000
TK
TK
MA 500 MA 500
GEZE SecuLogic System TZ 300 SN
System structure SecuLogic System TZ 300 SN
c
Functional description
The standard functions for securing a single emergency exit door are covered by the possibility of short-term release and permanent unlocking via the local operating elements as well as release via the emergency push button. In addition, there are inputs available for a hazard alarm system (e.g. BMA), access control (ZuKo) and a timer (ZSU). External alarm indicators such as  ashlights or sirens can be connected via a potential-free contact.
c
System components
– TZ 300 SN, AP/UP – Emergency exit opener with latch lock or holding magnet with installation set and door contact
Options
• Flashlight BLE 220, signal horn SLH 220
• External key switches SCT 220, SCT 221, SCT 222, SCT 320
• Uninterruptible power supply (USV)
Note
For further information about the individual system components see the chapter “System components” from page 18 onwards.
c
System structure
ZuKo
ZuKo
BMA
BMA
ZSU
ZSU
Mains
Mains
Panic lock Panic lock
Signal horn
or
or
Signal horn
Flashlight
Flashlight
Fixed leaf Active leaf
Alarm message
Alarm message
9
GEZE System Documentation RWS GEZE SecuLogic System TZ 320
TS 5000
TK
V
TZ 320 SN UP
TK
TSA 160 NT Slimdrive EMD
MST 210
TZ 320 SN
+ FS
GEZE SecuLogic System TZ 320 Standard
System structure SecuLogic System TZ 320
c
Functional description
The GEZE door control unit TZ 320 secures and monitors the opening and closing processes of emergency exit doors on escape routes. The modes “permanent unlocking”, “short-term release” and “locking for alarm reset” are available. An integrated LED indicates the door modes “locked/unlocked”, “open/closed” and alarms. A large number of additional functions can be implemented using 3 programmable inputs (for the connection of e.g. access control systems, timer,  re and burglar alarm system) and 2 programmable outputs (for the connection of e.g. swing door drive, motor lock, additional door openers, optical/
acoustic alarm messages or relaying of system states). The integrated weekly timer and the air lock function allow  exible use in the system. The GEZE door control unit TZ 320 using bus technology has been tested in accordance with the EltVTR guideline (see p. 62  ).
c
System components
– Door control unit TZ 320 SN AP/UP – Emergency exit opener with latch lock or holding magnet with installation set and door contact
Options
• Flashlight BLE 220, signal horn SLH 220
• External key switches SCT 220, SCT 221, SCT 222, SCT 320
• External emergency push button NOT 320
• Uninterruptible power supply (USV)
• Terminal T 320
• Service terminal ST 220
• GEZE IQ Lock EM, EL, M and C
• Control panel TE 220/TTE 220
• Visualisation software VAT 220 SN
• OPC interface OPC 220
Note
For further information about the individual system components see the chapter “System components” from page 18 onwards.
c
System structure
ZuKo
BMA
Mains 230 V AC 50 Hz
Mains 230 V AC 50 Hz
GEZE IQ Lock EL Motor lock
EMA
Signal horn
Flashlight
GEZE BUS
Alarm message
GEZE IQ Lock C Contact lock
GEZE BUS
BMA EMA
ZuKo
Key switch
Key switch
Sensor strips
Contact sensor
Move­ment detector
Main switch
10
GEZE System Documentation RWS GEZE SecuLogic System TZ 320
KL 220
TK
TSA 160 NT Slimdrive EMD
MST 210
TZ 320 SN
+ FS
KL 220
TZ 320 S
MST 210
TS 5000
+ FS
GEZE SecuLogic System TZ 320 Komfort
System structure SecuLogic System TZ 320 + KL 220
c
Functional description
The door control unit TZ 320 can be used even more intensively in connection with the terminal box KL 220. The terminal box provides further inputs and outputs, so that even more devices can be connected to extend the area of application, e.g. by a combination of swing door drive with BMA, EMA and relaying messages. The respective terminal box is connected to a system-internal bus. This means a separate, higher-capacity power supply is available, as well as additional inputs and outputs for which parameters can be set, resulting in even more application possibilities.
c
System components
– Door control unit TZ 320 S AP/UP – Terminal box KL 220 AP/UP – Emergency exit opener with latch lock or holding magnet with installation set and door contact
Options
• Flashlight BLE 220, signal horn SLH 220
• External key switches SCT 220, SCT 221, SCT 222, SCT 320
• External emergency push button NOT 320
• Uninterruptible power supply (USV)
• Terminal T 320
• Service terminal ST 220
• GEZE IQ Lock EM, EL, M and C
• Swing door drive TSA 160, Slimdrive EMD
• Control panel TE 220/TTE 220
• Visualisation software VAT 220 SN
• OPC interface OPC 220
• GEZE SecuLogic access control system
Note
For further information about the individual system components see the chapter “System components” from page 18 onwards.
c
System structure
ZuKo ZuKo
BMA
GEZE IQ Lock EL Motor lock
GEZE IQ Lock EL Motor lock
EMA
Signal horn Signal horn
Flashlight Flashlight
GEZE BUS GEZE BUS
Alarm message Alarm message
Key switch Key switch
Mains 230 V AC 50 Hz
Mains 230 V AC 50 Hz
Move­ment detector
Contact sensor
Main switch
Sensor strips
11
GEZE System Documentation RWS GEZE SecuLogic System TZ 320
TZ 320 UP
TS 5000
FTÖ+ FS
NT
V
GEZE SecuLogic System TZ 320, 1-box solution
System structure SecuLogic System TZ 320
c
System structure
GEZE IQ Lock C Contact lock
ZuKo
BMA EMA
Signal horn
Flashlight
GEZE BUS
Alarm message
Mains 230 V AC 50 Hz
Key switch
c
Functional description
The full functionality of the emergency exit back-up can only be realised using a  ush-mounted box. Control of the operating modes and acknowledgement of alarms is taken over by the key of the GEZE IQ Lock. This variant is possible as standard with the door control unit TZ 320 or as “Komfort” with an additional terminal box KL 220.
c
System components
– Door control unit TZ 320, UP – GEZE IQ Lock EM, EL, C – Emergency exit opener 331 with latch lock
Options
• Holding magnet MA 500
• Signal horn SLH 220
• GEZE SecuLogic access control system
• Terminal 320
• External emergency push button NOT 320
• Flashlight BLE 220
• Terminal T 320
• Visualisation software VAT 220 SN
• OPC interface OPC 220
Note
For further information about the individual system components see the chapter “System components” from page 18 onwards.
12
GEZE System Documentation RWS GEZE SecuLogic System TZ 320
TZ 320 TZ 320 TZ 320 TZ 320 TZ 320 TZ 320
VAT 220 SN
TE 220/TTE 220
GEZE SecuLogic Vernetzt
System structure SecuLogic Vernetzt
c
Functional description
The system SecuLogic Vernetzt is used to secure emergency exit doors subject to central control and monitoring in large buildings, e.g. shopping centres, malls, public institutions. The individual control components (visualisation software, control panels and door control units) can be assigned anywhere in the individual bus systems. The maximum cable length for each bus system is 1000 m.
VAT 220
8 bus systems with a maximum of 63 door control units each can be displayed and operated using the visualisation software VAT 220 SN. The VAT 220 SN can work both as a central and as a parallel operating spot. There is no classic server-client relationship, because with VAT 220 SN all the doors in the system can be controlled centrally and without a loop via a server. It is possible to set up further lower-order operating spots with the aid of control panels TE 220/TTE 220.
TE 220/TTE 220
The control panel TE 220 wall panel and the control panel TTE 220 desk panel are used as control and display units for up to 20 individual door control units via a bus system (max. 5 TE 220 per bus system).
OPC
The software interface OPC is used in the escape route system so that data can be transmitted to higher-level building management systems. The OPC interface guarantees simple communication between devices from di erent manufacturers.
c
System structure
Bus system 1
... up to 63
Bus system 2
Bus system 3
Bus multiplexer
Bus system 4
BMA
EMA
ZSU
13
GEZE System Documentation RWS GEZE SecuLogic System TZ 320
c
System components
– Door control unit TZ 320 SN AP/UP – Door control unit TZ 320 S AP/UP + terminal box KL 220 AP/UP – Emergency exit opener with latch lock or holding magnet with installation set and door contact – Visualisation software VAT 220 SN
Options
• Flashlight BLE 220, signal horn SLH 220
• External key switches SCT 220, SCT 221, SCT 222, SCT 320
• External emergency push button NOT 320
• Uninterruptible power supply (USV)
• Control panel TE 220/TTE 220
• Terminal T 320
• Service terminal ST 220
• GEZE IQ Lock EM, EL, M
• Swing door drive TSA 160, Slimdrive EMD
• OPC interface OPC 220
• GEZE SecuLogic access control system
Note
For further information about the individual system components see the chapter “System components” from page 18 onwards.
14
GEZE System Documentation RWS GEZE special systems
TZ 300 SN UP
TS 5000
FTÖ
SCT 221
GEZE special system for children’s nurseries
Special system for children’s nurseries
c
Functional description of the children’s nursery solution
The door is permanently locked and secured by the door control unit TZ 300 SN.
Passage by nursery sta
The sta trigger a short-term release at the TZ 300 SN via the outer key switch and so can pass through the door using the key on the panic lock. The outer door handle is coupled in during the day via the switchover function “B” of the panic lock.
Arrival and collection times
The external push button can be activated or deactivated via the switch in the “sta room”. This means that parents can trigger a short-term release when they are bringing or collecting their children, and open the door via the coupled-in door handle. Parents can leave the nursery again by opening the door using the push button mounted at a height of 1.80 m. This installation height of
1.80 m means that children cannot reach the button.
Emergencies
In an emergency, the door can always be passed through in the direction of emergency exit by pressing the emergency push button. Triggering of the emergency push button is indicated by both an optical and acoustic signal on the TZ 300. Optionally, the alarm can be relayed. This allows an external light or siren to be triggered.
Fire
A  re alarm system can be connected to the TZ 300 for immediate emergency unlocking in the event of a  re. This means the door control unit has already been unlocked when people escaping the  re arrive at the door.
c
System components
– Door control unit TZ 300 SN – Emergency exit opener with latch lock or holding magnet with installation set and door contact – Release push button inside at a height of 1.80 m – Release push button outside – Circuit breaker – External key switch SCT 221 – Panic lock, function “B” (on site)
Options
• Flashlight BLE 220, signal horn SLH 220
• Uninterruptible power supply (USV)
Note
For further information about the individual system components see the chapter “System components” from page 18 onwards.
c
System structure children’s nursery solution
Push button
1.80 m
Key switch (sta room)
Alarm message
Push button outside
Mains
Panic lock Function “B” (handle/handle)
BMA
15
GEZE System Documentation RWS GEZE special systems
TZ 320 SN innen
T 320 außen
TS 5000
FTÖ
Special system for bi-directional emergency exit route
c
Functional description for bi-directional emergency exit route
To secure a door with two directions of escape, the terminal T 320 is connected to the door control unit TZ 320 via an internal bus. This allows the door to be released safely from both sides via an emergency push button in the event of a hazard. The door can be controlled via the terminal T 320 and via the door control unit TZ 320. This allows authorised passage to take place via the integrated key switch. In addition, external triggering elements such as access controls or key switches can be connected to the TZ 320. The integrated bus function of the TZ 320 allows networking and thus circuit-entering to central operating spots such as the control panel TE 220, visualisation software VAT 220 or a higher-level building management system.
c
System components
– Door control unit TZ 320 SN AP/UP – Terminal T 320 AP/UP – Emergency exit opener 331 with latch lock 807-10
Options
• Holding magnet MA 500
• Access control
• Signal horn SLH 220
• Flashlight BLE 220
• Signal light SLE 220
• Key switches SCT 221, SCT 220, SCT 320
• IQ Lock EL, EM, M, C
• Swing door drive Slimdrive MED, TSA 160 NT
• Control panel TE 220
• Visualisation software VAT 220 SN
• OPC interface OPC 220
Note
For further information about the individual system components see the chapter “System components” from page 18 onwards.
c
System structure bi-directional emergency exit route
GEZE Bus
Mains
Signal horn
ZuKo
Key switch
TOP LOCK
Alarm message
BMA
Panic lock
GEZE special system for bi-directional emergency exit route
inside
outside
16
GEZE System Documentation RWS GEZE special systems
+ FS
TS 5000
NT
+ FS
TS 5000
NT
+ FS
TS 5000
NT
GEZE special system for areas without local emergency push button
Special system for areas without local emergency push button
c
Functional description
Securing emergency exit doors in areas with a local emergency push button in accordance with EltVTR (DIBT 5/98) section 2.6, para. 3.1.3 and building regulation list A Part 1, e.g. psychiatric units, care areas for dementia patients, forensic areas. The safety circuit is a separate power circuit to realise a safety-related (indirect) release of several door control units in connection with central emergency push buttons, BMA or similar. The safety circuit is used in particular when there is no local emergency push button on the door control unit. This must be approved by national top-level building authorities in individual cases.
c
System components
– Door control unit TZ 322 SN AP/UP without emergency push button – Key switch SCT 222 with LEDs – Relay board RP 220 – Emergency push button NOT 320 – Emergency exit opener with latch lock or holding magnet with installation set and door contact
Options
• GEZE IQ Lock EL, EM, M and C
• Flashlight BLE 220/signal horn SLH 220
• Swing door drive TSA 160, Slimdrive EMD
• Control panel TE 220/TTE 220
• Terminal T 320
• Service terminal ST 220
• Visualisation software VAT 220 SN
• Uninterruptible power supply (USV)
Note
For further information about the individual system components see the chapter “System components” from page 18 onwards.
c
System structure
Panic lock
Safety circuit
Mains
Mains
Central spotBMA
TZ 322
+
RP 220
TZ 322
+
RP 220
TZ 322
+
RP 220
USV
NOT 320
TE 220
Mains
Mains
SCT 222
inside
SCT 222
outside
SCT 222
outside
SCT 222 outside
SCT 222
inside
SCT 222
inside
ZuKo
Panic lock
Panic lock
17
GEZE System Documentation RWS GEZE special systems
+ FS+ FS
VBVB
+ FS+ FS
TS 5000TS 5000
TS 5000
TS 5000
TZ 320 SN TZ 320 SNTZ 320 SN TZ 320 SN
GEZE special system for air locks on emergency exit routes
Special system for air locks on emergency exit routes
c
Functional description
Realisation of air locks on emergency exit routes; e.g. operating theatre areas, laboratories and quarantine areas. A maximum of 10 air lock groups with up to 10 door control units each (total of max. 63 door control systems/bus system) can be realised per bus system. The door control units in one group lock mutually. A door can be assigned to several groups at the same time. This assignment can be changed at any time, thus forming new air lock relationships. Signal light displays can be triggered via two programmable outputs on the TZ 320.
Active air lock:
Basically, all the doors in one air lock group for which parameters are set as an active air lock are locked and thus also closed. If one of these doors is unlocked short-term via respective control elements, it transmits a signal to all the other doors in the group at the same time and blocks the control elements of the other (still locked) doors and vice versa.
Passive air lock:
In contrast to the active air lock, all the doors in one air lock for which parameters are set as a passive air lock are not generally locked, but are closed. If one of these doors is opened, i.e. the door leaf moves, this transmits a signal to all the other doors and locks them and vice versa. In the case of both air lock types, immediate passage is possible by actuating the emergency push button.
The air lock function can be switched on or o via the local key switch.
c
System components
– Door control unit TZ 320 SN AP/UP – Emergency exit opener with latch lock or holding magnet with installation set and door contact – Service terminal ST 220
Options
• Flashlight BLE 220, signal horn SLH 220
• GEZE IQ Lock EL, EM, M
• External key switches SCT 220, SCT 221, SCT 222
• Swing door drive TSA 160, Slimdrive EMD
• Control panel TE 220/TTE 220
• External emergency push button NOT 320
• Visualisation software VAT 220 SN
• Terminal T 320
• OPC interface OPC 220
• Uninterruptible power supply (USV)
Note
For further information about the individual system components see the chapter “System components” from page 18 onwards.
c
System structure
Key switch or card reader on the outside
Panic lock
Signal light
Mains Mains Mains Mains
Signal light
Signal light
Signal light
GEZE Bus
Panic lock Panic lock Panic lock
Key switch or card reader on the outside
Key switch or card reader on the outside
Key switch or card reader on the outside
Distributor bus Distributor bus
18
GEZE System Documentation RWS GEZE Door Control Unit TZ 300 SN
GEZE Door Control Unit TZ 300 SN
GEZE door control unit TZ 300 UP GEZE door control unit TZ 300 AP
c
Product features
– 3 LED displays for door modes
• Locked, unlocked
• Door leaf open, closed
• Alarm, pre-alarm – Integrated illuminated emergency push button – integrated key switch for
• Unlocking, short-term release
• Locking
• Alarm reset – Integrated di erentiated acoustic alarm for indication of the pre-alarm or actuation of the emergency push button
– Integrated sabotage protection – Automatic abortion of short-term release when the door is closed – Automatic storage and activation of operating state before and after power failure. – Flush-mounted installation in 3  ush-mounting boxes 62.5 mm deep
The GEZE door control unit TZ 300 SN is part of the SecuLogic escape route system and is used to control and monitor electrically locked doors on emergency exit routes. Doors on emergency exit routes are reliably protected against unauthorised passage by the GEZE door control unit. At the same time, the integrated emergency push button guarantees passage at all times in emergency situations.
Technical product description
Dimensions (B x H x D) Flush-mounted version 81 x 223 x 62.5 mm
Surface-mounted version 77 x 197 x 88 mm
Integrated power supply Flush-mounted version 500 mA, 350 mA for peripherals
Surface-mounted version 800 mA, 350 mA for peripherals
Connections Input for emergency unlocking through hazard alarm system
Input for access control system and timer Potential-free output for optical/acoustic alarm indication or
alarm relaying
Connection possibility for locking elements
Flush-mounted version 2 x FTÖ, 1 x holding magnet
Surface-mounted version 3 x FTÖ, 2 x holding magnet
Area of use Dry rooms
c
Technical data GEZE door control unit TZ 300 SN
19
GEZE System Documentation RWS GEZE Door Control Unit TZ 320
GEZE Door Control Unit TZ 320
GEZE door control unit TZ 320 UP GEZE door control unit TZ 320 AP
c
Product features
– Flexible concept: Available as a tailor-made solution in 3, 2 or 1-box version – Available as  ush-mounted or surface-mounted version
– Surface-mounted version: Also available turned through 180° (emergency push button at the top) – Flush-mounted version: Suitable for all 55-size switch ranges such as those from Berker, Feller, Gira, Jung, Merten – Attractive design – 3 inputs and 2 outputs for more functions – Straightforward installation thanks to clearly separated connections – Parameter setting via the service terminal ST 220 – Operation via integrated power supply (option) – Alarm memory with date and time – Completely compatible with the predecessor version TZ 220
The GEZE door control unit TZ 320 is part of the SecuLogic escape route system and is used to control and monitor electrically locked doors on emergency exit routes. In addition, it o ers numerous interfaces to other products and systems. Swing door drives, motor locks, signal sensors and much more can be connected. Messages to higher-order building management systems or central control via PC or control panel are also possible. Intelligent functions between the door control units can be realised via the GEZE bus system, e.g. air lock functions or circuit-entering and relaying of  re alarm or burglar alarm systems.
Technical product description
Dimensions (B x H x D) Flush-mounted 3-fold 81 x 223 x 62.5 mm
Surface-mounted version 77 x 197 x 88 mm
Integrated power supply Flush-mounted version 500 mA, 350 mA for peripherals
Surface-mounted version 800 mA, 650 mA for peripherals
Connections 3 programmable
inputs for
• Emergency unlocking through hazard alarm system or central emergency push button
• Access control system
• Timer etc.
2 programmable, potential-free outputs for
• Optical/acoustic alarm indication or
• GEZE IQ Lock EL, EM, M or
• Door opener ZuKo or
• Signal light in combination with air lock or
• Output system states
Connection possibility for • Terminal T 320 Input for • Indirect release through central emergency push button
Connection possibility for locking elements
Flush-mounted version 2 x FTÖ, 1 x holding magnet Surface-mounted version 3 x FTÖ, 2 x holding magnet
Area of use Dry rooms
c
Technical data GEZE door control unit TZ 320
20
GEZE System Documentation RWS GEZE Terminal Box KL 220
GEZE Terminal Box KL 220
GEZE Terminal Box KL 220
c
Product features
– Operation of the KL 220 only possible in combination with a TZ 320 – Voltage supply to the TZ 320 via KL 220 – Communication of TZ 320 with KL 220 via RS 485 interface – With sabotage monitoring
Extension of functions of the door control unit TZ 320 by a further 4 inputs and 6 outputs.
Technical product description
Dimensions (H x B x D) Flush-mounted version 107 x 107 x 57 mm
Surface-mounted version 113 x 113 x 58 mm
Installation board 90 x 90 mm Integrated power supply 800 mA, 600 mA for peripherals Connections 4 programmable inputs
6 programmable, potential-free outputs
Connection possibility for locking elements
3 x FTÖ, 2 x holding magnet
Protective class IP 55 ID no. Flush-mounted version 089317
Surface-mounted version 087262
c
Technical data GEZE terminal box KL 220
21
GEZE System Documentation RWS GEZE Control Panel TE 220/TTE 220
GEZE Control Panel TE 220/TTE 220
GEZE control panel TE 220 GEZE control panel TE 220
c
Product features
– Modular design and building-related con guration – Master panel MTA 220 for the convenient control of all functions incl. bus interface – Emergency push button NTA 220 for the central unlocking of all doors on the bus line. – Slave panel STA 220 for operation/display of one respective assigned door control unit. – LED displays for door modes locked/unlocked, open/closed, alarm – Operating panel for unlocking, short-term release, locking – Forming several doors into groups through parameter setting via ST 220 – Blind cover BTA 220 for covering any door modules not used – Protection against misuse through integrated key switch – Power supply for supplying the control panel – Two  ush-mounting boxes 62.5 mm deep are required for  ush-mounted installation
As a control and display unit, the control panel TE 220/TTE 220 is suitable for up to 20 individual door control units via a bus system.
Technical product description
Dimensions Width Variable, depending on the number of doors: max. 884 mm
Height 160 mm Depth 22/55 mm (with/without emergency push button)
Colour Frame and side parts Aluminium, anodised
Operating panel Light grey Mains voltage 230 V AC Operating voltage 24 V DC Current consumption MTA 220 30 mA
NTA 220 30 mA
STA 220 30 mA Protective class IP 20 ID no. TE 220 098283
TTE 220 125920
c
Technical data GEZE control panel TE 220/TTE 220
22
GEZE System Documentation RWS Accessories
Accessories
Virtual display and operating panel VAT 220 SN
GEZE Virtual Display and Operating Panel VAT 220 SN
Technical product description
Minimum con guration PC with 586 processor from 500 MHz 64
MB RAM, 2 GB hard disk, CD ROM drive VGA monitor (1024 x 768) 30 MB free memory Windows 98, 2000, XP or Vista
ID no. 105278
c
Technical data
– For large buildings e.g. shopping centres, hotels, hospitals – Multi-door systems on several levels – Scaleable up to 504 doors – Clearly structured user-friendly interface – Central locking and unlocking of all doors without a server system
being necessary – Display of alarm or door mode – Password protection – Individual control possibilities:
• Speci c locking and unlocking of both all or individual doors
• Unlocking of all the doors connected via a central emergency push button
• Event memory with protocol function
– OPC = OLE for Process Control
The software interface OPC is used in the escape route system for the transmission of data to higher-level building management systems. The OPC interface guarantees simple communication between devices
from di erent manufacturers.
– Up to 8 bus lines with 63 participants each are possible.
OPC
Technical product description
ID no. 107732
c
Technical data
23
GEZE System Documentation RWS Accessories
Emergency exit opener type 331
GEZE Emergency Exit Opener Type 331
Technical product description
Resistant against attempts to break open 7500 N Operating voltage 24 V DC Current consumption 160 mA Enclosure rating IP 30
c
Technical data
– For locking emergency exit doors according to the quiescent current
principle
– Guarantees secure unlocking of the door even when there is a lot of
pressure against the door
– Integrated feedback contacts to monitor door locking (locked/
unlocked) and the door mode (open/closed) – Not suitable for retro tting to  reproof doors Installation o set from the existing panic lock in connection with latch
lock
Note
Di erent variants can be ordered, see Price List GEZE Safety Technology.
24
GEZE System Documentation RWS Accessories
– Mortice latch lock as counterpart to the emergency exit door opener – Adjustable latch
Latch lock 807/10
GEZE Latch Lock 807/10
Technical product description
Slideway 5 mm ID no. 076019
c
Technical data
– For the magnetic locking of emergency exit doors according to the
quiescent current principle – With integrated Hall sensor for locked / unlocked message – Bi-colour LED for indicating state
(green = locked, red = fault) – Complete with counterplate – Suitable for retro tting to  reproof doors – Installation o set from the existing panic lock
– Installation only in connection with the installation set and door
contact
Holding magnet MA 500
GEZE Holding Magnet MA 500
Technical product description
Resistant against attempts to break open 5000 N
Rated operating voltage 24 V DC
Current consumption 250 mA
Connection PG9
ID no. 024740
c
Technical data
25
GEZE System Documentation RWS Accessories
c
Technical data
GEZE Installation Set for MA 500
Technical product description
Screw  tting PG9 Metal tube 400 mm ID
no.
Hinge side silver-coloured 024731 Opposite hinge side silver-
coloured
024732
So t installation silver­coloured
025727
c
Technical data
– For additional monitoring of the door mode (open/closed) – Non-contact actuation through permanent magnet
(reed contact) with connection cable 2 m
– Use version 069607 for steel doors
GEZE Door Contacts
Technical product description
Switching current 0.5 A Switching voltage 24 V ID no. Flat reed contact with  xture,
reacting distance approx. 10 mm
069288
Flat reed contact with cross hole and mounting base, reacting distance approx. 10 mm
069606
Block reed contact with  xture, reacting distance approx. 20 mm for steel doors
069607
– For installation of the MA 500 on an emergency exit door – Retro tting to a  reproof door only after agreement with the door
manufacturer and use of rivet nuts – Universal  xing possibility thanks to variable hole pattern – Self-locking attachment screws
Installation set for MA 500
Door contacts
26
GEZE System Documentation RWS Accessories
NOT 220 AP (plastic)
GEZE Emergency Push Button NOT 220 AP (plastic)
Technical product description
Dimensions (W x H x D) 94 x 94 x 122 mm Operating voltage 24 V DC Current consumption 17 mA Enclosure rating IP 65 Colour Grey/light grey ID no. 076777
c
Technical data
– External emergency push button for release of the emergency exit
door in an emergency – Lighting with long-life LED – Lead-sealable, reusable cover hood – Surface-mounted installation – Complete with “emergency exit” sign – Plastic housing – One-pole opener contact with forced opening – One-pole closer contact with forced opening
– External emergency push button for release of the emergency exit
door in connection with a door control unit – Lighting with long-life LED – Reusable cover hood – Surface-mounted installation – With AP cap Jung AS 500, white WW – One-pole opener contact with forced opening – One-pole closer contact with forced opening
Emergency push button NOT 320 AP
GEZE Emergency Push Button NOT 320 AP
Technical product description
Operating voltage 24 V DC Current consumption approx. 30 mA Enclosure rating IP 20 Dimensions (W x H x D) 55 x 55 x 27 mm
W x H: Slam button D: Distance upper edge supporting ring to rear edge clamps
ID no. 137967
c
Technical data
27
GEZE System Documentation RWS Accessories
c
Technical data
– External emergency push button for release of the
emergency exit door in connection with a door control unit – Lighting with long-life LED – Reusable cover hood – Flush-mounted installation – One-pole opener contact – One-pole closer contact – Note: The frame must be ordered separately.
Emergency push button NOT 320 UP with frame
GEZE Emergency Push Button NOT 320 UP
c
Technical data
Technical product description
Dimensions (W x H x D) 55 x 55 x 27 mm
W x H: Slam button D: Distance upper edge supporting ring to rear
edge clamps Operating voltage 24 V DC Current consumption approx. 30 mA Enclosure rating IP 20 ID no. 136571
Delivered without frame
– Labelling of all emergency push buttons – Self-adhesive and  uorescent in accordance with DIN 4844-2
GEZE signs for emergency push button
Technical product description
Dimensions (W x H x D) 72 x 72 mm
ID no. Arrow upwards 088090
Arrow downwards 084992
Arrow to the right 100025
Arrow to the left 100017
Signs for the emergency push button
28
GEZE System Documentation RWS Accessories
Key switch SCT 221
GEZE Key Switch SCT 221
Technical product description
Dimensions (W x H x D)
Flush-mounted version 75 x 75 x 61 mm
Surface-mounted version 75 x 75 x 50 mm Enclosure rating IP 54 ID no. Flush-
mounted version
with pro le half cylinder 054245 without pro le half
cylinder
054240
Surface­mounted version
with pro le half cylinder 054533 without pro le half
cylinder
054532
c
Technical data
– External key switch for authorised door passage by actuating the short-
term release function by key – Connection to all door control units – Surface-mounted or  ush-mounted installation – With or without pro le half cylinder – Metal housing – One-sided switching operation – One-pole closer – Zamak  ush-mounted box 50 mm deep included in the scope of
supply
– GEZE surface-mounted  xture for mounting the emergency exit route
sign
GEZE  xture for emergency exit sign
Technical product description
ID no. 089361
c
Technical data
– Flush-mounted unit suitable for switch ranges of the size 55 x 55 mm – Variants: illuminated, non-illuminated
GEZE Emergency Exit Route Sign FWS
Technical product description
ID no. illuminated 130383
non-illuminated 130381
c
Technical data
Fixture for emergency exit sign
29
GEZE System Documentation RWS Accessories
– External key switch for authorised door passage by actuating the short-
term release function by key – Connection to all door control units – Flush-mounted installation – Complete with pro le half cylinder in single frame – One-pole reversible switch (2 closers) – With pro le half cylinder
Key switch SCT 220 UP, LS 990 stainless steel
GEZE Key Switch SCT 220 UP
Technical product description
Dimensions (W x H x D) 81 x 81 x 62.5 mm Enclosure rating IP 20 ID
no.
Jung AS 500 alpine
white
115442
LS 990 stainless
steel
094170
Gira E2 pure
white
094012
c
Technical data
– External operating element for connection to GEZE SecuLogic door
control units – LED left: red/green 24 V DC displaying locked/unlocked – LED right: yellow for 24 V DC for displaying alarm – Connection via integrated terminal strip and RP 220 – Aluminium front plate – Complete with pro le half cylinder – Surface-mounted or  ush-mounted installation
– Switching operating to both sides, one-pole (closer)
Key switch SCT 222 with LED display
GEZE Key Switch SCT 222 with LED display
Technical product description
Dimensions Flush-mounted version Front plate:
110 x 100 mm Flush-mounted box: ap-
prox. 70 x 80 x 45 mm
Surface-mounted (W x H x D)
70 x 80 x 45 mm
Enclosure rating IP 54 ID
no.
with
pro le half cylinder
Flush-mounted version
100065
Surface-mounted version
100064
c
Technical data
30
GEZE System Documentation RWS Accessories
Key switch SCT 320
GEZE Key Switch SCT 320
Technical product description
Dimensions (W x H x D) 55 x 55 x 41 mm
W x H: Cover D: Distance upper edge supporting ring to at­tached clamp
Operating voltage 24 V DC (±10 %)
Enclosure rating IP 20
ID no. white GIRA E2 130370
anthracite 132278
pure white Jung AS 500 131984
c
Technical data
– External signal horn for acoustic alarm indication – Connection possibility to all door control units – Surface-mounted or  ush-mounted installation – 26 settings for signal tone
Signal horn SLH 220
GEZE Signal Horn SLH 220
– Key switch with sabotage transmission
Technical product description
Dimensions Flush-mounted version 81 x 81 x 62.5 mm
Surface-mounted (Ø x H) 111 x 25,5 mm
Operating voltage 10-28 V DC
Current consumption 16 mA
Enclosure rating Flush-mounted version IP 20
Surface-mounted version
IP 54
ID no. Flush-
mounted version
Jung alpine white 091436
stainless steel
091437
Surface-mounted version 072112
c
Technical data
31
GEZE System Documentation RWS Accessories
External  ashlight for optical alarm indication
– Connection possibility to all door control units – Surface-mounted installation – Sturdy, maintenance-free and fail-safe design, polycarbonate housing – Xenon tubes for high light output
Flashlight BLE 220 AP
GEZE Flashlight BLE 220 AP
Technical product description
Dimensions (Ø x H) 93 x 72 mm
Operating voltage 20-30 V DC
Current consumption 90 mA
Enclosure rating IP 54
Flashing frequency 1 Hz
Re ector colour red
ID no. 089353
c
Technical data
Signal horn with  ashlight SHB 220 AP
GEZE Signal Horn with Flashlight SHB 220 AP
Technical product description
Dimensions (Ø x H) 111 x 97 mm
Flashing frequency 1 Hz, ± 20 %
Volume max. 94 dB (at a distance of 1 m)
Operating voltage 20-30 V DC
Current consumption max. 110 mA at 24 V DC
Enclosure rating IP 54
Colour white
ID no. 089354
c
Technical data
– External signal horn with  ashlight for optical and acoustic alarm
indication – Connection possibility to all door control units – Comprising an external signal horn and external  ashlight – Surface-mounted installation
32
GEZE System Documentation RWS Accessories
– External signal light for optical alarm indication – Connection to all control units – Flush-mounted or surface-mounted installation
Signal light SLE 220
GEZE Signal Light SLE 220
c
Technical data
– For power supply to various components – For installation in a  ush-mounted box 62.5 mm deep plastic housing,
cast module
Power supply NET 220
GEZE Power Supply NET 220
Technical product description
Dimensions (Ø x D) 50 x 40 mm
Enclosure rating IP 54
Voltage Primary 230 V AC, 50 Hz
Secondary 24 V DC
Current consumption
Primary 0.15 A
Current output Secondary 500 mA, 12 W
ID no. 087243
c
Technical data
Technical product description
Dimensions (W x H x D) Flush-mounted
version
81 x 81 x 25 mm
Surface-mounted version
61 x 61 x 47 mm
Operating voltage 24 V DC
Current consumption 85 mA
Enclosure rating IP 20
Re ector colour red
ID no. Flush-
mounted version
alpine white 089348
stainless steel 089349
Surface­mounted version
alpine white 080866
33
GEZE System Documentation RWS Accessories
Power supply NT 19.2-24
GEZE Power Supply NT 19.2-24
c
Technical data
– For parameter setting and diagnosis in connection with TZ 320,
TZ 320 + KL 220 and TE 220/TTE 220 – For battery operation with 4 micro cells – Integrated IrDA interface – Plain text display of all events, menu items and settings on an
illuminated 4-line display – Automatic cut-o
– Keypad with 5 operating buttons
Service terminal ST 220
GEZE Service Terminal ST 220
c
Technical data
– For power supply to various components – Plastic housing
Technical product description
Dimensions (W x H x D) 80 x 125 x 37 mm Enclosure rating IP 40 Colour green-blue (similar to RAL
5020)
ID no. 087261
Technical product description
Dimensions (W x H x D) 100 x 32 x 32 mm
Enclosure rating IP 54 Voltage Primary 230 V AC, 50 Hz
Secondary 24 V DC
Current consumption
Primary 0,25 A
Current output Secondary 800 mA, 19.2 W ID no. 089862
34
GEZE System Documentation RWS Accessories
Relay board RP 220
– For universal use – 2 potential-free changeover contacts
GEZE Relay Board RP 220
Technical product description
Dimensions (W x H x D) 28 x 25 x 18 mm Switching load 30 V / 1 A Operating voltage 24 V DC Current consumption 10 mA ID no. 102355
c
Technical data
35
GEZE System Documentation RWS Dimensional drawings
31.5
197
88
77
Mounting plate
Door control unit TZ 300 AP
Speci cations in mm
Dimensional drawings
Door control unit TZ 300 AP with emergency push button
36
GEZE System Documentation RWS Dimensional drawings
55 37
55
Door control unit TZ 300 UP
Door control unit TZ 300 UP
Speci cations in mm
37
GEZE System Documentation RWS Dimensional drawings
77 88
197
31.5
197
88
77
Door control unit TZ 322 AP
Door control unit TZ 322 AP
Door control unit TZ 320 AP with emergency push button
Door control unit TZ 320 AP with emergency push button
Mounting plate
Mounting plate
Speci cations in mm
38
GEZE System Documentation RWS Dimensional drawings
Jung, AS500
152
81
81
223
49 11
Jung, Edelstahl
81
81
152
223
49 8
Door control unit TZ 320 UP Jung AS 500
Door control unit UP Jung AS 500
Speci cations in mm
Door control unit TZ 320 UP Jung stainless steel
Door control unit TZ 320 UP Jung stainless steel
39
GEZE System Documentation RWS Dimensional drawings
22.4
14
25
19
12
200
43
3 39
27.75 38134.25
21.5
91.5 49
33
12
60
53
7 186
43
220
42
4.9
106.5 64.549
10
200
42.75 43.25
134
21.7
3
20
30
20
30
3
48
35
15
Emergency exit door opener with short  at strike plate (diagram shows DIN left, DIN right is mirror-inverted)
Emergency exit door opener with short  at strike plate (diagram shows DIN left, DIN right is mirror-inverted)
Emergency exit door opener with short angled strike plate (diagram shows DIN left, DIN right is mirror-inverted)
Emergency exit door opener with short angled strike plate (diagram shows DIN left, DIN right is mirror-inverted)
Speci cations in mm
40
GEZE System Documentation RWS Dimensional drawings
18
110
64
ø5.5
ø10.4
514
39
32
3
37
7
96
3
24
12
17
12
24
Emergency exit door opener with lock latch guide (diagram shows DIN left, DIN right is mirror-inverted)
Emergency exit door opener with lock latch guide (diagram shows DIN left, DIN right is mirror-inverted)
Speci cations in mm
Latch lock
Latch lock
Set dimension x to approx. 1 mm using the setting screw!
Adjustment from 5 mm (12 - 17 mm) continuously from the housing rear wall possible
41
GEZE System Documentation RWS Dimensional drawings
A
Ansicht "A"
12
19
41
66
266
26
52
254`0.1
20`0.1
ø6.4
ø10.3
27
10`0.1
M6x20
M6x20
RWS
FFB
72
75
8 8
17
8
8
270
26
33
29
26
30
155
20
20
20
20
30
155
20
20
20
20
26
26
29
33
29
26
20
115
115
Holding magnet MA 500
Holding magnet MA 500
Installation set for jamb (cable routing from the top or side)
Installation set for jamb (cable routing from the top or side)
Diagram sticker 21206-2-0374 applied to the inside of the cover
E-connection (thread)
View “A”
Type plate 21206-2-0279 29535
Status LED
Attachment bracket on the jamb
Drilling template Jamb installation
DIN right
Holding plate on the door
DIN left
Holding plate on the door
Lintel
Holding plate
Lock washer
Attachment bracket
Magnet with counterplate
min 2m clear passage height
required
Door DIN left
Door DIN right
CAUTION
Jamb lock side
Jamb lock
side
Speci cations in mm
42
GEZE System Documentation RWS Dimensional drawings
RWS
Mat.Nr. 25719
FFB
M6x20
M6x20
8 8
17
154
270
146
16
17
71
33
2626 24
33
20
115
115
30
20 20
75
20 20
26
26
57
M6x20
M6x20
RWS
146
16 2423
37
330
88
17
270
2426 33
115
115
95
95
75
75
115
115
26
26 33
24
Installation set for the opposite hinge side (cable routing from the top)
Installation set for the opposite hinge side (cable routing from the top)
Speci cations in mm
Installation set for hinge side (cable routing from the top or side)
Installation set for hinge side (cable routing from the top or side)
Drilling template Opposite hinge side
Depending on air humidity, paper template can change considerably. For this reason, only our dimensional speci ca­tions are applicable. Before you use the paper template, please check the dimen­sions and correct them if necessary.
Holding plate
Lock washer
Attachment bracket
Magnet with counterplate
min 2m clear passage height
required
Door DIN left
Door DIN right
CAUTION
Frame lock side
Frame lock
side
Installation bracket
Slideway 33 mm
perforated Centre line
UK frame
Drilling template Hinge side
Lock washer
Attachment bracket
Magnet with counterplate
Door DIN right
Door DIN left
Door edge
lock side
Door edge
lock side
Mounting plate
Slideway 33 mm
OK door
Installation bracket
43
GEZE System Documentation RWS Dimensional drawings
M3
10
15
23
ø8
1.7
10
15
23
ø8
1.7
27
57
15
23.3
45
10.3
18
ø3.2
ø5.8
ø3.2
ø5.5
ø3.2
ø5.5
23
2.5
30
2.2
5.2
60
ø3.2
9
9
64
ø3.2
94
4
60
ø3.2
52
452
682
4.5
9
2
12
9
18
4.5
9
Round reed contact with  xture (reacting distance 5 mm)
Round reed contact with  xture (reacting distance 5 mm)
Flat reed contact with  xture (reacting distance 10 mm)
Flat reed contact with  xture (reacting distance 10 mm)
Connection cable approx. 2 m long
Magnetic housing
Reacting distance: approx. 5 mm
Installation  xtureContact housing
Connection cable approx. 2 m long
Reacting distance: approx. 10 mm
FixtureMagnet Flat reed contact
Speci cations in mm
44
GEZE System Documentation RWS Dimensional drawings
60
ø3.2
60
452
452
5.5
11
4.5
9
4.5
9
4
4
65
14
ø4.3
65
14
ø4.3
54
5.5
54
6.5
13
6.5
13
Speci cations in mm
Flat reed contact with cross hole and mounting base (reacting distance approx. 10 mm)
Flat reed contact with cross hole and mounting base (reacting distance approx. 10 mm)
Block reed contact with mounting base for steel doors (reacting distance 20 mm)
Block reed contact with mounting base for steel doors (reacting distance 20 mm)
Connection cable approx. 2 m long
Reacting distance: approx. 10 mm
Scope of supply:
1  at reed contact
1 magnet
12 mounting bases
MagnetFlat reed contact with cross hole
Connection cable
approx. 2 m long
Block magnet with mounting base
Reacting distance:
approx. 20 mm
Scope of supply:
1 block magnet
1 block reed contact
6 mounting bases
Block reed contact
45
GEZE System Documentation RWS Dimensional drawings
3
94
94
41
94
94
79
50
79
50
47
47
39
81
122
ø22.5
3
21206-2-0350 76799
2-
3-
1-
21206-6-0852 24249
21206-1-0114 24463
21206-1-1018 76778
1-
3-
2-
21206-2-0291 69449
2
Emergency push button 220 AP (plastic housing IP 65)
Emergency push button 220 AP (plastic housing IP 65)
Bottom part of housing 21206-1-1018
7 x M16/20 break-out
Top part of housing 21206-1-1018
Speci cations in mm
46
GEZE System Documentation RWS Cable diagrams
3
2
1
71mm
190.00
71.00
71.00
24.50
11.75
11.75
30.00
23.00
50.00
50.00
25.00
7.50
30.00
5.50
22.00
Cable diagrams
Installation instructions
TZ 320 AP and TZ 320 UP
UP versions AP versions
NYM-J 3 x 1.5 with earth conductor -> for mains supply cable
J-Y (ST) Y 2 x 2 x 0.6 -> for peripherals
J-Y (ST) Y 4 x 2 x 0.6 -> for peripherals
Cable types
Installation in standard
 ush-mounted boxes 62.5
mm deep
Distance  ush-mounted boxes
Cable feed 24 V from behind
for variants without power supply.
Cable feed peripherals,
GEZE BUS, messages
Cable feed 230 V from behind in upper
box for variants with power supply.
Recommended height min. 850 mm max. 1200 mm
Emergency push button
Cable feed from behind for
peripherals, GEZE BUS, messages
Cable feed 230 V from behind
for variants with power supply.
Upper edge  nished  ooring (OKFF)
Cables routed in accordance with VDE 0100
Sabotage-proof cable routing in accordance with VDE 0833
Surface-mounted cables in metal tube or plastic cable channel
with spiral protective tube made of metal.
Only connect components approved by the manufacturer.
Cable routing, connection and start-up may only be carried out by experts.
Installation instructions for the door control unit:
Installation height of the emergency push button: 850 - 1200 mm
Recommended installation height: 850 mm
Installation of the door control unit in the direct vicinity of the emergency
exit doors to be secured.
When a holding magnet is installed, the clear passage height under the
magnet must be at least 2000 mm.
Flush-mounted door control unit:
Number of  ush-mounted boxes required, depth 62.5 mm:
3 boxes with TZ 320 BSN / SN / BN, TZ 300 SN
2 boxes with: TZ 320 S / BN / B / N, TZ 300 S
1 box with: TZ 320 (power supply + SCT external)
Recommended height min. 850 mm max. 1200 mm
47
GEZE System Documentation RWS Cable diagrams
Active leaf
Fixed leaf
Panic lock
Active leaf
Fixed leaf
Active leaf
Fixed leaf
Active leaf
Fixed leaf
Active leaf
Fixed leaf
Active leaf
Fixed leaf
Mains
Mains
Door control unit
TZ 320 SN, UP
Door control unit
TZ 320 SN, AP
2 x holding magnet + door contact 1 x holding magnet + door contact
1 x door contact on  xed leaf
2 x holding magnet + door contact
1 x emergency exit door opener + latch lock
Heed max. power consumption.
Current consumption
per MA 50 = 250 mA
Only on rebated doors Heed max. power consumption.
Current consumption
per MA 50 = 250 mA
Panic lock Panic lock
Panic lock Panic lock Panic lock
2 x emergency exit door opener + latch lock
1 x emergency exit door opener + latch lock
1 x door contact on  xed leaf
3 x emergency exit door opener + latch lock
Only on rebated doors Heed max. power consumption.
Current consumption
per FTÖ 331 = 160 mA
Locking elements 2-leaf
Installation instructions for the door control unit:
Please also heed installation instructions TZ 320 no. 131537 and
sk089-281
Flush-mounted door control unit:
Installation in 3 standard  ush-mounted boxes 62.5 mm deep
Power supply cable in upper box
Supply cables for peripherals in lower box
Installation height of the emergency push button: max. 1200 mm
Recommended installation height: 850 mm
Surface-mounted door control unit:
Cable routing in accordance with sketch
Cable feed 230 V
Cable feed peripherals
Cables routed in accordance with VDE 0100
Sabotage-proof cable routing in accordance with VDE 0833
Surface-mounted cables in metal tube or plastic cable channel with spiral protective tube made of metal.
Only connect components approved by the manufacturer.
Cable routing, connection and start-up
may only be carried out by experts.
NYM-J (ST) 3 x 1.5 with earth conductor
J-Y(ST)Y 2x2x0.6
J-Y(ST)Y 4x2x0.6
J-Y(ST)Y 2x2x0.8
FTÖ331U Emergency exit opener
FS807-10 Latch lock
USV Emergency power supply
RP220 Relay board
GCDU100 Door unit
GCFP Fingerprint
GCRR / GCVR Card reader
LI-Y (ST) Y 4x2x0.6
48
GEZE System Documentation RWS Cable diagrams
Standard
TZ 300 SN, UP
Mains
Alarm
message
Flash-
light
Signal
horn
or
or
or
Fire
alarm
system
Timer
Access
control/
intercom
Key
switch
with
display
Key
switch
Door control unit
Panic lock
Installation instructions for the door control unit:
Please also heed installation instructions TZ300 no. 137351
and sk089-281.
Installation height of the emergency push button: 850 - 1200mm
Recommended installation height: 850 mm
Flush-mounted door control unit:
Installation in 3 standard  ush-mounted boxes 62.5 mm deep
Mains supply cable from behind into the upper box
Supply cables for peripherals from behind into the lower box
Surface-mounted door control unit:
Cable routing in accordance with sketch
Cable feed 230V
Cable feed peripherals
Cables routed in accordance with VDE 0100
Sabotage-proof cable routing in accordance with VDE 0833
Only connect components approved by the manufacturer
Potential-free contact, opener
Potential-free contact, closer, permanent contact
Potential-free contact, closer, impulse
Voltage supply via door control unit possible.
Note maximum power consumption
Potential-free contact (30V/1A) from the TZ
FTö331U Emergency exit opener
FS807-10 Latch lock
USV Emergency power supply
RP220 Relay board
DCDU100 Single Door Unit
GCDU200 Door Unit
GCDU Fingerprint
GCRR / GCVR Card reader
Door contact
Holding magnet
NYM-J 3x1.5 with earth conductor
J-Y (ST) Y 2x2x0.6
J-Y (ST) Y 4x2x0.6
J-Y (ST) Y 2x2x0.8
49
GEZE System Documentation RWS Cable diagrams
TZ 300 SN AP, IQ Lock C
Mains
Alarm
message
Flash-
light
Signal
horn
or
or
or
Fire
alarm
system
Timer
Access
control/
intercom
Key
switch
with
display
Key
switch
Door control unit
Contact lock
Installation instructions for the door control unit:
Please also heed installation instructions TZ300 no. 137351
and sk089-281.
Installation height of the emergency push button: 850 - 1200mm
Recommended installation height: 850 mm
Flush-mounted door control unit:
Installation in 3 standard  ush-mounted boxes 62.5 mm deep
Mains supply cable from behind into the upper box
Supply cables for peripherals from behind into the lower box
Surface-mounted door control unit:
Cable routing in accordance with sketch
Cable feed 230V
Cable feed peripherals
Cables routed in accordance with VDE 0100
Sabotage-proof cable routing in accordance with VDE 0833
Only connect components approved by the manufacturer
Potential-free contact, opener
Potential-free contact, closer, permanent contact
Potential-free contact, closer, impulse
Voltage supply via door control unit possible.
Note maximum power consumption
Potential-free contact (30V/1A) from the TZ
FTö331U Emergency exit opener
FS807-10 Latch lock
USV Emergency power supply
RP220 Relay board
DCDU100 Single Door Unit
GCDU200 Door Unit
GCDU Fingerprint
GCRR / GCVR Card reader
Cable transition
V Distributor on-site
Door contact
Holding magnet
NYM-J 3x1.5 with earth conductor
J-Y (ST) Y 2x2x0.6
J-Y (ST) Y 4x2x0.6
J-Y (ST) Y 2x2x0.8
Empty pipe inner diameter 10mm
Connection cable 10m, scope of supply IQ Lock EM
50
GEZE System Documentation RWS Cable diagrams
Signal horn 4)
Flashlight 4)
Alarm message 5)
1) Potential-free contact, opener
2) Potential-free contact, closer, permanent contact
3) Potential-free contact, closer, impulse
4) Voltage supply via door control unit possible,
note maximum power consumption
5) Potential-free contact, changeover (30 V / 1 A) from the TZ
NYM-J (ST) 3 x 1.5 with earth conductor
J-Y(ST)Y 2x2x0.6
J-Y(ST)Y 4x2x0.6
Door contact
Holding magnet
Panic lock
Fire alarm
system 1)
Timer 2)
Burglar
alarm
system
Access control/
Intercom 3)
Key switch
with display
Key switch
Lock or
unlock 3)
Mains
Number codelock
CTI / CTI B 4)
Door control unit
GEZE BUS
Message
sabotage 5)
Message door
open 5)
Message door
unlocked 5)
J-Y(ST)Y 2x2x0.8
*) 3 inputs and 2 outputs available
FTÖ331U Emergency exit opener
FS807-10 Latch lock
USV Emergency power supply
RP220 Relay board
GCDU100 Door unit
GCFP Fingerprint
GCRR / GCVR Card reader
Installation instructions for the door control unit:
Please also heed installation instructions TZ 320
no. 131537 and sk089-281
Flush-mounted door control unit:
Installation in 3 standard  ush-mounted boxes
62.5 mm deep
Power supply cable in upper box
Supply cables for peripherals in lower box
Installation height of the emergency push button: max. 1200 mm
Recommended installation height: 850 mm
Surface-mounted door control unit:
Cable routing in accordance with sketch
Cables routed in accordance with VDE 0100
Sabotage-proof cable routing in accordance with VDE 0833
Only connect components approved by the manufacturer.
Cable feed 230 V
Cable feed peripherals
Mains
TZ 320 SN Standard
51
GEZE System Documentation RWS Cable diagrams
TZ 320 Standard
1-box solution with IQ Lock EL
*) 3 inputs and 2 outputs available
For the IQ Lock at least 1 input and 1 output
are required. 2 inputs and 2 outputs can be
occupied per function by the IQ Lock.
**) Only use power supply approved by GEZE.
NT19.2-24, No. 089862, NET 24-5, No. 111182,
or power supply 1.3 A, No. 078401. Housing on-site.
Installation instructions for door control unit:
Please also heed installation instructions TZ320 or 131537
and sk089-281.
Installation height of the emergency push button: max. 1200 mm
Recommended installation height: 850 mm
Flush-mounted door control unit:
Installation in 2 standard  ush-mounted boxes 62.5 mm deep
24 V supply cable in lower box
Supply cables for peripherals in lower box
Cable routing in accordance with VDE 0100
Sabotage-proof cable routing in accordance with VDE 0833.
Only connect components approved by the manufacturer.
1) Potential-free contact, opener or closer
2) Potential-free contact, closer, permanent contact
3) Potential-free contact, closer, impulse
4) Heed max. power consumption
5) Potential-free contact (30 V / 1 A) from the TZ
NYM-J 3x1.5 with earth conductor
J-Y (ST) 2x2x0.6
J-Y (ST) 4x2x0.6
J-Y (ST) 2x2x0.8
Empty pipe inner diameter 10 mm
Connection cable 10 m, scope of supply GEZE IQ LOCK EL
FTÖ331U Emergency exit opener
FS807-10 Latch lock
RP220 Relay board
GCDU100 Door unit
GCFP Fingerprint
GCRR/VR Card reader
NET220 Power supply
MST210 Motor lock control
Mains
230 VAC
50 Hz
Message 5)
Sabotage
Message
Door 5)
open
Message
Door 5)
unlocked
Alarm
message 5)
Flash-
light 4)
Signal
horn 4)
GEZE Bus
Burglar
alarm
system 2)
Fire alarm
system 1)
Timer 2)
Access
control
inter-
com 3)
Key switch
with display
Key switch
Door control unit
TZ320, UP
Emergency exit
route sign non-
illuminated
GEZE IQ Lock EL
Motor lock
Door contact
Holding magnet
GEZE MA500
Mains 230 VAC
52
GEZE System Documentation RWS Cable diagrams
TZ 320 UP Standard
IQ Lock EM, external power supply
Message 5)
Sabotage
Message
Door 5)
open
Message
Door 5)
unlocked
Alarm
message 5)
Flashlight
4)
Signal
horn 4)
GEZE Bus
Burglar
alarm
system 2)
Fire alarm
system 1)
Timer 2)
Access
control
inter-
com 3)
Key switch
with display
Key switch
Mains 230 VAC
Mains
230 VAC
50 Hz
Door contact
Holding magnet
GEZE MA500
Door control unit
TZ 320 S, UP
GEZE IQ Lock EM
Lever lock
*) 3 inputs and 2 outputs available
For the IQ Lock at least 1 output is required.
2 inputs and 2 outputs can be
occupied per function by the IQ Lock.
**) Only use power supply approved by GEZE.
NT19.2-24, No. 089862, NET 24-5, No. 111182,
or power supply 1.3 A, No. 078401. Housing on-site.
Installation instructions for door control unit:
Please also heed installation instructions TZ320 or 131537
and sk089-281.
Installation height of the emergency push button: max. 1200 mm
Recommended installation height: 850 mm
Flush-mounted door control unit:
Installation in 2 standard  ush-mounted boxes 62.5 mm deep
24 V supply cable in lower box
Supply cables for peripherals in lower box
Cable routing in accordance with VDE 0100
Sabotage-proof cable routing in accordance with VDE 0833.
Only connect components approved by the manufacturer.
1) Potential-free contact, opener or closer
2) Potential-free contact, closer, permanent contact
3) Potential-free contact, closer, impulse
4) Heed max. power consumption
5) Potential-free contact (30 V / 1 A) from the TZ
NYM-J 3x1.5 with earth conductor
J-Y (ST) Y 2x2x0.6
J-Y (ST) Y 4x2x0.6
J-Y (ST) Y 2x2x0.8
Empty pipe inner diameter 10 mm
Connection cable 10 m, scope of supply GEZE IQ LOCK EM
FTÖ331U Emergency exit opener
FS807-10 Latch lock
RP220 Relay board
GCDU100 Door unit
GCFP Fingerprint
GCRR/VR Card reader
NET Power supply
V Distributor on-site
53
GEZE System Documentation RWS Cable diagrams
Burglar
alarm
system 2)
Fire alarm
system 1)
Timer 2)
Access
control
inter-
com 3)
Key switch
with display
Key switch
Lock or
unlock 3)
Mains 230 VAC
Message 5)
Sabotage
Message
Door 5)
open
Message
Door 5)
unlocked
Alarm
message 5)
Flash-
light 4)
Signal
horn 4)
GEZE Bus
TZ320SN Komfort
with IQ Lock EL
Mains
230 VAC
50 Hz
GEZE IQ Lock EL
Motor lock
Door contact
Holding magnet
GEZE MA500
Door control unit
TZ320S
Installation instructions for door control unit:
Please also heed installation instructions TZ320 or 131537
and sk089-281.
Installation height of the emergency push button: max. 1200 mm
Recommended installation height: 850 mm
Flush-mounted door control unit:
Installation in 3 standard  ush-mounted boxes 62.5 mm deep
Mains supply cable in upper box
Supply cables for peripherals in lower box
Cable routing in accordance with VDE 0100
Sabotage-proof cable routing in accordance with VDE 0833.
Only connect components approved by the manufacturer.
AP door control unit:
Cable routing according to sketch
Cable feed 230 V
Cable feed peripherals
1) Potential-free contact, opener or closer
2) Potential-free contact, closer, permanent contact
3) Potential-free contact, closer, impulse
4) Heed max. power consumption for the KL220
5) Potential-free contact (30 V / 1 A) from the TZ
NYM-J 3x1.5 with earth conductor
J-Y (ST) Y 2x2x0.6
J-Y (ST) Y 4x2x0.6
J-Y (ST) Y 2x2x0.8
Empty pipe inner diameter 10 mm
Connection cable 10 m, scope of supply GEZE IQ LOCK EM
FTÖ331U Emergency exit opener
FS807-10 Latch lock
KL220 Terminal box
GCDU100 Door unit
GCFP Fingerprint
GCRR/VR Card reader
NET220 Power supply
MST210 Motor lock control
*) There are 4 inputs and 6 outputs on the KL220. If the 3 inputs and/or 2 outputs of the TZ320
are required in addition, more wires must be planned accordingly between KL220 and TZ320.
2 inputs and 2 outputs can be occupied by the IQ Lock depending on the function.
54
GEZE System Documentation RWS Cable diagrams
Installation height of the emergency push button: max. 1200 mm
Recommended installation height: 850 mm
Flush-mounted door control unit:
Installation in 3 standard  ush-mounted boxes 62.5 mm deep
Mains supply cable in upper box
Supply cables for peripherals in lower box
Cable routing in accordance with VDE 0100
Sabotage-proof cable routing in accordance with VDE 0833.
Only connect components approved by the manufacturer.
AP door control unit:
Cable routing according to sketch
Cable feed 230 V
Cable feed peripherals
NYM-J 3x1.5 with earth conductor
J-Y (ST) Y 2x2x0.6
J-Y (ST) Y 4x2x0.6
J-Y (ST) Y 2x2x0.8
Empty pipe inner diameter 10 mm
FTÖ331U Emergency exit opener
FS Latch lock
MST210 Motor lock control
GCDU100 Door unit
GCFP Fingerprint
GCRR/VR Card reader
NET220 Power supply
MST210 Motor lock control
RSZ Smoke switch control unit
RS Smoke switch
ATÖ Working current door opener ( re protection)
TÜK Door transition cable (GEZE scope of supply)
Cable transition
Mains
230 VAC
50 Hz
Door control unit
TZ 320 S
Note for securing emergency exit route:
- Please also heed installation instructions TZ 320 (ID no. 131537 and sk089-281)
*) 3 inputs and 2 outputs available
1) Potential-free contact, opener or closer
2) Potential-free contact, closer, permanent contact
3) Potential-free contact, closer, impulse
Note for swing door drive:
- Also heed the installation instructions from the product-speci c documents.
Planning documents: TSA 160 NT (ID no. 121988), Slimdrive EMD (ID no. 110450)
- Allow the cable to project at least 1 m out of the wall.
GEZE Bus
Burglar
alarm
system 2)
Fire alarm
system 1)
Timer 2)
Access
control
inter-
com 3)
Key switch
Special
element
or
Panic lock
Sensor strips
Display
or button
programme
switch
Movement
detector
inside
Movement
detector
outside
Contact
sensor
inside
Contact
sensor
outside
Cut-out
button
Emer-
gency o
button
optional
Main
switch
Close door
TZ 320 SN Standard
TSA160 NT_Slimdrive EMD, 1-leaf “F”
55
GEZE System Documentation RWS Cable diagrams
Flush-mounted door control unit:
Installation in 3 standard  ush-mounted boxes 62.5 mm deep
Power supply cable in upper box
Supply cables for peripherals in lower box
Installation height of the emergency push button: max. 1200 mm
Recommended installation height: 850 mm
Surface-mounted door control unit:
Cable routing in accordance with sketch
Cables routed in accordance with VDE 0100
Sabotage-proof cable routing in accordance with VDE 0833
Only connect components approved by the manufacturer.
Cable feed 230 V
Cable feed peripherals
NYM-J (ST) 3 x 1.5 with earth conductor
J-Y(ST)Y 2x2x0.6
J-Y(ST)Y 4x2x0.6
J-Y(ST)Y 2x2x0.8
Note for securing emergency exit route:
- Please also heed installation instructions TZ 320 (ID no. 131537 and sk089-281)
*) 3 inputs and 2 outputs available
FTÖ331U Emergency exit opener
FS Latch lock
RSK Bolt switch contact
GCDU100 Door unit
GCFP Fingerprint
GCRR / GCVR Card reader
NET 220 Power supply
MST210 Motor lock control
RSZ Smoke switch control unit
RS Smoke switch
ATÖ Working current door opener ( re protection)
TÜK Door transition cable (GEZE scope of supply)
Cable transition
LI-Y (ST) Y 2x2x0.6
Empty pipe inner diameter 10 mm
1) Potential-free contact, opener or closer
2) Potential-free contact, closer, permanent contact
3) Potential-free contact, closer, impulse
Note for swing door drive:
- Also heed the installation instructions from the product-speci c documents.
Planning documents: TSA 160 NT (ID no. 121988), Slimdrive EMD (ID no. 110450)
- Allow the cable to project at least 1 m out of the wall.
Active leaf
Fixed leaf
Panic lock
Display
or button
programme
switch
Movement
detector
inside
GEZE Bus
Burglar
alarm
system 2)
Fire alarm
system 1)
Timer 2)
Access
control
inter-
com 3)
Key switch
Mains
230 VAC
50 Hz
Door control unit
TZ 320 SN
Movement
detector
outside
Contact
sensor
inside
Contact
sensor
outside
Cut-out
button
Emer-
gency o
button
optional
Main
switch
Special
element
or
Sensor stripsSensor strips
TZ 320 SN Standard
TSA 160 NT Slimdrive EMD, 2-leaf
Close door
56
GEZE System Documentation RWS Cable diagrams
2  oors with 1x TE 220 / TTE 220
Mains
Mains
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Panic lock Panic lock
Panic lock Panic lock Panic lock Panic lock
Panic lock Panic lock
Fire alarm system
Burglar alarm system
Message Door mode
Message Locked
Message Alarm
Door contact
Holding magnet
Installation instructions for the door control unit:
Please also heed installation instructions TZ300 no. 137351
and sk089-281.
Installation height of the emergency push button: 1200mm
Recommended installation height: 850 mm
Flush-mounted door control unit:
Installation in 3 standard  ush-mounted boxes 62.5 mm deep
Mains supply cable from behind into the upper box
Supply cables for peripherals from behind into the lower box
1) Potential-free contact, opener
2) Potential-free contact, closer, permanent contact
3) Potential-free contact, closer, impulse
4) Voltage supply via door control unit possible.
Note maximum power consumption
5) Potential-free contact (30V/1A) from the TZ
FTö331U Emergency exit opener
FS807-10 Latch lock
USV Emergency power supply
TE220 Control panel
TT220 Table-top control panel
VB Bus distributor on-site
installed near the door
VN Mains distributor on-site
TS5000 Door closer
NYM-J 3x1.5 with earth conductor
J-Y (ST) Y 2x2x0.6
J-Y (ST) Y 4x2x0.6
J-Y (ST) Y 2x2x0.8
Installation instructions for control panel:
Please also heed installation instructions in the user manual
Control Panel no. 10786.
2 standard  ush-mounted boxes 6.25 mm deep are required
behind the control panel for installation.
The control panels TE220/TTE220 can be positioned
anywhere in the bus line.
Cables routed in accordance with VDE 0100
Sabotage-proof cable routing in accordance with VDE 0833
Only connect components approved by the manufacturer
Overall length of BUS (over all control panels and door control units) max. 900m.
The  re alarm system and burglar alarm system can be connected to one TZ320 and relayed via the GEZE bus to all other TZ320s.
5  re alarm or EMA lines can be realised. Only 1 line can be connected to one TZ320.
All messages can also be connected separately to the respective door control units.
The messages ‚Alarm‘, ‚Locked‘ and ‚Door mode‘ can be outputted as a collective message from one TZ320.
1
st
 oor
Ground  oor
57
GEZE System Documentation RWS Cable diagrams
2  oors with 1x VAT 220 SN + TCP/IP
Mains
Mains
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
outside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Key switch
without
card reader
on the
inside
Panic lock Panic lock
Panic lock Panic lockPanic lock Panic lock
Panic lock Panic lock
Fire alarm system
Burglar alarm system
Message Door mode
Message Locked
Message Alarm
Door contact
Holding magnet
Installation instructions for the door control unit:
Please also heed installation instructions TZ300 no. 137351
and sk089-281.
Installation height of the emergency push button: 1200mm
Recommended installation height: 850 mm
Flush-mounted door control unit:
Installation in 3 standard  ush-mounted boxes 62.5 mm deep
Mains supply cable from behind into the upper box
Supply cables for peripherals from behind into the lower box
NYM-J 3x1.5 with earth conductor
J-Y (ST) Y 2x2x0.6
J-Y (ST) Y 4x2x0.6
J-Y (ST) Y 2x2x0.8
1) Potential-free contact, opener
2) Potential-free contact, closer, permanent contact
3) Potential-free contact, closer, impulse
4) Voltage supply via door control unit possible.
Note maximum power consumption
5) Potential-free contact (30V/1A) from the TZ
FTö331U Emergency exit opener
FS807-10 Latch lock
USV Emergency power supply
VAT220SN Visualisation software
(PC on-site)
VB Bus distributor on-site
installed near the door
VN Mains distributor on-site
TS5000 Door closer
Overall length of BUS (over all control panels and door control units) max. 900m.
The  re alarm system and burglar alarm system can be connected to one TZ320 and relayed via the GEZE bus to all other TZ320s.
5  re alarm or EMA lines can be realised. Only 1 line can be connected to one TZ320.
All messages can also be connected separately to the respective door control units.
The messages ‚Alarm‘, ‚Locked‘ and ‚Door mode‘ can be outputted as a collective message from one TZ320.
Installation instructions for visualisation software VAT220SN:
Please also heed installation instructions from user manual
VAT220SN no. 098316, as well as the installation drawing
no. 35204-9-0955.
The VAT220SN can be positioned anywhere in the bus line.
Cables routed in accordance with VDE 0100
Sabotage-proof cable routing in accordance with VDE 0833
Only connect components approved by the manufacturer
On-site TCP/IP network
to further PCs
On-site TCP/IP network
USB dongle
USB port
1
st
 oor
Ground  oor
58
GEZE System Documentation RWS Cable diagrams
4  oors with 1x VAT 220 SN + TCP/IP
Mains 250V AC 50Hz
Mains 250V AC 50Hz
Mains 250V AC 50Hz
Mains 250V AC 50Hz
On-site TCP/IP network to further PCs
On-site TCP/IP network
USB dongles
Line 1-4
USB port
Panic lock
Panic lock
Panic lock
Panic lock
Panic lock
Panic lock
Panic lock
Panic lock
Panic lock
Panic lock
Panic lock
Panic lock
Key switch without card reader on the outside
Key switch without card reader on the inside
Key switch without card reader on the outside
Key switch without card reader on the inside
Key switch without card reader on the outside
Key switch without card reader on the inside
Key switch without card reader on the outside
Key switch without card reader on the inside
Key switch without card reader on the outside
Key switch without card reader on the inside
Key switch without card reader on the outside
Key switch without card reader on the inside
Key switch without card reader on the outside
Key switch without card reader on the inside
Key switch without card reader on the outside
Key switch without card reader on the inside
Key switch without card reader on the outside
Key switch without card reader on the inside
Key switch without card reader on the outside
Key switch without card reader on the inside
Key switch without card reader on the outside
Key switch without card reader on the inside
Key switch without card reader on the outside
Key switch without
card reader on the inside
Installation height of the emergency push button: 1200mm Recommended installation height: 850 mm
Flush-mounted door control unit: Installation in 3 standard  ush-mounted boxes 62.5 mm deep Mains supply cable from behind into the upper box Supply cables for peripherals from behind into the lower box
NYM-J 3x1.5 with earth conductor J-Y (ST) Y 2x2x0.6 J-Y (ST) Y 4x2x0.6 J-Y (ST) Y 2x2x0.8
FTö331U Emergency exit opener FS807-10 Latch lock USV Emergency power supply VAT220SN Visualisation software (PC on-site) VB Bus distributor on-site installed near the door VN Mains distributor on-site TS5000 Door closer
Installation instructions for visualisation software VAT220SN: Please also heed installation instructions from user manual VAT220SN no. 098316, as well as the installation drawing no. 35204-9-0955.
The VAT220SN can be positioned anywhere in the bus line.
Cables routed in accordance with VDE 0100 Sabotage-proof cable routing in accordance with VDE 0833 Only connect components approved by the manufacturer
Installation instructions for the door control unit: Please also heed installation instructions TZ300 no. 137351 and sk089-281.
1) Potential-free contact, opener
2) Potential-free contact, closer, permanent contact
3) Potential-free contact, closer, impulse
4) Voltage supply via door control unit possible. Note maximum power consumption
5) Potential-free contact (30V/1A) from the TZ
Overall length of BUS (over all control panels and door control units) max. 900m.
The  re alarm system and burglar alarm system can be connected to one TZ320 and relayed via the GEZE bus to all other TZ320s. 5  re alarm or EMA lines can be realised. Only 1 line can be connected to one TZ320. All messages can also be connected separately to the respective door control units. The messages ‚Alarm‘, ‚Locked‘ and ‚Door mode‘ can be outputted as a collective message from one TZ320.
Fire alarm system
Burglar alarm system
Message Door mode
Message Locked
Message Alarm
Door contact
Holding magnet
1st  oor
Ground  oor
2nd  oor
3rd  oor
59
GEZE System Documentation RWS Notes
Notes
GEZE GmbH P.O. Box 1363 71226 Leonberg Germany
GEZE GmbH Reinhold-Vöster-Straße 21-29
71229 Leonberg Germany Telefon +49 (0) 7152-203-0 Telefax +49 (0) 7152-203-310
www.geze.com
Germany
GEZE Sonderkonstruktionen GmbH Planken 1 97944 Boxberg-Schweigern Tel. +49 (0) 7930-92 94-0 Fax +49 (0) 7930-92 94-10 E-Mail: sk.de@geze.com
GEZE GmbH Niederlassung Nord/Ost
Bühringstraße 8 13086 Berlin (Weissensee) Tel. +49 (0) 30-47 89 90-0 Fax +49 (0) 30-47 89 90-17 E-Mail: berlin.de@geze.com
GEZE GmbH Niederlassung West Nordsternstraße 65 45329 Essen Tel. +49 (0) 201-83 082-0 Fax +49 (0) 201-83 082-20 E-Mail: essen.de@geze.com
GEZE GmbH Niederlassung Mitte Adenauerallee 2 61440 Oberursel (b. Frankfurt) Tel. +49 (0) 6171-63 610-0 Fax +49 (0) 6171-63 610-1 E-Mail: frankfurt.de@geze.com
GEZE GmbH Niederlassung Süd Breitwiesenstraße 8 71229 Leonberg Tel. +49 (0) 7152-203-594 Fax +49 (0) 7152-203-438 E-Mail: leonberg.de@geze.com
GEZE Service GmbH NL Südwest Reinhold-Vöster-Straße 25 71229 Leonberg Tel. +49 (0) 7152-92 33 34
GEZE Service GmbH NL Nord-Ost Bühringstraße 8 13086 Berlin (Weissensee) Tel. +49 (0) 30-47 02 17 32
GEZE Service GmbH NL West Nordsternstraße 65 45329 Essen Tel. +49 (0) 201-8 30 82 16
GEZE Service GmbH NL Mitte Feldbergstraße 59 61440 Oberursel Tel. +49 (0) 6171-63 327-0
GEZE Service GmbH NL Süd Parkring 17 85748 Garching bei München Tel. +49 (0) 89-120 07 42-0
Austria
GEZE Austria Wiener Bundesstrasse 85 A-5300 Hallwang Tel: +43/6225/87180 Fax: +43/6225/87180-299 E-Mail: austria.at@geze.com
Baltic States
GEZE GmbH Baltic States o ce Dzelzavas iela 120 S 1021 Riga Tel. +371 (0) 67 89 60 35 Fax +371 (0) 67 89 60 36 E-Mail: o ce-latvia@geze.com
Benelux
GEZE Benelux B.V. Leemkuil 1 Industrieterrein Kapelbeemd 5626 EA Eindhoven Tel. +31 (0) 40-26 290-80 Fax +31 (0) 40-26 290-85 E-Mail: benelux.nl@geze.com
Bulgaria
GEZE Bulgaria - Trade Representative O ce 61 Pirinski Prohod, entrance „B“, 4th  oor, o ce 5, 1680 So a
Tel. +359 (0) 24 70 43 73 Fax +359 (0) 24 70 62 62 E-Mail: o ce-bulgaria@geze.com
India
GEZE India Private Ltd. MF 2 & 3, Guindy Industrial Estate Ekkattuthangal Chennai 600 097 Tamilnadu Tel. +91 (0) 44 30 61 69 00 Fax +91 (0) 44 30 61 69 01 E-Mail: o ce-india@geze.com
Italy
GEZE Italia Srl Via Giotto, 4 20040 Cambiago (MI) Tel. +39 (0) 29 50 695-11 Fax +39 (0) 29 50 695-33 E-Mail: italia.it@geze.com
GEZE Engineering Roma Srl Via Lucrezia Romana, 91 00178 Roma Tel. +39 (0) 6-72 65 311 Fax +39 (0) 6-72 65 3136 E-Mail: roma@geze.biz
Poland
GEZE Polska Sp.z o.o. ul. Annopol 21 03-236 Warszawa Tel. +48 (0) 22 440 4 440 Fax +48 (0) 22 440 4 400 E-Mail: geze.pl@geze.com
Romania
GEZE Romania s.r.l. IRIDE Business Park, Str. Dimitrie Pompeiu nr. 9-9a, Building 10, Level 2, Sector 2, 020335 Bucharest Tel.: +40 (0) 21 25 07 750 Fax: +40 (0) 21 25 07 750 E-Mail: o ce-romania@geze.com
Russian Federation
GEZE GmbH Representative O ce Russia Kolodesnij pereulok3, str. 25 O ce Nr. 5201-5203 107076 Moskau Tel. +7 (0) 49 55 89 90 52 Fax +7 (0) 49 55 89 90 51 E-Mail: o ce-russia@geze.com
Scandinavia – Sweden
GEZE Scandinavia AB Mallslingan 10 Box 7060 18711 Täby, Sweden Tel. +46 (0) 8-7323-400 Fax +46 (0) 8-7323-499 E-Mail: sverige.se@geze.com
Scandinavia – Norway
GEZE Scandinavia AB avd. Norge Industriveien 34 B 2073 Dal Tel. +47 (0) 639-57 200 Fax +47 (0) 639-57 173 E-Mail: norge.se@geze.com
Scandinavia – Finland
Branch o ce of GEZE Scandinavia AB Herralantie 824 Postbox 20 15871 Hollola Tel. +358 (0) 10-40 05 100 Fax +358 (0) 10-40 05 120 E-Mail:  nland.se@geze.com
Scandinavia – Denmark
GEZE Danmark
Branch o ce of GEZE Scandinavia AB Mårkærvej 13 J-K 2630 Taastrup Tel. +45 (0) 46-32 33 24 Fax +45 (0) 46-32 33 26 E-Mail: danmark.se@geze.com
South Africa
DCLSA Distributors (Pty.) Ltd. 118 Richards Drive, Halfway House, Ext 111 P.O. Box 7934, Midrand 1685 Tel. +27 (0) 1131 58 286 Fax +27 (0) 1131 58 261 E-Mail: info@dclsa.co.za
Switzerland
GEZE Schweiz AG Bodenackerstrasse 79 4657 Dulliken Tel. +41 (0) 62-285 54 00 Fax +41 (0) 62-285 54 01 E-Mail: schweiz.ch@geze.com
Turkey
GEZE GmbH Türkiye - İstanbul İrtibat Bürosu
Ataşehir Bulvarı, Ata 2/3 Plaza Kat: 9 D: 84 Ataşehir Kadıköy / İstanbul Tel. + 90 (0) 21 64 55 43 15 Fax + 90 (0) 21 64 55 82 15 E-Mail: o ce-turkey@geze.com
Ukraine
GEZE Ukraine TOV ul. Viskoznaya, 17, Building 93-B, O ce 12 02094 Kiev Tel./Fax +38 (0) 44 501 22 25 Tel. +38 (0) 44 499 77 25 E-Mail: o ce-ukraine@geze.com
United Arab Emirates/GCC
GEZE Middle East P.O. Box 17903 Jebel Ali Free Zone Dubai Tel. +971 (0) 4-88 33 112 Fax +971 (0) 4-88 33 240 E-Mail: geze@emirates.net.ae
United Kingdom
GEZE UK Ltd. Blenheim Way Fradley Park
Lich eld Sta ordshire WS13 8SY Tel. +44 (0) 1543 44 30 00 Fax +44 (0) 1543 44 30 01 E-Mail: info.uk@geze.com
China
GEZE Industries (Tianjin) Co., Ltd. Shuangchenzhong Road Beichen Economic Development Area (BEDA) Tianjin 300400, P.R. China Tel. +86 (0) 22-26 97 39 95-0 Fax +86 (0) 22-26 97 27 02 E-Mail: Sales-info@geze.com.cn
GEZE Industries (Tianjin) Co., Ltd.
Branch O ce Shanghai Unit 25N, Cross Region Plaza No 899, Ling Ling Road, XuHui District 200030 Shanghai, P.R China Tel. +86 (0) 21-523 40 960 Fax +86 (0) 21-644 72 007 E-Mail: chinasales@geze.com.cn
GEZE Industries (Tianjin) Co., Ltd. Branch O ce Guangzhou Room 17C3 Everbright Bank Building, No.689 Tian He Bei Road 510630 Guangzhou P.R. China Tel. +86 (0) 20-38 73 18 42 Fax +86 (0) 20-38 73 18 34 E-Mail: chinasales@geze.com.cn
GEZE Industries (Tianjin) Co., Ltd Branch O ce Beijing Room 1001, Tower D Sanlitun SOHO No. 8, Gongti North Road, Chaoyang District 100027 Beijing, P.R.China Tel. +86 (0) 10-59 35 93 00 Fax +86 (0)10-59 35 93 22 E-Mail: chinasales@geze.com.cn
France
GEZE France S.A.R.L. ZAC de l’Orme Rond RN 19 77170 Servon Tel. +33 (0) 1-60 62 60-70 Fax +33 (0) 1-60 62 60-71 E-Mail: france.fr@geze.com
Hungary
GEZE Hungary Kft. Bartók Béla út 105-113.
Budapest H-1115 Tel. +36 (1) 481 4670 Fax +36 (1) 481 4671 E-Mail: o ce-hungary@geze.com
Iberia
GEZE Iberia S.R.L. Pol. Ind. El Pla C/Comerc, 2-22, Nave 12 08980 Sant Feliu de Llobregat (Barcelona) Tel. +34 9-02 19 40 36 Fax +34 9-02 19 40 35 E-Mail: info@geze.es
GEZE SAFETY TECHNOLOGY
ID no. 132410 · Vers. EN 110715 · Subject to alterations
According to manufacturer’s liability de ned
in the “product liability law”, the manufacturer
is obliged to provide the information (product
information and proper use, misuse, product
capacity, product maintanence, the duty to in-
form and the duty to instruct) contained in this
brochure. Non-obser vance of this information
relieves the manufacturer from any liability.
GEZE representative
The
measure
for our actions
Loading...