GEZE IO 420 User Manual

IO 420
EN User manual
164898-03
GEZE IO 420
Contents
1 About this document .............................................................................................................................................3
1.1 Product description .........................................................................................................................................................................................3
1.2 Further documents ..........................................................................................................................................................................................3
2.1 Fundamental safety precautions ...............................................................................................................................................................3
2.2 Assigning sta ...................................................................................................................................................................................................4
3.1 Technical data ....................................................................................................................................................................................................4
4 Parameter setting GEZE IO 420 ...........................................................................................................................8
5 Module description ...............................................................................................................................................11
5.1 Module type “watchdog” ............................................................................................................................................................................11
5.2 Module type “1 door” ...................................................................................................................................................................................12
5.3 Module type “2 doors” .................................................................................................................................................................................13
5.4 Module type “4 doors” ..................................................................................................................................................................................14
5.5 Module type “automatic stat” / “automatic 4 sec” .............................................................................................................................15
5.6 Module type “window” ............................................................................................................................................................................... 16
5.7 Module type “universal” ............................................................................................................................................................................. 16
5.8 Module type “IQ lock El + Aut” ..................................................................................................................................................................17
5.9 Module type “RWS + KL” ..............................................................................................................................................................................19
5.10 Module type “DCU1, 2 and 8”.................................................................................................................................................................... 21
5.11 Module type “DCU6” (revolving door) ................................................................................................................................................... 21
5.12 Module type “DCU128+RWS+KL” .......................................................................................................................................................... 21
6 Annex ....................................................................................................................................................................... 22
6.1 EDE lists .............................................................................................................................................................................................................22
6.2 State text ........................................................................................................................................................................................................... 26
6.3 Service menu................................................................................................................................................................................................... 29
6.4 Passwords for BACnet .................................................................................................................................................................................. 33
7 Firmware update for IO 420 .............................................................................................................................. 33
2
GEZE IO 420
1 About this document
This user manual describes the installation, commissioning and parameter setting of the GEZE IO 420. Installation and commissioning of the windows and doors are not part of this user manual.
1.1 Product description
With GEZE IO 420, GEZE components for door and window systems as well as the RWS-system of GEZE are controlled. The IO 420 is a coupler module for the networking of components and for the integration of non-bus­compliant components in the GEZE system. This user manual describes the individual module types th implemented using this system
.
1.2 Further documents
The components supplied by GEZE include the relevant data sheets with technical data. These must be heeded. All data sheets and further documents can also be found on the internet at www.geze.com.
1.3 Symbols and illustrations
Warning notices
Warning notices are used in these instructions to warn you of property damage and personal injury.
X
Always read and observe these warning notices.
X
Follow all measures that are labelled with the warning symbol and warning word.
Warning symbol Warning word Meaning
CAUTION
at can be
Information to prevent property damage, to understand or optimise the operation sequences.
More symbols and illustrations
In order to illustrate proper operation, important information and technical information is highlighted.
Symbol Meaning
X
means “important information”
means “additional Information”
Symbol for an action: Here you have to do something. If there are several actions to be taken, keep to the given order.
Abbreviations
ANSI American National Standard Institute APDU application layer protocol data unit B/IP BACnet/IP broadcasting management device BACnet Building Automation and Control networks BBMD BACnet/IP broadcasting management device BIBBs BACnet Interoperability Building Blocks BMA Fire alarm system COV change of value CP Capacitor plate (capacitor power) DCC Device communication control EDE Engineering Data Exchange IQ Lock Aut Motor lock for the passive leaf IQ Lock EL Motor lock KL 220 Terminal box 220 KZF Short-term release MAC medium access control
MS/TP Master Slave Token Passing NC Opening contact (normally closed) NO Closing contact (normal open) PICS RWA Smoke and heat extraction SCT Key operated button ST 220 Service terminal TZ 320 Door control unit 320 TE 200 Control panel 200 VAT 220 Virtual display indicator board ZSU Timer AL Active leaf IL Passive leaf BMA Fire alarm system. RWS Escape route system.
Protocol Implementation Conformance Statement
2 Safety and responsibility
2.1 Fundamental safety precautions
X
Use only original GEZE parts for repair work.
X
Unauthorised changes to the system exclude GEZE's liability for any resulting damage.
X
Primary protective measures are to be carried out on site.
X
Follow the VDE 0100 and VDE 0815 standards when laying the cables.
3
2.2 Assigning sta
Installation, commissioning and repair work must be performed by properly trained personnel authorised by GEZE.
2.3 Product liability
In compliance with the manufacturer’s product liability as dened in the German "Product Liability Act", the inst­ructions included here must be noted and followed. Failure to comply releases the manufacturer from his statuto­ry liability. Only experts authorised by GEZE may carry out installation, functional checks and maintenance work.
2.4 Guidelines
The GEZE IO 420 fulls the following standards:
à DIN EN 61000-6-2: 2005 (in accordance with VDE 0839 Part 6-2 / March 2006) à DIN EN 61000-6-6: 2007+ A1:2011 in accordance with VDE 0839 Part 6-3 / September 2011
3 Product overview/installation details
3.1 Technical data
GEZE IO 420
Device name: IO 420 Function: Universal IO modules Installation: Fitting to top hat rail Main dimensions [mm] (W x H x D): 107 x 111 x 59 Operating voltage: 24 V DC +/-15 % with reverse polarity protection Induced current intake: max. 300 mA at 24 V Total power consumption: 2 A at 24 V Output current (pin 1 and 2): max. 1 A at 24 V Contact rating for relay: 1 A at 30 V Operating temperature [°C]: -20 to 80°C Safetey use: F900: Value 2.5 A
3.2 LEDs, connections and conguration of the IO 420
T
H
B
Fig. 1: LEDs and connections GEZE IO 420
4
GEZE IO 420
3.2.1 LEDs
LED 1 - (red) LED ashes if the microSD card is read or written. LED 2 - (yellow) LED lights up if “CP” (capacitor plate) is connected. LED 3 - (red) LED ashes in case of a fault. LED 4 - (green) LED ashes during normal operation. LED 5 - (green) LED lights up if voltage supply for microcontroller is active. LED 6 - (yellow) LED ashes if data is exchanged via BACnet. LED in - (green) LED-in 4/3/2/1 lights up if input “in” 4/3/2/1 is active. LED out - (red) LED-out 4/3/2/1 lights up if output “out” 4/3/2/1 is active.
3.2.2 Interfaces / GEZE IO 420
Interfaces
à CAN: 50 kBit/s, used for TE 200, VAT 220, TZ 320. à ST 220: used for ST 220, IQ-Aut passive leaf. à GEZE-Bus: used for IQ-Aut active leaf. à BACnet: used for BACnet MS/TP interface.
3.2.3 DIP switch conguration
CAN:
BACnet:
GEZE-Bus: DIP switch terminating resistor “GEZE-Bus” 120 Ohm
Network bias: DIP switch “Network bias”
Terminating resistor “CAN” 120 Ohm
X
Set the DIP switch at the start and end of the CAN-BUS to ON
Terminating resistor “BACnet” 120 Ohm
X
Set the BACnet DIP switch on the rst and last IO 420 of the BACnet MS/TP bus to ON
X
When GEZE motor lock or TZ 320 (connection for KL 220) is connected, set DIP switch to ON.
X
Set the DIP switch to ON to enable the network bias for BACnet MS/TP. Only one bias may be enabled in a BACnet MS/TP network system.
3.2.4 microSD
microSD card
The microSD card (SDHC) is written and read in the FAT16/32 le format. Other formats are not sup­ported. The IO 420 les can be copied to a microSD card. The ST 220 is required for this. The data can be adapted further at the PC if necessary (parameter setting or changing of BACnet names). A microSD card can then be used to load the prole to another IO 420 with the same rmware.
The following les are created on the card:
à Name le for BACnet names: “IO420_V1.BAC”; à Conguration le: “IO420_V1.CON”; contains all parameters for the IO 420. à Log le: “IO420_00.LOG” to “IO420_39.LOG”;
Depending on the setting, alarm messages and actions are written into the log le.
.
.
3.2.5 Reset
Reset push button
If the LED for microSD card is ashing, the microSD card must not be taken out of the slot. The IO 420 must be de­energised for the microSD card to be removed and inserted.
The factory settings can be restored using the reset push button.
Carrying out a reset
X
De-energise the device.
X
Keep the reset button pressed on the printed circuit board.
X
Switch the voltage supply on. The device is restored to the factory settings after 6 seconds. LED 3 “fault” and LED 4 “normal mode” ash simultaneously in 0.4 second cycle.
X
Release the reset button when the LEDs start to ash.
X
To return the device to operating mode, switch the voltage supply o and on again.
5
3.3 BACnet for GEZE IO 420
Networked MS/TP devices
When MS/TP devices are networked, the line topology must always be observed. To avoid branch lines, each IO 420 has two BACnet connections.
Termination 120 Ohm Router Termination 120 Ohm
GEZE IO 420
Only one bias may be enabled in a BACnet
Only one bias may be enabled
in a BACnet MS/TP network system.
MS/TP network system.
Fig. 2: Wiring of BACnet MS/TP and setting of terminating resistor and network bias.
A BACnet MS/TP network requires one active network-bias. The “BACnet” terminating resistor built inside the device must be switched on at the beginning and end of the bus using the respective DIP switch. Maximum 32 MS/TP devices can be connected in one segment. The wiring must meet or exceed the BACnet and MS/TP EIA-485 network standard and be specied as follows:
à Shielded cable, pair-wise twisted. à Impedance 100-130 Ohm. à Capacity between the wires < 100 pF/m (30 pF/ft). à Capacity between the wire and the shield < 200 pF/m (60 pF/ft). à The maximum length of any individual segment is 900 m (AWG18 cable; wire cross-section 0.82 mm²).
With large cable lengths, an amplier may have to be integrated in the bus to guarantee function.
Standard setting of the interface:
à Baud rate:
76.8 kB
à Data bit: 8 à Stop bit: 1 à Parity: none
The following BACnet object types are used for the GEZE IO 420:
à Device object (one object) à Binary input (up to four objects) à Multi state value (up to ten objects) à Notication class object (one object)
3.3.1 Object structure of BACnet for GEZE IO 420
The IO 420 oers 12 module types, each of which can be used with up to 22 objects. The BACnet objects are adapted to the selected module type. The respective EDE lists can be found in the annex to this document.
Index Object Instance number Explanation
1
2 multistate value 1 shows the current module type. 3 multistate value 2 shows the current alarm message.
6
device object 1 contains the device description.
GEZE IO 420
4 binary input 1 5 binary input 2
6 multistate value 3 status message 7 multistate value 4 command 8 notication class object 1 object for alarm message 9 multistate value 5 status message 10 multistate value 6 command 11 binary input 3 12 binary input 4 13 multistate value 7 status message 14 multistate value 8 command 15 multistate value 9 status message 16 multistate value 10 command 17 multistate value 11 alarm 1 for DCU 18 multistate value 12 alarm 1 for DCU 19 multistate value 13 alarm 1 for DCU 20 multistate value 14 command 21 multistate value 15 command 22 multistate value 16 command
3.3.2 Changing the object description
The object description is changed through the BACnet connection. Any BACnet congurator can be used for this.
3.3.3 Changing the BACnet parameters
The IO 420 has four BACnet parameters which can be set using the GEZE service terminal ST 220 or by editing the
conguration le at the PC using the microSD card.
à Device ID: à MAC address: à Baud rate: 76.8 kB (standard setting). à Instance number of “notication class object”: The IO 420 only has one “notication class object” since there
is only one object for alarm messages. In the factory setting, multi state value #2 is allocated to this, but it can be changed by the user. The value range is between 1 and 90.
must be unambiguous in the BACnet network. It may not be allocated twice.
must be unambiguous in an MS/TP network.
assigned dierently depending on the module type
assigned dierently depending on the module type
3.3.4 Changing the object name
This change is carried out by editing the name le “IO420_V1.BAC” at the PC (microSD card).
If the LED for microSD card is ashing, the microSD card must not be taken out of the slot. The IO 420 must be de-energised for the microSD card to be removed and inserted.
X
After the name le has been edited and entered, the following function must be carried out in the service menu for the changes to be applied: “Parameter SD-Card” --> “BAC-Name SD -> IO420”.
Title Name of BACnet object
0.Device object =BAC-PR47-232;
1.binary input 1 =GEZE047AE1E2EL32B125000801;
2.binary input 2 =GEZE047AE1E2EL32B225000801;
3.binary input 3 =not_used;
4.binary input 4 =not_used;
5.Multistate value 1 =module_type;
6.Multistate value 2 =GEZE047AE1E2EL32A106000801;
7.Multistate value 3 =TZ320_state;
8.Multistate value 4 =TZ320_command;
9.Multistate value 5 =alarm_details;
10.Multistate value 6 =not_used;
11.Multistate value 7 =not_used;
12.Multistate value 8 =not_used;
13.Multistate value 9 =not_used;
14.Multistate value 10 =not_used;
15.Multistate value 11 =not_used;
16.Multistate value 12 =not_used;
17.Multistate value 13 =not_used;
7
18.Multistate value 14 =not_used;
19.Multistate value 15 =not_used;
21.Notication class =xxxyyy; END OF FILE----------------------------------------------
The title part including the “=” sign must not be changed. The “=” has the function of separating the title and BACnet name. The name of the individual BACnet objects may be changed. Care must be taken that the line ends with a semicolon “;” and the name does not contain more than 32 characters. Special characters may not be used, with the exception of space, underscore, hyphen, full stop and comma.
4 Parameter setting GEZE IO 420
The rst time parameters are set for the IO 420, the GEZE service terminal ST 220 should always be used. Once entered, the conguration le “IO420_V1.CON” can be copied to a microSD card and adapted further at the PC if necessary. A microSD card can then be used to load this prole to another IO 420 with the same rmware.
GEZE IO 420
If the LED for microSD card is ashing, the microSD card must not be taken out of the slot. The IO 420 must be de-energised for the microSD card to be removed and inserted.
The following points must be remembered when the conguration le is modied at the PC:
à The parameter name including the “=” sign must not be changed. The “=” has the function of separating the
title part and the value. à The parameter value may only contain numbers. à Heed the min./max. values given in brackets.
Parameter name Value Description
0.CAN_ADDR1(0~63) = 1; CAN address for door #1
1.CAN_ADDR2(0~63) = 0; CAN address for door #2
2.CAN_ADDR3(0~63) = 0; CAN address for door #3
3.CAN_ADDR4(0~63) = 0; CAN address for door #4
4.BACNET_MACADR(0~127) = 1; BACnet MAC address
5.BACNET_DEVICEID(1~4194303) = 1; BACnet DEVICE-ID
6.BACNET_BAUDRATE(0~6) = 5; 0 = Not active
7.BACNET_NOTIFYCLASS(1~90) = 50; Instance number of the notication class object.
8.VALUE_UTC_OFFSET(0~780) = 60; UTC time oset in minutes; amount shown without sign (e.g. EN = 60 min.)
9.SIGN_UTC_OFFSET(1:-/0:+) = 1; Sign for UTC oset.
10.CONF_OUTPUT3(0~4)
11.CONF_OUTPUT4(0~4)
12.INPUT1_TYPE(0~10)
13.INPUT2_TYPE(0~10)
14.INPUT3_TYPE(0~12)
15.INPUT4_TYPE(0~12)
16.KZF1_ABORT(0/1) = 0; 0: Short-term release door #1 not interruptible
17.KZF1_AFTERTRG(0/1) = 0; 0: Short-term release door #1 cannot be triggered later
18.KZF1_TIME(3~30) = 10; Short-term release time door #1 (3 to 30 seconds)
19.KZF2_ABORT(0/1) = 0; 0: Short-term release door #2 not interruptible
==0;0;Conguration of output 3 and 4 for door solution
= = = =
1= 9.6 kB
1 : Negative oset 0: Positive oset Oset = [UTC] - [local time], which is why Germany has a negative value.
0: Output inactive 1: Alarm 2: Locked
10;
The valid value range for the respective input varies depending on the module
10;
type.
10;
The following list is used to decipher the numbers. Changes to the inputs must be
10;
made using the GEZE service terminal ST 220. 0: Inactive
1: Active leaf unlocked 2: Unlock active leaf (command) 3: Short-term release (KZF) active leaf (AL) and passive leaf (IL) (commands) 4: Active leaf closed 5: Fire alarm system (opener) 6: RWA (opener)
1: Short-term release door #1 interruptible
1: Short-term release door #1 can be triggered later
1: Short-term release door #2 interruptible
2= 19.2 kB 3= 38.4 kB
4= 57.6 kB 5= 76.8 kB
3: Closed 4: Locked and closed.
7: Passive leaf closed 8: KZF-AL (command) 9: Time switch (ZSU) master 10: Switch function 11: Fire alarm system for universal module (closer) 12: RWA for universal module (closer)
6= 115.2 kB
8
GEZE IO 420
20.KZF2_AFTERTRG.(0/1) = 0; 0: Short-term release door #2 cannot be triggered later
21.KZF2_TIME(3~30) = 10; Short-term release time door #2 (3 to 30 seconds)
22.KZF3_ABORT(0/1) = 0; 0: Short-term release door #3 not interruptible
23.KZF3_AFTERTRG.(0/1) = 0; 0: Short-term release door #3 cannot be triggered later
24.KZF3_TIME(3~30) = 10; Short-term release time door #3 (3 to 30 seconds)
25.KZF4_ABORT(0/1) = 0; 0: Short-term release door #4 not interruptible
26.KZF4_AFTERTRG.(0/1) = 0; 0: Short-term release door #4 cannot be triggered later
27.KZF4_TIME(3~30) = 10; Short-term release time door #4 (3 to 30 seconds)
28. ADJ_DAY_LIGHT_SAVING (0/1) = 1; 0: Automatic switch over between summer and winter time is disabled
29.not_used = 0;
30.AL_SUPPR_DUR(0~250) = 50; Duration of the alarm suppression with “watchdog” module type in seconds
31.AL_DELAY_TIME(0~250) = 100; Duration of the alarm delay with “watchdog” module type in seconds
32.MODULETYPE(0~12) = 10; 0: Watchdog;
33.LOGFILE_LEVEL(0~2) = 0; 0: Level 0. No protocol is written in the log le
34.ZSUMASTER1_ACTIVITY(0/1) = 0; 0: As “ZSU master group 1” not active
35.ZSUMASTER1_SUNDAY(0/1)
36.ZSUMASTER1_MONDAY(0/1)
37.ZSUMASTER1_TUESDAY(0/1)
38.ZSUMASTER1_WEDNESDA(0/1)
39.ZSUMASTER1_THURSDAY(0/1)
40.ZSUMASTER1_FRIDAY(0/1)
41.ZSUMASTER1_SATURDAY(0/1)
42.ZSUMASTER1_START_HH(0~23)
43.ZSUMASTER1_START_MM(0~59) ==0;0;
44.ZSUMASTER1_END_HH(0~23)
45.ZSUMASTER1_END_MM(0~59) ==0;0;
46.ZSUMASTER2_ACTIVITY(0/1) = 0; 0: As “ZSU master group 2” not active.
47.ZSUMASTER2_SUNDAY(0/1)
48.ZSUMASTER2_MONDAY(0/1)
49.ZSUMASTER2_TUESDAY(0/1)
50.ZSUMASTER2_WEDNESDAY(0/1)
51.ZSUMASTER2_THURSDAY(0/1)
52.ZSUMASTER2_FRIDAY(0/1)
53.ZSUMASTER2_SATURDAY(0/1)
54.ZSUMASTER2_START_HH(0~23)
55.ZSUMASTER2_START_MM(0~59) ==0;0;
56.ZSUMASTER2_END_HH(0~23)
57.ZSUMASTER2_END_MM(0~59) ==0;0;
58.ZSUMASTER3_ACTIVITY(0/1) = 0; 0: As “ZSU master group 3” not active.
59.ZSUMASTER3_SUNDAY(0/1)
60.ZSUMASTER3_MONDAY(0/1)
61.ZSUMASTER3_TUESDAY(0/1)
62.ZSUMASTER3_WEDNESDAY(0/1)
63.ZSUMASTER3_THURSDAY(0/1)
64.ZSUMASTER3_FRIDAY(0/1)
65.ZSUMASTER3_SATURDAY(0/1)
66.ZSUMASTER3_START_HH(0~23)
67.ZSUMASTER3_START_MM(0~59) ==0;0;
68.ZSUMASTER3_END_HH(0~23)
69.ZSUMASTER3_END_MM(0~59) ==0;0;
70.ZSUMASTER4_ACTIVITY(0/1) = 0; 0: As “ZSU master group 4” not active.
= = = = = = =
= = = = = = =
= = = = = = =
1: Short-term release door #2 can be triggered later
1: Short-term release door #3 interruptible
1: Short-term release door #3 can be triggered later
1: Short-term release door #4 interruptible
1: Short-term release door #4 can be triggered later
1: Automatic switch over between summer and winter time is enabled
1: One-door solution 2: Two-door solution 3: Four-door solution 4: IQ Lock EL + AUT 5: IQ Lock 72 + AUT version 2)
1: Level 1. Alarm messages are written in the log le 2: Level 2. Alarm messages and actions are written in the log le
1: As “ZSU master group 1” active
0;
Day conguration “ZSU master group 1”
0;
0: As “ZSU master group 1” inactive on this day of the week
0;
1: As “ZSU master group 1” active on this day of the week 0; 0; 0; 0;
Start time “ZSU master group 1”
Specication of “hours” 0-23; specication of “minutes” 0-59
End time “ZSU master group 1”
Specication of “hours” 0-23; specication of “minutes” 0-59
1: As “ZSU master group 2” active. 0;
Day conguration “ZSU master group 2”. 0;
0: As “ZSU master group 2” inactive on this day of the week 0;
1: As “ZSU master group 2” active on this day of the week 0; 0; 0; 0;
Start time “ZSU master group 2”
Specication of “hours” 0-23; specication of “minutes” 0-59
End time “ZSU master group 2”
Specication of “hours” 0-23; specication of “minutes” 0-59
1: As “ZSU master group 3” active. 0;
Day conguration “ZSU master group 3”. 0;
0: As “ZSU master group 3” inactive on this day of the week 0;
1: As “ZSU master group 3” active on this day of the week 0; 0; 0; 0;
Start time “ZSU master group 3”
Specication of “hours” 0-23; specication of “minutes” 0-59
End time “ZSU master group 3”
Specication of “hours” 0-23; specication of “minutes” 0-59
1: As “ZSU master group 4” active.
(from software
6: Automatic stat. 7: Automatic 4Sec 8: Window 9: Universal 10: RWS + KL400
9
GEZE IO 420
71.ZSUMASTER4_SUNDAY(0/1)
72.ZSUMASTER4_MONDAY(0/1)
73.ZSUMASTER4_TUESDAY(0/1)
74.ZSUMASTER4_WEDNESDAY(0/1)
75.ZSUMASTER4_THURSDAY(0/1)
76.ZSUMASTER4_FRIDAY(0/1)
77.ZSUMASTER4_SATURDAY(0/1)
78.ZSUMASTER4_START_HH(0~23)
79.ZSUMASTER4_START_MM(0~59) ==0;0;
80.ZSUMASTER4_END_HH(0~23)
81.ZSUMASTER4_END_MM(0~59) ==0;0;
82.ZSUMASTER5_ACTIVITY(0/1) = 0; 0: As “ZSU master group 5” not active
83.ZSUMASTER5_SUNDAY(0/1)
84.ZSUMASTER5_MONDAY(0/1)
85.ZSUMASTER5_TUESDAY(0/1)
86.ZSUMASTER5_WEDNESDAY(0/1)
87.ZSUMASTER5_THURSDAY(0/1)
88.ZSUMASTER5_FRIDAY(0/1)
89.ZSUMASTER5_SATURDAY(0/1)
90.ZSUMASTER5_START_HH(0~23)
91.ZSUMASTER5_START_MM(0~59) ==0;0;
92.ZSUMASTER5_END_HH(0~23)
93.ZSUMASTER5_END_MM(0~59) ==0;0;
94.DOOR1_SLAVEZSU_GR1(0/1)
95.DOOR1_SLAVEZSU_GR2(0/1)
96.DOOR1_SLAVEZSU_GR3(0/1)
97.DOOR1_SLAVEZSU_GR4(0/1)
98.DOOR1_SLAVEZSU_GR5(0/1)
99.DOOR1_SLAVEZSU_ABORT(0/1) = 0; 0: Time switch function for door #1 not interruptible
100.DOOR2_SLAVEZSU_GR1(0/1)
101.DOOR2_SLAVEZSU_GR2(0/1)
102.DOOR2_SLAVEZSU_GR3(0/1)
103.DOOR2_SLAVEZSU_GR4(0/1)
104.DOOR2_SLAVEZSU_GR5(0/1)
105.DOOR2_SLAVEZSU_ABORT(0/1) = 0; 0: Time switch function for door #2 not interruptible
106.DOOR3_SLAVEZSU_GR1(0/1)
107.DOOR3_SLAVEZSU_GR2(0/1)
108.DOOR3_SLAVEZSU_GR3(0/1)
109.DOOR3_SLAVEZSU_GR4(0/1)
110.DOOR3_SLAVEZSU_GR5(0/1)
111.DOOR3_SLAVEZSU_ABORT(0/1) = 0; 0: Time switch function for door #3 not interruptible
112.DOOR4_SLAVEZSU_GR1(0/1)
113.DOOR4_SLAVEZSU_GR2(0/1)
114.DOOR4_SLAVEZSU_GR3(0/1)
115.DOOR4_SLAVEZSU_GR4(0/1)
116.DOOR4_SLAVEZSU_GR5(0/1)
117.DOOR4_SLAVEZSU_ABORT(0/1) = 0; 0: Time switch function for door #4 not interruptible
118.TYPE OF CP(0~3) = 0; 0: No CP
END OF FILE---------------------------
=
0;
= = = = = =
= = = = = = =
= = = = =
= = = = =
= = = = =
= = = = =
Day conguration “ZSU master group 4” 0;
0: As “ZSU master group 4” inactive on this day of the week 0;
1: As “ZSU master group 4” active on this day of the week 0; 0; 0; 0;
Start time “ZSU master group 4”
Specication of “hours” 0-23; specication of “minutes” 0-59
End time “ZSU master group 4”
Specication of “hours” 0-23; specication of “minutes” 0-59
1: As “ZSU master group 5” active 0;
Day conguration “ZSU master group 5” 0;
0: As “ZSU master group 5” inactive on this day of the week 0;
1: As “ZSU master group 5” active on this day of the week 0; 0; 0; 0;
Start time “ZSU master group 5”
Specication of “hours” 0-23; specication of “minutes” 0-59
End time “ZSU master group 5”
Specication of “hours” 0-23; specication of “minutes” 0-59 0;
Slave assignment of door #1 to “ZSU master group” 1 to 5 0;
0: Door #1 is not part of this ZSU group 0;
1: Door #1 is part of this ZSU group 0; 0;
1: Time switch function for door #1 interruptible 0;
Slave assignment of door #2 to “ZSU master group” 1 to 5 0;
0: Door #1 is not part of this ZSU group 0;
1: Door #1 is part of this ZSU group 0; 0;
1: Time switch function for door #2 interruptible 0;
Slave assignment of door #3 to “ZSU master group” 1 to 5 0;
0: Door #3 is not part of this ZSU group 0;
1: Door #3 is part of this ZSU group 0; 0;
1: Time switch function for door #3 interruptible 0;
Slave assignment of door #4 to “ZSU master group” 1 to 5 0;
0: Door #4 is not part of this ZSU group 0;
1: Door #4 is part of this ZSU group 0; 0;
1: Time switch function for door #4 interruptible
3: Pin “+24V” and pin “DET” of the con-
1: One CP
2: Two CPs
nector “CP” are short-circuited together. “CP” are short-circuited together.
10
GEZE IO 420
5 Module description
The IO 420 oers 10 module types. The respective inputs/outputs are used in dierent ways depending on the module type.
5.1 Module type “watchdog”
The “watchdog” module type can be used for monitoring a door. When the monitoring function is armed, the door may only be opened by release. In all other cases, an alarm message is sent after the alarm suppression and alarm delay times have expired. When the monitoring function is not armed, the door can be opened without release.
Connections Assignment/function description Menu Input 1 à Rising ank - monitoring is disarmed
à Falling ank - monitoring is armed
2 Release with short-term release function; only with rising ank 3 Lock feedback 4 Door contact
Output 1 Monitoring state; enabled with armed monitoring
2 Electric strike fail safe 3 Alarm suppressed: 1 sec cycle
Alarm delayed: on Alarm enabled: o
4 Alarm suppressed: o
Alarm delayed: o Alarm enabled: Permanently on
Duration for short-term release
Tab. 1: Pin assignment for “watchdog” module type
Funktionsbeschreibung der Ein- und Ausgänge
current state State changes to State changes with
Monitoring disarmed Alarm active Sabotage
Monitoring armed à Falling ank at input 1
Monitoring armed Alarm active Sabotage
Monitoring disarmed à Rising ank at input 1
Alarm suppressed If the door is locked but open
Alarm suppressed (output 1 enabled and output 3 ashing every few seconds)
Alarm active Sabotage Monitoring disarmed à Rising ank at input 1
Monitoring armed
Alarm delayed If the alarm suppression time has expired
Alarm delayed (output 1 and 3 enabled.)
Alarm enabled (output 1 and 4 enabled.)
Alarm active à Sabotage
Monitoring armed (if the alarm actuation has been cancelled and a command sent either via input 2, CAN or BACnet as acknowledgement to the IO 420.)
Monitoring armed (if the alarm actuation has been cancelled and a command sent either via input 2, CAN or BACnet as acknowledgement to the IO 420.)
à CAN command “watchdog enable” à BACnet command “watchdog enable”
à CAN command “watchdog disable” à BACnet command “watchdog disable”
à CAN command “watchdog disable” à BACnet command “watchdog disable”
If the alarm actuation has been cancelled and the alarm acknowledged
à If the alarm delay time has expired à Short-term release through input 2
à CAN command “watchdog enable”,
“watchdog disable” or “KZF”
à BACnet command “KZF”
à Short-term release through input 2 à CAN command “watchdog enable”,
“watchdog disable” or “KZF”
à BACnet command “KZF”
11
5.2 Module type “1 door”
The “1 door” module type can be used for controlling one door. The connection of release switch, short-term release push button, reed contact and lock feedback is possible. The messages are forwarded via bus.
Connections Assignment/function description
Input
Output
Tab. 2-pin assignment module type “1-door”
à Rising ank - unlock
1
à Falling ank - lock
Short-term release is triggered with rising ank
2
Lock feedback
3
Door contact
4
Electric strike fail safe
1
Electric strike fail secure
2
Can be congured à Inactive
3
Can be congured à Inactive
4
GEZE IO 420
à Sabotage alarm à Closed à Locked à Closed and locked
à Sabotage alarm à Closed à Locked à Closed and locked
Current state State changes to State changes with
unlocked In this state output 1 is enabled and output 2 is disabled. Output 3 and 4 are enabled or disabled depending on the conguration.
locked In this state output 2 is enabled and output 1 is disabled. Output 3 and 4 are enabled or disabled depending on the conguration.
short-term release (KZF) In this state output 1 is enabled and output 2 disabled. Output 3 and 4 are enabled or disabled depending on the conguration. KZF time can be extended by input 2 if “KZF re­triggering” is enabled.
time switch (ZSU) In this state output 1 is enabled and output 2 disabled. Output 3 and 4 are enabled or disabled depending on the conguration.
locked if time switch is not enabled.
time switch (ZSU) If ZSU is active and one of the above-menti-
unlocked à Rising ank from input 1
short-term release (KZF) à Rising ank from input 2
time switch (ZSU) If ZSU message is enabled and ZSU was not
locked If KZF time has expired
unlocked à Rising ank from input 1
locked with enabled option time switch inter­ruption
locked without enabled option time switch interruption
à Falling ank from input 1 à CAN command “lock” à BACnet command “lock” à Sabotage
oned release devices occurs
à CAN command “unlock” à BACnet command “unlock”
à CAN command “short-term release” à BACnet command “short-term release”
interrupted
If KZF interruptible is enabled and the door is closed again after opening. KZF is enabled for at least 2.5 seconds
à CAN command “unlock” à BACnet command “unlock”
à Falling ank from input 1 à CAN command “lock” à BACnet command “lock”
à Sabotage à If time switch message is no longer
enabled
Time switch interruption
If “time switch interruptible” is enabled in the IO 420 conguration, the “time switch” state can be interrupted using the “lock” command. The state then changes to “locked” and the ag “time switch aborted” is set. No further change in state can take place when the ag is set. The ag is reset again when the door is unlocked and locked. The mes­sage “time switch” has to be enabled.
12
GEZE IO 420
5.3 Module type “2 doors”
The “2 doors” module type can be used for controlling two mutually independent doors. The connection of door contacts and lock feedback to the inputs is possible. The connection of a release switch is not designated for this module type.
Connections Assignment/function description
Input
Output
Tab. 3: Pin assignment module type “2-doors”
Lock feedback door #1
1
Door contact door #1
2
Lock feedback door #2
3
Door contact door #2
4
Electric strike fail safe door #1
1
Electric strike fail safe door #2
2
Can be congured for door #1 à Inactive
3
Can be congured for door #2 à Inactive
4
à Sabotage alarm à Closed à Locked à Closed and locked
à Sabotage alarm à Closed à Locked à Closed and locked
Current state State changes to State changes with
unlocked In this state output 1 or 2 is enabled. Output 3 and 4 are enabled or disabled depending on the conguration.
locked In this state output 1 or 2 is disabled. Output 3 and 4 are enabled or disabled depending on the conguration.
short-term release (KZF) In this state output 1 or 2 is enabled. Output 3 and 4 are enabled or disabled depending on the conguration. KZF re­triggering is not possible in this mode.
time switch (ZSU) In this state output 1 or 2 is enabled. Output 3 and 4 are enabled or disabled depending on the conguration.
locked if time switch is not enabled.
time switch (ZSU) If ZSU is active and one of the above-men-
unlocked à CAN command “unlock”
short-term release (KZF) à CAN command “short-term release”
time switch (ZSU) If ZSU message is enabled and if ZSU was
locked à If KZF time has expired
unlocked à CAN command “unlock”
locked with enabled option time switch interrup­tion
locked without enabled option time switch interruption
à CAN command “lock” à BACnet command “lock” à Sabotage
tioned release devices occurs.
à BACnet command “unlock”
à BACnet command “short-term release”
not interrupted.
à If KZF interruptible is enabled and the
door is closed again after opening. The min. KZF time is 2.5 seconds.
à BACnet command “unlock” à CAN command “lock”
à BACnet command “lock”
à Sabotage à If time switch message is no longer
enabled
13
5.4 Module type “4 doors”
The “4 doors” module type can be used for controlling four mutually independent doors. Only the connection of door contacts to the inputs is possible. The connection of a lock feedback or a release switch is not designated for this module type.
Connections Assignment/function description
Input
Output
Tab. 4: Pin assignment module type “4-doors”
Current state State changes to State changes with
unlocked In this state output 1, 2, 3 or 4 is enabled.
locked In this state output 1, 2, 3 or 4 is disabled.
short-term release (KZF) In this state output 1, 2, 3 or 4 is enabled. KZF re-triggering is not possible in this mode.
time switch (ZSU) In this state output 1, 2, 3 or 4 is enabled.
Door contact door #1
1
Door contact door #2
2
Door contact door #3
3
Door contact door #4
4
Electric strike fail safe door #1
1
Electric strike fail safe door #2
2
Electric strike fail safe door #3
3
Electric strike fail safe door #4
4
GEZE IO 420
locked if time switch is not enabled.
time switch (ZSU) If ZSU is active and one of the above-men-
unlocked à CAN command “unlock”
short-term release (KZF) à CAN command “short-term release”
time switch (ZSU) If ZSU message is enabled and if ZSU was
locked If KZF time has expired
unlocked à CAN command “unlock”
locked with enabled option time switch interrup­tion
locked without enabled option time switch interruption
à CAN command “lock” à BACnet command “lock” à Sabotage
tioned release devices occurs
à BACnet command “unlock”
à BACnet command “short-term release”
not interrupted
If KZF interruptible is enabled and the door is closed again after opening. The min. KZF time is 2.5 seconds.
à BACnet command “unlock” à CAN command “lock”.
à BACnet command “lock”
à Sabotage à If time switch message is no longer
enabled.
14
GEZE IO 420
5.5 Module type “automatic stat” / “automatic 4 sec”
With this module type, the IO 420 can control a GEZE door drive via inputs/outputs. Switches can be connected at input 1 and 2 for this. Input 3 and 4 are used to evaluate the door feedback.
With this module type, no fault messages of the drive can be evaluated via the IO 420, since the drive com­municates via the inputs/outputs rather than via RS485.
Connections Assignment/function description
Input
1
2
3 4
Output
1 2 3 4
Tab. 5: Pin assignment of module type “automatic”
State State changes to State changes with
automatic Output 3 is enabled. If module type “automatic 4 sec” is enab­led, output 3 is switched o again after 4 seconds.
shop closed (shop closing) Output 2 is enabled. If module type “automatic 4 sec” is enabled, output 2 is switched o again after 4 seconds.
permanently open: Output 4 is enabled. If module type “automatic 4 sec” is enabled, output 4 is switched o again after 4 seconds.
night Output 1 is enabled. If module type “automatic 4 sec” is enabled, output 1 is switched o again after 4 seconds.
à Rising ank: change of state to “automatic” à Falling ank: change of state to “night”
à Rising ank: change of state to “permanently open” à Falling ank: no eect
Lock state Door contact Command to DCU “night” Command to DCU “shop closed” Command to DCU “automatic” Command to DCU “permanently open”
night à Falling ank input 1
shop closed à CAN command “close shop”
permanently open à The rising ank input 2
night à The falling ank input 1
automatic à The rising ank input 1
permanently open à The rising ank input 2
night à The falling ank input 1
shop closed à CAN command “close shop”
automatic à The rising ank input 1
automatic à The rising ank input 1
shop closed à CAN command “close shop”
permanently open à The rising ank input 2
à CAN command “night” à BACnet command “night”
à BACnet command “close shop”
à CAN command “permanent open” à BACnet command “permanent open”
à CAN command “night” à BACnet command “night”
à CAN command “automatic” à BACnet command “automatic”
à CAN command “permanent open” à BACnet command “permanent open”
à CAN command “night” à BACnet command “night”
à BACnet command “close shop”
à CAN command “automatic” à BACnet command “automatic”
à CAN command “automatic” à BACnet command “automatic”
à BACnet command “close shop”
à CAN command “permanent open” à BACnet command “permanent open”
15
5.6 Module type “window”
With this module type, the IO 420 can control two windows via inputs/outputs. Switches can be connected at input 1 and 3 for this. Control is by means of collective commands i.e. the windows are triggered together.
With this module type, no fault messages of the drive can be evaluated, since the drive communicates via the inputs/outputs rather than via RS485.
Connections Assignment/function description
Input
Output
Tab. 6: Pin assignment of module type “window”
Current state State changes to State changes with
stop all outputs are disabled.
closing Output 2 or 4 is enabled.
opening Output 1 or 3 is enabled.
Collective command “open windows” with rising ank. The falling ank has no function.
1
Collective command “close windows” with rising ank. The falling ank has no function.
2
Collective command “stop windows”.
3
Feedback “closed” for window 1 and 2. The contacts should be closed in series.
4
Relais_open_win1. This relay is enabled if window 1 is to be opened.
1
Relais_close_win1. This relay is enabled if window 1 is to be closed.
2
Relais_open_win2. This relay is enabled if window 2 is to be opened.
3
Relais_close_win2. This relay is enabled if window 2 is to be closed.
4
GEZE IO 420
Whether a stop is triggered by falling or rising ank can be congured.
opening à Rising ank from input 1
à BACnet command “open window” à CAN command “open window”
closing à Rising ank from input 2
à BACnet command “close window” à CAN command “close window”
opening à Rising ank from input 1
à BACnet command “open window” à CAN command “open window”
stop à Rising ank from input 3
à If the time of 90 sec has expired. à BACnet command “stop” à CAN command “stop”
closing à Rising ank from input 2
à BACnet command “close window” à CAN command “close window”
stop à Rising ank from input 3
à If the time of 90 sec has expired. à BACnet command “stop” à CAN command “stop”
5.7 Module type “universal”
With this module type, the IO 420 has universal control via inputs/outputs. Switches can be connected at input 1 and 4 for this. The inputs can be congured as ZSU masters and the ZSU master can be actuated via the respecti­ve switch or internal timer. In addition, inputs 3 and 4 can be congured for RWA or BMA.
Connections Assignment/function description
Input
Output
Tab. 7 Pin assignment module type “universal”
16
à Switch for relay 1:
1
2
3
4
1 2 3 4
Output 1 is switched on for rising ank, the output is switched o for falling ank.
à ZSU master 1: ZSU master #1 is enabled as long as the switch is switched on. à Switch for relay 2
à ZSU master 2 à Switch for relay 3
à ZSU master 3 à BMA (closer) à RWA (closer)
à Switch for relay 4 à ZSU master 4 à BMA (closer) à RWA (closer)
Output relay 1 Output relay 2 Output relay 3 Output relay 4
GEZE IO 420
State State changes to State changes with
o The corresponding output is disabled.
on The corresponding output is enabled.
time switch The corresponding output is enabled.
on à With rising ank of the corresponding
time switch If ZSU message is enabled and if ZSU was
o if ZSU is not enabled.
time switch à With the above-mentioned release
o à If the ZSU message is disabled.
5.8 Module type “IQ lock El + Aut”
The module type “IQ Lock EL + Aut” is used to activate GEZE motor locks. IQ Aut is connected with the IO 420 via bus (terminal “ST 220”) and controlled accordingly. All the states and fault messages of IQ Aut can be read out and forwarded via BACnet. IQ Lock EL is connected with the IO 420 via inputs/outputs and controlled accordingly. For this reason, the IO 420 can neither read out fault messages of IQ Lock EL nor forward these via BACnet.
input, if this is congured as a switch. à BACnet command “on” à CAN command “on”
not interrupted.
à Falling ank of the corresponding
input, if this is congured as a switch. à BACnet command “o” à CAN command “o”
devices if the ZSU message is enabled.
à BACnet command “o” can trigger this
change in state if ZSU is congured as
“interruptible”. à CAN command “o” can trigger this
change in state if ZSU is congured as
“interruptible”.
CAUTION
In the case of re protection door, capacitor power (CP) must be connected to terminal CP and the parameter “Conf. CP” must be set accordingly (see chapter 6.3 Service menu).
Release of the passive leaf
When the passive leaf is released, the active leaf is automatically released immediately.
Permanently open
With IQ Lock EL the state “permanently open” is possible. With IQ Aut the door remains opened for the hold-open time set in the IO 420 conguration. The shoot bolt is held by the switch lock as long as the door is open.
Connections Assignment/function description
Input
Output
AL_locked (feedback)
1 2
3
4
1 2 3 4
à Release_AL (command, factory setting) à KZF_AL_IL (command), triggered with rising ank
à KZF_AL_IL (command, factory setting), triggered with rising ank à AL_closed (feedback) à BMA (evaluated as opener) à RWA (evaluated as opener)
à BMA (factory setting, opener) à RWA (opener) à IL_closed (feedback) à KZF_AL (command), triggered with rising ank
Release for IQ Lock EL
Day/night for IQ Lock EL
Feedback Relay active when AL is locked
Feedback Relay active when AL is locked
Tab. 8: Pin assignment of module type “IQ lock”
17
5.8.1 Active leaf
Current state State changes to State changes with
night Outputs 1, 2 and 3 are disabled.
day Output 2 is enabled
released Output 3 is enabled.
short-term release Output 1 is enabled.
error The error can be acknowledged with
GEZE IO 420
day à BACnet command “day”
à CAN command “day”
released à Rising ank of input “release”
à BACnet command “release” à CAN command “release”
short-term release (KZF) à Rising ank of input “KZF”
à BACnet command “short-term release” à CAN command “short-term release”
night à Falling ank from input “day/night”
à BACnet command “night” à CAN command “night”
released à Rising ank of input “release”
à BACnet command “release” à CAN command “release”
short-term release à Rising ank of input “KZF”
à BACnet command “short-term release” à CAN command “short-term release”
night à Falling ank of input “release” (the last
previous state was “night”) à BACnet command “night” à CAN command “night”
day à BACnet command “day”
à CAN command “day”
short-term release à Not possible night à Falling ank of input “release” (the last
previous state was “night”) à BACnet command “night” à CAN command “night”
day à BACnet command “day”
à CAN command “day”
released à Rising ank of input “release”
à BACnet command “release” à CAN command “release”
any command.
5.8.2 Passive leaf
current state State changes to State changes with
unlock (shown as “release” in VAT 220): Output 4 is enabled.
lock (shown as “night” in VAT 220): Output 4 is disabled.
into lock (shown as “day” in VAT 220): This state is an intermediate state between “unlock” and “lock”.
into unlock (shown as “day” in VAT 220): This state is an intermediate state between “lock” and “unlock”.
error (shown as “error” in VAT 220):
lock à BACnet command “lock”
unlock if ZSU is not enabled.
The error can be acknowledged with any command.
à CAN command “lock”
à The rising ank of input “release_IL” à BACnet command “unlock” à CAN command “unlock”
18
GEZE IO 420
5.9 Module type “RWS + KL”
In the module type “RWS + KL” the IO 420 works as a gateway between the CAN bus and BACnet and translates the lifetime message of the TZ 320 into the BACnet protocol. The control commands generated are turned into CAN commands by the IO 420 and forwarded to the TZ 320.
Gateway CAN BACnet
à TZ 320 transmits a lifetime message every second, which is transformed into the BACnet protocol and forwar-
ded on BACnet MS/TP level.
à BACnet object multi state value 4 is dened for activating the TZ 320. This object comprises three commands:
“short-term release”, “unlock” and “lock”.
à The bus functions of the TZ 320 e.g. “collective locking”, “BMA group over BUS” etc. are currently not suppor-
ted by the IO 420. The bus function “timer” is implemented and is supported. à If a ZSU master transmits a ZSU message via BACnet, the IO 420 translates this into a CAN message. à If the IO 420 is congured as a timer master, the IO 420 transmits the ZSU message both via CAN bus and
BACnet.
Terminal box
The inputs and outputs of the IO 420 can be used as an IO extension for the TZ 320. KL 220 has 4 inputs and 6 outputs. Since the IO 420 has 4 inputs and 4 outputs, the conguration for the fth and sixth output of the KL 220 is not evaluated.
Fig. 3: Composition BACnet MS/TP and CAN for GEZE IO 420 as Gateway for TZ 320
Setting in TZ 320 and IO 420
à CAN: The CAN address in TZ 320 and IO 420 must be identical for both devices to be able to communicate with
one another via CAN. à CAN terminating resistor The CAN terminating resistor in TZ 320 and IO 420 must be switched on. à The terminating resistor for the GEZE bus in IO 420 must be switched on. This setting is important for the
“terminal box” function. à Timer function:
The TZ 320 must be congured as a “slave”.
The IO 420 per segment must be congured as “master”. à The ZSU master function is supported by the IO 420 with the following module types:
à 1-door solution à 2-door solution à 4-door solution à Universal
19
X104 (red terminal strip)
GND supply
24 V DC supply
GEZE IO 420
Fig. 4: Connection example for the module type “RWS + KL 220”
20
GEZE IO 420
5.10 Module type “DCU1, 2 and 8”
“DCU 1, 2 and 8” are type identications of swing door and sliding door drive with DCU light (CAN interface). In this type of module, the IO 420 functions as gateway as in module type “RWS + KL”. Therefore, drives require DCU light so that the lifetime report is forwarded to IO 420 via Can. Active leaves and passive leaves can also be connected.
Gateway CAN BACnet
à Automatic drive transmits a lifetime message every second, which is transformed into the BACnet protocol
and forwarded on BACnet MS/TP level. à BACnet object multistate value 3 represents the current operating mode. à BACnet object multistate value 4 can change the operating mode. à The inputs and outputs must be used freely as in module type “universal”.
Setting in DCU
à CAN: The CAN address in DCU and IO 420 must be identical for both devices to be able to communicate with
one another via CAN. E.g. DCU-GF has CAN-Address 7 and DCU-SF has 8. Then you must set CAN addresses in
IO 420:
In „Buskonf.“ „konf.CAN“ „1.CAN-Adresse:“ muss die CAN-Adresse für DCU-GF eingetragen werden.
In „Buskonf.“ „konf.CAN“ „2.CAN-Adresse:“ soll die CAN-Adresse für DCU-SF eingetragen werden. à CAN-terminating resistor on the rst and last device must be activated.
Device Parameter Value DCU-GF Bus address 1 DCU-SF Bus address 2
IO 420
Buskonf./ 1.CAN-Adr 1 Buskonf./ 1.CAN-Adr 2
5.11 Module type “DCU6” (revolving door)
In this type of module, the IO 420 functions as gateway as in module type “DCU 1, 2 and 8”. Therefore, drives require DCU light so that the lifetime report is forwarded to IO 420 via Can. Active leaves and passive leaves can also be connected.
Gateway CAN BACnet
à Automatic drive transmits a lifetime message every second, which is transformed into the BACnet protocol
and forwarded on BACnet MS/TP level. à BACnet object multistate value 3 represents the current operating mode. à BACnet object multistate value 4 can change the operating mode. à The inputs and outputs must be used freely as in module type “universal”.
Setting in DCU
à CAN: The CAN address in DCU and IO 420 must be identical for both devices to be able to communicate with
one another via CAN. In “Buskonf.” “konf.CAN” “1.CAN-Adresse:” the CAN address of the revolving door drive
must be entered. à CAN-terminating resistor of both devices must be activated.
5.12 Module type “DCU128+RWS+KL”
à This type of module is a summary of “RSW+KL” and “DCU 1, 2 and 8”. TZ 320, DCU-GF and DCU-SF are con-
nected by CAN. Terminals 45 and 46 of TZ 320 are connected to the GEZE BUS of IO 420. Thus, the inputs and
outputs of IO 420 are used as terminal box for RWS.
Setting in DCU
à CAN address of DCU-GF and TZ320 must have the same CAN address. This address is entered in IO 420 under
“Buskonf.” “Konf. CAN” “CAN-Adr[DCU GF,TZ]“. à CAN-Address of DCU-SF is entered in IO 420 under “Buskonf.” “Konf. CAN” “CAN-Adr[DCU SF]”.
Device Parameter Value Parameter DCU-GF Bus address 1 Bus address DCU-SF Bus address 2 Bus address TZ 320 Bus address 1 Bus address
IO 420
Buskonf./ 1.CAN-Adr 1 Buskonf./ 2.CAN-Adr 2
21
6 Annex
6.1 EDE lists
6.1.1 1-door solution
Mandatory Optional
Key name / Object name
lock_state 1 3 1 N Y 3 close_state 1 3 2 N Y 4 Device_IO420 1 8 1 N N
Alarm_message 1 15 50 N N module_type 1 19 1 1 11 N Y 1
alarm_type 1 19 2 1 15 N Y 2 50 door_state 1 19 3 1 4 N Y 5 door_command 1 19 4 1 1 3 Y Y 6
6.1.2 2 door-solution
Mandatory Optional
GEZE IO 420
device
obj. inst.
object type
object
inst.
present-va-
lue-default
min-pre-
sent-value
max-pre-
sent-value
command-
able
supports
COV
state-text-
reference
notif.
class
Key name / Object name
door1_lock_state 1 3 1 N Y 3 door1_close_state 1 3 2 N Y 4 door2_lock_state 1 3 3 N N 3
door2_close_state 1 3 4 N N 4 Device_IO420 1 8 1 N Y
Alarm_message 1 15 50 N Y module_type 1 19 1 1 11 N Y 1 alarm_type 1 19 2 1 15 N Y 2 50 door1_state 1 19 3 1 4 N Y 5 door1_command 1 19 4 1 1 3 Y Y 6 door2_state 1 19 5 1 4 N Y 5 door2_command 1 19 6 1 1 3 Y Y 6
6.1.3 4 door-solution
Mandatory Optional
Key name / Object name
door1_close_state door2_close_state 1 3 2 N Y 4 door3_close_state 1 3 3 N N 4 door4_close_state 1 3 4 N N 4 Device_IO420 1 8 1 N Y Alarm_message 1 15 50 N Y module_type 1 19 1 11 N Y 1 alarm_type 1 19 2 1 15 N Y 2 50 door1_state 1 19 3 1 4 N Y 5 door1_command 1 19 4 1 1 3 Y Y 6 door2_state 1 19 5 1 4 N Y 5 door2_command 1 19 6 1 1 3 Y Y 6 door3_state 1 19 7 1 4 N Y 5 door3_command 1 19 8 1 1 3 Y Y 6 door4_state 1 19 9 1 4 N Y 5 door4_command 1 19 10 1 1 3 Y Y 6
device
obj. inst.
object type
object
inst.
present-va-
lue-default
min-pre-
sent-value
max-pre-
sent-value
command-
able
supports
COV
device
obj. inst.
object type
object
inst.
present-va-
lue-default
min-pre-
sent-value
max-pre-
sent-value
command-
able
supports
COV
1 3 1 N Y 4
state-text-
reference
notif.
class
state-text-
reference
notif.
class
22
GEZE IO 420
6.1.4 Module type automatic
Mandatory Optional
Key name / Object name
device
lock_state close_state 1 3 2 Device_IO420 1 8 1 Alarm_message 1 15 50 module_type 1 19 1 alarm_type 1 19 2 DCU_state 1 19 3 DCU_command 1 19 4 1 1 4 Y Y 61
1 3 1
6.1.5 Module type IQ lock EL + Aut
Mandatory Optional
Key name / Object name
obj. inst.
object type
object
inst.
present-va-
lue-default
min-present-
value
max-present-
value
command-
able
supports COV
state-text-
reference
notif.
class
1 11 N Y 1 1 15 N Y 2 50 1 5 N Y 51
N Y 3 N Y 4 N N N N
unlock_state_AL close_state_AL 1 3 2 unlock_state_IL 1 3 3 close_state_IL 1 3 4 Device_IO420 1 8 1 Alarm_message 1 15 50 module_type 1 19 1 alarm_type 1 19 2 ActiveLeaf_state 1 19 3 ActiveLeaf_command 1 19 4 1 1 4 Y Y 62 InactiveLeaf_state 1 19 5 InactiveLeaf_command 1 19 6 1 1 2 Y Y 82
6.1.6 Module type RWS
Mandatory Optional
Key name / Object name
lock_state close_state 1 3 2 Device_IO420 1 8 1 Alarm_message 1 15 50 module_type 1 19 1 alarm_type 1 19 2 TZ320_state 1 19 3 TZ320_command 1 19 4 1 1 4 Y Y 63
device
obj. inst.
object type
1 3 1
device
obj. inst.
object type
1 3 1
object
inst.
object
inst.
present-va-
present-va-
lue-default
min-present-
value
max-present-
value
command-
able
supports COV
N Y 32 N Y 4 N N 32 N N 4 N Y
N Y 1 11 N Y 1 1 15 N Y 2 50 1 5 N Y 52
1 5 N Y 72
lue-default
min-present-
value
max-present-
value
command-
able
supports COV
N Y 3 N Y 4 N N
N N 1 11 N Y 1 1 15 N Y 23 50 1 11 N Y 53
state-text-
reference
notif.
class
state-text-
reference
notif.
class
23
6.1.7 Module type universal
Mandatory Optional
Key name / Object name
input1_state input2_state 1 3 2 input3_state 1 3 3 input4_state 1 3 4 Device_IO420 1 8 1 Alarm_message 1 15 50 module_type 1 19 1 alarm_type 1 19 2 output1_state 1 19 3 output1_command 1 19 4 1 1 2 Y Y 54 output2_state 1 19 5 output2_command 1 19 6 1 1 2 Y Y 54 output3_state 1 19 7 output3_command 1 19 8 1 1 2 Y Y 54 output4_state 1 19 9 output4_command 1 19 10 1 1 2 Y Y 54
device
obj. inst.
object type
1 3 1
object
inst.
present-va-
GEZE IO 420
lue-default
min-present-
value
max-present-
value
command-
able
supports
COV
state-text-
reference
notif.
class N Y 34 N Y 34 N N 34 N N 34 N Y N Y
1 11 N Y 1 1 15 N Y 2 50 1 3 N Y 44
1 3 N Y 44
1 3 N Y 44
1 3 N Y 44
6.1.8 Module type watchdog
Mandatory Optional
Key name / Object name
lock_state 1 3 1 close_state 1 3 2 Device_IO420 1 8 1 Alarm_message 1 15 50 module_type 1 19 1 alarm_type 1 19 2 watchdog_state 1 19 3 watchdog_command 1 19 4 1 1 3 Y Y 66
6.1.9 Module type window
Mandatory Optional
Key name / Object name
window1_close_state 1 3 1 window2_close_state 1 3 2 Device_IO420 1 8 1 Alarm_message 1 15 50 module_type 1 19 1 alarm_type 1 19 2 window1_state 1 19 3 window1_command 1 19 4 1 1 3 Y Y 55 window2_state 1 19 5 window2_command 1 19 6 1 1 3 Y Y 55
device
obj. inst.
object type
object
inst.
present-va-
lue-default
min-present-
value
max-present-
value
command-
able
supports COV
state-text-
reference
notif.
class
value
N Y 3 N Y 4 N N N N
max-present-
value
N Y 4 N Y 4 N N N N
command-able
supports COV
state-text-
reference
notif.
class
1 11 N Y 1 1 15 N Y 2 50 1 6 N Y 56
device
obj. inst.
object type
object
inst.
present-value-
default
min-present-
1 11 N Y 1 1 15 N Y 2 50 1 4 N Y 45
1 4 N Y 45
24
GEZE IO 420
6.1.10 Module type „DCU 1,2 and 8“ and „DUC 6“
mandatory optional
object-name
object-type
object-in-
stance
present-value-
default
Input1 Input2 3 2 Input3 3 3 Input4 3 4 Device_IO420 8 1 N N notication_class_obj 15 50 module_type 19 1 alarm_type 19 2 operating_mode 19 3 mode_command 19 4 1 1 7 Y N 85 lock_state 19 5 door_command 19 6 1 1 4 Y N 87 door_state 19 7 reduced_width 19 8 1 2 Y N 89 master_key 19 9 output1_command 19 10 1 1 3 Y N 91 alarm_dcu_1 19 11 1 31 N N 92 50 alarm_dcu_2 19 12 1 31 N N 93 50 alarm_dcu_3 19 13 1 31 N N 94 50 output2_command 19 14 1 1 3 91 output3_command 19 15 1 1 3 91 output4_command 19 15 1 1 3 91
3 1
N N N N
N 1 1 1
1
1
1
min-present-
value
max-present-
value
commanda-
ble
supports COV
N 83 N 83 N 83 N 83
N
13 N N 1 15 N N 2 50 14 N N 84
5 N N 86
5 N N 88
4 N N 90
state-text-
reference
notif-class
6.1.11 Module type “DCU 128+RWS+KL”
mandatory optional
object-name
object-type
lock_state_TZ door_state_TZ 3 2 door_state_DCU_GF 3 3 door_state_DCU_SF 3 4 Device_IO420 8 1 notication_class_obj 15 50 module_type 19 1 Alarm_TZ 19 2 operating_mode_DCU 19 3 mode_command 19 4 1 1 7 Y N 95 lock_state_DCU 19 5 door_command 19 6 1 1 4 Y N 87 mode_TZ 19 7 reduced_width 19 8 1 2 Y N 89 maintennance 19 9 emergency open 19 10 1 1 2 Y N 97 dcu_alarm1 19 11 1 31 N N 92 50 dcu_alarm2 19 12 1 31 N N 93 50 dcu_alarm3 19 13 1 31 N N 94 50
3 1
object-instance
present-value-
default
min-present-
value
max-present-
value
commanda-
ble
supports COV
state-text-
reference
notif-class
N N N N N N
13 N N 1
1
15 N N 6 50
1
14 N N 84
1
5 N N 86
1
5 N N 53
1
4 N N 96
1
N 3 N 4 N 4 N 4 N N
25
6.2 State text
GEZE IO 420
Watchdog
IQ lock 72
error
IQ lock El
error
IQ Aut inacti-
ve leaf error
IQ Aut active
leaf error
BACnet
disturbed
can/power
supply
disturbed
RTC distur-
bed-TZ
Comm. TT
disturbed
Comm. KL
disturbed
fault-TZ
relay fault-TZ exit opener
can distur-
bed
open-BUS
automatic_4sec windows universal rws _kl400
re alarm group
conict
tic_stat
burglary
group
conict
time switch
group
conict
sabotage
alarm
burglary
alarm
Text 3 Text 4 Text 5 Text 6 Text 7 Text 8 Text 9 Text 10 Text 11 Text 12 Text 13 Text 14 Text 15
Text 2 or
Active-Text
alarm
time switch
active
release
sabotage-TT sabotage-KL emergency
open-TT
sabotage-TZ emergency
door alarm-
TZ
release
hazard
alarm-TZ
open-TZ
DCU error
open
active
service mode alarm active active sluice passive sluice sluice busy
release
IQ lock error
release
pre-lock lock burglar-lock short-term
active
alarm active
alarm de-
layed
alarm sup-
pressed
open
release
short-term
release
watchdog
disabled
release
short-term
release
disable
watchdog
26
Inactive-Text
Ref. no Text 1 or
1 watchdog 1_door 2_doors 4_doors iq_ lock_el iq_lock_bus automa -
2 no alarm re alarm smoke heat
3 unlocked locked
4 open closed
5 unlock lock short-term
6 unlock lock short-term
23 no alarm emergency
32 locked unlocked
34 inac tive active
44 o on time switch
45 stopped opening closing window error
51 automatic night shop closed permanently
52 night day released shor t-term
53 unlock time switch
54 o on
enabled
55 stop open close
56 watchdog
61 automatic night shop closed permanently
62 night day release shor t-term
watchdog
63 no command unlock lock short-term
66 enable
72 unlock lock into unlock into lock IQ lock error
82 unlock lock
GEZE IO 420
RTC distur-
bed-TZ
DCU Type/
GF-SF incon-
volving_door
maintenance
due GF and
maintenance
due SF
maintenance
due GF
sistent
SF
present
BACnet
disturbed
can/power
supply
automatic_4sec windows universal RWS_ KL400 DCU_1_2 DCU_6_re-
re alarm group
conict
tic_stat
burgalry
group
time switch
group
sabotage
alarm
burglary
alarm
active sluice passive sluice sluice busy power-o DCU not
disturbed
conict
conict
smoke alarm
DCU disturbed heat and
DCU not
initialized
re alarm
active
RWS turn o
time switch
active
open
unknown
unknown
open
locked
contact
authorized
closed
GF- and SF-
master key
active
turn o/
unlocked
RWS/ unlo-
cked
permanently
open/ unlo-
cked
automatic/
unlocked
maintenance
due GF and
SF
Text 3 Text 4 Text 5 Text 6 Text 7 Text 8 Text 9 Text 10 Text 11 Text 12 Text 13 Text 14 Text 15
Text 2 or
Active-Text
Text 1 or
Inactive-Text
# Refe-
rence
Number
alarm
watchdog 1_door 2_doors 4_doors iq_lock_el iq_lock_bus automa -
no alarm re alarm smoke heat
83 inac tive active
84 automatic night shop closed permanently
85 no command night shop close automatic permanently
contact
outside
inside
86 unlocked GF locked SF locked GF and SF
87 no command contact
88 not closed GF closed SF closed GF and SF
SF-master
key active
release(d)
unlocked
maintenance
due SF
winter mode
GF-master
key active
mode
key active
89 summer
90 no master
91 turn(ed) o turn(ed) on short time
maintenance
due GF
emergency
open active
tenance
required.
open inac tive
95 no command night/ locked shop close/
96 no main-
97 emergency
27
no alarm
15_DPS dis-
connected
46_Temp-
sens
(motor)
fault.- GF
14_MPS dis-
connected
45_Drive is
too hot-GF
13_SIS-GF
detective
active
12_Motor
fault-GF
no alarm 44_Stop is
11_Motor
short-GF
42_Emer-
gency lock
active
no_Alarm no_ Alarm
61_Battery
at.
29_SIO -SF
detective
control
unit-GF
28_Motor
relay-GF
27_SIO1/SIO2
active
no alarm no alarm 60_Err. in
26_Zero
position err.
alarm-SF
GEZE IO 420
no alarm no alarm
91_no
impluse
from enco-
der
unit defec-
tive.
err.-GF
41_Testing
SIO-GF
no alarm 10_Encoder
40_Perma-
nent actuati-
on KB
alarm
39_Perma-
nent actua-
tion KA
38_Permanent
actuation KI2/
PE3
37_Perma-
nent actuati-
on KI1
36_Internal
redundancy
fault/
no alarm no alarm no alarm 07_Fire alarm 08_Smoke
35_Phar-
machy/
Permanent
act.PE1
while ope -
ning
no alarm 25_Obstacle
no alarm no alarm 57_Smoke
23_Mecha-
nical fault
SF
54_DPS
comm. err.
22_Mechanical
fault GF
unlocked/230V
failure
21_Door(SF)
missing
52_CAN err. 53_Manual
20_Door(GF)
missing
51_
brake/24V-SF
failure
19_SIS-SF
defective
DCU1-T30
expansion
28
Text 3 Text 4 Text 5 Text 6 Text 7 Text 8 Text 9 Text 10 Text 11 Text 12 Text 13 Text 14 Text 15
03_230V
failure
34_TPS
comm.
err.
Text 2 or
Active-Text
failure
cking door
system err.
Text 1 or
Inactive-Text
# Refe-
rence
Number
92 01_24V failure 02_12V
93 32_Sabotage 33_Interlo-
18_Bolt
signal not
correct
no alarm 50_Fault/
17_Err.
unlocking-GF
48_Excess
temperature-
GF(180deg)
Text16 Text17 Text18 Text19 Text20 Text21 Text22 Text23 Text24 Text25 Text26 Text27 Text28 Text29 Text30 Text31
# Refe-
GF
(control) fault.-
GF
rence
Number
92 16_Err.locking-
93 47_Tempsens
no alarm no alarm no alarm no alarm no alarm no alarm no alarm no alarm no alarm no alarm 90_control
79_Motor
relay-SF
temperature-SF
94 78_ Excess
GEZE IO 420
6.3 Service menu
Level 0 Level 1 Level 2 Level 3 Value range Factory setting
Select a module
Module con­guration
Module type Watchdog
1-door solution (factory setting)
2-door solution Conf. output 3 disable
Conf. output 3 disable
Conf. output 4 disable
Conf. door 1 Conf. KZF 1 KZF 1duration
Conf. ZSU slave 1 ZSU slave size 1
Conf. ZSU inter­ruption
Conf. output 4 disable
Conf. door 1 Conf. KZF 1 KZF 1duration
Conf. ZSU slave 1
Conf. ZSU inter­ruption
Conf. door 2 Conf. KZF 2 KZF 2duration
Conf. ZSU slave 2 ZSU slave size 1
Conf. ZSU inter­ruption
KZF 1abort KZF 1re-trigger
ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5
KZF 1abort ZSU slave size 1
ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5
KZF 2abort
ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5
1-door solution 2-door solution 4-door solution IQ lock EL + AUT Automatic stat Automatic 4 sec Window Universal RWS + KL400 DCU 1,2 and 8 DCU 6 DCU 128+RWS+KL
Alarm Door1 locked Door1 closed Door1 closed & locked
Alarm Door1 locked Door1 closed Door1 closed & locked
3~90 Yes/no Yes/no
Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no No
Alarm Door1 locked Door1 closed Door1 closed & locked
Alarm Door1 locked Door1 closed Door1 closed & locked
3~90 Yes/no
Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no no
3~90 Yes/no
Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no no
1-door solution
disable
disable
10 No No
No No No No No
disable
disable
10 No
No No No No No
10 No
No No No No No
29
GEZE IO 420
4-door solution Conf. door 1 Conf. KZF 1 KZF 1duration
Conf. ZSU slave 1 ZSU slave size 1
Conf. ZSU inter­ruption
Conf. door 2 Conf. KZF 2 KZF 2duration
Conf. ZSU slave 2 ZSU slave size 1
Conf. ZSU inter­ruption
Conf. door 3 Conf. KZF 3 KZF 3duration
Conf. ZSU slave 3 ZSU slave size 1
Conf. ZSU inter­ruption
Conf. door 4 Conf. KZF 4 KZF 4duration
Conf. ZSU slave 4 ZSU slave size 1
Conf. ZSU inter­ruption
IQ lock EL + Aut Conf, inputs Input 1 AL unlocked
Conf. passive leaf IQ AUT
Conf. KZF 2 KZF1 duration
Conf. CP No CP
Automatic stat
KZF 1abort
ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5
KZF 2abort
ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5
KZF 3abort
ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5
KZF 4abort
ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5
Input 2 Release AL
Input 3 KZF AL and IL
Input 4 BMA
KZF1 abort
3~90 Yes/no
Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no No
3~90 Yes/no
Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no No
3~90 Yes/no
Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no No
3~90 Yes/no
Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no No
KZF AL and IL
AL closed BMA RWA
RWA IL closed KZF-AL (command)
No motor lock
3~90 Yes/no
One CP Two CPs DET short-circuited
10 No
No No No No No
10 No
No No No No No
10 No
No No No No No
10 No
No No No No No
Release AL
KZF AL and IL
BMA
IQ AUT
10 No
No CP
30
Automatic 4 sec
Window
GEZE IO 420
Universal Conf. relay 1 Conf. ZSU slave 1 ZSU slave size 1
Conf. ZSU inter­ruption
Conf. relay 2 Conf. ZSU slave 2 ZSU slave size 1
Conf. ZSU inter­ruption
Conf. relay 3 Conf. ZSU slave 3 ZSU slave size 1
Conf. ZSU inter­ruption
Conf. relay 4 Conf. ZSU slave 4 ZSU slave size 1
Conf. ZSU inter­ruption
Conf, inputs Input 1 Switch/ZSU master Switch
RWS + KL400
BusConf. Conf.BACnet MAC-Addr.
Device-ID Reboot BACnet Baud rate
Notication class
Conf.CAN auto. addr. as-
signm. 1st CAN-address:
2nd CAN-address: 3rd CAN-address:
(with 4-door sol.) 4th CAN-address:
(with 4-door sol.)
Conf.ZSU master ZSU master size 1 Enable ZSU1
ZSU1 start time ZSU1 start hour
ZSU1 end time ZSU1 end hour
ZSU1 weekday ZSU1 Sunday
ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5
ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5
ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5
ZSU slave size 2 ZSU slave size 3 ZSU slave size 4 ZSU slave size 5
Input 2 Switch/ZSU master Switch Input 3 Switch/BMA/RWA/
Input 4 Switch/BMA/RWA/
ZSU1 start minute
ZSU1 end minute
ZSU1 Monday ZSU1 Tuesday ZSU1 Wednesday ZSU1 Thursday ZSU1 Friday ZSU1 Saturday
Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no No
Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no No
Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no No
Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no No
ZSU master
ZSU master
0~100 1 0~4194303 1 enter not enabled/ 9.6
KB/ 19.2 KB/ 38.4 KB/ 57.6 KB/ 76.8 KB/ 115.2 KB
1 ~ 90 50 enter
1~63 1 1~63 0 1~63 0
1~63 0
Yes/no No 0~23
0~59
0~23 0~59
Yes/no Yes/no Yes/no Yes/no Yes/no Yes/no Yes/no
No No No No No
No No No No No
No No No No No
No No No No No
Switch
Switch
76.8 KB
0 0
0 0
No No No No No No No
31
GEZE IO 420
ZSU master size 2 Enable ZSU2
ZSU2 start time ZSU2 start hour
ZSU2 end time ZSU2 end hour
ZSU2 Weekdays ZSU2 Sunday
ZSU master size 3 Enable ZSU3
ZSU3 start time ZSU3 start hour
ZSU3 end time ZSU3 end hour
ZSU3 Weekdays ZSU3 Sunday
ZSU master size 4 Enable ZSU4
ZSU4 start time ZSU4 start hour
ZSU4 end time ZSU4 end hour
ZSU4 Weekdays ZSU4 Sunday
ZSU master size 5 Enable ZSU5
ZSU5 start time ZSU5 start hour
ZSU5 end time ZSU5 end hour
ZSU5 Weekdays ZSU5 Sunday
Device conf. Date/time display
Change date Change year
Change time Hour
Conf. summer time Conf. language
Conf. log le
System info HW ver.:
Local time
Change month Change day
Minute Second
ZSU2 start minute
ZSU2 end minute
ZSU2 Monday ZSU2 Tuesday ZSU2 Wednesday ZSU2 Thursday ZSU2 Friday ZSU2 Saturday
ZSU3 start minute
ZSU3 end minute
ZSU3 Monday ZSU3 Tuesday ZSU3 Wednesday ZSU3 Thursday ZSU3 Friday ZSU3 Saturday
ZSU4 start minute
ZSU4 end minute
ZSU4 Monday ZSU4 Tuesday ZSU4 Wednesday ZSU4 Thursday ZSU4 Friday ZSU4 Saturday
ZSU5 start minute
ZSU5 end minute
ZSU5 Monday ZSU5 Tuesday ZSU5 Wednesday ZSU5 Thursday ZSU5 Friday ZSU5 Saturday
Yes/no No 0~23
0~59
0~23 0~59
Yes/no Yes/no Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no No 0~23
0~59
0~23 0~59
Yes/no Yes/no Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no No 0~23
0~59
0~23 0~59
Yes/no Yes/no Yes/no Yes/no Yes/no Yes/no Yes/no
Yes/no No 0~23
0~59 0~23
0~59
Yes/no Yes/no Yes/no Yes/no Yes/no Yes/no Yes/no
10~99 1~12 1~31
0~23 0~59 0~59
Yes/no Yes German/English/
French Level 0 to level 2 Level 0
SW ver. : Ser.no. : Sys.err :
0 0
0 0
No No No No No No No
0 0
0 0
No No No No No No No
0 0
0 0
No No No No No No No
0 0
0 0
No No No No No No No
12 6 22
11 57 0
German
32
GEZE IO 420
Factory setting
Watchdog Conf. door 1 Conf. KZF 1 KZF1 duration 3~90 10
Alarm suppression 0~250 50
Alarm delay 0~250 100
Parameters SD card
Param. IO420 -> SD
Param. SD->IO420
BAC-Name IO420
-> SD BAC-Name SD-
>IO420
6.4 Passwords for BACnet
Password for DCC service in BACnet: GEZE Password for reinitialisation service (cold and warm start): GEZE-IO420
Reset parameter Reset BAC name Reset BAC descrip­tion Reset all
KZF1 abort Yes/ No
KZF1 retrigger Yes/ No
7 Firmware update for IO 420
All settings are lost when the rmware is updated.
Backup
X
Back up the name le “IO420_V1.BAC” to the SD card.
X
Conguration le: Back up “IO420_V1.CON” to the SD card.
The backed-up data may no longer be compatible after rmware conversion, but they can be adapted manually. Further information on this subject can be found in the respective information sheet. The object descriptions cannot be backed up and must be entered again manually.
Firmware update
Firmware updates are provided by GEZE in electronic form.
X
Copy the .hex le to the directory “../FlashData/IO420”.
X
Open “IO420_Flasher.bat” using the text editor. If the les reference is “IO420_V1.hex”, it must be changed to “IO420_V1”. CORRECT: “..\Flasher\STM32\ProgSTM32Pfs.bat 11 ..\FlashData\IO420\IO420_V1”
X
Save le.
X
Switch o the voltage supply for the IO 420.
X
Connect the adapter cable (mat.no.: 130829) to the IO 420.
33
GEZE IO 420
Fig. 5: Programming adapter cable
X
Switch on the voltage supply for the IO 420.
X
Execute “IO420_Flasher.bat”.
If the following error message appears, proceed as follows:
Fig. 6: Error “wrong COM port”
X
Adapt COM port in le “IO420_Flasher.bat”.
WRONG: ..\Flasher\STM32\ProgSTM32Pfs.bat 11 ..\FlashData\IO420\IO420_V1 CORRECT ..\Flasher\STM32\ProgSTM32Pfs.bat 3 ..\FlashData\IO420\IO420_V1
34
GEZE IO 420
Fig. 7: COM port setting in the device manager
X
Execute “IO420_Flasher.bat” again. The update progress is displayed in the window. The process takes several minutes.
Fig. 8: Software update in progress.
X
Switch o the voltage supply, unplug the cable.
X
Re-boot IO 420.
X
After the rmware update the IO 420 must be reset to factory settings.
35
Germany
GEZE GmbH Niederlassung Süd-West Tel. +49 (0) 7152 203 594 E-Mail: leonberg.de@geze.com
GEZE GmbH Niederlassung Süd-Ost Tel. +49 (0) 7152 203 6440 E-Mail: muenchen.de@geze.com
GEZE GmbH Niederlassung Ost Tel. +49 (0) 7152 203 6840 E-Mail: berlin.de@geze.com
GEZE GmbH Niederlassung Mitte/Luxemburg Tel. +49 (0) 7152 203 6888 E-Mail: frankfurt.de@geze.com
GEZE GmbH Niederlassung West Tel. +49 (0) 7152 203 6770 E-Mail: duesseldorf.de@geze.com
GEZE GmbH Niederlassung Nord Tel. +49 (0) 7152 203 6600 E-Mail: hamburg.de@geze.com
GEZE Service GmbH Tel. +49 (0) 1802 923392 E-Mail: service-info.de@geze.com
Austria
GEZE Austria E-Mail: austria.at@geze.com www.geze.at
Baltic States
GEZE GmbH Baltic States oce E-Mail: oce-latvia@geze.com www.geze.com
Benelux
GEZE Benelux B.V. E-Mail: benelux.nl@geze.com www.geze.be www.geze.nl
Bulgaria
GEZE Bulgaria - Trade E-Mail: oce-bulgaria@geze.com www.geze.bg
China
GEZE Industries (Tianjin) Co., Ltd. E-Mail: chinasales@geze.com.cn www.geze.com.cn
GEZE Industries (Tianjin) Co., Ltd. Branch Oce Shanghai E-Mail: chinasales@geze.com.cn www.geze.com.cn
GEZE Industries (Tianjin) Co., Ltd. Branch Oce Guangzhou E-Mail: chinasales@geze.com.cn www.geze.com.cn
GEZE Industries (Tianjin) Co., Ltd. Branch Oce Beijing E-Mail: chinasales@geze.com.cn www.geze.com.cn
France
GEZE France S.A.R.L. E-Mail: france.fr@geze.com www.geze.fr
Hungary
GEZE Hungary Kft. E-Mail: oce-hungary@geze.com www.geze.hu
Iberia
GEZE Iberia S.R.L. E-Mail: info@geze.es www.geze.es
India
GEZE India Private Ltd. E-Mail: oce-india@geze.com www.geze.in
Italy
GEZE Italia S.r.l E-Mail: italia.it@geze.com www.geze.it
GEZE Engineering Roma S.r.l E-Mail: roma@geze.biz www.geze.it
Poland
GEZE Polska Sp.z o.o. E-Mail: geze.pl@geze.com www.geze.pl
Romania
GEZE Romania S.R.L. E-Mail: oce-romania@geze.com www.geze.ro
Russia
OOO GEZE RUS E-Mail: oce-russia@geze.com www.geze.ru
Scandinavia – Sweden
GEZE Scandinavia AB E-Mail: sverige.se@geze.com www.geze.se
Scandinavia – Norway
GEZE Scandinavia AB avd. Norge E-Mail: norge.se@geze.com
www.geze.no
Scandinavia – Denmark
GEZE Danmark E-Mail: danmark.se@geze.com www.geze.dk
Singapore
GEZE (Asia Pacic) Pte, Ltd. E-Mail: gezesea@geze.com.sg www.geze.com
South Africa
GEZE Distributors (Pty) Ltd. E-Mail: info@gezesa.co.za www.geze.co.za
Switzerland
GEZE Schweiz AG E-Mail: schweiz.ch@geze.com www.geze.ch
Turkey
GEZE Kapı ve Pencere Sistemleri E-Mail: oce-turkey@geze.com www.geze.com
Ukraine
LLC GEZE Ukraine E-Mail: oce-ukraine@geze.com www.geze.ua
United Arab Emirates/GCC
GEZE Middle East E-Mail: gezeme@geze.com www.geze.ae
United Kingdom
GEZE UK Ltd. E-Mail: info.uk@geze.com www.geze.com
GEZE GmbH
Reinhold-Vöster-Straße 21–29 71229 Leonberg Germany
Tel.: 0049 7152 203 0 Fax.: 0049 7152 203 310
www.geze.com
Loading...