GEZE GC 335 Instruction Sheet

Instruction sheet
GB
GC 335
Active infrared safety sensor
Konformitätserklärung
Declaration of Comformity
Hersteller: GEZE GmbH Manufacturer: Reinhold-Vöster-Str. 21 - 29 Fabricant: D-71229 Leonberg
Produktbezeichnung: GEZE-Aktiv-Infrarot Sicherheitssensor Product identifier: TYP: GC 335 Désignation du produit:
Erklärung (Declaration, Déclaration):
Der GEZE-Sicherheitssensor entspricht bei bestimmungsgemäßer Verwendung den grundlegenden Anforderungen der nachfolgend genannten Richtlinien. The GEZE-active infrared safety sensor is, by the directed application, in accordance with the essential requirements of the following directives. Le détecteuer de sécurisation infrarouge actif de GEZE correspondent en cas d’utilisation appropriée aux exigences de la directives suivante.
• Maschinenrichtlinie (Machines Directive, Directive relative aux machines) 2006/42/EG Benannte Stelle (Notified Body): TÜV NORD CERT GmbH & Co. KG, Kennnummer 0044, Langemarckstraße 20, 45141 Essen EG-Baumusterprüfbescheinigung (EC Type Certificate) Nr. 44 205 13095702 Bevollmächtigt zur Zusammenstellung der technischen Unterlagen: GEZE GmbH, Anschrift s.o.
• EMV-Richtlinie (EMV Directive, Directive CEM) 2004/108/EWG
Folgende europäische Normen sind angewandt (the following European standards have been ap­plied, les normes européennes suivantes sont appliquées):
• EN 61000-6-2:2005 • EN 12978:2003+A1:2009
• EN 61000-6-3:2007/A1:2011 • EN ISO 13849-1:2008
Folgende nationale Normen sind angewandt (the following national standards have been applied. Sont appliquées les normes nationals)
• DIN 18650-1:2010 • DIN 18650-2:2010
Dokumentation und Betriebsanleitung
(Documentation and Operating Instrutions, Documentation et instructions de service): Die Konformitätserklärung und die Betriebsanleitung sind dem Produkt beigefügt. Produkt- und Konformitätsdokumentation sind bei GEZE GmbH archiviert. The declaration of conformity and operating instructions are included with the product. The product and conformity documentations have been archived at GEZE GmbH. La déclaration de conformité et les instructions de service sont jointes au produit. Les documents relatifs au produit et à son conformité sont archivés chez GEZE GmbH. Dokumentationsverantwortlicher war: Peter Igl / TBP5, Tel: +49(0)7152/203-0 The following party was responsible for the documentation: Peter Igl / TBP5, Tel: +49(0)7152/203-0 Responsable de la documentation: Peter Igl / TBP5, Tél: +49(0)7152/203-0
Bedienungsanleitung (User instructions, Mode d’emploi): Die Bedienungsanleitung in den europäischen Amtssprachen liegt vor und ist in der Betriebsanleitung
abgelegt. The user instructions are available in the European official languages have been deposited in the operating instruction. Le mode d’emploi est disponible dans les langues officielles européennes et est joint aux instructions de service.
• EN 16005:2012
Leonberg, den 02. September 2013
1 Design of the device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
EN
2 Description of Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.1 Principle of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3 Installation and initial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1 Installation Check List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 Setting the monitoring Beam - closing Edge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.3 Optical Setting of the Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Detection Field . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
5 Master / Slave Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.1 Difference between Master and Slave Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5.2 Installing Master / Slave Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
5.3 Removing the Configuration Bridge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
6 Fault analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7 Technical data / connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.1 Assignment of the Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8 Components of GC 335 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9 Disposal, Repair, Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9.1 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9.2 Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9.3 Servicing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
This manual is for V.01 device version
General information
This symbol points out German standard DIN 18650 / EN 16005 to the user.
All points described there are required to fulfill German standard DIN 18650 / EN 16005.
This symbol points out important notes to the user.
3

1 Design of the device

Figure 1.1 Internal design of the device
Figure 1.2 Design of the master module
Figure 1.3 Design of the slave module
Figure 1.4 Connection of two modules
Removable housing cover
a
Aluminum section
b
Module holder
c
Handle to set the angle of inclination
d
(chassis lever) Function display for detection
e
Screw for mechanical setting of the
f
detection range Screw to secure the angle of inclina-
g
tion Headless screw to secure the module
h
holder Terminal block for supply voltage, out-
i
put and test input Configuration bridge
j
Infrared transmitter
k
Infrared receiver
l
Flat cable
m
Module connector
n
Profile seal
o
End caps
q
Figure 1.5 Installation of the module holder and of the profile seal
4

2 Description of Function

EN
GC335 GC335GC335 GC335GC335
0 mm 100 mm 290 mm 480 mm 670 mm 860 mm
100 mm 190 mm 190 mm 190 mm 190 mm
The GC 335 is an active infrared triangulation scanner. The GC 335 has been designed for detection traveling on the door leaf.
The intended use of GC 335 is to secure automatic swinging door in keeping with German standard DIN ence the door movement through the safe door control only and not by direct inter­vention as only the entirety of safe door control and sensor constitute a protective device of Category 2 EN 954/1.
The modification of the construction/ arrangement of the installation without consul­tation with the manufacturer could lead to dangerous situations.
18650 / EN 16005. If used as intended, the sensor shall influ-

2.1 Principle of Operation

Any objects entering the protected area will be detected by the infrared beams and will cause the relay outputs to be switched off. The beam spot produced by the infrared beam on the ground is approx. 1,1 cm x 8,3 cm in size (at a mounting height of approx. 2 The angle of the two lens systems can be modified by an adjustment mechanism. A detection range (detection height of objects) of up to a maximum of 2.50 is set to maximum at the factory. The device has been fitted with an optical adjusting tool. The sensor reacts to objects in the detection range largely i ndependently of the surface color and struc­ture. Reflecting and very dark objects are detected as well. Several sensors can be operated in a master and slave combination in order to be able to adapt the area protected to the prevailing conditions. By means of a six-pole screw terminal the master module is connected to the door control. The slave modules are connected to and supplied by the master module by means of flat cables. The master module and the slave modules are located in an aluminum profile together.
m).
m can be set. The sensing range of the device

3 Installation and initial Operation

3.1 Installation Check List

3.1.1 Installation of Aluminum Section

1. Push the module holder (c) into the aluminum profile (b) and position the module holder at the points where the modules will be mounted later.
2. Drill the fastening holes in the middle between the module holders (in Fig. 3.1 grayed surface). Make sure that no chips remain in the aluminum section. Seal the borehole when fastening in such a way that no dripping water can penetrate. Mechanical information which may facilitate the positioning of screws:
Figure 3.1 Mounting the aluminum section
3. Only use screws with a flat head to fasten the aluminum section, and mount the aluminum section (b) at the intended mounting height (maximum 2.50
m).
5

3.1.2 Installation of the Module

Transmitter
leading edge
Transmitter
leading edge
1. Set the transmitters of the modules identically at all modules to be used (cf. Figure 3.3). -> For this purpose, push the transmitter adjustment always in direction of the flat conductor cable (the flat conductor cable side is opposite the closing edge).
2. Connect all required flat conductor cables to the modules prior to the installation of the modules.
3. Please make sure that the master module is always located on the hinge plate side.
4. Connect the terminal screw (i) of the master module to the transition cable of the door control.
5. Place the modules between the module holders (c). Subsequently use the screw M2.5 (h) to screw down to the module holder (cf.
6. Use nippers to cut the configuration bridge (j) out of the PCB of the last module (last slave module or individual master module) (cf.
7. Set the angle of inclination and the detection range in keeping with Chapter 3.2.
8. Place the housing orifice (a).
9. Subsequently screw down the end caps.
10. Finally, check the detection range for each beam.
The transition cable to the door control can be passed through the end cap by means of a cable bushing.
If you use the accessories "GC 335 Ergänzungskit IP54", please fix a double-faced scotch tape between the profile and the mounting surface. This avoids the intrusion
Figure 1.1).
Chapter 5).
of water through the drills of the sensor profile.

3.2 Setting the monitoring Beam - closing Edge

Set the transmitting or receiving beam upright in order to secure the closing edge as best as possible.
Position 1
Position 2
Figure 3.2 Explanation of the monitoring beam setting at the closing edge
Use two lock position to set a monitoring edge flush on the left or right side of the transmitter (cf. Figure
3.3.).
Figure 3.3 Setting the monitoring beam to the closing edge
In the factory default setting, all transmitter modules are preset to position 1 and the sensing range to maximum. Position 1 means that the transmitter is straight and the closing edge is on the left (cf.
3.2 left).
Make sure that the transmitters are all set identical in case of several slave modules (identical lock po­sition of the transmitter) ! The master module has to have the same transmitter setting as well.
6
Figure

3.3 Optical Setting of the Sensor

25˚
EN
You can swivel the detection field away from the door or towards the door by setting the angle of incli­nation. The angle of inclination can be varied continuously from 0° to + 25°. Use the handle on the chassis metal to set the angle of inclination. For the adjustment of the angle of inclination use the M3 screw (g) at the top of the module holder.
Figure 3.4 Setting the angle of inclination
Use the detection range screw (f) to adjust the detection range. By turning the detection range screw (f) with a screwdriver and the displacement of the receiver lens caused, the detection range can be set. An optical adjustment tool (LED green / red (p)) facilitates the exact adjustment of the detection range over the ground.
If the sensor is not used for protection in keeping with German standard DIN 18650 / EN
16005, a higher adjustment (no more than 80 cm) is possible.
Figure 3.5 Adjustment of the detection range
LED display: LED red: Lens has been detected. LED green: Free protected area and the sensor sees the ground.
If used as a means of protection in keeping with German standard DIN 18650 / EN
16005, the angle of inclination and the detection range have to be adjusted as
follows:
Use the optional calibration tool (test card and square) for adjustment.
Detection range adjustment of the Sensor:
1. Use the chassis lever to set the module to the first marking line on the module holder (cf. Illustration 6.3), and use the M3 screw to fasten (g).
2. Turn the detection range screw (f) counterclockwise until the overturn protection is activated (slight "clicking" noise). Now the maximum detection range has been set.
3. Now use the test card and place it on the test specimen in such a way that it lays 12,5 cm above the ground.
4. Turn the detection range screw clockwise until the LED display just switches from red to green (if necessary turn back to red and then clockwise to just into green). The detection range adjustment is thus completed.
7
Angle of Inclination of the Sensor:
Marking on test card
12
20 cm
EN
750 mm
Width of door leaf
900 mm
Width of door leaf
1400 mm
Width of door leaf
closing edge
GC335 GC335GC335
Master
Slave
Slave
GC335 GC335GC335
Slave
Slave
Slave
GC335
Master
GC335 GC335GC335
Slave
Slave
Slave
GC335
Slave
GC335
Slave
GC335
Master
750 mm
900 mm
1400 mm
100 mm
5. Lay the test card on the ground with the marking parallel to the door.
6. Rest the test specimen to the marking on the side of the door (cf. Figure
3.6).
7. The sensor points down vertically.
8. Use the chassis lever to swivel the sensor forward until it detects the test specimen raised by 20
9. Swivel the sensor further to the front until it just sees the ground again (LED switches from red to green).
10. Now use the M3 screw (g) to attach the module to the module holder. The angle of inclination has now been set. This setting is now completed.
cm (LED = red).
Checking the Detection range adjustment
11. Use the test card to check the detection range adjustment once again.
Figure 3.6Positioning the test specimen
For the operation as a safety sensor in keeping with German standard DIN 18650 / EN 16005, the detection range has to be set to approx. 12,5 cm ± 1 cm over the ground.

4 Detection Field

Depending on the requirement and the door width, a master module can be supplemented with up to seven slave modules. We recommend to adjust the straight transmitting / receiving beam of the corresponding sensor mod­ule no further than 10 cm away from the closing edge. .Figure 4.1 renders information on the installation for different door leaf widths.
Figure 4.1 Detection field
The wider the door leaf is, the more slave modules are required.
The following sensor characteristics do not conform to the safety regulations outlined in the EC declaration of conformity:
- The distance between the modules and the main locking edge is greater than 10 cm.
- Gaps are left between the modules.
- The right/left adjustment position of the modules is not aligned with the main locking edge.
- The modules are set to a sensing height greater than 20 cm above ground level.
8

5 Master / Slave Operation

5.1 Difference between Master and Slave Module

It is possible to fit up to seven additional slave modules, apart from one master module. The differences between the master module and the slave module are as follows:
Master module: with relay; 6-pole connector; one red socket Slave module: no relay; no 6-pole connector; two red sockets

5.2 Installing Master / Slave Module

Make sure that the chassis neatly locks into the module holder during the installation of the master module and the slave module.
Figure 5.1 Master / slave module The chassis plate has to lock into the module holder as follows:
Figure 5.2 Installing master / slave module
• Please make sure that the arbor of the module holder locks into the borehole of the chassis safely. The chassis clip has to be visible in the middle of the module holder (
• Connect the master module only by means of the 6-pole terminal (i) to the door control.
• Connect the master module with the 24 cm flat cables provided for the purpose.
Figure 5.2 Circle).

5.3 Removing the Configuration Bridge

Disconnect the configuration bridge (j) at the last slave module or on the last slave module's PCB or on the master module's PCB. Disconnect the bridge when the sensor is not powered. Before carrying out this step, touch the chassis lever.
Figure 5.3 Configuration bridge

6 Fault analysis

Error Cause Remedy
The sensor does not initial­ize or react.
The door opens and closes cyclically.
The door opens and closes sporadically.
Test unit is not recognized.
Table 6.1 Fault analysis
Supply voltage is not correct. Check the voltage supply.
• The sensor is disturbed by the move­ment of the door.
• The door leafs are detected by the sen­sor.
• The door movement causes vibrations.
• There are objects in the detection field which move in the air current.
• The detection range has been wrongly set.
• The angle of inclination has been wrongly set.
• Change the adjustment an­gle.
• Check the attachment of the sensor.
• Remove the objects.
• Check the detection range and the test card.
• Readjust the angle of incli­nation (cf. Chapter 3.3).
9

7 Technical data / connection diagram

General data
Detection range min. 0 ... 1,500 mm Detection range max. 0 ... 2,500 mm Light transmitter IRED Black/white difference (6 % / 90 %) < 2 % at a detection range of 2,000 mm Marking CE, TÜV Number of beams Number of sensor modules GC 335 mounted Mode of operation Background evaluation Diameter of the light spot 1,1 cm x 8,3 cm at a detection range of 2 m for each module
Displays/operating elements
Function display LED red / green (cf. chapter titled Functional displays) Operating components Detection range adjustment Electrical data Operating voltage 24 VDC ± 20 % No-load current I
Input
Test input
Output
Switching type Relay released when objects are inside the detection range. Signal output Relay, 1 changeover unit Switching voltage V ... 30 VAC / VDC Switching current 0.001mA ...0.3 A Response time 70 ms
Maximum length of the connecting cables
Connection diameter 0.3 mm ... 1.3 mm (AWG26-16) Cu single/multicore
Optical data
Light wave length 875 nm ± 15 nm Classification according to EN 62471 free group Minimum degree of reflection of the
floor Minimum degree of reflection of the
objects to be recognized Mutual interference (cross-talk) No
Resolution
Functional safety related parameters
Safety Integrity Level (SIL) SIL 1 Category Cat. 2 Performance level (PL) PL c BWS-Typ Typ 2
Ambient conditions
Ambient temperature -10° Celsius ... 50° Celsius (263 K ... 323 K) Humidity at 20° Celsius < 90 % Humidity at 60° Celsius < 50 %
Mechanical data
Housing length L min. 310 mm Mounting height max. 2,500 mm Protection type IP52 Connection Screw terminal
0
Master: <75 mA Slave: <65 mA
-3 V ... +5 VDC or open: Test off +11 V...+24 V DC ± 20 % Test on
30 m
6 %
0 %
CA Reference body DIN 18650-1 / EN 16005 applicable in all positions
10
Material
1
2
3
4
5
6
-
+
TE
Housing Aluminum / ABS Light exit PMMA
Table 7.1 Technical data

7.1 Assignment of the Connections

Explanation:
Relay:
• Relay is inactive during detection
• Relay is active in free detection field
Test input:
• Test input is inactive at:U_low = -3 V ... +5 VDC
• Test input is active at: U_high = +11 V ... +24 V DC ± 20 %

8 Components of GC 335

Part Numbers Description
128074 GC 335, MASTERMODUL 128065 GC 335, SLAVEMODUL 120190 Prüfkörper GC 335
Table 8.1 Components of GC 335

9 Disposal, Repair, Maintenance

9.1 Disposal

Dispose of the useless device in keeping with the applicable national legal regulations. For example, take the sensor to a pertinent collection point for electronic waste.

9.2 Repair

Defective device may be repaired by the manufacturer only.

9.3 Servicing

Observe the applicable national regulations for servicing.
The sensor is maintenance-free by and large.
Nonetheless, check the technical safety of the sensor system in regular intervals, watching out for dam­age of the housing in particular. If it has to be assumed that a safe operation is no longer possible, the sensor system has to be shut down and secured against unintentional operation.
Check the sensor for soiling occasionally. In order to clean the sensor, use a dry or moist soft cloth to wipe across the sensor in regular intervals. This action will ensure an optimal function.
The housing is made of plastic. For this reason avoid contact with acetone and detergents containing solvents.
Pin Assignment
1 GND (0 V) 2 UB +24 VDC ± 20 % 3 Relay - center contact 4 Relay breakcontact 5 Relay make contact 6 Test input
11
Germany
GEZE Sonderkonstruktionen GmbH Planken 1 97944 Boxberg-Schweigern Tel. +49 (0) 7930-9294-0 Fax +49 (0) 7930-9294-10 E-Mail: sk.de@geze.com
GEZE GmbH Niederlassung Süd-West Tel. +49 (0) 7152-203-594 E-Mail: leonberg.de@geze.com
GEZE GmbH Niederlassung Süd-Ost Tel. +49 (0) 89-120 07 42-50 E-Mail: garching.de@geze.com
GEZE GmbH Niederlassung Ost Tel. +49 (0) 30-47 89 90-0 E-Mail: berlin.de@geze.com
GEZE GmbH Niederlassung Mitte/Luxemburg Tel. +49 (0) 6171-63610-0 E-Mail: frankfurt.de@geze.com
GEZE GmbH Niederlassung West Tel. +49 (0) 201-83082-0 E-Mail: essen.de@geze.com
GEZE GmbH Niederlassung Nord Tel. +49 (0) 40-2 19 07 16-13 E-Mail: hamburg.de@geze.com
GEZE Service GmbH Tel. +49 (0) 18 02/92 33 92 E-Mail: service-info.de@ge­ze.com
Austria
GEZE Austria E-Mail: austria.at@geze.com www.geze.at
Baltic States
GEZE GmbH Baltic States office E-Mail: office-latvia@geze.com www.geze.com
Benelux
GEZE Benelux B.V. E-Mail: benelux.nl@geze.com www.geze.be www.geze.nl
Bulgaria
GEZE Bulgaria - Trade E-Mail: office-bulgaria@geze.com www.geze.bg
China
GEZE Industries (Tianjin) Co., Ltd. E-Mail: Sales-info@geze.com.cn www.geze.com.cn
GEZE Industries (Tianjin) Co., Ltd. Branch Office Shanghai E-Mail: chinasales@geze.com.cn www.geze.com.cn
GEZE Industries (Tianjin) Co., Ltd. Branch Office Guangzhou E-Mail: chinasales@geze.com.cn www.geze.com.cn
GEZE Industries (Tianjin) Co., Ltd. Branch Office Beijing E-Mail: chinasales@geze.com.cn www.geze.com.cn
France
GEZE France S.A.R.L. E-Mail: france.fr@geze.com www.geze.fr
Hungary
GEZE Hungary Kft. E-Mail: office-hungary@geze.com www.geze.hu
Iberia
GEZE Iberia S.R.L. E-Mail: info@geze.es www.geze.es
India
GEZE India Private Ltd. E-Mail: office-india @geze.com www.geze.in
Italy
GEZE Italia S.r.l E-Mail: italia.it@geze.com www.geze.it
GEZE Engineering Roma S.r.l E-Mail: roma@geze.biz www.geze.it
Poland
GEZE Polska Sp.z o.o. E-Mail: geze.pl@geze.com www.geze.pl
Romania
GEZE Romania S.R.L. E-Mail: office-romania@geze.com www.geze.ro
Russia
OOO GEZE RUS E-Mail: office-russia@ geze.com www.geze.ru
Scandinavia – Sweden
GEZE Scandinavia AB E-Mail: sverige.se@geze.com www.geze.se
Scandinavia – Norway
GEZE Scandinavia AB avd. Norge E-Mail: norge.se@geze.com www.geze.no
Scandinavia – Finland
Branch office of GEZE Scandinavia AB E-Mail: finland.se@geze.com www.geze.com
Scandinavia – Denmark
GEZE Danmark E-Mail: danmark.se@geze.com www.geze.dk
Singapore
GEZE (Asia Pacific) Pte, Ltd. E-Mail: gezesea@geze.com.sg www.geze.com
South Africa
GEZE Distributors (Pty) Ltd. E-Mail: info@gezesa.co.za www.geze.co.za
Switzerland
GEZE Schweiz AG E-Mail: schweiz.ch@geze.com www.geze.ch
Turkey
GEZE Kapive Pencere Sistemleri E-Mail: office-turkey@geze.com www.geze.com
Ukraine
GEZE Ukraine TOV E-Mail: office-ukraine@geze.com www.geze.ua
United Arab Emirates/GCC
GEZE Middle East E-Mail: geze@emirates.net.ae www.geze.ae
United Kingdom
GEZE UK Ltd. E-Mail: info.uk@geze.com www.geze.com
GEZE GmbH
P.O.Box 1363 Reinhold-Voster-Straße 21-29 71229 Leonberg Ge r m a n y Tel.: 0049 7152 203-0 Fax: 0049 7152 203-310
www.geze.com
Id. No. 128557 - Printed in Germany - Subject to change without notice
Loading...