1 Symbols and illustrations ...................................................................................................................................4
2.1 Installation and electrical connection of the hold-open system ................................................................................................4
2.2 Installation of the lintel-mounted smoke switch...............................................................................................................................5
2.3 Protecting a smoke switch from soiling ................................................................................................................................................5
3 Hold-open system FA GC 150 ...........................................................................................................................6
3.1 Function ............................................................................................................................................................................................................6
3.2 Hold-open system with separate smoke control unit RSZ6 ..........................................................................................................7
3.3 Integrated hold-open systems .................................................................................................................................................................8
3.4 Classication in accordance with EN 14637 .........................................................................................................................................9
3.5 Planning of re alarms and manual trigger switches .......................................................................................................................9
3.5.1 Smoke detector or thermal detector .......................................................................................................................................................................9
3.5.2 Number and installation of re alarms .................................................................................................................................................................... 9
4 Technical data .......................................................................................................................................................12
4.1 Hold-open system FA GC 150 .................................................................................................................................................................12
4.3 Power supply .................................................................................................................................................................................................12
4.5.2 Set up wireless connection” mode ..........................................................................................................................................................................18
5.1.1 Mains connection for protection rating I .....................................................................................................................................................29
5.1.2 Mains connection for protection rating II
5.1.3 Mains connection for Slimdrive EMD F/R versions* ......................................................................................................................................30
5.1.4 Mains connection for Powerturn F/R versions* ...............................................................................................................................................30
5.3 Manual trigger switch or contact of the re alarm system ......................................................................................................... 33
5.3.2 Contact to the re alarm system .............................................................................................................................................................................. 34
5.3.3 Contact of the re alarm system and manual trigger switch UTA ...................................................................................................... 34
5.5.2 Contact to the re alarm system ...............................................................................................................................................................................37
5.5.3 Contact of the re alarm system and manual trigger switch UTA .......................................................................................................38
5.7 Mutual triggering of two hold-open systems ................................................................................................................................. 38
5.8.1 Hold-open system RSZ6 ...............................................................................................................................................................................................39
5.8.2 Hold-open system TS 4000 R, TS 4000 RFS ........................................................................................................................................................47
5.8.3 Hold-open system TS 4000 R-IS ................................................................................................................................................................................47
5.8.4 Hold-open system TS 5000 R ..................................................................................................................................................................................... 48
5.8.5 Hold-open system TS 5000 R-ISM /G/S/0 ........................................................................................................................................................... 48
5.8.6 Hold-open system TS 5000 R-ISM-EFS / TS 5000 R-ISM/0 with Free swing door closer ........................................................49
5.8.7 Hold-open system TS 5000 RFS .................................................................................................................................................................................49
5.8.8 Hold-open system TS 5000 RFS-KB .........................................................................................................................................................................49
5.8.9 Hold-open system Slimdrive EMD F/R ..................................................................................................................................................................50
5.8.10 Hold-open system Slimdrive EMD F/R-IS* ...........................................................................................................................................................51
5.8.11 Hold-open system Powerturn F/R* .........................................................................................................................................................................52
5.8.12 Hold-open system Powerturn F/R-IS* ....................................................................................................................................................................53
5.8.13 Hold-open system Powerturn F/R-IS/TS* ...........................................................................................................................................................54
6.1 Check the self-closing characteristic of the door ........................................................................................................................... 55
6.1.1 1-leaf door ...............................................................................................................................................................................................................................55
6.1.2 2-leaf door ...............................................................................................................................................................................................................................55
6.2 Testing the smoke detectors ................................................................................................................................................................. 55
9.2 Annual testing and maintenance .........................................................................................................................................................57
EN 14637
General construction technique permit:
Z-6.500-2308
Z-6.500-2309
Certication oce: BWU33
*The automatic swing door drives
TSA 160 NT F, TSA 160 NT F EN7, TSA 160 NT F-IS,
TSA 160 NT F-IS-TS,
Slimdrive EMD-F, Slimdrive EMD-F-IS,
Slimdrive EMD F/R, Slimdrive EMD F/R-IS,
Powerturn F/R, Powerturn F/R-IS,
Powerturn F/R-IS/TS
are hold-open mechanisms/systems which
are components of the general construction tech-
nique permit l Z-6.500-2308 or Z-6.500-2309, but
their testing according to EN 14637 has not yet
been completed.
3
Symbols and illustrations
1 Symbols and illustrations
Warning notices
Warning notices are used in these instructions to warn you of property damage and personal injury.
X
Always read and observe these warning notices.
X
Observe all the measures that are marked with the warning symbol and warning word.
Warning
symbol
Warning word Meaning
DANGER
Danger to persons.
Non-compliance will result in death or serious injuries.
GEZE hold-open system FA GC 150
–
More symbols and illustrations
Important information and technical notes are highlighted to explain correct operation.
SymbolMeaning
X
Abbreviations
CAUTION
means “important note”
means "additional information"
Symbol for an action: Here you have to do something.
X
If there are several actions to be taken, keep to the given order.
AL Alarm
AS Ceiling-mounted detector (additional sensor)
E Electrical hold-open device
EMV Electromagnetic compatibility
FA Hold-open system
FS Free-swing function
GC GEZE
GND Reference potential (ground)
HOD Hold-open device
IS Integrated door closing sequence
ISM
Integrated door closing sequence (mechanical)
KB Transom installation hinge side
LED Light-emitting diode
LK Luster terminal
MRB
Information to prevent property damage, to understand or optimise the operation
sequences.
NO NO contact (normal open)
R Electrical hold-open device with lintel-
mounted detector and power supply (hold-
open system)
RSZ Smoke control unit
TS = Door closer
UTA Circuit breaker
Colours
BK black
BN brown
BU blue
GN green
RD red
YE yellow
WH white
2 Notes
à In compliance with the manufacturer’s product liability as dened in the German „Product Liability Act“, the
information contained in this brochure is to be noted and followed. Failure to comply releases the manufacturer from his statutory liability.
à To ensure personal safety, it is important to follow these safety instructions. à Heed the installation instructions for the hold-open system and its assembly groups.à The country-specic regulations are to be observed if used on re and smoke protection doors.à Keep these documents.
2.1 Installation and electrical connection of the hold-open system
à The hold-open system must be installed by trained specialists. Refer also to the installation instructions for the
respective hold-open system.
à The connection of the hold-open system to the mains voltage must be carried out by a qualied electrician.à Hold-open systems may not trigger an re alarm signal for the building.à Only the devices specied in the construction technique permit may be installed and connected.à Before connecting hold-open system components to the power supply, the supply voltage must be switched o.
4
GEZE hold-open system FA GC 150
2.2 Installation of the lintel-mounted smoke switch
à Do not install the lintel-mounted smoke switch until
construction work for commissioning of the holdopen system has been completed.
à The lintel-mounted smoke switch is a sensitive
electronic product and must be protected against
electrostatic discharge:
à Only take the lintel-mounted smoke switch out of
the protective packaging directly before installation.
à Do not touch any electronic components.
à Interrupt the voltage supply before installing the
lintel-mounted smoke switch.
à The lintel-mounted smoke switch is clipped into the
housing of the hold-open system.
Notes
Fig. 2.2.1
2.3 Protecting a smoke switch from soiling
à Do not remove the dust protection lm or dust protec-
tion cap from the smoke switch until commissioning is
about to take place.
à After the smoke switch has been installed and the
dust protection removed, make sure no dust gets
into the measuring chamber. This leads to increased
soiling and can signicantly shorten the service life of
the smoke switch.
à The measuring chamber of a smoke switch must not
be opened.
2.4 Disposal
à The hold-open system is made up of materials that should be sent for recycling. The individual components
have to be sorted in accordance with their material type. The parts can be disposed of at the local recycling
depot or by a scrap recycling company.
à In accordance with the Battery Directive, we are obliged to inform you of the following in connection with
the sale of batteries or rechargeable batteries respectively in connection with the delivery of devices containing batteries or rechargeable batteries: Rechargeable batteries and batteries must not be disposed of with
household waste. Disposal with household waste is expressly forbidden according to the Battery Directive. As
the end-consumer, you are legally obliged to return used batteries. Please dispose of batteries at a municipal
collection point or in store. Batteries obtained from us can be returned to us by mail. The address is: GEZE
GmbH, Incoming Goods, Reinhold-Vöster-Str. 21-29, 71229 Leonberg/Germany. Batteries which contain harmful substances are identied by a symbol of a crossed-out rubbish bin.
Fig. 2.2.2
Fig. 2.3.1
5
Hold-open system FA GC 150
Ceilingmounted
detector
Wireless ceiling-mounted detector
Manual trigger switch
Manual trigger switch
Wireless ceiling-mounted detector
Wireless input moduleGC175
Wireless input moduleGC175
Manual
trigger
switch
Wireless ceilingmounted
detector
Wireless input
module
GC175
Manual
trigger
switch
Wireless input
module
GC175
3 Hold-open system FA GC 150
3.1 Function
Directly after a re or smoke protection door has been opened, it is closed again by the tted door closer. This
self-closing characteristic is cancelled in a controlled way by the hold-open system, so that a re or smoke protection door can remain open permanently. In the event of a power failure, response by a
push button, an open door is closed by the door closer.
GEZE hold-open system FA GC 150
re alarm or triggering by a
2
3
Integrated hold-open system
2
1
3
6
Smoke control unit RSZ6
Energy supply
11
Ceilingmounted
detector
2
2
Lintel-mounted detector
with trigger
mechanism
Manual
trigger
switch
Manual
trigger
switch
Hold-open
1
Wireless module
GC 171
mechanism
1-leaf / 2-leaf
1
Wireless ceiling-
3
3
mounted
detector
2
2
3
3
3
3
Fig. 3.1.1
GEZE hold-open system FA GC 150
3.2 Hold-open system with separate smoke control unit RSZ6
The hold-open system RSZ6 comprises:
à Energy supply (1)
à Power supply RSZ6
à Lintel-mounted smoke switch with trigger mechanism (1)
à GC 151, lintel-mounted smoke switch
à Wireless module (1)
for the wireless connection of ceiling-mounted detector and/or manual trigger switches
à GC 171, wireless module
à Ceiling-mounted detector (2)
à GC 152, smoke detector with relay base à GC 153, thermal detector with relay baseà ORS 142, smoke detector with base and load resistor module AM 142à GC 172, wireless smoke detectorà GC 173, wireless thermal detector
à Manual trigger switch (3)
à UTA, circuit breaker à GC 175, wireless input module
à Hold-open mechanism (1)
overhead door closer
à TS 4000 E
link arm, electrohydraulic hold-open device
à TS 4000 E
link arm with free-swing function, electrohydraulic hold-open device
à TS 4000 E-IS
link arm, 2-leaf with integrated door closing sequence, electromagnetic hold-open device for both leaves
à E guide rail
electromagnetic hold-open device
à E-ISM guide rail
2-leaf with integrated door closing sequence, electromagnetic hold-open device for both leaves
à E-ISM/G guide rail
2-leaf with integrated door closing sequence, electromagnetic hold-open device for the active leaf
à E-ISM/S guide rail
2-leaf with integrated door closing sequence, electromagnetic hold-open device for the passive leaf
à ISM-EFS guide rail
2-leaf with integrated door closing sequence, electromagnetic hold-open device for the active leaf with free-swing function
à TS 5000 EFS
guide rail with free-swing function, electrohydraulic hold-open device
Integrated door closers
à E guide rail Boxer
electromagnetic hold-open device
à E-ISM guide rail Boxer
2-leaf with integrated door closing sequence, electromagnetic hold-open device for both leaves
à ISM-EFS guide rail Boxer
2-leaf with integrated door closing sequence, electromagnetic hold-open device for the active leaf with free-swing function
à Boxer EFS
guide rail with free-swing function, electrohydraulic hold-open device
Floor springs
à TS 550 NV-E
electrohydraulic hold-open device
à TS 550 E
electromagnetic hold-open device
à TS 550 E-IS
2-leaf with integrated closing sequence control, electromagnetic hold-open device
Hold-open magnet
à GT 50 Rà GT 60 Rà GT 63 Rà GT 70 R
Hold-open system FA GC 150
7
Hold-open system FA GC 150
Automatic door drives
à TSA 160 NT F*
hydraulic swing door drive
à TSA 160 NT F-IS*
hydraulic swing door drive, 2-leaf with integrated mechanical door closing sequence
à Slimdrive EMD-F*
electromechanical swing door drive
à Slimdrive EMF-F-IS*
electromechanical swing door drive, 2-leaf with integrated mechanical door closing sequence
à Powerturn F*
electromechanical swing door drive
à Powerturn F-IS*
electromechanical swing door drive, 2-leaf with integrated mechanical door closing sequence
à Powerturn F-IS/TS*
electromechanical swing door drive on the active leaf, door closer on the passive leaf with integrated mechanical door closing sequence
3.3 Integrated hold-open systems
In addition to the hold-open system with separate smoke control unit RSZ6, the following hold-open systems
with integrated hold-open mechanism are available for overhead door closers:
à TS 4000 R
link arm, electrohydraulic hold-open device
à TS 4000 RFS
link arm with free-swing function, electrohydraulic hold-open device
à TS 4000 R-IS
link arm, 2-leaf with integrated door closing sequence, electrohydraulic hold-open device for both leaves
à TS 5000 R
guide rail, electromagnetic hold-open device or hold-open with hold-open magnet
à TS 5000 R-ISM
guide rail, 2-leaf with integrated door closing sequence, electromagnetic hold-open device for both leaves
à TS 5000 R-ISM/G
guide rail, 2-leaf with integrated door closing sequence, electromagnetic hold-open device for the active leaf
à TS 5000 R-ISM/S
guide rail, 2-leaf with integrated door closing sequence, electromagnetic hold-open device for the passive leaf
à TS 5000 R-ISM/0
guide rail, 2-leaf with integrated door closing sequence, without electromagnetic hold-open device in the guide rail
à TS 5000 R-ISM-EFS
guide rail, 2-leaf with integrated door closing sequence, electrohydraulic hold-open device for the active leaf
with free-swing function
à TS 5000 RFS
guide rail with free-swing function, electrohydraulic hold-open device
à TS 5000 RFS KB
guide rail with free-swing function, transom installation hinge side, electrohydraulic hold-open device
à Slimdrive EMD F/R*
electromechanical swing door drive
à Slimdrive EMD F/R-IS*
electromechanical swing door drive, 2-leaf with integrated mechanical door closing sequence
à Powerturn F/R*
electromechanical swing door drive
à Powerturn F-IS*
electromechanical swing door drive, 2-leaf with integrated mechanical door closing sequence
à Powerturn F/R-IS/TS*
electromechanical swing door drive on the active leaf, door closer on the passive leaf with integrated mechanical door closing sequence
GEZE hold-open system FA GC 150
8
GEZE hold-open system FA GC 150
3.4 Classication in accordance with EN 14637
Hold-open system
No. 1Class 3Application classFrequent use by the general public and other persons with
little incentive to take care
No. 2Class 8Permanent function500,000 test cycles
No. 3Class 1Door typeSwing leaf doors
Hold-open system FA GC 150
No. 4Class 1Suitability for use on re/
smoke protection doors
No. 5Class 1SafetyMeets all requirements of EN 14637
No. 6Class 0
Class 2
Class 3
Class 4Very high resistance in accordance with EN 1670
Suitable for use on re/smoke protection doors
No dened corrosion resistance
(in connection with automatic door drives)
Moderate corrosion resistance in accordance with EN 1670
(in connection with the hold-open magnet GT 60 R)
High resistance in accordance with EN 1670
(in connection with the hold-open magnets
GT 50 R, GT 63 R and GT 70 R)
(in connection with all other GEZE
hold-open mechanisms)
3.5 Planning of re alarms and manual trigger switches
3.5.1 Smoke detector or thermal detector
Smoke detectors detect smoke. They work using the light scatter principle. A light transmitter and a light receiver
are arranged in the measuring chamber in such a way that no light meets the receiver module in the normal
case. If there are suspended particles (smoke) in the measuring chamber, these scatter part of the light onto the
receiver module, which converts this into an electric signal.
Accordingly, a smoke detector not only detects smoke but all other suspended particles and responds sensitively
to soiling.
Thermal detectors measure the ambient temperature and respond if the temperature exceeds a certain maximum value or increases quickly within a certain time.
Usually, smoke and re gases spread quickly when a re breaks out. It is only later that the temperature increases.
Therefore smoke detectors must be used for hold-open systems on re protection doors on rescue routes. As far
as possible, smoke detectors should generally be used for hold-open systems. In areas where disruption such as
steam, dust or operation-related smoke development (workshops, kitchens) occurs, it may, however, be sensible
to use thermal detectors rather than smoke detectors.
3.5.2 Number and installation of re alarms
h Distance between lower edge of the lintel and ceiling or false ceiling (where a larger concentration of
smoke is to be expected rst in the event of a re).
Lintel-mounted smoke switch
Ceiling-mounted detec tor
9
Hold-open system FA GC 150
Usually there must be at least one ceiling-mounted
detector - i.e. one pair of detectors - tted in the
rooms adjacent to the smoke opening – and at least
one lintel-mounted detector on one side of the
lintel over the active leaf above the smoke opening.
If the following prerequisites are met, other installations are sucient
One lintel-mounted smoke switch
à if the distance h is smaller than 100 cm on both
sides of the door
and
GEZE hold-open system FA GC 150
if appropriate
smoke-permea-
ble false ceiling
7
à if the opening width of the swing leaf door is
smaller than 300 cm
One lintel-mounted smoke switch and
one ceiling-mounted detector on each side of
the door
à if the distance h is greater than 100 cm on at
least one side of the door
or
à if the opening width of the swing leaf door is
greater than 300 cm
7
Fig. 3.5.2.1
if appropriate
smoke-permea-
ble false ceiling
Fig. 3.5.2.2
Lintel-mounted smoke switch
à The lintel-mounted smoke switch is installed directly above the door, in the case of 2-leaf doors above the active leaf.
à The lintel-mounted smoke switch is installed in such a way that a minimum distance of 1 cm is observed
between the upper edge of the smoke switch housing and the component above it.
à The lintel-mounted smoke switch is only suitable for wall assembly, it must not be installed on the ceiling.à If the lintel-mounted smoke switch is subject to disruption such as steam, dust, condensation or operation-
related smoke development, it can make sense to cover the smoke chamber of the lintel-mounted smoke
switch and to install an additional thermal detector as lintel-mounted smoke switch above the door using a
mounting bracket instead
(not permissible on rescue routes)
Ceiling-mounted detector
à The ceiling-mounted detectors are installed on the ceiling above the door, the distance to the wall is bet-
ween 50 cm and 250 cm. The distance to any installation is at least 50 cm.
à If the distance h on one side of the door is greater than 500 cm, the corresponding ceiling-mounted detector can
be mounted on a projecting arm 50 cm in front of the wall and at least 350 cm above the lower edge of the lintel.
à In special ceiling situations (e.g. sloped ceilings, false ceilings, galleries) the re alarms must be installed
where a larger concentration of smoke is to be expected in the event of a re. If in doubt, a re protection
planner or expert should be consulted.
3.5.3 Manual trigger switch
Optional manual trigger switch:
The hold-open mechanisms
à TS 4000 E, TS 4000 E-ISà E guide rail, E-ISM guide rail, E-ISM/G guide rail, E-ISM/S guide railà E guide rail Boxer, E-ISM guide rail Boxerà TS 550 NV-E, TS 550 E, TS 550 E-IS
cannot be triggered by hand. For this reason, a manual trigger switch must be installed.
Hold-open system FA GC 150
Installation of the manual trigger switch
à Installation of the manual trigger switch in a clearly visible place in the direct vicinity of the door (not concealed
by the door leaf).
à Recommended installation height of the manual trigger switch: 140 cm ± 20 cm.
11
Technical data
4 Technical data
4.1 Hold-open system FA GC 150
GEZE hold-open system FA GC 150
Protection rating (according to DIN EN
61140)
IP rating (in accordance with DIN 60529)IP20, only for dry areas
Ambient temperature-5°C to 50°C
4.2 Guidelines
DIBt Directives:2015
DIN EN 14637:2008-01
DIN 14677:2011-03
DIN 18263-4:2015-04
DIN EN 54-4:1997-12Fire detection and re alarm systems - Part 4: Power supply equipment
DIN EN 54-5:2001-03
DIN EN 54-7:2006-09Fire detection and re alarm systems - Part 7: Smoke detectors - Point
DI N EN 5 4 -18:2005-12
DIN EN 54-25:2008-06
DIN EN 1155:2006-06
DIN EN 60950-1:2014-08;
VDE 0805-1:2014-08
DIN EN 61000-6-2:2016-05;
VDE 0839-6-2:2015-05
DIN EN 61000-6-3:2011-09;
VDE 0839-6-3:2011-09
ETSI EN 300 220-2, V3.1.1,2017-02Electromagnetic compatibility and Radio spectrum Matters (ERM);
ETSI EN 301 489-1, V1.9.2:2011-09Electromagnetic compatibility and Radio spectrum Matters (ERM);
General requirements and test regulations for the approval procedure for hold-open systems - version September 2015
Locks and building hardware - electrically controlled hold-open systems for re/smoke protection doors - requirements, test methods,
application and maintenance
Servicing of electrically controlled hold-open systems for re and
smoke protection closer
Locks and building ttings - Door closers with controlled locking structure - Part 4: Swing door drive with self-closing function
Fire detection and re alarm systems - Part 5: Heat detectors - point detectors
detectors using scattered light, transmitted light or ionisation
Fire detection and re alarm systems - Part 18: Input/output devices
Fire detection and re alarm systems - Part 25: Components which use
high-frequency connections
Locks and building hardware - electrically controlled hold-open mechanisms for swing leaf doors - requirements and test methods
Information technology equipment - Safety - Part 1: General requirements
Electromagnetic compatibility (EMC) - Part 6-2: Generic standards
- Interference immunity for industrial sectors
Electromagnetic compatibility (EMC) - Part 6-3 Generic standards
- Interference immunity for residence, business and commercial sectors
as well as small-sized business
Short Range Devices (SRD);
Radio equipment to be used in the 25 MHz to 1 000 MHz
frequency range with power levels ranging up to 500 mW;
Part 2: Harmonized EN covering essential requirements
under article 3.2 of the R&TTE Directive
Electromagnetic Compatibility (EMC)
standard for radio equipment and services;
Part 1: Common technical requirements
II
RSZ6
(if automatic swing door drives
are used as a hold-open mechanism,
they are connected up as protecting
rating I devices)
RFS
TS 5000 R-ISM /G/S/0
TS 5000 R-ISM EFS
TS 5000 R, TS 5000
4.3 Power supply
Power supply
- Cable length 230V / 24V
- Cable length 230V / 24V
- Cable length 230V / 24V
Input voltage230 V AC, +10 % / -15%, 50 Hz
Input currentMaximum of 80 mA
Output voltage24 V ± 0.5 V DC
Output currentMaximum of 260 mA
12
130 mm / 150 mm (ID 085391)
90 mm / 65 mm (ID 103354)
700 mm / 750 mm (ID 115818)
Input voltage24 V ± 0.5 V DC
Input currentMaximum of 15 mA
Installation positionWall (lintel) installation, horizontal
Output hold-open mechanismTransistor output, short-circuit proof
Additional detectors
Manual trigger switchLine monitoring (switchable) using terminating resistor (43kΩ) at the
Alarm outputPotential-free relay output, changer
Reset keyThe hold-open mechanism is switched o as long as the key is
Detector testAlarm triggering: with reset key or with test aerosol
Scatter light, adaption of the alarm threshold, no alarm saving (self-resetting as soon as there is no longer any smoke in the measuring chamber)
Free-wheeling diode for inductive load, maximum 24 V, 200 mA
in the event of an alarm switch-o of the hold-open mechanism for at least 4 s
Connection of up to 3 ceiling-mounted detectors using 3-line technology
Line monitoring (switchable) using two terminating resistors (43kΩ
each) at the end of the cable
end of the cable
maximum 24 V DC / maximum 1 A
pressed (for at least 4 s)
Reset of the smoke switch by activating the key
Technical data
Line monitoring may only be deactivated when used as a spare part in old systems without line monitoring (ORS 141).
Switch the supply voltage o before changing the jumper setting (remove terminal clamp KL1).
The new jumper setting only becomes active after the mains voltage has been switched back on again.
Supply
External hold-open
mechanism
Manual trigger switch
Ceiling-mounted
detector
Alarm output
Measuring chamber
without manual trigger switch
with manual trigger switch
without
ceiling-mounted detector
with
ceiling-mounted detector
without line monitoring
to the manual trigger switch
and ceiling-mounted detector
with line monitoring
to the manual trigger switch
and ceiling-mounted detector
Internal hold-open
mechanism
Reset key
LED for state
and fault display
Jumper set
Jumper not set
Fig. 4.4.1
13
Technical data
C
M
O
C
C
M
O
GEZE hold-open system FA GC 150
State / fault
Voltage -fre e
Normal operation
Soiling (warning)
The lintel-mounted smoke switch should be replaced.
Soiling limit reached
The lintel-mounted smoke switch must be replaced.
Lintel-mounted smoke switch fault
The lintel-mounted smoke switch must be replaced.
Short-circuit at the hold-open output
Disconnect the lintel-mounted smoke switch from the
supply voltage and eliminate the short-circuit.
Supply voltage for lintel-mounted smoke switch
too small
Broken cable manual trigger switch
Display only if line monitoring is active (jumper J3) Tab. 4.4.1
4.5 Wireless module GC 171
Wireless module GC 171 ID 163051
Colour RAL 7016 (anthracite grey)
Dimensions (W x H x D) 177 mm x 30 mm x 18 mm
Installation position Wall assembly
Input voltage 24 V DC
Input currentMaximum of 15 mA
FunctionThe wireless module GC 171 makes wireless communication possible
Number of wireless participantsThe wireless module GC 171 can communicate with a maximum of 6
Signal transfer period60 s
Antennaintegrated
yellow
red
AL_N
AL_CO
AL_N
10
11
12
0 V
0 V
between the lintel-mounted smoke switch GC 151 and various wireless
devices (wireless smoke detector GC 172, wireless thermal detector GC
173 and wireless input module GC 175).
The wireless module GC 171 forwards wireless signals to the lintelmounted smoke switch GC 151 as changes in resistance. These changes
in resistance correspond to those of the ceiling-mounted detectors GC
152 and GC 153 and the manual trigger switch.
An alarm triggered at a wireless module is indicated without delay (in less
than 10 s) at the lintel-mounted smoke switch GC 151.
Interference with a wireless device or a problem with communication
is indicated in less than 100 s on the lintel-mounted smoke switch GC 151.
wireless devices (GC 172, GC 173 or GC 175).
14
GEZE hold-open system FA GC 150
Technical data
Frequency range
Range
Number of frequency channels
Modulation technique
Radiated power
SW2
SW2
PB1
868.15 MHz to 869.85 MHz
10 m (100 m in space)
7
FSK (frequency shift keying)
5 dBm (3 mW)
LED2
LED2
LED11...LED16
SW11...SW16
KL1
AS
Fig. 4.5.1
KL1 Connection to the lintel-mounted smoke switch
24V Supply
GND Supply
MRB Manual trigger switch
AS Ceiling-mounted detector
PB1 Push button for mode selection
“Operating” mode
“Set up wireless connection” mode
LED1x Wireless device LEDs
6 LEDs, one LED belongs to exactly one wireless device.
SW1x Wireless device switch
6 sliding switches, one switch belongs to exactly one wireless device.
LED2 Status LED
Indicates the status of the GC 171.
SW2 Selection of the lintel-mounted smoke switch
SW2 is switched to ON for connection to lintel-mounted smoke switch GC 151.
Always remove jumpers J1 and J2 from the GC 151.
4.5.1 “Operating” mode
After the supply voltage has been switched on, the wireless module GC 171 is in “operating” mode.
LED displays
In “operating” mode the GC 171 monitors the set-up wireless connections and signals faults and alarms to the
lintel-mounted smoke switch. Faults and alarms are also indicated on the status LED and the wireless device LEDs
of the GC 171. The following table shows the states for various events which are signalled via the set-up wireless
connections:
à of the wireless device LEDs of the GC 171 à of the status LED of the GC 171 à of the LED of the lintel-mounted smoke switch GC 151à of the alarm output and the hold-open output of the lintel-mounted smoke switch GC 151
The wireless module GC 171 indicates an event until the cause has been eliminated. If the cause of an event is no
longer present, the wireless module GC 171 changes back to normal mode (the displays are deleted and 24 V is
applied to the hold-open output of the lintel-mounted smoke switch again.
15
Technical data
M
O
GEZE hold-open system FA GC 150
Wireless
connec-
State /
fault
tion
GC 171Connection
quality
General faultoyellow
GC 172
General faultred
GC 173
Sabotagered
Loss of connection
Low battery
charge
(warning)
Soiling
(warning)
Wireless module GC 171
(“operating” mode)
Wireless device LED 1xStatus
LEDs
ashes green Æ good
ogreen
ashes yellow Æ sucient
ashes red Æ poor
o
o
red
o
yellow
yellow
o
red/green briey
Lintel-mounted smoke switch GC 151
LEDsAlarm output
AL_NC
10
red
AL_COM
AL_N
11
O
12
aus
red
aus
AL_NC
10
green
AL_COM
AL_N
11
O
12
Hold-open
output
KL1: 3-4 /
KL3: 1-2
24 V
0 V
0 V
24 V
Soiling limit
reached
Wireless detector
alarm
GC 175General fault,
broken cable
Loss of connection
Low battery
charge
(warning)
Contact (NO contact) activated,
short-circuit
Connection quality
If the wireless device switch is in the OFF position during “operating” mode, the corresponding wireless device
LED indicates the connection quality to the corresponding wireless device:
- LED is o
- LED ashes green every 2 s
- LED ashes yellow every 2 s
- LED ashes red every 2 s
red/green longred
redredred
red
o
red
o
yellow
yellow
o
yellow
Jno wireless connection is set up
Jgood connection quality
Jsucient connection quality
Jstill connected but poor connection quality
Connection interference is possible, the quality of the wireless
connection should be optimised by changing the position of
the wireless device.
aus
AL_NC
AL_CO
AL_N
10
11
12
0 V
0 V
red
aus
green24 V
AL_NC
AL_COM
AL_NO
10
11
12
yellow0 V
Tab . 4.5.1
If the wireless device switch is in the OFF position in “operating” mode and the wireless device signals an event
(a warning, a fault or an alarm), the wireless device LED indicates this event in compliance with the table above
instead of the connection quality.
16
GEZE hold-open system FA GC 150
General fault
The wireless module GC 171 signals “general fault” if
à no wireless connection is set up,à the set-up switch is in the ON position with GC 172, GC 173 or GC 175, à a fault has occurred during smoke detection with GC 172,à the connection to the termination resistor is interrupted with GC 175, à the wireless module GC 171 is in the “set up wireless connection” mode.
Sabotage
The wireless module GC 171 signals “sabotage” if a wireless detector GC 172 or GC 173 has been removed from its
base.
Loss of connection
If the wireless module GC 171 does not receive a new message from a set-up wireless device within 100 s of the
last message, the wireless module signals “loss of connection” for the corresponding wireless connection. The wireless module GC 171 continues to monitor this wireless connection. If the wireless module sends a signal again
in time, the wireless module GC 171 returns to “normal operation”.
Low battery charge
The wireless module GC 171 signals “low battery charge” if the voltage of the main battery of the corresponding
wireless device falls to less than 2.6 V. Both batteries (main battery and slave battery) must be replaced.
Technical data
Soiling
The wireless module GC 171 signals “soiling” if the inside of the smoke chamber is heavily soiled. The corresponding wireless smoke detector GC 172 should be replaced.
Soiling limit reached
The wireless module GC 171 signals “soiling limit reached” if the inside of the smoke chamber is too heavily
soiled. The corresponding wireless smoke detector GC 172 must be replaced.
Wireless detector alarm
The wireless module GC 171 signals “wireless ceiling-mounted detector alarm” if the wireless smoke detector GC
172 or the wireless thermal detector GC 173 triggers. The signal is acknowledged automatically when the cause
of the alarm is no longer present. The wireless module GC 171 returns to “normal operation”.
Contact activated
The wireless module GC 171 signals “contact activated” if the input of the wireless input module GC 175 is shortcircuited (when the connected contact is closed or in the event of short-circuit of the connection to the contact).
The signal is acknowledged automatically when the short-circuit is no longer present.
The wireless module GC 171 returns to “normal operation”.
Event memory
The wireless module GC 171 saves the last event for every connected wireless device. A new event overwrites the
last event. In order to check whether an event has been saved for the wireless device, slide the corresponding
wireless device switch to the ON position. If an event has been saved for this wireless device, the corresponding
wireless device LED will then display this event as shown in the table above. If the wireless device LED is green,
then no event has been saved for this wireless device.
When the wireless device switch is slid back to the OFF position, any event saved is deleted.
17
Technical data
4.5.2 Set up wireless connection” mode
Set up a new wireless connection
In the “set up wireless connection” mode, new wireless connections can be set up to new wireless devices GC
172, GC 173 or GC 175. A maximum of 6 wireless connections can be set up.
X
1. All the wireless device switches of the wireless module
GC 171 are in the OFF position.
X
2. The set-up switch of the new wireless device is set to the
ON position.
GEZE hold-open system FA GC 150
SW1x
X
3. The protective lm is on the battery compartment of the
new wireless device and the main battery for the new wireless
device has not been tted
X
4. After the supply voltage has been switched on, the
wireless module GC 171 is in “operating” mode.
X
5. Press the PB1 push button on the wireless module GC
171 briey to change to the “set up wireless connection”
mode. The status LED2 of the wireless module GC 171 is
now permanently lit red.
X
6. Slide a free wireless device switch SW1x of the wireless
module GC 171 to the ON position.
If a connection has
already been set up for the wireless device switch
selected, this is overwritten by the following process.
The corresponding wireless device LED1x starts to
ash green. The wireless module GC 171 waits for
the connection query for a new wireless device. If a
wireless device does not
respond within 2 minutes,
the GC 171 cancels the connection attempt, the corresponding wireless device LED1x lights up red. To start
the connection attempt again, slide the corresponding wireless device switch SW1x to the OFF position
briey, then slide it back into the ON position. The
corresponding wireless device LED1x ashes green
again for 2 minutes.
X
7. Remove the protective lm from the battery compartment of the new wireless device and install the
main battery in the new wireless device (ensure correct
polarity).
PB1
SW1x
LED2
LED1x
18
GEZE hold-open system FA GC 150
Wireless ceiling-mounted detector GC 172 or GC 173
The LEDs of the new wireless ceiling-mounted detector
ash green twice rst, then light up yellow for one second and then ash
goes out after that, the connection can be set up.
Wireless input module GC 175:
The LEDs of the new wireless input module ash green
once rst, then light up yellow for one second and then
ash red four times. As soon as the LED goes out after
that, the connection can be set up.
X
8. Now slide the set-up switch on the new wireless
device to the OFF position. After a short time, the LED
of the new wireless device will ash green for a few seconds. The corresponding wireless device LED1x of the
wireless module GC 171 lights up green permanently.
Technical data
red four times. As soon as the LED
ON
X
9. If the LED on the new wireless device lights up red
permanently, no connection has been made. In this case,
remove the main battery from the new wireless device,
slide the set-up switch on the new wireless device back
and forward 6 times and start again with step 7.
X
10. Fit the wireless ceiling-mounted detector to the base
and close the housing of the wireless input module.
X
11. Slide the wireless device switch SW1x of the wireless module GC 171 to the OFF position again. The colour the corresponding wireless device LED1x ashes
indicates the quality of the wireless connection (see
Chapter 4.5.1). Optimise the quality of the wireless
connection if necessary by changing the position of
the wireless device.
X
12. The connection of the wireless module GC 171
to the new wireless device has been set up. It makes
sense to note the set-up connection (number of the
assigned wireless device switch) on the new wireless device (e.g. on its identication plate). To set up
further wireless connections, continue with step 6.
X
13. Press the PB1 push button on the wireless module
GC 171 briey to change to the “operating” mode.
The status LED2 of the wireless module GC 171 goes
o.
PB1
SW1x
LED1x
LED2
19
Technical data
Löschen aller Funkverbindungen
Im Modus „Funkverbindung einrichten“ können alle bereits eingerichteten Funkverbindungen gelöscht werden.
X
X
X
X
X
GEZE hold-open system FA GC 150
1. Nach dem Einschalten der Versorgungsspannung bendet sich das Funkmodul GC 171 im Modus „Betrieb“. Alle
Funkgeräteschalter SW1x benden sich in Position OFF.
2. Durch kurzes Betätigen des Tasters PB1 in den Modus
„Funkverbindung einrichten“ wechseln. Die Status-LED2 des
Funkmoduls leuchtet jetzt dauerhaft rot.
3. Alle 6 Funkgeräteschalter SW1x auf Position ON schieben.
Die Funkgeräte-LED1x leuchten nacheinander gelb, bis sich
alle Funkgeräteschalter in Position ON benden. Sie blinken
danach für 5 s rot. Innerhalb dieser 5 s kann das Löschen der
Funkverbindungen abgebrochen werden, indem ein oder
mehrere Funkgeräteschalter wieder zurück auf Position OFF
geschoben werden
4. Jetzt leuchten alle 6 Funkgeräte-LED1x dauerhaft gelb,
alle Funkverbindungen sind gelöscht
5. Alle 6 Funkgeräteschalter SW1x wieder zurück auf Position
OFF schieben.
PB1
SW1x
SW1x
SW1x
LED2
LED1x
X
6. Durch kurzes Betätigen des Tasters PB1 wieder in den
Modus „Betrieb“ wechseln. Die Status-LED2 des Funkmoduls
leuchtet jetzt dauerhaft gelb.
4.6 Ceiling-mounted smoke detector GC 152
Smoke detector with relay base GC 152 ID 139850
comprisingRelay base GC 150 B
Smoke detector GC 002 D
Smoke detector GC 002 DID 141458
Colourwhite, RAL 9016
Dimensions (with base, Dxh)110 mm x 67 mm
Functional principleScatter light, adaption of the alarm threshold, no alarm saving (self-
resetting as soon as there is no longer any smoke in the measuring
chamber)
Insect gridprevents insects getting into the measuring chamber.
Input voltage24 V DC
Input currentMaximum of 20 mA
Installation positionCeiling mounting
Terminating resistors2 x 43 kΩ, integrated, detachable
Alarm outputPotential-free relay output, NC contact
maximum 24 V DC / maximum 1 A
PB1
LED2
20
GEZE hold-open system FA GC 150
Detector testAlarm triggering
Signalling
LEDs Relay output
Volt age-free
o
Technical data
- using test magnet near the magnetic sensor (GEZE logo)
- using test aerosol
The detector test using a test magnet tests the electrical components.
The detector test which forms part of the regular testing of the hold-
open system must be carried out using a test aerosol (see 6.2.2).
24V
ASout
ASin
Normal
operation
Alarm
2
3
o
red
24V
ASout
ASin
Tab. 4.6.1
1
Fig. 4.6.1
GC 150 B
GND
24V
out
AS
ASin
1
Fig. 4.6.2
1 Breaking point (see Chapter 5.2)
2 Magnetic sensor for testing (behind the GEZE logo)
4.7 Ceiling-mounted thermal detector GC 153
Thermal detector with base GC 153ID 139881
comprisingRelay base GC 150 B
Thermal detector GC 003 D
Thermal detector GC 003 DID 141459
Colourwhite, RAL 9016
Dimensions (with base, Dxh)110 mm x 67 mm
Functional principleAlarm if the ambient temperature exceeds the alarm temperature or if
the ambient temperature increases very quickly, no alarm saving (self-
resetting as soon as the ambient temperature has dropped again)
Alarm temperature57°C
EN 54-5 classicationA1R
Input voltage24 V DC
Input currentMaximum of 20 mA
Installation positionCeiling mounting
Terminating resistors2 x 43 kΩ, integrated, detachable
The detector test using a test magnet tests the electrical components.
The detector test which forms part of the regular testing of the holdopen system must be carried out using a heat detector testing device
(see 6.3.1).
Normal operation
Alarm
o
red
24V
ASout
ASin
Tab . 4.7.1
2
3
1 Breaking point (see Chapter 5.2)
2 Magnetic sensor for testing (behind the GEZE logo)
GC 150 B
GND
24V
1
out
ASin
AS
3 LED for displaying state
1
Fig. 4.7.2
Fig. 4.7.3
4.8 Ceiling-mounted smoke detector ORS 142
Ceiling-mounted smoke detector kit ORS 142 with
- 2 x smoke detector ORS 142
- 2 x base ORS 143 A
- 1 x magnetic holder
Ceiling-mounted smoke detector ORS 142 with
- Smoke detector GC 142
- Base ORS 143 A
- 1 x magnetic holder
Colourwhite, RAL 9010
Dimensions (with base, DxH)
22
ID 141715
ID 091069
80 mm x 66 mm
GEZE hold-open system FA GC 150
Functional principle
- Smoke detection
hermal sensor
- T
Input voltage24 V DC
Input currentMaximum of 22 mA
Installation positionCeiling mounting
IP ratingIP42
Ambient temperature-20°C to 60°C
Alarm outputPotential-free relay output, NC contact maximum 24 V DC / maximum 1 A
Magnetic holder
Detector testAlarm triggering with test aerosol
Signalling
Volt age-freeaus
Normal operationgreen
Technical data
Scatter light, adaption of alarm threshold, self-resetting
70°C ±5
switches on in the last ceiling-mounted detector 2 x 43 kΩ
LEDRelay output
4
5
4
5
Soiling (warning)
The ceiling-mounted smoke detector
should be replaced.
Soiling limit reached
The ceiling-mounted smoke detector
must be replaced.
Fault
The ceiling-mounted smoke detector
must be replaced.
Dimensions (with base, DxH)110 mm x 65 mm
Functional principleScatter light, adaption of alarm threshold,
Insect gridprevents insects getting into the measuring chamber.
Installation positionCeiling mounting
Detector testAlarm actuation
Service life main battery5 years
Signal transfer period60 s
Antennaintegrated
Frequency range868.15 MHz to 869.85 MHz
Range10 m (100 m in space)
Number of frequency channels
Modulation techniqueFSK (frequency shift keying)
Radiated power5 dBm (3 mW)
ID 159656
Base GC 170 B
Wireless smoke detector GC 002 F
Main battery and slave battery
ID 183282
Type CR 123A (3 V DC)
Type CR 2032A (3 V DC)
white, RAL 9016
no alarm saving (self-resetting as soon as there is no longer any smoke
in the measuring chamber)
- using test magnet near the magnetic sensor (GEZE logo)
- using test aerosol
The detector test using a test magnet tests the electrical components.
The detector test which forms part of the regular testing of the
hold-open system must be carried out using a test aerosol (see 6.2.2).
7
1
2
1 Magnetic sensor for testing
(behind the GEZE log)
2 LED for displaying state
3 Set-up switch
4 Sabotage contact
5 Battery compartment
6 Main battery
7 Slave battery
8 Battery compartment cover
9 Base
CR2032
7
4
CR123A
6
8
5
50
3
60
Fig. 4.9.1
24
GEZE hold-open system FA GC 150
4.9.1 Signalling
The LEDs of the wireless ceiling-mounted smoke detector GC 172 indicates various states and events
State, eventLED for displaying state
Switch on
after removal of the insulation lm or after
the main battery has been inserted
Start set-up of the wireless connection
Fault during
Operation
Main battery discharged
Slave battery discharged
Main and slave batteries discharged
set-up of the wireless connectionred
Other faultsashes yellow/green alternately (0.5 s o each)
Alarmashes red (0.5 s on – 0.5 s o)
4.9.2 Battery replacement
The wireless detector signals “Low battery charge” to the wireless module GC 171 if the charge state of the batteries
is no longer sucient. Both batteries (main battery and slave battery) always have to be replaced together.
The set-up switch for the wireless detector must not be activated.
X
1. Take the wireless detector from the base.
X
2. Use a small screwdriver to remove the battery compartment cover.
X
3. Remove the main battery.
X
4. Use a small screwdriver to carefully remove the slave battery.
Ensure that the PCB does not become damaged.
X
5. Slide the new slave battery (type CR2032A) into place – the positive pole faces upwards.
X
6. Insert the new main battery (type CR123A) – make sure polarity is correct.
X
7. Fit the battery compartment cover back in lace.
X
8. Insert the wireless detector into the base.
X
9. Test the wireless detector. It can take up to a minute for the wireless detector to be
ready for operation after battery replacement.
Technical data
ashes 1 x green, then red for approx. 1 min, then green
briey, then the LED is o
ashes 2 x green, 1 x yellow, 4 x red
o
ashes yellow (0.1 s on – 5 s o)
ashes green (0.1 s on – 5 s o)
ashes yellow/green alternately (0.1 s on – 5 s o )
ID 159657
Base GC 170 B
Wireless smoke detector GC 003 F
Main battery and slave battery
ID 183282
Type CR 123A (3 V DC)
Type CR 2032A (3 V DC)
white, RAL 9016
110 mm x 65 mm
Alarm if the ambient temperature exceeds the alarm tempera-
ture or if the ambient temperature increases very quickly, no
alarm saving (self-resetting as soon as the ambient temperature
has dropped again)
25
Technical data
9
Detector testAlarm triggering
Service life main battery5 years
Signal transfer period60 s
Antennaintegrated
Frequency range868.15 MHz to 869.85 MHz
Range10 m (100 m in space)
Number of frequency channels
Modulation techniqueFSK (frequency shift keying)
Radiated power5 dBm (3 mW)
GEZE hold-open system FA GC 150
- using test magnet near the magnetic sensor
- using heat detector testing device
The detector test using a test magnet tests the electrical components.
The
detector test which forms part of the regular testing of the hold-open system must be carried out using a heat detector testing device (see 6.3.1).
7
CR2032
6
1
2
1 Magnetic sensor for testing (behind the GEZE logo)
2 LED for displaying state
3 Set-up switch
4 Sabotage contact
5 Battery compartment
6 Main battery
7 Slave battery
8 Battery compartment cover
9 Base
7
4
CR123A
8
5
50
3
60
Fig. 4.10.1
4.10.1 Signalling
The LEDs of the wireless ceiling-mounted smoke detector GC 173 indicates various states and events
State, eventLED for displaying state
Switch on
after removal of the insulation lm or after
the main battery has been inserted
Start set-up of the wireless connection
Fault during
Operation
Main battery discharged
Slave battery discharged
Main and slave batteries discharged
set-up of the wireless connectionred
Other faultsashes yellow/green alternately (0.5 s o each)
Alarmashes red (0.5 s on – 0.5 s o)
26
ashes 1 x green, then red for approx. 1 min, then
green briey, then the LED is o
ashes 2 x green, 1 x yellow, 4 x red
o
ashes yellow (0.1 s on – 5 s o)
ashes green (0.1 s on – 5 s o)
ashes yellow/green alternately (0.1 s on – 5 s o )
Tab. 4.10.1.1
GEZE hold-open system FA GC 150
4.10.2 Battery replacement
The wireless detector signals “Low battery charge” to the wireless module GC 171 if the charge state of the batteries is no longer sucient. Both batteries (main battery and slave battery) always have to be replaced together.
The set-up switch for the wireless detector must not be activated.
X
1. Take the wireless detector from the base.
X
2. Use a small screwdriver to remove the battery compartment cover.
X
3. Remove the main battery.
X
4. Use a small screwdriver to carefully remove the slave battery.
Ensure that the PCB does not become damaged.
X
5. Slide the new slave battery (type CR2032A) into place – the positive pole faces upwards.
X
6. Insert the new main battery (type CR123A) – make sure polarity is correct.
X
7. Fit the battery compartment cover back in lace.
X
8. Insert the wireless detector into the base.
X
9. Test the wireless detector. It can take up to a minute for the wireless detector to be
ready for operation after battery replacement.
4.11 Manual trigger switch UTA
TypeUTA, AS500
Circuit breakerID 116266
Surface-mounted boxID 120503
Spare resistor 43 kID 157093
Type of switchingChanger
Switching voltageMaximum 250 V
Switching currentMaximum of 10 A
Terminating resistor43 kΩ
Technical data
Close door
Fig. 4.11.1
4.12 Wireless input module GC 175
Wireless input module GC 175
comprising:
Battery set (VPE 10)
Spare resistor 2.2 k
Main battery
Slave battery
Colour
Dimensions (Ø x H)52 mm x 32 mm
Functional principleSignals the state of an external potential-free contact (NO contact)
Line length130 mm
Line monitoringTermination resistor 2.2 k at the end of the line
43kΩ
Fig. 4.11.2
ID 163068
Wireless input module GC 175
Main battery and slave batt
ID 183282
ID 163229
Type CR 123A (3 V DC)
Type CR 2032A (3 V DC)
Matt black
to the wireless module GC 171,
monitors the line to the contact for breaks
ery, resistor 2.2 k
27
Technical data
Installation positionInstallation in ush-mounted socket or cavity box
Service life main battery5 years
Signal transfer period60 s
Antennaintegrated
Frequency range868.15 MHz to 869.85 MHz
Range10 m (100 m in space)
Number of frequency channels 7
Modulation techniqueFSK (frequency shift keying)
Radiated power5 dBm (3 mW)
5
GEZE hold-open system FA GC 150
Installation in such a way that removing the wireless module and manual
trigger switch is only possible after these two assemblies have been disconnected from one another (e.g. installation of the two assemblies in two
dierent ush-mounted sockets).
6
1
CR123A
2
ON OFF
4
4.12.1 Signalling
The LED of the wireless input module GC 175 indicates various states and events.
State, eventLED for displaying state
Switch on
after removal of the insulation lm or after
the main battery has been inserted
Start set-up of the wireless connectionashes 1 x green, 1 x yellow, 4 x red
Fault during set-up of the wireless connectionred
Operationo
broken cableo
Main battery dischargedashes yellow (0.1 s on – 5 s o)
Slave battery dischargedashes green (0.1 s on – 5 s o)
Main and slave batteries dischargedashes yellow/green alternately (0.1 s on – 5 s o)
Other faultsashes yellow/green alternately (0.5 s o each)
Contact closed, short-circuitashes 1 x red
5 LED for displaying state
6 Main battery
7 Slave battery
8 Housing tab
Component at risk from electrostatic charge
Do not touch the antenna!
ashes 10 x green, then red briey, then the LED is o
28
GEZE hold-open system FA GC 150
4.12.2 Battery replacement
The wireless input module signals “low battery charge” to the wireless module GC 171 if the charge state of
the batteries is no longer sucient. Both batteries (main battery and slave battery) always have to be replaced
together.
X
1. Bend the tabs on the side of the bottom part of the housing open slightly and pull the top part of the
housing up
and o carefully (the antenna will be pulled out of the antenna socket at this point).
X
2. Remove the main battery.
X
3. Use a small screwdriver to carefully remove the slave battery.
X
4. Slide the new slave battery (type CR2032A) into place – the positive pole faces upwards.
X
5. Insert the new main battery (type CR123A) – make sure polarity is correct.
X
6. Replace the top part of the housing carefully, making sure the antenna meets the antenna socket.
X
7. Replace the top part of the housing in such a way that the two tabs engage again.
X
8. Test the wireless input module. To do this, activate the connected contact. The hold-open system must
trigger and close the door leaf. The status LEDs of the wireless module GC 171 and the lintel-mounted smoke
switch light up yellow.
5 Wiring diagram
à Note the requirements for selection and installation of the re alarms and manual trigger switches in Chapter 3.5.à In addition, heed the installation instructions for the respective hold-open system.à The connection of the hold-open system to the mains voltage must be carried out by a qualied electrician.à Before working on the electrical system interrupt the power supply and check for safe isolation from the sup-
ply. When an Uninterruptible Power Supply is used, the system will still be under voltage even when disconnected from the mains.
à Only use the specied cable types.à Marking of on-site cables in these instructions:
1
NYM-J, 3x1.5 mm
2
NYM-O, 2x1.5 mm2 or NYM-J, 3x1.5 mm
3
J-Y(ST)Y, 2x0.6 mm or J-Y(ST)Y, 2x0.8 mm, maximum length smaller than 15 m
4
J-Y(ST)Y, 2x0.6 mm or J-Y(ST)Y, 2x0.8 mm, maximum length smaller than 6 m
5
J-Y(ST)Y, 2x2x0.6 mm or J-Y(ST)Y, 2x2x0.8 mm, maximum length smaller than 15 m
6
J-Y(ST)Y, 2x2x0.6 mm or J-Y(ST)Y, 2x2x0.8 mm, maximum length smaller than 6 m
7
J-Y(ST)Y, 2x0.6 mm or J-Y(ST)Y, 2x0.8 mm, maximum length smaller than 3 m
8
J-Y(ST)Y, 2x2x0.6 mm or J-Y(ST)Y, 2x2x0.8 mm, maximum length smaller than 3 m
Non-marked connections are system cables, only these may be used.
à The cables must be suciently mechanically protected and attached.à Insulate wires that are not used.
Wiring diagram
2
2
5.1 Mains connection
à The GEZE hold-open systems are devices of protection rating I or protection rating II in accordance
with DIN EN61140.
à A 16A circuit breaker must be provided on site (suitable for the electrical installations).à The 230 V supply must be introduced into the connecting space doubly insulated (with cable sheath) at least 8 mm.à Overall current consumption at the power supply max. 260 mA.
5.1.1 Mains connection for protection rating I
Power supply for
ID103354
Cable length 230V / 24V90 mm / 65 mm
à Devices of protection rating I are connected using a three core cable NYM-J, 3x1.5 mm2 .
The protective earth conductor is connected to the PE terminal.
1
5.1.2 Mains connection for protection rating II
Power supply forSmoke control unit RSZ6TS 5000 R, TS 5000 RFS,
ID085391no. 115818
Cable length 230 V / 24 V130 mm / 150 mm700 mm / 750 mm
GEZE hold-open system FA GC 150
Power supplyGC 151
max.
Fig. 5.1.1.1
TS 5000 R-ISM /G/S/0, TS 5000 R-ISM-EFS
Devices of protection rating II
Connection can also be made using a three core cable NYM-J, 3x1.5 mm
not be connected and must be permanently insulated (e.g. additional luster terminal or shrink hose).
are connected using a two core cable NYM-O, 2x1.5 mm2 .
Power supplyGC 151
max. 260 mA
5.1.3 Mains connection for Slimdrive EMD F/R versions*
see 5.8.9 and 05/08/2010
5.1.4 Mains connection for Powerturn F/R versions*
see 5.8.11, 5.8.12 and 5.8.13
5.2 Ceiling-mounted detector
à Note the requirements on the number and installation of ceiling-mounted detectors in Chapter 3.5.à When ceiling-mounted detectors are connected, remove jumper J2 from the lintel-mounted smoke switch GC 151.
5.2.1 Ceiling-mounted detectors GC 152 and GC 153
2
. The protective earth conductor must
Fig. 5.1.2.1
30
à The ceiling-mounted smoke detector GC 152 is made up of the
smoke detector
GC 002 D and the relay base GC 150 B.
à The ceiling-mounted thermal detector GC 153 is made up of the
thermal detector GC 003 D and the relay base GC 150 B.
à Ceiling-mounted smoke detector with base GC 152, ID 139850
Ceiling-mounted thermal detector with base GC 153, ID 139881
Smoke detector GC 002 D, ID 141458
Thermal detector GC 003 D, ID 141459
à The resistors for line monitoring are already installed in the relay
base GC 150 B. The resistors can be disconnected using a breaking
point. To do this, insert a screwdriver 3 mm through the hole on
the back of the relay base into the slot of the PDB and turn it, the
connection to the resistors breaks.
Back of the relay base
Fig. 5.2.1.1
GEZE hold-open system FA GC 150
The resistors for line monitoring and alarm resistance are installed
in the relay base GC 150 B.
The resistors for line monitoring are located on
a PCB inside the relay base. These can be disconnected using a
screwdriver as described above.
The visible resistor is the alarm resistor.
This must not be disconnected.
Ceiling-mounted detectors GC 152 and GC 153 with line monitoring
The general construction technique permit requires the cable to the ceiling-mounted detectors to be monitored.
Line monitoring is active if:
à Jumper J3 of the lintel-mounted smoke switch to the measuring chamber is set (2-3 factory setting, see Chapter 4.4).
à the breaking point in the rst relay base GC 150 B is disconnected.à the breaking point in the last relay base GC 150 B is not disconnected.
Cables ASin and ASout must be laid separately or protected.
Wiring diagram
Alarm resistor
do not disconnect
Fig. 5.2.1.2
5
Disconnect the breaking point in the base of the rst ceiling-mounted detector .
5
Ceiling-mounted thermal detector GC 153 as lintel-mounted
detector with line monitoring
à If the lintel-mounted smoke switch GC 151 is subject to disruption
such as steam, dust, condensation or operation-related smoke development, it can make sense to use a thermal detector as a lintelmounted detector. See the notes in Chapter 3.5 on this subject.
à Install an additional thermal detector GC 153 as a lintel-mounted
detector above the door using the xing bracket DM GC. See the
notes in Chapter 3.5 (xing bracket, white, RAL 9016, ID 150264).
à Protect the smoke chamber of the integrated lintel-mounted smoke
switch with dust protection cap (ID 146407) from soiling.
A
Fig. 5.2.1.3
Fig. 5.2.1.4
31
Wiring diagram
Connection of a ceiling-mounted thermal detector GC 153 as a lintel-mounted detector
Connection of a ceiling-mounted thermal detector GC 153 as a lintel-mounted detector and two further
ceiling-mounted detectors
5
Ceiling-mounted detector as
lintel-mounted detector
GEZE hold-open system FA GC 150
Cover
smoke chamber
Fig. 5.2.1.5
PLEASE NOTE
When two oor springs TS 550 E are used, no more than two ceiling-mounted detectors may be connected.
555
A
Ceiling-mounted detectorCeiling-mounted detector
Ceiling-mounted detector as
lintel-mounted detector
A
Cover
smoke chamber
Fig. 5.2.1.6
32
Disconnect the breaking point in the base of the rst two ceiling-mounted detectors
The ASin and ASout cables must be laid separately or protected.
.
GEZE hold-open system FA GC 150
5.2.2 Ceiling-mounted smoke detector ORS 142
The ceiling-mounted detector ORS 142 is made up of the smoke detector ORS 142 and the base ORS 143 A.
Ceiling-mounted smoke detector kit ORS 142 with
à 2 x smoke detector ORS 142à 2 x base ORS 143 Aà 1 x Magnetic holder
Ceiling-mounted smoke detector ORS 142 with
à Smoke detector GC 142à Base ORS 143 Aà 1 x Magnetic holder
Ceiling-mounted smoke detector ORS 142 with line monitoring
The general construction technique permit requires the cable to the ceiling-mounted detectors to be monitored.
Line monitoring is active if:
à Jumper J3 of the lintel-mounted smoke switch to the measuring chamber is set (2-3 factory setting, see Chapter 4.4).
à the load resistor module AM 142 is connected in the last base.
Connection of the rst ceiling-mounted detector must not be executed as a parallel branch line (supply and return line
in the same cable)
Connection board
Wiring diagram
ID 141715
ID 091273
AS Ceiling-mounted detector (additional sensor)
GND Reference potential (ground)
5.3 Manual trigger switch or contact of the re alarm system
à Spare resistor 43 k, ID 157093
5.3.1 Manual trigger switch UTA
à Manual trigger switch UTA, AS500, ID 116266
Surface-mounted cap, single, AS500, ID 120503
à When a manual trigger switch is connected, remove jumper J1 from the lintel-mounted smoke switch.à Note the requirements on the installation of manual trigger switch in Chapter 3.5.
The general construction technique permit requires line monitoring to the manual trigger switch if the connection of a manual trigger switch is mandatory according to the standard (see Chapter 3.5.3).
Line monitoring is active if:
à Jumper J3 of the lintel-mounted smoke switch to the measuring chamber is set (2-3, see Chapter 4.4)à a 43 kΩ resistor is connected in parallel in the manual trigger switch.
Fig. 5.2.2.1
.
33
Wiring diagram
Connect the manual trigger switch as a NO contact.
Several manual trigger switches are connected in parallel. Only connect the 43 kΩ resistor in the last one.
GEZE hold-open system FA GC 150
3
Fig. 5.3.1.1
3
The cable to the rst manual trigger switch (UTA) must be laid separately or protected.
5.3.2 Contact to the re alarm system
à When a potential-free contact of the re alarm system is connected, remove jumper J1 from the lintel-mounted
smoke switch.
Line monitoring is active if:
à Jumper J3 of the lintel-mounted smoke switch to the measuring chamber is set (2-3, see Chapter 4.4)à a 43 kΩ resistor is connected in parallel at the contact of the re alarm system.
Connect the potential-free contact as a NO contact.
Potential-free contact (BMA)
3
Fig. 5.3.1.2
.
3
Fig. 5.3.2.1
5.3.3 Contact of the re alarm system and manual trigger switch UTA
The general construction technique permit requires line monitoring to the potential-free contact of the re
alarm system and to the manual trigger switch.
Line monitoring is active if:
à Jumper J3 of the lintel-mounted smoke switch to the measuring chamber is set (2-3, see Chapter 4.4)à a 43 kΩ resistor is connected in parallel at the end of the cable.
à Remove jumper J1 of the lintel-mounted smoke switch.à Connect the potential-free contact as a NO contact.
34
.
GEZE hold-open system FA GC 150
The cable to the potential-free contact (re-alarm system) must be laid separately or protected.
5.4 Wireless module GC 171
à Wireless module GC 171, ID 163051
Wireless ceiling-mounted smoke detector GC 172 - ID 159656
Wireless ceiling-mounted thermal detector GC 173 - ID 159657
Wireless input module GC 175, ID 163068
Battery set GC 17x, ID 183282
Ersatzwiderstand 2,2 k, ID 163229
à Remove jumper J1 and J2 of the lintel-mounted smoke switch GC 151 (see Chapter 4.4).à Jumper J3 of the lintel-mounted smoke switch to the measuring chamber is set (2-3 factory setting, see Chapter 4.4).à The area dened in Figure 5.4.1.1 must be kept free. Observe distances and specications in section 3.5.2.
Wiring diagram
Potentialfreier Kontakt (BMA)
33
30
5
30
5
Fig. 5.4.1.1
à Cable length between lintel-mounted smoke switch and wireless module GC 171 maximum 3mà Set switch SW2 of the wireless module GC 171 to the ON position (see Chapter 4.5).à See Chapter 4.5.2 for how to set up the wireless connections.
à Ceiling-mounted detectors are connected as described in Chapter 5.2.
8
Fig. 5.4.2.1
Fig. 5.4.3.1
5.5 Wireless input module GC 175
à Wireless input module GC 175, ID 163068
Battery set GC 17x, ID 183282
Spare resistor 2.2 k, ID 163229
à See Chapter 4.5.2 for how to set up the wireless connections.à The cable at the wireless input module GC 175 may only be extended to max. 3 m.
36
GEZE hold-open system FA GC 150
5.5.1 Manual trigger switch UTA
à Manual trigger switch UTA, AS500, ID 116266
Surface-mounted cap, single, AS500, ID 120503
à Note the requirements on the installation of manual trigger switch in Chapter 3.5.à Installation in ush-mounted socket or cavity boxà Installation in such a way that removing the wireless module and manual trigger switch is only
possible after these two assemblies have been disconnected
(e.g. installation of the two assemblies in two dierent ush-mounted sockets)
Wiring diagram
2,2 kΩ
7
Several manual trigger switches are connected in parallel. Only connect the 2.2 kΩ resistor in the last one.
UTA
2,2 kΩ
7
The cable to the rst manual trigger switch (UTA) must be laid separately or protected.
5.5.2 Contact to the re alarm system
Line monitoring is active if:
GC 175
Fig. 5.5.1.1
UTA
GC 175
7
Fig. 5.5.1.2
à a 2.2 kΩ resistor is connected in parallel at the contact of the re alarm system.
à Connect the potential-free contact as a NO contact.
Potential-free contact BMA
GC 175
2,2 kΩ
7
Fig. 5.5.2.1
37
Wiring diagram
GEZE hold-open system FA GC 150
5.5.3 Contact of the re alarm system and manual trigger switch UTA
The general construction technique permit requires line monitoring to the potential-free contact of the re
alarm system and to the manual trigger switch.
Line monitoring is active if:
à a 2.2 kΩ resistor is connected in parallel at the contact of the re alarm system.
à Connect the potential-free contact as a NO contact.
UTA
Potential-free contact BMA
2,2 kΩ
The cable to the potential-free contact (re-alarm system) must be laid separately or protected.
5.6 Alarm output
à Potential-free relay output, changer, maximum 24 V, 1 Aà In normal operation the contact 11-12 is open, in the event of power failure or alarm closed.à Do not supply alarm display from the hold-open system.
24 V external
Alarm
display
7
7
GC 175
Fig. 5.5.3.1
GND external
5.7 Mutual triggering of two hold-open systems
à Two hold-open systems can trigger each other mutually. For this purpose, the alarm contact of the one lintel-
mounted smoke switch is connected with the input MRB of the other lintel-mounted smoke switch.
à If additional manual trigger switches are required, these are connected in parallel to the connection at the
respective input MRB.
à Remove jumper J1 from both lintel-mounted smoke switches.
The general construction technique permit requires the monitoring of the lines between the two lintel-mounted smoke switches.
Line monitoring is active if:
à Jumper J3 of the two lintel-mounted smoke switches to the measuring chamber is set (2-3, see Chapter 4.4).à a 43 kΩ resistor is connected in parallel at both lintel-mounted smoke switches direct at the alarm output.
38
Fig. 5.6.1
GEZE hold-open system FA GC 150
Wiring diagram
5
5.8 Hold-open mechanism
à External hold-open mechanisms are connected to KL1 of the lintel-mounted smoke switch (screw-push-terminal).
Internal hold-open mechanisms are connected to KL3 of the lintel-mounted smoke switch (system plug-type connection).
5.8.1 Hold-open system RSZ6
Door closer TS 4000 E, TS 4000 EFS
Door leaf installation
à Connector box with plug-in cable transition, ID 052105
GC 151Connector box
Transom installation
Fig. 5.7.1
Door tran-
sitionTS 4000 E, TS 4000 EFS
3
24 VDC±15%
Res. rip. <20%
I=42 mA
Fig. 5.8.1.1
3
Res. rip.
2
1
Fig. 5.8.1.2
39
Wiring diagram
Door closer TS 4000 E-IS
Door leaf installation
à Connector box with plug-in cable transition, ID 052105
GC 151AnschlusskastenTS 4000 E-IS
GEZE hold-open system FA GC 150
3
Door
transition
Switch closed
if active leaf open
Active leaf
Transom installation
I=42 mA
Res. rip. <20%
4
3
4
Active leaf
I=42 mA
Res. rip. <20%
Passive leaf
Door
transition
Switch closed
if active leaf open
24 VDC±15%
Passive leaf
24 VDC±15%
Res. rip. <20%
I=42 mA
24 VDC±15%
Fig. 5.8.1.3
E guide rail, E guide rail Boxer
3
24 VDC±15%
I=42 mA
Res. rip. <20%
Fig. 5.8.1.4
E guide rail
24 VDC±15%
Res. rip. <0%3
I= mA85
Fig. 5.8.1.5
40
GEZE hold-open system FA GC 150
E-ISM guide rail, E-ISM guide rail Boxer
(E-ISM/G no hold-open device in the passive leaf, E-ISM/S no hold-open device in the active leaf)
Wiring diagram
Connection board
for active leaf
3
E-hold-open device
passive leaf
24 VDC±15%
Res. rip. <0%3
I= mA85
ISM-EFS guide rail, ISM-EFS guide rail Boxer
à No hold-open mechanism for the passive leafà Connector box with plug-in cable transition, ID 052105
GC 151Connector box
(only with ISM-EFS guide rail)
E-hold-open device
active leaf
Door trans-
mission
24 VDC±15%
Res. rip. < 0%3
I= mA85
Fig. 5.8.1.6
TS 5000 EFS /
Boxer EFS
3
Door closer TS 5000 EFS
Door leaf installation
à Connector box with cable transition, ID 162723
GC 151Connector box
3
Door
transition
24 VDC±15%
Res. rip. <20%
I=42 mA/80 mA
TS 5000 EFS
3
2
24 VDC±15%
Res. rip. <20%
1
I=42 mA
Fig. 5.8.1.7
Fig. 5.8.1.8
41
Wiring diagram
Transom installation
Integrated door closer Boxer EFS
Floor spring TS 550 NV-E
GEZE hold-open system FA GC 150
3
24 VDC±15%
Res. rip.
<20%
I=42 mA
Fig. 5.8.1.9
BoxerEFS
3
24 VDC±15%
Restw. <20%
I=80 mA
Fig. 5.8.1.10
Floor spring TS 550 E
3
24 VDC±15%
Res. rip.
<20%
I=42 mA
Fig. 5.8.1.11
24 VDC±1 %0
Res. rip.
<20%
I=100 mA
Fig. 5.8.1.12
42
GEZE hold-open system FA GC 150
Floor spring TS 550 E-IS
à Connection PCB, ID 001102à Terminal box on site
Wiring diagram
Connection board
3
Hold-open magnets GT 50 R, GT 63 R, GT 70 R
Active leaf
24 VDC±1 %0
Res. rip. <20%
I=100 mA
Switch closed if active
leaf open
6
Passive leaf
24 VDC±1 %0
Res. rip. <20%
I=100 mA
Ter min al b ox
Fig. 5.8.1.13
3
24 VDC±1 %5
Res. rip. <30%
I=63 mA/68 mA
Fig. 5.8.1.14
43
Wiring diagram
Hydraulic swing door drive TSA 160 NT F*, TSA 160 NT F EN7*
Accessories TSA 160 NT F, ID 019654
Follow the wiring diagram for the TSA 160 NT swing door drive.
GEZE hold-open system FA GC 150
3
F board
Reset key
Hydraulic swing door drive TSA 160 NT F-IS*
Accessories TSA 160 NT F, ID 019654
Follow the wiring diagram for the TSA 160 NT swing door drive.
3
F board
Fig. 5.8.1.15
44
Reset key
Fig. 5.8.1.16
GEZE hold-open system FA GC 150
Electromechanical swing door drive Slimdrive EMD F*
Follow wiring diagram for the Slimdrive EMD swing door drive.
Wiring diagram
3
Reset
key
Latching
action
cam
Fig. 5.8.1.17
Electromechanical swing door drive Slimdrive EMD-IS*
Follow wiring diagram for the Slimdrive EMD swing door drive.
3
3
Reset key
Latching
action
cam
Fig. 5.8.1.18
45
Wiring diagram
Electromechanical swing door drive Powerturn F*
Follow wiring diagram for the Powerturn swing door drive.
GEZE hold-open system FA GC 150
3
Powerturn F
DCU8
DCU801
DCU802DCU800
Reset
key
Latching
action
cam
Fig. 5.8.1.19
Electromechanical swing door drive Powerturn F-IS*
Follow wiring diagram for the Powerturn swing door drive.
3
3
Powerturn F GF
DCU8
DCU801
Powerturn F SF
DCU8
DCU801
46
Reset
key
DCU802DCU800
Latching
action
cam
DCU802DCU800
Fig. 5.8.1.20
GEZE hold-open system FA GC 150
Electromechanical swing door drive Powerturn F-IS/TS*
Follow wiring diagram for the Powerturn swing door drive.
Wiring diagram
3
Latching
action cam
Fig. 5.8.1.21
5.8.2 Hold-open system TS 4000 R, TS 4000 RFS
Reset
key
3
Door closer
3
Hold-open magnet
Reed switch
Reed switch closed if passive
leaf is closed
5.8.3 Hold-open system TS 4000 R-IS
Fig. 5.8.2.1
Active leaf
Switch closed if active
leaf open
Second unit
Passive leaf
Fig. 5.8.3.1
47
Wiring diagram
5.8.4 Hold-open system TS 5000 R
5.8.5 Hold-open system TS 5000 R-ISM /G/S/0
TS 5000 R-ISM/G - no hold-open device in the passive leaf
TS 5000 R-ISM/S - no hold-open device in the active leaf
TS 5000 R-ISM/0 - no hold-open device in the passive and active leaf
3
GEZE hold-open system FA GC 150
Connection board for
active leaf
R-hold-open device
active leaf
Fig. 5.8.4.1
R-hold-open device
passive leaf
Fig. 5.8.5.1
48
GEZE hold-open system FA GC 150
5.8.6 Hold-open system TS 5000 R-ISM-EFS / TS 5000 R-ISM/0 with Free swing door closer
à No hold-open mechanism for the passive leafà Connector box with plug-in cable transition, ID 052105
GC 151Connector box
Door
transition
TS 5000 EFS
3
5.8.7 Hold-open system TS 5000 RFS
à Door leaf installationà Connector box with cable transition, ID 162723
GC 151Connector box
Door
transition
TS 5000 EFS
Wiring diagram
Fig. 5.8.6.1
3
5.8.8 Hold-open system TS 5000 RFS-KB
à Transom installation
3
2
1
Fig. 5.8.7.1
Fig. 5.8.8.1
49
Wiring diagram
5.8.9 Hold-open system Slimdrive EMD F/R
Follow wiring diagram for the Slimdrive EMD swing door drive.
5
5
24 V
1
2
GND
GEZE hold-open system FA GC 150
24 V
GND
Reset -
Fig. 5.8.9.1
key
Latching
action
cam
50
GEZE hold-open system FA GC 150
5.8.10 Hold-open system Slimdrive EMD F/R-IS*
Follow wiring diagram for the Slimdrive EMD swing door drive.
5
5
24 V
1
2
GND
Wiring diagram
3
3
24 V
GND
Reset
key
Latching
action cam
Fig. 5.8.10.1
51
Wiring diagram
5.8.11 Hold-open system Powerturn F/R*
Follow wiring diagram for the Powerturn swing door drive.
5
5
1
24 V
GND
2
Powerturn F
DCU8
GEZE hold-open system FA GC 150
Reset
key
DCU801
DCU802DCU800
Latching action
cam
24 V
GND
Fig. 5.8.11.1
52
GEZE hold-open system FA GC 150
5.8.12 Hold-open system Powerturn F/R-IS*
Follow wiring diagram for the Powerturn swing door drive.
5
5
24 V
GND
1
2
Wiring diagram
3
3
Powerturn F GF
DCU8
Reset
key
DCU801
DCU802DCU800
Latching action
cam
Powerturn F SF
DCU8
DCU801
DCU802DCU800
Fig. 5.8.12.1
53
Wiring diagram
5.8.13 Hold-open system Powerturn F/R-IS/TS*
Follow wiring diagram for the Powerturn swing door drive.
24 V
1
2
GND
GND
HOD
GEZE hold-open system FA GC 150
Powerturn F GF
Latching
action cam
DCU8
5
DCU800
DCU801
Reset
key
55
PA
DCU802
56
PE2
3
Door closer
2
51
3
SF
GND
24 V
63 mA
Hold-open magnet
Reed switch
Reed switch closed if passive
leaf is closed
Fig. 5.8.13.1
54
GEZE hold-open system FA GC 150
6 Commissioning
1. Switch on the mains voltage.
The state display of the lintel-mounted smoke switch lights up green.
2. Remove the dust protection lm or dust protection cap from the housing of the housing so that the smoke
openings are clear.
3. Remove the protective covers from the ceiling-mounted detectors.
6.1 Check the self-closing characteristic of the door
6.1.1 1-leaf door
1. Open the door leaf completely. The door leaf is held in the open position by the hold-open system.
2. Activate the reset key on the lintel-mounted smoke switch. The state display lights up yellow for approx. 4 s.
The door leaf closes and snaps into the latch.
3. If necessary, adjust the manual disengaging torque in the opened position:
Open the door leaf completely. According to EN 1155, the disengaging torque should be between 40Nm
and 120Nm at an opening angle of 90°.
6.1.2 2-leaf door
1. Open both door leaves completely. The door leaves are held in the open position by the hold-open system.
2. Activate the reset key on the lintel-mounted smoke switch. The state display lights up yellow for approx. 4 s.
The door leaves close, following the closing sequence. Both door leaves close completely and the active leaf
snaps into the latch.
3. If necessary, adjust the manual disengaging torque in the opened position:
Open both door leaves completely. According to EN 1155, the disengaging torque should be between 40 Nm
and 120Nm at an opening angle of 90°.
4. Push the active leaf out of electromechanical hold-open device, the passive leaf closes automatically. The
active leaf comes to a standstill and then closes when the passive leaf is closed.
Commissioning
6.2 Testing the smoke detectors
Test aerosol, ID 059168
Systems may only be tested with an aerosol that evaporates without leaving any residue.
6.2.1 GC 151
Carry out the following steps within approx. 2 minutes:
1. Press the reset switch, the status display changes from green to red.
Wait until the status display lights up green again.
2. Open the door leaf completely. The door leaf is held in the open
position by the hold-open system.
3. Now spray the test aerosol from a distance of about 15 cm into the
free smoke opening in short bursts lasting about 1s with 1s between bursts, covering the upper smoke opening for this.
The smoke detector must trigger (change of the state display from
green to red). The door closes.
6.2.2 GC 152, ORS 142 and GC 172
1. Open the door leaf completely. The door leaf is held in the open position by the hold-open system.
2. Spray the test aerosol from a distance of 10 cm to 15 cm into the free smoke opening in short bursts lasting
about 1s with 10s between bursts.
The smoke detector must trigger (change of the state display of the lintel-mounted smoke detector from
green to red). The door closes.
Fig. 6.2.1.1
55
Conrmation of conformity for the installatio n of th e h o ld-open sy s tem
GEZE hold-open system FA GC 150
6.3 Testing the thermal detectors
6.3.1 GC 153 and GC 173
1. Open both door leaves completely. The door leaves are held in the open position by the hold-open system.
2. Test the thermal detector GC 153 using a tester for heat detectors.
The thermal detector must trigger (change of the state display of the lintel-mounted smoke detector from
green to red).
temperature of at least 60°C but must not exceed 90°C.
The door closes. The test can also be carried out using a hair dryer. The air ow must reach a
7 Conrmation of conformity for the installation of the hold-open system
The contractor who installed the hold-open system must issue a certicate of conformity for each construction
project, certifying that the hold-open system has been professionally installed with regard to all details
and in compliance with all provisions of the respective general construction technique permit
(and, if applicable, the provisions of the modication and supplementary notices) as well as the assembly instructions provided by GEZE. This conrmation must be entered in the GEZE test book for hold-open systems.
Alternatively, this conrmation may be based on the model from the general construction technique permit.
The conrmation is to be sent to the client for any necessary forwarding to the responsible building inspectorate.
8 Ocial approval test
An ocial approval test must be carried out in order to ascertain the correct function and installation according
to the regulation once the installation of the hold-open system has been completed at the set-up location.
The owner-operator must arrange this ocial approval test.
The acceptance test may only be carried out by GEZE specialists, specialists authorised by GEZE (with GEZE competence training ) or specialists from an ocial test centre named by DIBt in the approval procedure.
The ocial approval test must include at least the following points:
1. It must be checked that the installed devices and device combinations of the hold-open system correspond
to the devices and device combinations specied in the general construction technique permit.
2. It shall be veried that the marking of the installed equipment and equipment combinations conforms to
the marking specied in the general construction technique permit or standard.
3. The interaction of all devices and device combinations must be checked on the basis of the general
construction technique permit, whereby triggering must take place both by simulation of the re characteristic the re detector is based on as well as by hand.
4. It must be checked whether the door is released for automatic closing if the hold-open system is not
functional (e.g. through removal of a detector or power failure).
After the ocial approval test has taken place, the owner-operator must attach a sign (set 10 pcs. ID 79142) in the
size 105 mm x 52 mm, which is provided by GEEZE, stating the following:
à Hold-open systemà Number of the general construction technique permit
à Approved by .. .. (company logo as well as month and year of the ocial approval) and must be axed
permanently.
The owner-operator is to be given a certicate for the successful ocial approval test; this must be kept by the
owner-operator.
56
GEZE hold-open system FA GC 150
9 Maintenance
9.1 Routine testing / Monthly inspection
à The hold-open system must be kept permanently in a good operating condition by the owner-operator; in
particular the door leaves must not be blocked (e.g. by wedges, chains or other objects which prevent the
door leave closing automatically).
à In order to ensure that the hold-open system is in a good condition, a routine test must be carried out at regu-
lar intervals on site.
If twelve monthly functional tests in succession do not reveal functional faults,
the hold-open system only needs to be checked at intervals of 3 months. If a functional fault is established
during the quarterly functional tests, serviceability is to be re-established without delay and proved through at
least three successive monthly functional tests.
à This routine test may be carried out by anyone, following appropriate brieng through GEZE.
The functional test of a hold-open system must contain at least the following elements:
à Check on the manual trigger (manual trigger switch or by manual disengagement if permitted);à Check on triggering of the hold-open system by testing the re alarms (see Chapter 6);à Check on automatic resetting of the re alarms from the alarm state;à Check on whether environmental inuences impair the function of the hold-open system installed;à Check on whether the environment in the direct vicinity of the hold-open system has a negative inuence on
it (e.g. occurrence of dust or steam);
à Check on whether constructional changes and/or interaction with other trades in the direct vicinity of the hold-
open system has a negative inuence (e.g. later installation of intermediate ceilings) and whether the positio-
ning of the re alarms complies with the general construction technique permit (see Chapter 3.5);
à Check on whether the re or smoke protection closer is released for automatic closure after triggering.
Maintenance
When wireless assemblies are used in the hold-open system:
à The quality of the wireless connections must be tested (see Chapter 4.5.2 Connection quality). Construction
changes or new electronic assemblies in the direct vicinity of the hold-open system can interfere with the
wireless connections.
à The charge state of the batteries in the wireless assemblies GC 172, GC 173 and GC 175 must be tested.
An empty battery is indicated as a warning at the status LED of the wireless module GC 171 (see Chapter 4.5.1)
Scope, result and time of the functional test must be documented in the GEZE test log for hold-open systems
and made available to the owner-operator. These records must be stored by the owner-operator.
The owner-operator must be informed if obvious functional problems and/or damage to the re or smoke protection closer occur.
9.2 Annual testing and maintenance
à In addition, the owner-operator is responsible for the organisation of the testing and maintenance of all the
components of the hold-open system, so that it is guaranteed that these components work properly and
without interference. This testing and maintenance must be carried out at least once a year in accordance with
the recommendations of the manufacturer. Scope, results and date of this annual testing must be recorded in
the GEZE test log for hold-open systems which must be kept by the owner-operator.
à Regular maintenance and testing may only be carried out by a specialist or a person trained for this purpose.
Maintenance of the hold-open system must include the elements of a functional test in accordance with Chapter
8.1 and the following additional elements:
à Check of the correlation with documentation and à Cleaning of the function-related components of a hold-open system, in as far as their soiling can lead to im-
pairment; (the measuring chamber of a smoke detector must not be opened).
à Check on the release of the hold-open system in the event of a power failure.à Check on the release of the hold-open system in the event of a re alarm being removed.
When wireless assemblies are used in the hold-open system:
à Change the main battery and the slave battery in a 5-year cycle, even without “battery empty” display on the
GC 171.
Scope, result and time of the maintenance carried out must be documented and made available to the owneroperator.