GEZE E 260 N4, E 260 N2, E 260 N4/1, E 260 N4/2, E 260 N8/1 Installation And Operating Manual

...
grn rot rot blinkend
Notstrom
steuerzentrale
Em
ergency P
er C
on
trol System
E 260 N
O
K
S
törung
N
etzausfall
O
K
Fault
Pow
er outage
grün gelb gelb blinkend
green yellow yellow flashing

RWA-Emergency Power Control System

E260 N2/N4/N8/N12

Installation and Operating Manual
GB

DE Material-Nr. 104361 IT N. mat. 113961

FR N° de suite 113960

Id. No. 113959-04

Symbols and conventions

Danger and information symbols

DANGER

Indication of danger which can lead to death or injury.

Indication of danger which can lead to material damages.

Tips for optimum working.

Conventions within the text

Enumeration mark
Introduces an action to be executed Multi-stage activities are numbered:

1. First activity

2. Second activity

3. ...

2

Contents

1 Operation ............................................................................................................. 4
1.1 Safety instructions for the operator and the user .................................................... 4
1.2 Overview of the RWA-Emergency Power Control System ...................................... 5
1.2.1 The electrical components of the RWA-Emergency Power Control System ........... 6
1.2.2 Components for ventilation operation ...................................................................... 8
1.2.3 Components used in the case of alarm ................................................................... 8
1.3 Ventilation operation ................................................................................................ 9
1.4 Fire alarm .............................................................................................................. 10
1.5 Power outage and fault ......................................................................................... 13
1.6 What to do when …? ............................................................................................. 14
2 Installation and maintenance ....................................................................... 15
2.1 Safety instructions for installation and maintenance ............................................. 15
2.2 Storage .................................................................................................................. 16
2.3 Components of the RWA-Emergency Power Control System ............................... 17
2.4 Connection options and configurations ................................................................. 19
2.4.1 Alarm group ........................................................................................................... 20
2.4.2 Ventilator groups ................................................................................................... 21
2.4.3 External equipment ............................................................................................... 25
2.4.4 Complete the configuration table ........................................................................... 27
2.4.5 Summary of the jumper settings ............................................................................ 27
2.5 Installation ............................................................................................................. 28
2.5.1 Preparation ............................................................................................................ 28
2.5.2 Assembly ............................................................................................................... 28
2.5.3 Configuration ......................................................................................................... 29
2.5.4 Electrical connection ............................................................................................. 29
2.6 Function test .......................................................................................................... 32
2.7 Operating states and faults ................................................................................... 33
2.8 What to do when …? ............................................................................................. 34
2.9 Testing and maintenance ...................................................................................... 35
3 Appendix ............................................................................................................ 36
3.1 Technical data ....................................................................................................... 36
3.2 Fuses ..................................................................................................................... 37
3.3 Configuration table ................................................................................................ 38
4 Index .................................................................................................................... 39
3

1 Operation

1.1 Safety instructions for the operator and the user

Intended use The RWA system is used to ventilate and, in the event of a fire, automatically extract

smoke from rooms. Your RWA-Emergency Power Control System is a state of the art system and
complies with the valid safety regulations. GEZE shall not be responsible for damage resulting from changes made to the RWA-Emergency Power Control System arbit­rarily.
Obligations of the user As the user, you must ensure that the person operating the RWA-Emergency Power
Control System has been instructed in the operation of the system as described in Chapter 1 of this manual. Please ensure that the key for the RWA switch can only be accessed by authorised persons.
Please keep this manual and the connection diagram where it can be easily accessed.
Check the display of the RWA-Emergency Power Control System on a regular basis
- at least every 4 days. In the event of a fault, read Section 1.6, What to do when …?
In the event of a fire The emergency functions of the RWA-Emergency Power Control System can be
triggered in the event of a fire from a smoke extractor.
To reset a fire alarm, the RWA-Emergency Power Control System may only be operated by an operator who has read Chapter 1, Operation in this manual. In particular, the safety instructions in Section 1.4, Fire alarm must be complied with.
Instruction The client or the owner-operator has to be instructed in proper use of the RWA system
during commissioning or handing over. The client or the owner-operator has to confirm in writing that the instruction has been
carried out.
Maintenance As needed - but at least once a year - you must have a specialist approved by GEZE
inspect the system and perform any necessary maintenance. You will receive a written report regarding the inspection. The two batteries must be replaced after no more than 4 years.
4

1.2 Overview of the RWA-Emergency Power Control System

INFO
INFO
2
3 4
5
10
6
8
9
7
11
1
Notstromsteuerzentrale
Emergency Power Control System
E 260 N
OK
Störung
Netzausfall
OK
Fault
Power outage
grün gelb gelb blinkend
green yellow yellow flashing

Function The RWA-Emergency Power Control System controls the extraction of smoke and

heat (RWA) from staircases, factory halls, etc. Windows and smoke extraction vents are controlled for normal ventilation operation.

If a fire alarm is triggered, the windows and smoke extraction vents are automatically opened or closed, depending on the configuration of your RWA-Emergency Power Control System.

The RWA-Emergency Power Control System controls the components, supplies them with current and provides backup in mains failure conditions.

1 RWA-Emergency Power Control System 2 Drives for the windows and smoke extraction vents 3 Ventilator switch 4 Timer switch 5 Rain and wind control/sensor 6 Window Open signal (optional) 7 Fault signal (optional) 8 Alarm from external fire alarm system 9 Alarm signal (retransmission of alarm signal) (optional) 10 Smoke sensors and heat differential sensors 11 RWA switch
5
1.2.1 The electrical components of the RWA-Emergency Power Control
L1 PEN
12
3
5
3
F3 F4
43
251
3343
3
System

E 260 N2

E 260 N4

6

E 260 N8

2
1
5
3
3
F2
F8
F7
F6
F5F4
F3
F1
343
F1
F2
F3
F4 F6
F8
1
5
3
34323

E 260 N12

1 Main circuit board 2 Batteries 3 Fuses 4 Terminal compartment 5 Transformer
7
1.2.2 Components for ventilation operation
Drives The drives open and close windows and/or smoke extraction vents.
Ventilator switches The user can operate the window drives using the ventilator switches.
Timer switch If a timer switch is connected, windows can be opened or closed at preset times.
Rain/wind sensor If a rain/wind sensor is connected, all windows will be closed in the event of rain or
strong wind. The ventilator switches are then disabled.
Window Open signal The Window Open signal lamp is lit when a window is open or not completely closed.
The controller sets this signal based on the switching signals from the ventilator swit­ch.

The windows are not directly monitored.

1.2.3 Components used in the case of alarm
RWA switch In the event of a fire, you can manually trigger an alarm by pressing the RWA switch.
The RWA-Emergency Power Control System then initiates the alarm program set by the service technician.
See Section 1.4, Fire alarm for details on how to clear the alarm. The 4 signal lamps on the RWA switch signify the following:
Symbol LED Meaning
red Illuminates when the fire alarm is triggered by a
RWA switch, smoke sensor or an external fire alarm system.
yellow Illuminates when a window is open or not fully
closed. Flashes for 60 seconds when a window is opened or closed.
green Illuminates when the RWA switch and the
RWA-Emergency Power Control System are functioning properly.
yellow Illuminates in the event of a fault.
8
Smoke sensor and heat differential
sensor
Alarm signal (optional) The RWA-Emergency Power Control System transmits an external alarm signal if the
External fire alarm system If your RWA-Emergency Power Control System is connected to an external fire alarm
Fault signal (optional) The RWA-Emergency Power Control System transmits an external signal in the event
If a smoke sensor detects smoke or a heat differential sensor registers a sharp incre­ase in temperature, the fire alarm is triggered.

See Section 1.4, Fire alarm, for details on how to clear the alarm.

fire alarm is triggered. This can be used, for example, to trigger an audible alarm or the alarm can be relayed to the fire station.
system, this can also trigger the fire alarm. See Section 1.4, Fire alarm, for details on how to clear the alarm.
of a fault. This can, for example, be connected to a warning lamp.

1.3 Ventilation operation

Opening and closing windows The windows are divided into ventilator groups. For each ventilator group, there are

one or more ventilator switches which can be used to open or close all the windows in that ventilator group at the same time.
Press the Open button to open a window.Press the Close button to close a window.Press the Stop button to stop the opening or closing of a window.

The opening and closing of the windows is indicated by LEDs on the RWA switches and ventilator switches in the following manner:

Window RWA switch
yellow signal lamp Window OPEN
fully closed off on off
opens flashes (for 60 s) off flashes (for 60 s)
fully or partly open
closes flashes (for 60 s) flashes (for 60 s) off

The signal on the ventilator switch only applies for the windows in its ventilator group, while the signal on the RWA switch refers to all the attached ventilator groups.

Therefore, the yellow Window Open signal lamp on an RWA switch is not ex­tinguished until the windows in all the ventilator groups in its alarm group are closed.
on off on
Ventilator switch green signal lamp
Ventilator switch red signal lamp
9
Rain/wind sensor If a rain/wind sensor is installed, the windows will close automatically in the event of
rain or strong wind. As long as the rain/wind sensor is active, the windows cannot be opened with the ventilator switch.

In the event of a fire alarm, the windows will also open when the rain/wind sensor is active.

Power outage In the event of a power outage, ventilation operation is disabled, which saves the bat-
teries for use in the event of a fire. It is only possible to close the windows which are already open.

1.4 Fire alarm

Triggering the fire alarm To manually trigger the fire alarm:

Procedures and signals during the fire
alarm
1. Break the glass on the RWA switch.
2. Depress the pushbutton until it clicks into place.

The fire alarm is triggered automatically in the following situations:

A smoke sensor detects smoke.
A heat differential sensor detects a sharp increase in temperature.
A fire alarm system transmits an alarm signal to the RWA-Emergency Power
Control System.
If a fire alarm is triggered, the alarm program of the RWA-Emergency Power Control System executes:
Windows and smoke extraction vents open (normal configuration) or close.
The red fire alarm signal lamp on the RWA switch is illuminated.
The RWA-Emergency Power Control System transmits external signals, for
example to an audible signal or the fire station.
The ventilator switches are disabled.
The rain/wind sensor is ignored.
10
Stopping the fire alarm You can clear the alarm condition in two ways:
12 3 4
Geprüft nach VdS 2592
Reset the RWA-Emergency Power Control System. or
Reset any RWA switch.

When the alarm condition has been cleared, the audible alarm signal stops and the ventilator switches are again useable.

GEFAHR

If the system is not fully reset (the red fire alarm LED is still lit), the system will not function properly if a new alarm is triggered!

Always reset the system fully after an alarm.
Resetting the system fully The way in which the RWA-Emergency Power Control System is prepared for another
alarm is dependent on the cause of the alarm:
If the fire alarm has been triggered by an RWA switch, reset this RWA switch (see next section).
If the fire alarm was triggered by a smoke sensor or a heat differential sensor, reset the RWA-Emergency Power Control System (see next but one section).
If the fire alarm was triggered by an external fire alarm system, please ensure that the alarm signal from this fire alarm system is switched off.
Resetting an RWA switch
1. Open the RWA switch using the key.
2. Release the black pushbutton (2) using the slider (1).
3. Reset the fire alarm by pressing the green Close button "ZU" (3). The windows and smoke extraction vents Close again, the alarm is cleared and the RWA-Emergency Power Control System is reset.
4. Replace the broken glass (4).
5. Lock the RWA switch again.
11
Reset the RWA-Emergency Power
765432198765412121213
321
L1 PEN
1
Notstromsteuerzentrale
Emergency Power Control System
E 260 N
OK
Störung
Netzausfall
OK
Fault
Power outage
grün gelb gelb blinkend
green yellow yellow flashing
Control System

DANGER Risk of death through electrical shock!

Do not touch anything inside the control panel case of the RWA-Emergency
Power Control System except the white Reset button (1).
Relock the control panel case immediately after use.
1. Unscrew the lid that covers the terminal compartment of the control panel case.
2. Press the white Reset button (1). The alarm is cleared, the RWA-Emergency Power Control System and the smoke sensors are reset.
3. Relock the control panel case.
4. Close the windows and smoke extraction vents using the ventilator switches.
Checking the reset After the alarm is reset, the red fire alarm signal lamp on the RWA switches is ex-
tinguished, the audible alarm stops and the windows can again be opened and closed with the ventilator switches. The RWA-Emergency Power Control System is ready for another alarm.

If the red fire alarm signal lamp is not extinguished, there is at least one of the following alarm signals on the RWA-Emergency Power Control System which you must clear:

Alarm signal from an RWA switch
Alarm signal from a smoke sensor
Alarm signal from an external fire alarm system
12

1.5 Power outage and fault

The operating condition of the RWA-Emergency Power Control System is indicated by an LED on the front door:

LED operating condition
illuminated green normal operation, no fault
yellow flashing power outage
illuminated yellow other fault
Power outage The RWA-Emergency Power Control System has an integrated emergency power
supply, that can bridge a power outage of at least 72 hours, for example during main­tenance work or in the event of a fire. The prerequisite is that the batteries are in pro­per working order.
The emergency functions of the RWA-Emergency Power Control System are susta­ined during a power outage. However, the normal operation of the ventilation using the ventilator switch is disabled to maintain the capacity of the battery for as long as possible. It is only possible to close already open windows.

DANGER Risk of death through electrical shock!

Any work on the power supply should only be performed by a qualified
electrician.

Rectify the cause of the power failure: Check the power supply to which the RWA-Emergency Power Control System is

connected and, if necessary, replace the fuse. If the power supply is in order: Contact a GEZE-approved specialist.
Fault In the event of a fault with an LED illuminated yellow, work is required in the control
panel case. Contact a GEZE-approved specialist.
13

1.6 What to do when …?

Problem Cause Action
Yellow signal lamp is illuminated on the RWA­Emergency Power Control System.
Yellow signal lamp is flashing on the RWA­Emergency Power Control System.
Depressing the ventilator switch does not move the windows.
Fault Contact a GEZE-approved
specialist.
Mains power outage
Mains power outage or other fault
Rain/wind sensor active
Check the power supply to which the RWA-Emergency Power Control System is connected and, if necessary, replace the fuse. If the power supply is in order: Contact a GEZE-approved specialist.
Check whether the signal lamp on the RWA-Emergency Power Control System is flashing or illuminated yellow.
The windows can only be opened again once the rain or wind has subsided.
14

2 Installation and maintenance

2.1 Safety instructions for installation and maintenance

Authorised personnel Installation may only be performed by qualified electricians or GEZE-approved

specialists.
Repair and maintenance work, however, may only be performed by GEZE-
approved specialists.

Working with safety in mind Before any maintenance or installation work is carried out on the RWA-

Emergency Power Control System, disconnect the power supply.
Comply with the regulations, standards and guidelines and, in particular, the latest
version of the VDE 0833/0815 guidelines.
Consult the local approval authorities to determine the type of cable (for example
fire protection cable) and the required type of protection.
Use only original GEZE parts for repair and retrofitting work.
When replacing the batteries, use only batteries recommended by GEZE.

Disclaimer If any changes are made to the system by an unauthorised person, or if components

other than GEZE original parts or GEZE recommended batteries are used, GEZE shall not be liable for any resultant damage.
15

2.2 Storage

Storing the RWA-Emergency Power
Control System

Storing lead gel batteries The lead gel batteries will discharge automatically when stored. Therefore:

Recharging the batteries For recharging the batteries, there are two options:
Store the RWA-Emergency Power Control System in a protected area.
If the unit has already been in use:
Disconnect the RWA-Emergency Power Control System from the mains and
remove the battery fuse (see Section 2.5.4, Electrical connection).
Minimise the storage time.
Store batteries or packed RWA-Emergency Power Control System protected from
heat at temperatures of less than 30 °C.
If the system is not operated in the meantime, recharge the batteries no later than 7 months after the previous charge (for the charging date, see the label).
1. Disconnect or remove the batteries from the RWA-Emergency Power Control System and recharge them using a standard charger.
or
1. Charge the batteries in the RWA-Emergency Power Control System. Connect the RWA-Emergency Power Control System to the mains, insert the battery fuse and charge the battery for about 36 hours (see Section 2.5.4, Electrical connection).
2. Note the new charging date on the battery.
16
2.3 Components of the RWA-Emergency Power Control
3
2
1
5
4
System
The RWA-Emergency Power Control System controls the extraction of smoke and heat (RWA) from staircases, factory halls, etc. Windows and smoke extraction vents are controlled for normal ventilation operation. In the event of a fire alarm, the windows are automatically opened or closed.
The RWA-Emergency Power Control System offers several configuration and expan­sion options which are described in the following sections.
1. RWA-Emergency Power Control System
2. Alarm group
3. Ventilator group 1
4. Ventilator group 2 (maximum of 4 ventilator groups with E 260 N8/4)
5. Rain/wind sensor and signals Window Open, Fault and Alarm
17
RWA-Emergency Power Control
System
The RWA-Emergency Power Control System is the central control unit to which all the other components are connected. The RWA-Emergency Power Control System cont­rols the components and supplies them with power.

The type designation of the RWA-Emergency Power Control System specifies the maximum permissible output current for the drives and the number of ventilator groups that can be connected:

Type designation Maximum output
current to the drives
E 260 N2/1 2.0 A * 1
E 260 N4/1 to E 260 N4/2 4.0 A 1–2
E 260 N8/1 to E 260 N8/4 7.5 A 1–4
E 260 N12/1 to E 260 N12/2 12 A 1–2

* or 2 x E205/206 drives, E212-24 V

The number before the slash specifies the power group, the number following the slash gives the number of ventilator groups which can be connected.

Alarm group The RWA-Emergency Power Control System has one alarm group. The alarm group
consists of two lines:
An RWA switch line
A smoke/heat differential sensor line

If either of these lines triggers the alarm, the drives of all of the ventilator groups will be actuated in accordance with the set alarm program.

Moreover, the alarm group can be connected to an external fire alarm system. If the external fire alarm system triggers a fire alarm, it starts the same alarm program as for an alarm from an RWA switch or smoke/heat differential sensor.

Ventilator groups Depending on the version, the RWA-Emergency Power Control System supports one,
two, three or four ventilator groups. Each ventilator group has two lines:
A drive line
A ventilator switch line

All drives for a ventilator group are controlled jointly by one of the associated ventilator switches or by the optional timer switch.

Maximum number of ventilator groups
18

Ventilator groups cannot be retrofitted.

Rain/wind sensor You can connect a rain/wind sensor, which closes all the windows in the event of rain
or strong winds. The ventilator switches are disabled as long as the rain/wind sensor is active.
Signals An optional daughter card provides 3 additional contacts for signals or alarm lines:
•Alarm: On which you can, for example, connect an audible alarm or an alarm line
to the fire station.
•Fault: On which you can, for example, connect a warning lamp.
Window Open: On which you can, for example, connect a warning lamp.

2.4 Connection options and configurations

321
L1 PEN
765432198765412121213
1
Notstromsteuerzentrale
Emergency Power Control System
E 260 N
OK
Störung
Netzausfall
OK
Fault
Power outage
grün gelb gelb blinkend
green yellow yellow flashing
Before the installation, plan all the connections and the configuration of the RWA­Emergency Power Control System. The various options are explained in the following sections.

Discuss the design with the operator. Afterwards, complete the configuration table found in the Appendix. The configuration table is an important reference aid for future maintenance and repair.

Carry out the installation and commissioning work in the sequence described in Sec­tion 2.5, Installation.
Main circuit board The components of the RWA-Emergency Power Control System are connected to the
main circuit board (1).
19
2.4.1 Alarm group
321
L1 PEN
765432198765412121213

The alarm group consists of a smoke/heat differential sensor line, an RWA switch line and an input for an external fire alarm system.

E 260 N2/N4/N8/N12

The alarm from the alarm group acts on all the ventilator groups of the RWA-Emer­gency Power Control System.
RWA switch A maximum of four (E 260 N2/1) or ten (E 260 N4/1 to N12/2) RWA switches of type
FT 4/24 V DC can be connected in line to the alarm group. With the exception of the last RWA switch, remove both terminating resistors from each RWA switch.
Smoke/heat differential sensor Optical smoke sensors of type RM 1003/24V DC or heat differential sensors of type
WM 1005/24V DC can be connected to the alarm group - either a max. total of 10 sen­sors (E 260 N2/1 to N8/4) or a max. total of 20 sensors (E 260 N12).
Both types can be used in any combination since they have the same socket. The ter­minating resistor, which is delivered with the RWA Emergency Power Control System clamped in the terminal strip, has to be installed in the last socket in the line.
External fire alarm system An external fire alarm system with a floating (potential-free) make contact can be con-
nected to the alarm group.
20
Setting the direction the drives should
XB1
L1 PEN
F3
Auf Zu
run when the alarm is triggered

You can configure the direction that the drives will run in the event of an alarm: The drive direction is set with Jumper XB1 at the back of the main circuit board.

E 260 N2/N4/N8/N12

Jumper Position Function
XB1 (red) "Auf"
(open)
XB1 (red) "Zu"
(close)
If you change the running direction of the drives, you must also re-label all the RWA switches.
Replace the word "Zu" (close) with the word "Auf" (open) on every RWA switch.
2.4.2 Ventilator groups

A ventilator group consists of a ventilator switch line and a drive line to open and close the windows. As an option, a timer switch can be connected to the ventilator switch line.

Every drive in a ventilator group reacts simultaneously to the signal from any ventila­tor switch or timer switch for this ventilator group.

One ventilator group is integrated on the main circuit board. For additional ventilator groups, optional daughter cards are added.

Additional ventilator groups cannot be retrofitted; the number of additional ventilator groups must be specified in the order.

With alarm from alarm group: Drives in Auf (opening) direction With Zu/Reset (close/reset): Drives in Zu (closing) direction (Standard setting)
With alarm from alarm group: Drives in Zu (closing) direction With Zu/Reset (close/reset): Drives in Auf (opening) direction
21

E 260 N2

321
L1 PEN
765432198765412121213

E 260 N4

22

E 260 N8

E 260 N12

23
Drives The drives of a ventilator group are connected in line. Some of the drives recom-
mended by GEZE have an integrated line monitor, which transmits an error message to the RWA-Emergency Power Control System in the event of line break.

For the windows and smoke extraction vents you must use 24 V DC drives with an integrated limit (end position) switch. Recommended drives are:

GEZE actuating, spindle and chain drives
Drives which conform with the GEZE specifications
Maximum number of drives: The total number of drives on a RWA-Emergency Power Control System is limited by
the maximum output current of the RWA-Emergency Power Control System:
Type designation Maximum output current
E 260N 2/1 2.0 A or 2 drives E205/E206/E212-24 V
E 260N 4/1 to E 260N 4/2 4 A
E 260N 8/1 to E 260N 8/4 7.5 A
E 260N 12/1 to E 260N 12/2 12 A
Ventilator switches The ventilator switches for a ventilator group are connected in a line. Every ventilator
switch on the line simultaneously controls all the drives which are connected to its ventilator group.

Maximum number of ventilator switches:

3 ventilator switches with LED, types E 50/5 or E 50/7
any number of ventilator switches without LED, types E 50/1 or E 50/3
Timer switch As an option, a timer switch - such as the GEZE 2-channel timer switch - can be con-
nected to each ventilator switch line. The timer switch must be set to pulse rather than continuous signal.

Since the timer switch and ventilator switch are considered as equal control elements, the RWA-Emergency Power Control System will react to the last signal received.

24
2.4.3 External equipment
1

You can connect external equipment to the RWA-Emergency Power Control System. This equipment can then either send signals to the RWA-Emergency Power Control System or receive signals from it.

L1 PEN
212121
1 2
Rain/wind sensor (floating (potential-free) make contact) (1)
External fire alarm system (floating (potential-free) make contact) (2)
Alarm signal (floating (potential-free) alarm contact)*
Window Open signal (floating (potential-free) alarm contact)*
Fault signal (floating (potential-free) alarm contact)*

* optional daughter card required

Connecting a rain/wind sensor You can connect a rain/wind sensor with a floating (potential-free) make contact.

If the rain/wind sensor is triggered:

The ventilator switch is disabled.
All the connected drives are run in the "Zu" (closing) direction.

The alarm program takes precedence over the rain/wind sensor. Which means in the event of an alarm:

The windows are opened even if the rain/wind sensor is active.
The windows will not be closed, if the rain/wind sensor is triggered after the alarm.
Connecting an external fire alarm
system

You can connect an external fire alarm system with a floating (potential-free) make contact.

If the external fire alarm system triggers an alarm, the same alarm program will be started as for an alarm from an RWA switch or smoke/heat differential sensor.

The system is reset by the Reset button on the RWA-Emergency Power Control Sys­tem or with the "Zu" (close) button on an RWA switch. Before the system can be re­set, the external alarm signal must be switched off so that the RWA-Emergency Power Control System can respond properly should a new alarm signal arrive from the fire alarm system.
25
Connecting alarm contacts for Alarm,
76543219
321
123
1
2
Window Open and Fault

There are 3 floating (potential-free) alarm contacts for output signals: Alarm, Window Open (optional, cannot be retrofitted) and Fault. You can connect signal lamps, audible alarms or alarm signal lines to the fire station

to these contacts. The maximum load for each contact is 30 W at 24 V. The black jumpers (1), (2) and (3) behind the associated contact terminals
configure the contacts as make (NO) or break (NC) contacts.
Jumper Position Function
Installing the "Alarm Contacts"
daughter card
(1) left Alarm contact acts as make (NO) contact.
(1) right Alarm contact acts as break (NC) contact.
(2) left Window Open contact acts as make (NO) contact.
(2) right Window Open contact acts as break (NC) contact.
(3) left Fault contact acts as make (NO) contact.
(3) right Fault contact acts as break (NC) contact.
26
1. Switch off the mains and remove the battery fuse. The system is now off the circuit and de-energised.
2. Open the case.
3. Insert four spacers (2) into the holes in the main circuit board.
4. Push the "Alarm Contacts" daughter card (1) onto the spacers.
2.4.4 Complete the configuration table
2.4.5 Summary of the jumper settings
Jumper XB1 on the main circuit board

Once you have discussed the configuration with the operator: Complete the configuration table found in the Appendix.

Jumper Position Function
Alarm contacts Alarm, Fault and
Window Open
XB1
(red)
XB1 (red)

(also see Section 2.4.1 Alarm group)

Jumper Position Function
(1) (black) left Alarm contact acts as make (NO) contact.
(1) (black) right Alarm contact acts as break (NC) contact.
(2) (black) left Window Open contact acts as make (NO) contact.
(2) (black) right Window Open contact acts as break (NC) contact.
(3) (black) left Fault contact acts as make (NO) contact.
(3) (black) right Fault contact acts as break (NC) contact.

(also see Section "Connecting alarm contacts for Alarm, Window Open and Fault" on the previous page)

"Auf" (open)
"Zu" (close)
With alarm from the alarm group: Drives in "Auf" (opening) direction With "Zu/Reset" (close/reset): Drives in "Zu" (closing) direction
With alarm from the alarm group: Drives in "Zu" (closing) direction With "Zu/Reset" (close/reset): Drives in "Auf" (opening) direction
27

2.5 Installation

A
B
1
2

2.5.1 Preparation

Discuss and coordinate the configuration with the owner, designer or operator.
Consult the local approval authorities to determine the type of cable (for example
fire protection cable) and the required type of protection.
Comply with the maximum permissible cable length and required cable cross­sections.
Ensure that all the necessary equipment, cable, cable clamps, screws and bolts, etc., are available.
Ensure that the RWA-Emergency Power Control System installation is protected against excess heat.

2.5.2 Assembly

Mount the RWA-Emergency Power Control System on a vertical wall, in such a manner that the terminal compartment (1) and the cable feed (2) are at the bottom.

28
Drilling dimensions
E 260 N2 E 260 N4 E 260 N8/E 260 N12
Dimension A 242 281 345
Dimension B 177 220 275
Mount the RWA-Emergency Power Control System in a location protected against ex­cess heat:
1. Mark the holes.
2. Drill and plug the holes.
3. Have someone hold the RWA-Emergency Power Control System while you screw it to the wall.
2.5.3 Configuration

DANGER Risk of death through electrical shock!

Damage to sensitive components!

Disconnect the mains supply for the RWA-Emergency Power Control System
and take precautions that it is not reconnected while you are working.
Remove the battery fuse.
Before carrying out any configuration changes or expansions, you must isolate the RWA-Emergency Power Control System from the mains power and remove the bat­tery fuse. Configure the RWA-Emergency Power Control System in accordance with Section 2.4, Connection options and configurations:
1. Install the required daughter card.
2. Set and check the jumpers.
3. Enter the configuration in the configuration table in the Appendix.
2.5.4 Electrical connection
Connection diagrams You will find the connection diagrams in the packaging of the RWA-Emergency Power
Control System.
Cable lengths/cross-sections Please comply with the requirements for the cross-section of the cables to the drives:
The formula for the required cable cross-section based on the cable length and
the total current (of all drives):

Required cable cross-section = cable length x total current / 73

Minimum cross-section: 1.5 mm
Maximum cross-section (limited by the diameter of the wiring terminals):
maximum 4.0 mm
2

Table showing the maximum permissible line lengths in relation to total current and cable cross-section::

2
1.5 mm
2.5 mm
4.0 mm
5.0 mm
1 A 2 A 4 A 6 A
2
100 m 50 m 25 m 16 m
2
180 m 90 m 45 m 30 m
2
280 m 140 m 70 m 45 m
2
360 m 180 m 90 m 60 m
29
Connecting components
765432198765412121213
321
1
2
1. Break out the openings in the case required for the lines.
2. Insert cable glands (2) (not included in the delivery) to achieve the required protection type (see table below).
3. Feed the cables through the case and the cable glands into the RWA-Emergency Power Control System.
4. Feed the cables to the wiring terminals (1).

The enclosure of the RWA Emergency Power Control System without cable lead-in fulfils degree of protection IP54.

The degree of protection of cable glands with sealing ring is also IP54. Thus, the maximum possible degree of protection for the enclosure is achieved by
using cable glands with sealing ring. The recommended sequence for connecting the components is as follows:
1. Connect the RWA switch, smoke sensor and heat differential sensor for the alarm group.
2. Connect the drives and ventilator switches (possibly timer switch) from ventilator group 1.
3. Connect consecutively the drives and ventilator switches (possibly timer switches) from the other ventilator groups.
4. Connect external equipment: Rain/wind sensor, fire alarm system, floating (potential-free) contacts for Alarm, Fault and Window Open.
30
Check connections Before connecting to the mains and to the battery, check the following:
the component connections
the configuration (jumper settings)
that the cable clamps are firmly fixed
Things that are often forgotten The two terminating resistors should only be left in the last RWA switch on the line.
F3
Install a terminating resistor in the last smoke sensor or heat differential sensor on the line.
Install a terminating resistor at the "External alarm" input.
In the case of drives without line monitoring, connect the line monitor terminal to
GND (see connection diagram).
If a ventilator group has not been used, connect the line monitor terminal to GND (see connection diagram).
Connecting the mains and batteries After you have connected and configured all the components and checked the con-
nections, connect the battery and mains supply.
L1 PEN
212121
12

DANGER Risk of death through electrical shock!

Before connecting the RWA-Emergency Power Control System to the mains
supply, switch off the mains circuit and take precautions to prevent others from switching it back on.
1. Switch off the mains circuit and take precautions to prevent others from switching it back on.
2. Connect the mains cable (2).
3. Place the cover over the terminal compartment.
4. Switch the mains circuit back on.
5. Insert the battery fuse F3 (1).
31

2.6 Function test

Before handing over the system, you must test all the functions of the RWA-Emer­gency Power Control System. These tests must also be performed during the annual maintenance work.

DANGER Risk of death through electrical shock!

Before touching terminals or mountings, switch off the mains circuit and take
precautions to prevent others from switching it back on.
1. Check - with the mains power switched off - that the terminals and mountings are tight.
2. Check the power supply unit and charger.
3. Check the batteries.
4. Check the ventilation operation (opening and closing, LEDs).
5. Check the alarm functions (smoke sensor, heat differential sensor, RWA switch, coupled RWA-Emergency Power Control System) both operating from the mains as well as from emergency power (battery).
6. Check external connections (such as rain/wind sensor).
32

2.7 Operating states and faults

The operating state and any faults are shown on the 7-segment display of the RWA­Emergency Power Control System. If several states or faults occur at the same time, the display will cycle through them one per second.
Operating state codes The operating state codes provide information regarding the various alarm states of
the RWA-Emergency Power Control System and about the rain/wind sensor. The operating state codes are continuously updated on the 7-segment display.
Display Operating state
0 System is in order, no fire alarm, system in Open Window (Auf) mode
in the event of fire alarm
1 System is in order, no fire alarm, system in Close Window (Zu) mode
in the event of fire alarm
2 Fault - battery not connected
3 Fault - battery discharged
4 Fault - smoke sensor line broken or short circuit
5 Fault - RWA switch alarm line broken or short circuit
6 Fault - RWA switch closed line broken or short circuit
7 Fault - motor lines
8 Fault - fuse logic power supply (F8)
9 Fault - fuse motor supply mains-side (F2)
a Fault - fuse battery (F3)
B Rain/wind sensor active
c Fire alarm acknowledged, but signal from source is still present
D Fire alarm from external alarm
e Fire alarm from smoke sensor
f Fire alarm from RWA switch
l Charger faulty
u Fault - external alarm line broken or short circuit
33

2.8 What to do when …?

Problem Cause Action
Yellow signal lamp is illuminated on the RWA-Emergency Power Control System.
Yellow signal lamp on the RWA­Emergency Power Control System is flashing.
Depressing the ventilator switch does not move the windows.
7-segment display shows: a Battery fuse F3 is either missing or
7-segment display shows:
LED alarm on the RWA switch illuminated, although the system is not in an alarm state.
7-segment display indicates fault in an RWA switch line:
5
6
or
2 Connection to battery is broken. Check battery connection.
There are many possible causes. Evaluate the operating state and fault codes
Mains connection broken. Check mains connection.
Primary fuse F1 is faulty. Check fuse F1 and replace if necessary.
Mains power failure or other fault has occurred.
Rain/wind sensor active. If there is neither rain nor wind: Check the
blown.
Alarm has been reset, but there is still an active alarm signal.
Line to the RWA switch is broken. Check lines.
on the 7-segment display.
Evaluate the operating state and fault codes on the 7-segment display. Check drives.
rain/wind sensor.
Check fuse F3 and replace if necessary.
Check whether the alarm switch in the RWA switch is released. Check the smoke sensor and heat differential sensor, external alarm, etc., accordingly.
Check the series connection of the RWA switches.
7-segment display indicates fault in a motor line:
7
7-segment display indicates fault in a smoke sensor line:
4
7-segment display indicates fault in the "External alarm" line"
u
Terminating resistors have not been installed correctly.
Motor fuse is blown (green LED next to the motor terminal strip is illuminated).
Motor line monitor fault (green LED next to the motor terminal strip is illuminated).
Line to the smoke sensor is broken. Check lines.
Terminating resistor missing. Check the terminating resistor (only leave one
Line is broken or has a short circuit.
Terminating resistors are missing or placed incorrectly.
Check both terminating resistors (only leave them in the last switch of the line!).
Check the fuse.
Check motor lines (motor line 3 may only be connected to the last motor). If there is no motor monitor, terminal 3 must be connected to GND. Check, which motor line has a fault.
Check that the smoke sensor is seated firmly in the socket.
in the last socket of the line!).
Check the resistance value.
Check the circuiting and the value of the terminating resistors.
34

2.9 Testing and maintenance

The RWA-Emergency Power Control System must be checked annually by a GEZE­approved specialist. The operator must be given a written report covering the tests and maintenance done.

DANGER Risk of death through electrical shock!

Before beginning maintenance work on the RWA-Emergency Power Control
System, switch off the mains supply and take precautions to prevent others from switching it back on.
Test steps The complete test consists of the following steps:
1. Perform a complete function test (see Section 2.6, Function test).
2. Every 4 years, replace both batteries and update the charging date on the battery.
3. Check that the drives are clean, if necessary clean and lubricate them.
4. Submit a written report covering the tests and maintenance performed.
35

3 Appendix

3.1 Technical data

Technical characteristics Mains supply 230 V AC 50 Hz, in accordance with DIN IEC 38, 10 A max. back-

up fuse
Motor output voltage 24 V DC unregulated, residual ripple <20 %, max. 30 V
Control voltage 24 V DC ±10 %
Protection type IP54 (using cable glands with sealing rings)
At least 72 hours of emergency power with 2 x 12 V lead gel batteries
Integrated regulated charger for the batteries
In ventilation operation, the opening time is limited to 300 s by a timer

Performance characteristics The following table presents the performance data for the various types of transfor-

mers and batteries as well as the maximum permissible output current for all drives::
Type designation Transfor
E 260N 2/1 80 VA 1.2 Ah 2.0 A*
E 260N 4/1 to E 260N 4/2 130 VA 2.1 Ah 4.0 A
E 260N 8/1 to E 260N 8/4 260 VA 6–7.2 Ah 7.5 A
E 260N 12/1 to 12/2 480 VA 6–7.2 Ah 12 A

* or 2 drives E205/206, E212-24 V

Motor operation start-up time (mains operation): 25 %, max. start-up time: 5 min
Switching capacity of the floating (potential-free) alarm contacts: 30 W at 24 V
Maximum conductor cross-section Control lines: 2.5 mm
Motor lines: 4.0 mm
Smoke sensor and heat differential
sensor
Emergency Power Control System
case
Optical smoke sensor with two-wire system using scattered light method,
sensitivity in accordance with EN 54/Part 7
Heat differential sensor with two-wire system, reacts to increase in temperature, sensitivity in accordance with EN 54/Part 5, temperature limit 57 °C
Plastic
Cables fed from below
Colour: grey
mer
2
maximum
2
maximum
Power pack
Maximum output current
36
Dimensions Width (mm) x Height (mm) x Depth (mm):
E 260 N2/1 256 x 217 x 112
E 260 N4/1-2 295 x 261 x 112
E 260 N8/1-4 362,4 x 318,5 x 130,5
E 260 N12/1-2 362,4 x 318,5 x 130,5
Ambient temperature –5 °C to 40 °C, environmental protection type III
Environmental conditions Contamination level 2 in accordance with EN 60730 (normal environmental condi-
tions)

3.2 Fuses

Fused with either glass cartridge 5 x 20 mm (AT) fuses or automotive blade-type fu­ses. The following fuses are used in the systems:
Designation System N2/1 System N4/x
Mains fuse F1 0.8 A T 2 A T
Charger supply F8 0.8 A T 1.25 A T
Motor power supply F2 3.15 A T 5 A T
Battery fuse F3 3 A blade 5 A blade
Motor line 1 F4 3 A blade 4 A blade
Motor line 2 F5 - 4 A blade
Motor line 3 F6 - -
Motor line 4 F7 - -

Only use glass cartridge fuses 5 x 20 mm (F1, F2, F8) as per EN 60127-2/3.

Designation System N8/x System N12/x
Mains fuse F1 3.15 A T 4 A T
Charger supply F8 2 A T 2 A T
Motor power supply F2 10 A T 16 A T
Battery fuse F3 10 A blade 15 A blade
Motor line 1 F4 7.5 A blade 15 A blade
Motor line 2 F5 7.5 A blade 15 A blade (F6)
Motor line 3 F6 7.5 A blade -
Motor line 4 F7 7.5 A blade -

Only use glass cartridge fuses 5 x 20 mm (F1, F2, F8) as per EN 60127-2/3

37

3.3 Configuration table

System model E 260N /

Alarm group
Ventilator groups
External connections
Number of RWA switches
Number of smoke sensors/heat differential sensors
Closes the windows
Opens the windows
Ventilator group 1
Ventilator group 2
Ventilator group 3
Ventilator group 4
External connection Connections/Configurations
Rain/wind sensor
Fire alarm system
External alarm signal
Make contact
Break contact
Number of drives
Timer switch
Number of drives
Timer switch
Number of drives
Timer switch
Number of drives
Timer switch
Number of ventilator switches
Number of ventilator switches
Number of ventilator switches
Number of ventilator switches
External fault signal
Make contact
Break contact
Window Open
Make contact
Break contact
38

4Index

A
Alarm group ........................18, 20
C
Components ..................... 6, 8, 17
Configuration ............................. 19
Connection options ................... 19
D
Drives .......................................... 8
E
Electrical components ................ 6
F
Fault
for the operator .................. 13
Fire alarm
Procedures and signals
Stopping ............................ 11
Triggering .......................... 10
Fire alarm system
..................9, 20
..... 10
H
Heat differential sensor ............... 9
I
R
Rain/wind sensor .............8, 10, 18
RWA switch
RWA-Emergency Power Control System
................................. 8
Resetting ............................ 11
Components
Reset .................................. 12
...................... 18
S
Safety instructions ....................... 4
Signals
.................................. 18
Alarm
Fault ..................................... 9
Window Open Smoke sensor
Storage ...................................... 16
Symbols and conventions ........... 2
System
Resetting
...................... 8
....................... 9, 20
............................ 11
T
Timer switch ................................ 8
V
Ventilation operation ................... 9
Ventilator groups ....................... 18
Ventilator switches ...................... 8
Installation ................................. 15
M
Maintenance ............................. 15
O
Overview ..................................... 5
P
Power outage ............................ 13
39

Germany

GEZE Sonderkonstruktionen GmbH Planken 1 97944 Boxberg-Schweigern Tel. +49 (0) 7930 9294 0 Fax +49 (0) 7930 9294 10 E-Mail: sk.de@geze.com
GEZE GmbH Niederlassung Süd-West Tel. +49 (0) 7152 203 594 E-Mail: leonberg.de@geze.com
GEZE GmbH Niederlassung Süd-Ost Tel. +49 (0) 7152 203 6440 E-Mail: muenchen.de@geze.com
GEZE GmbH Niederlassung Ost Tel. +49 (0) 7152 203 6840 E-Mail: berlin.de@geze.com
GEZE GmbH Niederlassung Mitte/Luxemburg Tel. +49 (0) 7152 203 6888 E-Mail: frankfurt.de@geze.com
GEZE GmbH Niederlassung West Tel. +49 (0) 7152 203 6770 E-Mail: essen.de@geze.com
GEZE GmbH Niederlassung Nord Tel. +49 (0) 7152 203 6600 E-Mail: hamburg.de@geze.com
GEZE Service GmbH Tel. +49 (0) 1802 923392 E-Mail: service-info.de@geze.com
Austria
GEZE Austria E-Mail: austria.at@geze.com www.geze.at
Baltic States
GEZE GmbH Baltic States oce E-Mail: oce-latvia@geze.com www.geze.com

Benelux

GEZE Benelux B.V. E-Mail: benelux.nl@geze.com www.geze.be www.geze.nl
Bulgaria
GEZE Bulgaria - Trade E-Mail: oce-bulgaria@geze.com www.geze.bg
China
GEZE Industries (Tianjin) Co., Ltd. E-Mail: chinasales@geze.com.cn www.geze.com.cn
GEZE Industries (Tianjin) Co., Ltd. Branch Oce Shanghai E-Mail: chinasales@geze.com.cn www.geze.com.cn
GEZE Industries (Tianjin) Co., Ltd. Branch Oce Guangzhou E-Mail: chinasales@geze.com.cn www.geze.com.cn
GEZE Industries (Tianjin) Co., Ltd. Branch Oce Beijing E-Mail: chinasales@geze.com.cn www.geze.com.cn
France
GEZE France S.A.R.L. E-Mail: france.fr@geze.com www.geze.fr
Hungary
GEZE Hungary Kft. E-Mail: oce-hungary@geze.com www.geze.hu
Iberia
GEZE Iberia S.R.L. E-Mail: info@geze.es www.geze.es
India
GEZE India Private Ltd. E-Mail: oce-india@geze.com www.geze.in
Italy
GEZE Italia S.r.l E-Mail: italia.it@geze.com www.geze.it
GEZE Engineering Roma S.r.l E-Mail: roma@geze.biz www.geze.it
Poland
GEZE Polska Sp.z o.o. E-Mail: geze.pl@geze.com www.geze.pl
Romania
GEZE Romania S.R.L. E-Mail: oce-romania@geze.com www.geze.ro
Russia
OOO GEZE RUS E-Mail: oce-russia@geze.com www.geze.ru
Scandinavia – Sweden
GEZE Scandinavia AB E-Mail: sverige.se@geze.com www.geze.se
Scandinavia – Norway
GEZE Scandinavia AB avd. Norge E-Mail: norge.se@geze.com
www.geze.no
Scandinavia – Denmark
GEZE Danmark E-Mail: danmark.se@geze.com www.geze.dk
Singapore
GEZE (Asia Pacic) Pte, Ltd. E-Mail: gezesea@geze.com.sg www.geze.com
South Africa
GEZE Distributors (Pty) Ltd. E-Mail: info@gezesa.co.za www.geze.co.za
Switzerland
GEZE Schweiz AG E-Mail: schweiz.ch@geze.com www.geze.ch
Turkey
GEZE Kapı ve Pencere Sistemleri E-Mail: oce-turkey@geze.com www.geze.com
Ukraine
LLC GEZE Ukraine E-Mail: oce-ukraine@geze.com www.geze.ua
United Arab Emirates/GCC
GEZE Middle East E-Mail: gezeme@geze.com www.geze.ae

United Kingdom

GEZE UK Ltd. E-Mail: info.uk@geze.com www.geze.com

GEZE GmbH

Reinhold-Vöster-Straße 21–29 71229 Leonberg Germany
Tel.: 0049 7152 203 0 Fax.: 0049 7152 203 310

www.geze.com

Loading...