118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
Contents
1. Short description...............................................................................................................................................................2
3.2 Connection of the battery ...........................................................................................................................................4
3.3 Connection of smoke and heat difference sensor...........................................................................................4
3.4 Operation without smoke or heat difference senosr.......................................................................................4
3.5 Connection of SHE switch FT4/24V DC - VdS....................................................................................................5
3.6 Connection of fire alarm system (BMS) / remote trip release .....................................................................5
3.7 Operation without central fire alarm system (BMS) / remote trip release.............................................5
4.1 Connection of motors...................................................................................................................................................6
4.1.2 Branched, 2 or more cable sections...................................................................................................................6
4.1.3 Connections of motors without integrated line monitoring.....................................................................7
4.1.4 Unused motor group..................................................................................................................................................7
4.2 Motor lines.........................................................................................................................................................................7
4.2.1 Calculation of the cross-sections for motor lines........................................................................................7
4.2.2 Examples for max. line lengths in [m]................................................................................................................7
5.1 Connection of ventilator switch...............................................................................................................................8
5.2 Connection of several ventilator switches per ventilator group................................................................9
6 Connection of timer.........................................................................................................................................................10
6.1 Timer per ventilator group........................................................................................................................................10
6.2. Several ventilator groups with 1 timer...............................................................................................................10
7.1 Connection of rain/wind control unit ...................................................................................................................11
7.2 Connection of several emergency power control units E260N to 1 rain/wind control unit..........11
• Illuminated display at the front of the housing:
green: system ready for operation
yellow: malfunction
yellow blinking: power failure
• RESET of smoke alarm detector line: RESET button in
the connection compartment of the housing
cable entry
Connection possibilities:
SHE-switch FT4-24V DC – VdS
Id.-no. 099561
E260N2/1
Smoke detector RM 1003 or
heat diff. sensor WM 1005
for E260N12
Alarm contact
from external fire alarm
system/remote trip release
Ventilator switch LTA-230
Ventilator switch LTA-24
Rain/wind control unit
SHE – drives 24V DC with
total current:
optional:
volt-free contract for
alarm, malfunction, window OPEN
E205/206,E212
IMPORTANT !!!
Routing of cables and connection to the mains voltage must be carried out by a qualified electrician
GEZE does not uphold any warranty if the product is used in combination with products by third parties
For all types of installations the relevant regulations must be observed, in particular VDE 0833/0815.
The type of cable used must be approved by the local authorities, if necessary use fire-protection cables
(E30 or E90).
The battery must be replaced after 4 years
Important installation regulations for the user
10 pcs.
max. 4 pcs.
10 pcs.
20 pcs.
arbitrary
3 ea per group
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
2
CLOSED
CLOSED
t
t
t
V
2. Layout plan
Smoke detector RM 1003/24V
or heat diff .
Mains 230V AC
N
Mains connect ion
230V AC 50H z
3 x 1,5mm²
with GN/YE
Switch off batter y and power
supply befor e replacing
the plug-in cir cuit boards.
SHE switches of type FT4-24V
DC-VdS must be used only!
Alarm switch
CLOSE switch
Resistor s:
leave in the last
switch!
Resistor 15k, 5%
(for N12: 3K9, 1%)
detector W M 1005/24V
Alarm resistance
22k
Resistor
33k
Rain /
wind
PE
L1
Inpu
Malfunct.
Oper. OK
Win. OPEN
LED-fire
-
2
1
3
4
5
+
Last
smoke detector
Rain /
wind
2 1
GND
Type
N2/1, N4/1, N8/1, N1 2/1
N4/2, N8/2, N12/2
N8/3
N8/4
YE
GN
YE
RD
+24V
OPE
GND
-
2
1
3
4
5
+
s
smoke
1
detector
2 1
Alarm
external
Smoke
detector
InputGND
Colour coding:
BN = brown = braun
BK = black = schwarz
BU = blue = blau
GN/YE = green/ yellow = grün/gelb
Number of the equipp ed
ventilator gr oups
9
8
7
6
5
4
3
2
1
Last motor
3
Motor
2
24V DC
1
Insula ted
conductor
3
3
Motor
2
24V DC
1
s
1
motor
22 23 24 2526 2721
21
3 41
5 6 7 8
SHE switch
-
+24
Ventilator s witch 2
GND OPEN
Ventilator s witch 1
2 3 4 5 6 71
CLOSED
9
+24V
STOP
2 31
Motor
group 1
LED
LED OPEN
1 2 4 4 3 5 6 7
1
2
3
4
C
O
S
CLOSED
L
P
T
O
E
O
green
S
P
E
LTA-24
LED
OPEN
red
Connect all other ventilator groups
as per ventilator group 1
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
3
3.1 Mains connection
24V
r
r
r
24V
Terminal block E260N
Mains 230V AC
N L1 PE
Mains connection
230V AC 50Hz
3 x 1,5mm²
with GN/YE
3.2 Connection of the battery
Insert fuse F3 prior to commissioning.
3.3 Connection of smoke and heat difference sensor
a total of max. 10 sensors in series (for N12 max. 20 senors)
1. Smoke detecto
Information on the mains connection:
- mains voltage 230V AC, 50Hz, back-up fuse10A,
connecting line 3x1,5mm² or 3x2,5mm² with
GN/YE
- connect protection earth to PE-terminal
- to switch off the system the building installation must
include an isolating device (switch, disengageable
safety cutout that can be turned off). The isolating
device must be marked accordingly and must not be
freely accessible.
Check button and motor connections prior to
connecting power and battery supply.
Last smoke detecto
2
1
3
4
5
Term. block
E260N
Alarm
extern
2 1
2 1
Smoke
detector
+
+
3 4 1
5 6 7 8
RWA –Switch
-
+
3.4 Operation without smoke or heat difference senosr
Resistor 15kΏ, 5%
(for N12: 3K9Ώ, 1%
-
Terminal
block E260N
Alarm
external
from term.1 to term. 2
2 1
Smoke-
detector
+
2 1
3 4 1
5 6 7 8
SHE –switch
-
2
1
3
4
5
9
Resistor
15kΏ 5%,
(for N12: 3k9 , 1%)
to be installed in the
last senso
Heat diff. sensor type WM 1005/24V
or
smoke detector type RM1003/24V
9
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
4
A
,
9
8
7
6
5
4
3
A
A
A
t
A
60
3.5 Connection of SHE switch FT4/24V DC - VdS
last SHE switch
GND
1
Terminal block
GND
LARM
CLOSE
+ 24V
LED fire
LED win.OPEN
LED-oper.OK
LED-malfunct
1
3 4 1
5 6 7 8
9
2
3
OPEN
4
+24V
5
RD
6
YE
7
GN
8
YE
9
2. SHE-switch
1
2
3
OPEN
4
+24V
5
RD
6
YE
7
GN
8
YE
9
s
1
SHE switch
1
2
3
OPEN
4
+24V
5
RD
6
YE
7
GN
8
YE
9
SHE switch
GND
+24V
3.6 Connection of fire alarm system (BMS) / remote trip release
External volt-free
normally-open contact
by fire alarm unit required
For line monitoring the contact must be
connected including resistors
Terminal block
E260N
Alarm
external
Input
GND
larm resistor
22kΏ
Resistor
33kΏ
2 1 2 1
Smoke
detector
3.7 Operation without central fire alarm system (BMS) / remote trip release
LED-fire
Win. OPEN
Oper. OK
Malfunction
Both
resistors:
leave in the last
switch
CLOSE
larm switch
Both
resistors:
remove in all
preceding switches!
CLOSE switch
larm switch
Both
resistors:
remove in all
preceding switches!
CLOSE switch
larm switch
Terminal block
E2
N
Alarm
external
33kΏ
Smoke
detector
2 1 2 1
If no contact is connected, a resistor 33 kΏ
must be connected between terminal 1 and
terminal 2.
Input GND
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
Resistor
5
g
d
r
)
g
t
r
d
r
)
4.1 Connection of motors
4.1.1 Linear, 1 cable section
Monitoring of the motor supply line:
using conductor no. 3 in each group.
Insulate conductor no. 3 of all other motors of the group
n
2
moto
Motor
24V DC
1
2
Conduit box
Hint:
The motor line monitoring function responds as soon as either
conductor 1 and 2 or conductor 3 is interrupted.
Insulate
conduct. 3
3
Last motor
Motor
24V DC
1
2
3
Change of direction:
Interchan
Terminal block
E260N
e cond. 1+2
2 3 1
Motor
group
s
1
Motor
24V DC
1
moto
2
Insulate
conduct. 3
3
-
(if
OPEN
Monitorin
4.1.2 Branched, 2 or more cable sections
Insulate
conduct. 3
Motor
24V DC
Insulate
conduct. 3
Motor
24V DC
Terminal block
E260N
3
2
1
Cable section 2
3
2
1
4-core
cable
2 3 1
Motor
group
-
(if
OPEN
Monitorin
For cable junction a 4-core cable
is required
3-core
cable
g
n
2
moto
Motor
24V DC
1
2
Conduit box
Supply conductors branch off parallel.
Pilot core no.3 is looped through all cables up
to the end of the group.
Insulate
conduct. 3
3
Cable section 1
Last motor
Motor
24V DC
1
2
3
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
6
)
g
d
r
t
)
V
4.1.3 Connections of motors without integrated line monitoring
n
2
moto
Motor
24V DC
Conduit box
Terminal block
E260N
2 3 1
Motor
group
s
1
motor
Motor
24V DC
-
(if
OPEN
Monotirn
4.1.4 Unused motor group
Terminal block
E260N
2 3 1
Motor
group
Jumper cl.3 on GND
2 31
4 5 6 7
entilat. switch
-
(if
OPEN
GND
Monitoring
D
OPEN
CLOSE
STOP
4.2 Motor lines
4.2.1 Calculation of the cross-sections for motor lines
Cable cross-section (min.1,5²)
Cable length * Total current of all drives
Cable cross-section =
73
4.2.2 Examples for max. line lengths in [m]
Power consumption
1A 2A4A6A10A
3*1,5mm² 100 50251610
3*2,5mm² 180 90453018
3*4,0mm² 280 140704528
Cross-Sect.
Last motor
Motor
24V DC
2k2
Install 1 resistor 2k2Ώ and
2 diodes e.g. 1N4007
for line monitoring
in last conduit box.
If a motor group is not used, terminal 3
must be bridged to GND in order to
avoid error messages.
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
7
V
V
r
5.1 Connection of ventilator switch
Terminal block E260N
Terminal block E260N
Terminal block E260N
entilat. switch
2 3 4 5 6 7 1
GND
1 3 4 4 2
O
P
E
N
S
T
O
P
Ventil. switch
2 3 4 5 6 7 1
GND
1 3 4 4 2
O
P
E
N
S
T
O
P
Ventil. switch
2 3 4 5 6 7 1
GND
1 3 4 4 2
O
P
E
N
S
T
O
P
+24
C
L
O
S
E
C
L
O
S
E
C
L
O
S
E
5
CL
green
6 7
LED
OPEN
red
LTA-24
LTA-230
LTA-SCT
Terminal block E260N
Ventil. switch
2 3 4 5 6 7 1
GND
1 3 4 4 2
O
P
E
N
Watchdog circuit in the case of ventilation
(Motors are running as long as the button is pushed)
S
T
O
P
e.g.
LTA-230
C
L
O
S
E
2 diodes
e.g. 1N4007
to be con. by
custome
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
8
5.2 Connection of several ventilator switches per ventilator group
5.2.1 Ventilator switch LTA-230
Terminal block E260N
Ventilat. switch
GND
st
1 switch
1 3 4 4 2
2 3 4 5 6 71
1 3 4 4 2
S
O
P
E
N
C
L
T
O
O
P
S
E
O
P
E
N
S
T
O
P
1 3 4 4 2
C
L
O
S
E
For LTA-24 the terminals 5, 6 and 7 are always connected in parallel.
LTA-230
last switch
C
O
P
E
N
S
T
L
O
O
P
S
E
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
9
)
7
7
6 Connection of timer
6.1 Timer per ventilator group
Terminal block E260N
Ventil. switch
2 3 4 5 6 7 1
GND
OPEN
1 3 4 4 2
O
P
E
N
CLOSE
S
T
O
P
STOP
LTA-230
C
L
O
S
E
1 2 35 6 7
Channel AChannel B
4 8
N
L1
Mains
230V AC
Timer and ventilator switch have mutual priority switching
6.2. Several ventilator groups with 1 timer
1 switch contact is required for each direction of each ventilator group (OPEN/CLOSED
The timer settings must be
programmed as pulse signals.
The ventilator switch will not
function properly with sustained
signal.
e.g.
timer
2 channel
(Müller SC28.21)
Terminal block E260N
Ventil. switch
2 3 456
1
1 3 4 4 2
O
P
E
N
S
T
O
P
Group 4
Terminal block E260N
Ventil. switch
23456 71
1 3 4 4 2
C
L
O
S
E
O
P
E
N
S
T
O
P
C
L
O
S
E
Group 4
Terminal block E260N
Ventil, switch
23456
1
1 3 4 4 2
O
P
E
N
S
T
O
P
1 2 35 6 7
Channel
C
L
O
S
E
e.g.
time
2 channel
4 8
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
10
7.1 Connection of rain/wind control unit
Terminal block
Evaluation unit for
rain/wind control unit
Set mode of operation
“relay in common“
using jumper.
Mains
230V AC
Mains
N PEL1
Wind
Terminal block
E260N
N PEL1
Mains
Rain
Rain/
wind
Weather
station
2 31
LEDs
W R
+
Connect weather station, etc. in acc.
with connection scheme 45600-9-9520
sheet 1+2.
2 1
GND
7.2 Connection of several emergency power control units E260N to 1 rain/wind control unit
Terminal block
Evaluation unit
for rain/wind control
unit
Mains
230V AC
Mains
N PEL1
Wind
Rain
Weather
station
2 31
+
LEDs
W R
Terminal block
E260N
N PEL1
Mains
Rain/
wind
2 1
N PEL1
Mains
Rain/
wind
2 1
N PEL1
Mains
2 1
Rain/
wind
1. Emergency pow. control unit 2. Emergency pow. control unit3. Emergency pow. control unit
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
11
j
r
(
V
8.1 Potential-free signaling contacts (optional)
By changing the position of the corresponding
umper, the function (opener or closer) of the
signaling contacts can be altered.
Jumper position A:
Signaling contacts have the function of a closer,
i.e. the contact is made in the case of pending
messages (alarm, malfunction, ...) (default setting)
Jumper position B:
Signaling contacts have the function of an
opener, i.e. the contact is broken in the
case of pending messages.
The built-in relays are only suited
for low voltage up to 40V. If 230Vappliances are to be connected,
additional relays must be installed
downstream by the customer.
8.2 Connection with externals supply voltage
Terminal block
Emergency power control
unit
Volt-free signal. contacts
defaults)
NO
COM
Relay
Alarm
2 1
NO
COM
Relay
Wind. OPEN
2 1
NO
COM
Relay
Malfunction
2 1
Contact rating:
max.30W at 24V
24V
exte
n
24V
extern
24V
extern
8.3 Connection of a sounder with internal supply voltage (max.30mA)
NO
COM
Mains 230V AC
N L1 PE
e.g. GEZE
Sounder 24V DC
Id. no. 072112
entil. switch
2 3 14 5 6 7
+24V, max. 30mA
GND
Relay
Alarm
2 1
Relay
Alarm
Relay
Wind. OPEN
2 1
Position of the jumpers:
Jumper f. select. of function
Relay
Wind. OPEN
2 1
Terminal blocks
2 1
Relay
Malfunction
2 1
Relay
Malfunction
2 1
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
12
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC
13
118533-4 Connection Schema Emergency Power Supply System E260 N2/1 to N12/2-24V DC