Content of this Manual .................................................................................................................................... 5
Scope of delivery/Product package ................................................................................................................5
How to use this Manual ................................................................................................................................... 6
Illustrations and symbols used ....................................................................................................................... 6
Hazard symbols in this Manual .......................................................................................................................6
Types of warning .............................................................................................................................................7
URB 60 specialist terms and abbreviations ...................................................................................................8
Usage for the intended purpose .................................................................................................................... 11
IT security and rules for the use of Ethernet devices .................................................................................11
Applicable directives and standards .......................................................................................................... 11
Improper use .................................................................................................................................................12
Notes on product liability .............................................................................................................................. 13
Function ......................................................................................................................................................... 14
Technical data ...............................................................................................................................................15
Name plate/identification..............................................................................................................................17
Dimensions of the URB 60 ............................................................................................................................. 18
Ports and sockets on the URB 60 ..................................................................................................................19
Connecting the supply voltage......................................................................................................................20
Connecting the CAN bus system ...................................................................................................................20
Bus line, cable length and cross-section ...................................................................................................20
Important notes on connecting the CAN bus system .................................................................................. 21
Pin assignment of the CAN bus connector and coupling for non pre-wired
control cables ........................................................................................................................................... 22
Operation and navigation .............................................................................................................................. 23
User interface (example) ........................................................................................................................... 23
Starting up for the first time ......................................................................................................................... 27
Bringing the boiler, feedwater/condensate tank into service (Group 1..3) ................................................. 28
Home screen .................................................................................................................................................. 29
Alarms and error messages .......................................................................................................................... 31
Opening the Alarm History - the complete list of all alarms .......................................................................32
Opening the alarm and error list automatically .......................................................................................... 32
System settings ............................................................................................................................................. 33
Viewing CAN bus nodes.................................................................................................................................34
Setting the date/time.....................................................................................................................................35
System information ....................................................................................................................................... 39
Selecting the language ..................................................................................................................................40
Configuring the level controller ....................................................................................................................41
Testing the relays of the connected level controller ...................................................................................42
Pump control ............................................................................................................................................ 42
Setting manual control or the control point for manual pump operation ..................................................... 43
Switching actuator operation between automatic and manual ................................................................... 43
Valve calibration in manual mode when a feedback potentiometer is connected to the NRR 2-60 ............44
Calibrating the boiler level ........................................................................................................................45
Setting the level controller ........................................................................................................................46
Guide to setting control parameters .......................................................................................................... 46
Setting the level controller for 3-component control .................................................................................. 47
Configuring the conductivity controller ........................................................................................................ 48
Testing the limiter .....................................................................................................................................58
System malfunctions ..................................................................................................................................... 59
Display of system malfunctions in the alarm and error list using fault codes .............................................59
Fault codes for the URS 60/URS 61 safety control unit .........................................................................59
Fault codes for the NRR 2-60 / NRR 2-61 level controller,
LRR 1-60 conductivity controller and URW 60 universal converter ........................................................60
Common faults during use ........................................................................................................................ 62
What to do in the event of system malfunctions..........................................................................................62
Checking installation and function ............................................................................................................62
Data exchange via Modbus TCP ...................................................................................................................63
Taking out of service .....................................................................................................................................63
EU Declaration of Conformity ........................................................................................................................64
All rights reserved. Any misuse, particularly reproduction and dissemination to third parties, is not permitted. The General Terms & Conditions of GESTRA AG apply.
Scope of delivery/Product package
1 x URB 60 visual display and operating unit
6 x retaining clips
1 x power supply connector
1 x URB 60 data cable with integrated 120 Ω terminating resistor
This Installation & Operating Manual describes the correct use of the URB 60 visual display and operating
unit. It applies to all persons who integrate this equipment in control systems, install, bring into service,
operate, maintain and dispose of this equipment. Anyone carrying out the above-mentioned activities
must have read this Installation & Operating Manual and understood its contents.
Read this Manual in full and follow all instructions.
Please also read the instructions for use of any accessories.
The Installation & Operating Manual is part of the equipment package. Keep it in an easily accessible
location.
Availability of this Installation & Operating Manual
Make sure this Installation & Operating Manual is always available to the operator.
If you pass on or sell the equipment to a third party, please also hand over the Installation & Operating
Manual.
Safety integrity levels SIL 1 to 4 are used to quantify risk reduction. SIL 4 is the highest level of risk reduction. International standard IEC 61508 forms the basis for establishing, testing and operating technical
safety systems.
Continuous blowdown
As the boiler water begins to evaporate, the concentration of non-volatile dissolved solids (TDS) left
behind in the boiler increases over time as a function of steam consumption. If the TDS (= total dissolved
solids) concentration exceeds the limit defined by the boiler manufacturer, foaming and priming occur as
the density of the boiler water increases, resulting in the carry-over of solids with vapour into steam and
superheater lines.
The consequences are adverse effects on reliability and severe damage to steam generating units and
pipes.
To keep the TDS concentration within admissible limits, a certain portion of boiler water must be removed
continuously and/or periodically (by means of a continuous blowdown valve) and the boiler must be
replenished with fresh feedwater to compensate for the water lost through blowdown.
Intermittent blowdown
During the evaporation process, fine sludge is deposited on heating surfaces and on the floor of the steam
generating unit. The accumulated sludge sediments form a thermally insulating layer and can damage the
boiler walls due to excessive heat.
Intermittent blowdown is achieved by the abrupt opening of the intermittent blowdown valve. The resulting suction effect occurs only at the moment the valve is first opened. The opening time should therefore
not exceed about 2 seconds. Longer opening times result in a loss of water.
Time-based pulse/interval actuation of the intermittent blowdown valve optimises the removal of sludge
from the boiler. The interval between the intermittent blowdown pulses can be set between 1 and 120
hours (intermittent blowdown interval). The duration of intermittent blowdown can be set between 1 and
60 seconds.
For large boilers, repeated intermittent blowdown pulses may be required. Repetition can be set between 1
and 5 (intermittent blowdown pulses) with an interval from 5 – 30 seconds (pulse interval).
Damping (filter constant, conductivity and level control)
This parameter is used to settle the oscillations of the input signal.
Standby mode (conductivity control)
To prevent loss of water, continuous blowdown control and automated intermittent blowdown
(if enabled) can be disabled in standby mode or when the burner is switched off.
The continuous blowdown valve moves to CLOSED position, triggered by an external control command. In
standby mode, the “MIN/MAX” limits and monitoring functions remain active. When the equipment is back
in normal mode, the continuous blowdown valve returns to the control position.
An intermittent blowdown pulse is also triggered (if automated intermittent blowdown is enabled and a
blowdown interval and blowdown time have been set).
Cell constant (conductivity control)
The cell constant is a geometric variable of the conductivity electrode and is taken into account when
calculating the conductivity. However, this constant may change during operation, e.g. due to dirt deposits
on the measuring electrode.
If a reference measurement yields a result that differs from the indicated conductivity value, first check
the temperature compensation.
Modify the cell constant only if the temperature coefficient setting is no longer adequate for correct compensation. In this case, change the cell constant until the reading and the indicated conductivity match.
Flushing the continuous blowdown valve (conductivity control)
The continuous blowdown valve can be flushed automatically to prevent it from sticking. In this case, the
continuous blowdown valve is actuated at the flushing interval and opened for a defined flushing time.
After the flushing time, the valve moves to the position set by the control.
RefReading (reference reading)
The reference reading is the conductivity of the boiler water directly measured by the boiler service
technician. Using this parameter, the measured conductivity can be entered and the correction factor
automatically calculated (within its limits). This is then copied to the conductivity electrode and stored, so
that conductivity is then adjusted to the correct level.
The control direction indicates whether control is for supplying (positive) or draining (negative).
Pb (proportional band)
The proportional band enables the controller amplification to be adapted to suit the controlled system. For
further information, see page 46/55, guide to setting control parameters.
Ti (reset time)
The integral element ensures that control deviations can be fully corrected, with no remaining deviation.
For further information, see page 46/55, guide to setting control parameters.
Neutral zone
If the actual value reaches the (setpoint +/- of the neutral zone), the control point does not
change in this range.
Forced switchover
This parameter defines the level at which an automatic change of pump must take place. The assumption
here is that since the level cannot be maintained, the pump is faulty.
The URB 60 visual display and operating unit can be used in conjunction with various GESTRA CAN bus
units from the SPECTOR
The URB 60 is designed for installation in a control cabinet door or switch panel. It may only be used
when correctly installed.
Please read the supplied Installation Manual.
IT security and rules for the use of Ethernet devices
The plant operator is responsible for the security of his/her IT network and must take appropriate action to
protect equipment, systems and components from unauthorised access.
Pay attention to the following instructions when using Ethernet devices in your system:
Do not connect equipment, systems or components to an open network, such as the internet, without
safeguards in place.
To fully protect a PLC runtime system on a control system that is available on the internet, the use of
common security mechanisms (firewall, VPN access) is absolutely essential.
Restrict access to all components to authorised persons.
Change default factory passwords before bringing into service for the first time!
Deploy defence in depth mechanisms in your system security, to restrict access and control to
individual products and networks.
Applicable directives and standards
The URB 60 has been tested and approved for use in the scope governed by the following directives and
standards:
connect
series.
Directives:
Directive 2014/30/EU EMC Directive
Directive 2011/65/EU RoHS II Directive
Standards:
61000-6-2 Immunity for industrial environments
61000-6-3 Emission standard for residential, commercial and
light-industrial environments
61000-6-4 Emission standard for industrial environments
To ensure the proper use of equipment during all types of use, you must also read the Installa-
tion & Operating Manuals for the system components used.
You can find the latest Installation & Operating Manuals on our website:
http://www.gestra.com/documents/brochures.html
The URB 60 visual display and operating unit collects the data telegrams in the CAN bus from
GESTRA sensors and control units using the CANopen protocol.
When the system is started, the connected devices are automatically recognised by the URB 60 and
entered in a list of equipment along with all parameters. The groups, their home screens and navigation
buttons are displayed dynamically.
Readings, parameters, settings and messages are shown in plain text. When used as the second water
level indicator in boiler systems (TRD 401, EN 12952/ ...53), the level is also presented as a bar chart.
You can select various languages for the plain text display, see page 27 and 40.
Entering parameters with multilevel password security
Multilevel password security prevents parameters and settings from being changed by unauthorised
persons.
Password level (PWL)
PWL 1 = protected parameter settings
PWL 2 = safety-relevant values can only be set at this level
Operation and configuration, see page 23
The URB 60 is operated and configured on the unit itself using the colour touchscreen or via Ethernet
using remote software.
Limitations
In the event of signal multiplication, as can occur with a level control system (NRR 2-60 and NRR
2-61), only one level controller can be presented as a bar chart on the home screen.
This is indicated by different graphics in the chart and controller/limiter icons at the bottom of the
screen.
If the system has more than one STL (safety temperature limiter), the one with the lowest ID is shown
on the home screen.
On the limiter screens, all connected temperature sensors are shown with their actual value and limit
value.
Switchover between µS and ppm must take place both on the URB 60 and the LRG 1x-6x, so that the
displays match.
The URB 60 visual display and operating unit is designed for installation in control cabinet doors or switch
panels.
Please read the supplied Installation Manual. There you will find the installation instructions
from the manufacturer, plus further diagrams and mounting dimensions.
Criteria for the installation position:
Do not expose the URB 60 to direct sunlight.
Plastic parts of the unit may become brittle under exposure to UV light, shortening its service life.
Without external ventilation, the unit may have a maximum inclination of 45 °C from the vertical when
installed.
The controls on the service panel of the unit and the ports and cable connections must be freely
accessible after installation.
The installation aperture may have a panel thickness of 2 to max. 5 mm.
Ensure adequate ventilation (cooling).
Provide minimum space of 3 cm around ventilation grilles on the unit.
Provide minimum space of 15 cm around components that emit heat (e.g transformers).
Use a shielded, multi-core, twisted-pair control cable, e.g. UNITRONIC® BUS CAN 2 x 2 x .. mm2 or
RE-2YCYV-fl 2 x 2 x .. mm2, as the bus line.
Pre-wired control cables (with plug and coupling) are available as accessories in various lengths.
The baud rate (transfer rate) is determined by the cable length between the bus terminal devices, and
the wire cross-section is determined by the overall power input of the measuring sensors.
0.2 A at 24 V is required per sensor. With five sensors, there is therefore a voltage drop of approx. 8V
per 100 m when using cables of 0.5 mm². In this case, the system is operating at its limits.
With five or more sensors and a cable length of ≥ 100 m, the wire cross-section needs to be doubled
to 1.0 mm².
At larger distances of > 100 m, the 24 V DC supply can also be connected on site.
A dedicated 24 V DC SELV power supply unit that is isolated from connected loads must be used to
supply the SPECTOR
Make sure wiring is in line, not in a star!
Avoid potential differences in system parts by connection to a central earthing point.
connect
system.
Connect the bus line shields to one another all the way along, and connect them to the central
earthing point (CEP).
If two or more system components are connected in a CAN bus network, a 120 Ω terminating resistor
must be connected to the first and last units between terminals CL / CH.
If you are using the URB 60 as the first or last device, connect the terminating resistor between pins 2
and 7 in the CAN bus connector.
Connect the supplied data cable to terminals 14 (CHigh) and 15 (CLow) of the last safety control unit
or controller in the control cabinet. The connector of the data cable leading to the URB 60 contains a
120 Ω terminating resistor, so that the terminating resistor on the safety control unit or controller is no
longer required.
Only one URS 60 and one URS 61 safety control unit may be used in the CAN bus network.
The CAN bus network must not be interrupted during operation!
The URB 60 is operated on the unit itself using the colour touchscreen or via Ethernet using remote
software.
User interface (example)
The URB 60 visual display and operating unit shows parameters, operating states, etc. on a display.
The user interface of the URB is divided into three areas:
Alarm, system and group icons
Display area
Limiter and controller icons
The display window shows operating states and actual values.
The icons open the associated parameter screens. These icons change dynamically and are either
shown or hidden, depending on the current page and configuration.
Parameter entries can be disabled via the struck through padlock icon at the bottom right.
From PWL 1 onwards, this icon appears after a successful login.
Operation
All entries and actions, e.g. opening setup menus
and parameter screens, are initiated by tapping
the buttons and input fields.
Tapping an input field opens a numeric virtual
keypad.
This keypad shows the old value (Old) and the
limits (Min/Max).
Your entries must remain within these
limits.
Function keys:
Delete last digit.
Confirm entry.
Reject entries and close
keypad.
Entering parameters with multilevel password security
Multilevel password security prevents parameters
and settings from being changed by unauthorised
persons. The password prompt appears automatically when you tap an input field.
If you do not input anything for 10
minutes, you will be logged off again.
Factory set password level:
PWL 1 = 111
PWL 2 = 222
Recommendation for initial setup
Log on using the factory setting, then safeguard
your system by setting your own password.
When starting up for the first time, a Setup Wizard
opens. This guides you through the setting of the
most important parameters.
In addition, when the unit is switched on
the CAN bus searches for devices (nodes).
Navigation with the Setup Wizard
/ Go to previous/next page.
Confirm settings.
close the Setup Wizard.
Setup Wizard settings
On the last page, permanently
1. Language
Select the user language you require.
2. Conductivity
The unit can be configured in µS/cm or ppm.
This globally affects the display of the URB 60.
3. Time
Set the current time.
When the system is started, the connected devices (CAN bus nodes) are automatically detected and
entered in a list of equipment along with all parameters. The groups, their home screens and navigation
buttons are displayed dynamically.
If a CAN bus node is not on the list, check the node and set the correct parameters. After this, you must
import the device list again in the “Device settings” menu, see page 37.
During initial setup, always check the number of connected devices!
Bringing the boiler, feedwater/condensate tank into service (Group 1..3)
As level and conductivity controllers are factory-set on delivery, they all have the same settings and, if
they are not assigned to different groups, they will be in conflict. This would lead to malfunctions.
For this reason, please follow the procedure below:
1. Bring Group 1 + Group 2 + Group 3 into service one after another in that order,
so, first Group 1 only, e.g. with the limiters.
2. Correctly install 120-ohm terminating resistors in the bus at the beginning and end of Group 1.
3. Once Group 1 is functioning, set the units for the feedwater tank as Group 2, then connect the units of
the second group to Group 1.
You can set the groups to which the level and conductivity controllers belong via a 4-pole DIP
switch in each controller. Set the electrode groups using the rotary knob on the front of each
electrode.
4. Perform the same steps for the third group, the condensate tank.
The home screen provides an overview of the
status of available limiters and controllers. Bar
charts display current readings and change colour
depending on their status. This enables you to
rapidly assess the state of the system.
Limiter icons above the bar charts indicate the
status of the connected electrodes.
Opening the parameter screens:
Use the following buttons to open the parameter
screens:
Limiters,
see page 56
Level controllers,
see page 41
Conductivity controllers,
see page 48
Opening alarm and system screens:
Alarms and error messages,
see page 31
System settings,
see page 33
Opening groups:
Up to four groups may be available, depending
on the system. You can navigate between the
individual groups.
Group 1
e.g. controlling and configuring limiters
and controllers in pressurised steam
and hot-water plants.
Group 2
Example
If the level controller is a 3-compo-
nent (3C) controller, the level shown
on the home screen may differ from
the level displayed for the electrode,
as compensation is taking effect in
the controller.
Group 3
Group 4
Groups 2 - 4
Controlling and configuring controllers
and plant, e.g. feedwater and condensate plants, etc.
Alarms (Max/Min limit values, limiter triggered)
and error messages (offline, hardware errors)
are entered in the columns (Pending (= Come),
Expired (= Gone)) with a timestamp.
The most recent alarm is always shown at the top
of the list. To select an alarm message, select the
line in question.
Description of display:
Come (= Pending)
Time at which the event occurred.
Gone (= Expired)
Time at which the event disappeared
but was not acknowledged.
Description and abbreviations:
G1...4Groups 1 to 4
L1..2Limiter 1 or 2
C1..4Limiter channel
NRG / LRG /
NRR / LRR ...
NRR 2 =Level controller NRR 2-61
E001...E027
MAX alarm,
offline, etc.
Example: G1 – LRR Max Alarm
Type of equipment
Fault codes based on specific
device or system *
Error/malfunction/status
Options:
Opens the alarm history,
see page 32.
Alarm Info, opens a list of the
descriptions and abbreviations
used:
This button is displayed
dynamically if a limiter (L1.. / L2..)
alarm message is selected, and
pressing the button causes the
screen to jump to the limiter page.
Acknowledges alarms. Expired
“alarms” are deleted from the
list.
After the system is started, all CAN bus nodes
of the system are entered here. To achieve this,
the communication between CAN bus nodes is
constantly monitored after the system has been
started for the first time.
The CAN bus is re-analysed after a restart. New
nodes are found and entered.
The parameters of all CAN bus nodes
are only collected and continuously
updated following complete analysis.
You can see this from the progress
number (127/127) at the top right of
the display.
Description of the list:
No.
Consecutive number.
Node ID
The node ID of the CAN bus node.
ID
The ID (channel) of the limiter electrode. No
other CAN bus nodes have an ID.
Type
Designation of control unit/electrode (e.g. NRG
1x-60).
Version
Unit version number.
Group
The group containing the CAN bus node.
Reimporting the device list
If a CAN bus node is not on the list, check the
node.
You can then reimport the device list by tapping
the “Type” input field or via the “Device settings”
menu, see page 37.
This deletes all devices from the list and then lists
them afresh.
The URB 60 can be operated remotely from a PC
using VNC remote software, e.g. UltraVNC Viewer.
This allows a 1:1 display of the URB 60 on the
computer.
To access the URB 60, use the previously set
network parameters.
View a list of the last ten device restarts (e.g.
due to power failure), with the date and time.
Login
View a list of the last ten device logins with
date, time and password status.
PWL0 = failed login
PWL1/2 = successful login
Datalogs/Alarms
Save the data logs and alarm list to a USB
stick.
The file timestamps are in the Unix time stamp format and can be counted back using
Excel formulae:
=DATE(1970;1;1)+(LINKS([CELL];10)/86400).
Error memory
Export the internal error log of selected CAN
bus nodes to a USB stick. To do this, you can
switch the desired devices in the lists on/off
and select them.
PLC
Status display of the URB software.
Run = OK
Stop = error
“PLC Reset” followed by “PLC Start” completely deletes all internal parameters.
In the event of an error, please contact
GESTRA Service.
The data export („Reading“) takes
approx. 6 minutes per device.
Firmware Vx.x
Updates provided by GESTRA can be copied
onto the device using a USB stick.
1. To do so, insert the USB stick in the device
and reboot the device.
This makes sure the USB stick is detected.
Displays the connected conductivity controller
and its status:
OK
The conductivity controller is functioning
without problem.
Offline
No communication with the URB 60.
Collective fault
A fault has occurred in the conductivity
controller.
Alarm
Value above or below limit.
Electrode
Displays the conductivity electrode in question, and its status. For status messages, see
controller.
Max
Set the Max switchpoint.
W
Set the setpoint.
Min
Set the Min switchpoint.
If the “Max/Min” switchpoints are reached,
the parameter row changes colour.
“Intermittent blowdown”
If the Min contact of the LRR 1-60 conductivity
controller was configured as
“Intermittent blowdown” (see page 52), the
display changes and the time until the next blowdown is shown.
Description of bar charts:
X = actual value
W = setpoint
Yw = control point in % based on the
continuous blowdown valve stroke
You can change the unit between
“µS/cm” and “ppm” if required, see
page 37, Device settings.
conductivity controller, an external signal (24 V DC) can switch the controller
to standby mode. This causes the control to switch off and the valve to close.
The switchpoints (Max/Min) and the
monitoring function remain active
in standby mode.
Testing the relays of the connected conductivity controller
1. Tap the “Max1” or “Min1” input field. The
required test window now opens.
2.
3. The relay in the conductivity controller
Initiate the relay test by pressing
and holding the button until
the controller status and
parameter field change
colour.
remains active while you are pressing the
button.
Display when the conductivity controller has
been switched to standby mode
Display and functions after quitting standby
mode
If you quit standby mode, the controller returns
to control mode and intermittent blowdown is
re-enabled once more.
Reference reading, correction factor, temperature coefficient, damping, or 100% range.
2. The “Safety parameters” menu opens.
The current safety parameter values are
displayed.
3. Entry of safety parameters.
You can change the safety parameters within
the admissible limits.
After entry, the format of the value is converted. It is then sent to the electrode, which
sends it back as a “Reference value”.
The “input” fields below are hidden to
prevent the wrong one being filled.
4. If the reference value is the same as the input
value, it is shown with a green background.
Input = reference value
Confirm the input value.
If there is a problem with transmission, a red
background is shown.
Input ≠ reference value
Reject the entered value
and enter a new one.
If you do not enter anything for 20
seconds, the window closes automatically.
Description of safety parameters:
ReferenceReading (“Ref. meas. value”)
The reference reading is the conductivity
of the boiler water directly measured by the
boiler service technician.
Enter the measured reference reading here.
The correction factor is calculated automatically (within its limits of 0.05 to 5.00 1/cm),
transmitted to the electrode and then copied
back to the “Reference value” field.
If the calculated correction factor is outside its
limits, the entered value is rejected.
Correction factor
During operation, the indicated conductivity
may differ from the reference reading gained
from a reference measurement, e.g. due to
soiling.
In this case, change the correction factor
until the displayed “Reading” matches the
reference reading from the reference measurement.
TemperatureCoeff. (temperature coefficient) when service temperature has been
reached.
Proceed as described above for the correction
factor.
Damping (“Attenuation”)
This parameter is used to settle the oscillations of the input signal.
mine the current conductivity of the boiler
water.
2. Setup: Tap the Setup button.
3. The “Safety parameters” menu opens.
The current safety parameter values are
displayed.
4. Entry of safety parameters.
You can change the safety parameters within
the admissible limits.
After entry, the format of the value is converted. It is then sent to the electrode, which
copies it back as a “Reference value”.
5. If the reference value is the same as the input
value, it is shown with a green background.
Input = reference value
Confirm the input value.
If there is a problem with transmission, a red
background is shown.
Input ≠ reference value
Reject the entered value
and enter a new one.
If you do not enter anything for 20
seconds, the window closes automatically.
Description of safety parameters:
ReferenceReading (“Ref. meas. value”)
The reference reading is the conductivity
of the boiler water directly measured by the
boiler service technician.
Enter the measured reference reading here.
The correction factor is calculated automatically (within its limits of 0.05 to 5.00 1/cm),
transmitted to the electrode and then copied
back to the “Reference value” field.
If the calculated correction factor is outside its
limits, the entered value is rejected.
Correction factor
During operation, the indicated conductivity
may differ from the reference reading gained
from the reference measurement, e.g. due to
soiling.
In this case, change the correction factor
until the displayed “Reading” matches the
reference reading from the reference measurement.
TemperatureCoeff. (temperature coefficient) when service temperature has been
reached.
Proceed as described above for the correction
factor.
The URB 60 visual display and operating unit has a Modbus TCP server. This enables all values to be forwarded
to a higher-level control system or control centre.
Parameter:
Modbus ID: 1
Port: 502
Modicon Modbus: based on 1
You can find the latest list of datapoints on our website at:
http://www.gestra.com/documents/brochures.html
Taking out of service
1. Switch off the supply voltage and secure so that it cannot be turned on again.
2. Unplug the mains connector from the unit.
3. Remove all plug and socket connections (e.g. CAN bus line, Ethernet connection, etc.).
4. Unscrew the screws and remove the retaining clips.
5. Carefully push the unit out of the cutout in the door of the control cabinet.
An alarm is triggered when the CAN bus cable is interrupted.
Disposal
Dispose of the URB 60 visual display and operating unit in accordance with statutory waste disposal
regulations.
If goods have come into contact with media that are hazardous to health, they must be
drained and decontaminated before being returned to GESTRA AG!
Such media include solid, liquid or gaseous substances, mixtures of these, or radiation.
GESTRA AG can accept returned products only if accompanied by a completed and signed
return note and also a completed and signed declaration of decontamination.
The return confirmation and declaration of decontamination must be attached to the returned
products and be accessible from the outside. Otherwise, the products cannot be dealt with and
will be returned at the customer’s expense.
Please proceed as follows:
1. Let GESTRA AG know about the return beforehand by e-mail or phone.
2. Wait until you have received the return confirmation from GESTRA.
3. Return the products to GESTRA AG together with the completed return confirmation (and
declaration of decontamination).
EU Declaration of Conformity
We hereby declare that the URB 60 visual display and operating unit conforms to the following European
Directives:
Directive 2014/30/EU EMC Directive
Directive 2011/65/EU RoHS Directive
Please see our Declaration of Conformity for details on the conformity of our equipment with European
Directives.
The current Declaration of Conformity can be found online at www.gestra.com or can be requested from
us.