GE Security ZP720-3 Installation Sheet

Installation Sheet No. 1015ZE R2.0 ZP720-3 Heat Analogue Sensor
2436-01
Based on advanced thermistor technology, the heat analogue sensor provides a reliable response to fires in areas where environmental conditions prohibit the use of smoke detection.
The heat analogue sensor is a temperature dependent analogue sensor. It is intended for applications where fluctuations of ambient temperature may be expected for example, over machinery in laundries, or factory locations where industrial processes may cause sharp temperature increases.
Specifications
General information
Designation Heat analogue sensor Specification AS1603 Part 1 Model number ZP720-3 Part number 1015 Sensitivity Level 1 58°C fixed temperature
Level 2 58°C rate compensated Level 3 75°C rate of rise Level 4 75°C fixed temperature
Mounting Plugs into surface or semi-
recessed base Area coverage 50m², subject to local codes Wiring 2 core loop or spur Monitoring Open and short circuit fault.
Sensor removal and device type. Indication Alarm LED (red) Addressing method 7-way Dipswitches in head
Environmental
Application Indoor use Temperature range -10 to +75ºC Operating temperature 58 to +75ºC (4 software settings) Quiescent temperature -10 to +65ºC (75ºC setting) Humidity range 20% to 95% RH (non condensing) Environmental rating IP32
Primary supply
Operating voltage Address line pulsed 20 V (19.5 to
20.5 V). Max line less 4 V Current (quiescent) 600 µA Current (alarm) 700 µA
Mechanical details
Material Moulded ABS Colour White Dimensions (D x H) 106 x 52 mm (excluding base) Height (from ceiling
with base) ZP7-SB1 surface base – 60 mm ZP7-RB1 recessed based – 38 mm
Weight 85 g (excluding base)
Manufacturer traceability
A barcode label is affixed to each product (see example below). This label reflects, amongst other things, the date of manufacture of the product in the form YYDDD.
These numbers are interpreted as follows: YY = year of manufacture DDD = day of manufacture For example the numbers 07134 would indicate that the
product was manufactured on the 134
th
day of the year 2007,
that is 14
th
May 2007.
Page 1 501-1015ZE-1 www.gesecurity.eu Copyright © 2007 GE Security B.V. All rights reserved 12 November 2007
Installation Sheet No. 1015ZE R2.0 ZP720-3 Heat Analogue Sensor
Page 2 501-1015ZE-1 www.gesecurity.eu Copyright © 2007 GE Security B.V. All rights reserved 12 November 2007
A switch only represents its coded value (i.e. 1st switch = 1, 2nd switch = 2, 4th switch = 8 etc) position. In the OFF position it represents a zero.
Installation instructions
Note: No wiring is required during sensor installation. Refer
to base datasheet for line wiring installation. All installation should be in accordance with the requirements of the authority having jurisdiction.
To arrive at the address number of a device, add the representative numbers of all switches which are in the ON position: for example 2+4+32=38.
Warnings: This device is intended to be installed in
conjunction with, and in applications where, smoke sensors would be likely to give unwanted alarms and should only be used as part of a broad-based life safety system. For further information consult your local fire protection specialist.
Refer to Figure 1. The sensor attaches to compatible bases with a plug-and-twist action as follows:
1. Align the sensor with the base and turn it slowly until the location lugs and grooves mate, allowing the sensor to slide completely into the base.
2. Rotate the sensor clockwise until it locks. To remove the unit from the base, perform these steps in reverse order.
Maintenance should be planned in accordance with the requirements of the authority having jurisdiction.
Note: To prevent unauthorized removal, a plastic breakout
tab is provided in the sensor housing. Once the breakout tab is removed the sensor can only be released by use of a special tool.
3. Prior to initial testing remove the yellow plastic dust cover from the sensor and notify the proper authorities that the fire alarm system is undergoing maintenance and will be temporarily out of service.
4. An indent is provided on the sensor exterior for application of Zone number labelling to allow easy zone identification.
Figure 1: Installing the sensor
Sensor Housing
Component
Cover Plate
Component Cover Plate
Housing Assy Screw
Housing Assy Screw
Housing Assy
Screw
Housing Assy
Screw
2524-01
Top V iew
Bottom View
Thermistor
Indent ­Device Address Labeling
Address switch
Setting the address
The heat analogue sensor contains a 7-way dipswitch. The switch is used to set the device address in binary code. The switch may be set to represent any addresses from 1 to 127.