Overview
The TS7 Series features photoelectric smoke detectors with an easy
to install and maintain head and base design. The photoelectric
smoke detector heads are self diagnostic and have field replacable
optical chambers. They feature automatic drift compensation
which adjusts the sensitivity if the detector becomes dirty over time,
greatly reducing the chance of a nuisance alarm.
Additional diagnostic information is activated by applying a magnet
near the detector’s integral reed switch. This initiates a self-diagnostic routine and provides visual indication of sensitivity level, or if
service is required.
The TS7 smoke detector heads meet NFPA 72 field sensitivity testing requirements without the need for external meters. Orders are
shipped with the appropriate six-inch base to support either two- or
four- wire TS7 Series smoke detector heads.
Standard Features
•
Two- or four- wire head and terminal base models (packaged
together)
Self-diagnostic capabililty continually monitors operation
•
Built-in drift compensation
•
Field replaceable optical chamber
•
Low-profile design blends in with the environment
•
Available with integral heat detectors and auxiliary relay
•
Meets NFPA 72 field sensitivity testing without the need for exter-
•
nal meters
Extensive 2-wire compatibility listings
•
12/24VDC
•
Two- and Four-Wire
Conventional Smoke
Detectors & Bases
TS7 Series
U.S.
T 888-GESECURITY
F 503-691-7566
Canada
T 519 376 2430
F 519 376 7258
Asia
T 852 2907 8108
F 852 2142 5063
Latin America
T 305 593 4301
F 305 593 4300
© 2009 General Electric Company
All Rights Reserved
Specifications
Electrical
Voltage 8.5 -33VDC, non-polarity sensitive
Max ripple (peak to peak) 10% (Vp - p)
Typical standby current (24V) 70μA
Typical alarm current 24V 2-wire up to 60mA max, if not limited by control panel
Typical alarm current 24V 4-wire 50mA max, 50mA min
Relay contacts 2A @ 30VDC, 1A @ 120VAC
Photoelectric Sensitivity 2.85%, +0.37, -1.00%
Operating temperature 32°F -120°F (0°C - 49°C)
Operating humidity range 0 -95% Non-condensing
RFI immunity 20V/m min; 0-1000MHz
Remote LED output current 5mA min, 8.5mA max
Drift compensation adjustment 1.0%/ft max
Heat Sensor Ratings Fixed 135F°/Rate-of-rise 15° (721UT, 741UT)
Maximum wind velocity 300ft/min
Environmental
Field wiring size 12-24AWG
Remote test input (721UT) 100ohm max
Reset voltage 2.5V max
Reset time 1 second max
UL two-wire compatibility identifier S10A (711U, 711UT, 721UT), S11A (731U), S00 (all bases)
Physical
Color White head and base
Detector head dimensions 4” D x 1.75” H (10cm x 4.44cm)
Detector packaging 10 detectors per carton
Total height (head and base): 1.98” H (5cm)
Regulation
Listing UL 268, FM, CSFM, MEA approved
Head ships with terminal base:
TS7-2
TS7-2T
701U 3*
TS7-2R
TS7-4
702U 6
TS7-4T
*Note: 702 Series bases come with 6 terminals
and 701 Series bases come with 3 terminals.
Ordering Information
Model Description (wall mount)
TS7-2
TS7-2T
TS7-2R
TS7-4
TS7-4T
Accessories
204-12/24V 12/24V, end of line power supervision relay for 4-wire applications, UL listed
211-10PKG Replacement optical block cover for all photoelecric models (package of 10)
706U2A Remote visible alarm indication, with test only, for use with TS7-2R
706U3A Remote visible alarm indication, with test and reset, for use with TS7-2R
SM-200 Smoke! in a Can® (aerosol spray) for functional testing of smoke detectors
Note 1: Go to the www.gesecurity.com resource library for a complete compatibility index.
Conventional photoelectric smoke detector, 2-wire, 6” 3-terminal
base, 12/24VDC
Conventional photoelectric smoke detector, 2-wire, fixed/rate-of-rise
heat, remote alarm/trouble LED, 6” 6-terminal base, 12/24VDC
Conventional photoelectric smoke detector, 2-wire, form C aux. relay, 6”
6-terminal base, 12/24VDC
Conventional photoelectric smoke detector, 4-wire, 6” 6-terminal
base, 12/24VDC
Conventional photoelectric smoke detector, 4-wire, fixed/rate-of-rise
heat, 6” 6-terminal base, 12/24VDC
Compatibility
Listing
S10A
S10A
S11A
See note 1
below