GE Security GuardSwitch Series 100 171 Installation Guide

Warning! To avoid switch failure determine the actual load of the switch circuit and
take steps to protect the switch from voltage spikes, current inrush and line/load capacitance using the following recommendations.
• Surges from coils, motors, contactors, solenoids and tungsten filaments. Transient protection, such as back-to-back zener diodes (Transorb) or an RC network, is recommended for such loads to ensure that maximum ratings of the switch are not exceeded.
Voltage drop = I • R
2
Watts = I
• R
( I = maximum continuous current of the load)
To verify switch operation with an ohmmeter:
Set range at 20 mega ohms (switches with triac output, set ohm range at 20 kilo ohms). For a normally open switch, the meter will read a high impedance with the actuator away. It will read very high to infinity range (triac switches will read high kilo ohm to infinity range) with the actuator within sense range. You will see the opposite reading for a normally closed switch.
Dimensions
0.83''
2.11cm
2.03''
5.16cm
Figure 1
0.24''
0.61cm
0.42''
1.07cm
0.64''
1.63cm
0.64''
1.63cm
Actuator
Switch
0.24''
0.61cm
5.92cm
2.33''
5.75''
14.61cm
5.27''
13.39cm
0.56cm
5.75''
14.61cm
5.26''
13.36cm
1.10''
2.79cm
sensing face
sensing face
conduit
0.22''
dia.
0.28''
0.71cm
1.51''
3.84cm
1.49''
3.78cm
1.12''
2.84cm
GuardSwitch™ Series 100
Non-Contact Interlock/Position Switch
171-3Z
171
171-6Z 171-7Z
Installation
Use non-removable screws, bolts, or nuts to mount the switch and actuator. Do not over-torque mounting hardware.
1. Using the following guidelines, determine a suitable mounting location:
• The switch and actuator must be within the listed sense range. See Ordering/ Electrical Specifications.
• The actuator must be aligned with the switch—labels facing the same direction. (See Figure 1.)
Important: When mounting in proximity to ferrous material (steel), the sense range can be reduced 50% minimum depending on the shape and type of material. Test the switch in specific applications to determine the actual sense range.
•When mounting on a ferrous material (steel), a 1/4" nonferrous (plastic or aluminum) spacer may be used under the actuator and switch to restore most of the lost gap.
•When mounting on a hinged gate or door, mount the switch and actuator at least 6" away from the hinges to achieve the maximum movement.
• The switch and actuator must move in one of the approved directions. See Figure 2.
• The actuator can be mounted at a 90° rotation to the switch.
•Do not mount for parallel actuation. An on-off-on signal may result when the actuator passes by the switch.
2. Mount the switch on the stationary frame of the machine and connect the electrical wiring. When mounting the switch on an ungrounded machine, connect the ground lead to one of the mounting screws.
3. Mount the actuator on the movable guard, door, or gate.
171-8Z 171-M10 171-_________
Mounting Configurations
Figure 2
Perpendicular
Actuation
Best Best
Three configurations are appropriate for interlock applications. The parallel actuation can result in on/off/on signal if the actuator passes by the switch rather than coming to rest in proximity to it. This is NOT a recommended configuration for interlock applications.
Door
Actuation
Pivot Actuation
Good
Parallel Actuation
Not Recommended
General Specifications
Enclosure UL Explosion proof, Die Cast Aluminum
Class I, Group B, C
Class II, Group E, F, G
Class III, Divisions 1 & 2
Temperature Range -40°F to 180°F (-40°C to 80°C)
Environmental Hermetically Sealed Contact Switch
Sealed in Polyurethane
NEMA Rating 1, 2, 5
Protection Class IP 64
Response Time 1 msec; 10msec (150VA)
Life Cycles 100,000 Under Full Load;
Up to 200,000,000 Under Dry Circuit
Lead Type for 171-M10/O.D. 16/6 Fly lead THHN Blue / 0.11" (0.28 cm) each O.D.
Conduit Connection 1/2" Threaded NPT
UL Enclosure Only
Wiring Table for 171-M10
Wire Circuit
#1 & #2 1
#3 & #4 2
#5 & #6 3
Ordering/Electrical Specifications
PART NUMBER CONTACT1LOAD RATING SWITCHING VOLTAGE SWITCHING CURRENT CONTACT SENSE RANGE2BREAK RANGE TERMINAL
171-3Z N.C. 100VA/84W 120V@0.8A 28V@3.0A
171-6Z N.O. 25VA/25W 120V@0.2A 120V@0.2A 0.7A@35V 1.0 A@25V 0.2 Ohms 1.5"(3.8cm) 2.4"(6.1cm) #6 Screw
171-7Z N.O. 100VA/84W 120V@0.8A 28V@3.0A
5
171-8Z
171-M10 TPST; 3 N.O. 100VA/84W 120V@0.8A 28V@3.0A
171-Z Actuator Only Included with all switches unless otherwise noted.
Warning— Each electrical rating is an individual maximum and cannot be exceeded!
1
Configuration with actuator away from the switch
2
Proximity of ferrous materials usually reduces sense range — typically by 50%. The shape and type of material cause a wide diversity of effects. Testing is required to determine actual sense range for specific applications.
3
Rated at 3.0A for 6,000 cycles only. Other ratings are at 100,000 cycles.
4
Can withstand inrush surge up to 4 amps. Voltage Drop 1.5V, minimum switch current 30mA.
5
Maximum 10 switches in series.
CONFIG. AC/DC MAXIMUM, AC/DC MAXIMUM, AC/DC RESISTANCE NOMINAL NOMINAL TYPE
3
3.0A3@34V 3.0A3@28V 0.2 Ohms 1.2"(3.0cm) 1.5"(3.8cm) #6 Screw
3
3.0A 3@34V 3.0A3@28V 0.2 Ohms 1.2"(3.0cm) 1.5"(3.8cm) #6 Screw
triac
N.O./ 150VA/NA 120V@1.25A NA 1.25A@120V4NA NA 1.5"(3.8cm) 1.7"(4.3cm) #6 Screw
output
3
3.0A 3@34V 3.0A3@28V 0.2 Ohms 1.2"(3.0cm) 1.8"(4.6cm) NA
GE Security
Industrial