GE Security GuardSwitch Series 100 126 Installation Guide

Warning! To avoid switch failure determine the actual load of the switch circuit and
take steps to protect the switch from voltage spikes, current inrush and line/load capacitance using the following recommendations.
• Surges from coils, motors, contactors, solenoids and tungsten filaments. Transient protection, such as back-to-back zener diodes (Transorb) or an RC network, is recommended for such loads to ensure that maximum ratings of the switch are not exceeded.
• Line capacitance and load capacitance. An in-line resistor can be added in series immediately before the load to limit the inrush current. The resistor can only be added in series with the last wire just before the load. The voltage drop and the power rating of the resistor must also be calculated as follows:
Voltage drop = I • R
2
Watts = I
• R
( I = maximum continuous current of the load)
To verify switch operation with an ohmmeter:
Set range at 20 mega ohms (switches with triac output, set ohm range at 20 kilo ohms). For a normally open switch, the meter will read a high impedance with the actuator away. It will read very high to infinity range (triac switches will read high kilo ohm to infinity range) with the actuator within sense range. You will see the opposite reading for a normally closed switch.
Dimensions
Figure 1
Figure 2
1.20"
3.05cm
1.20"
3.05cm
0.05"
0.13cm
0.05"
0.13cm
2.84cm
Switch
1.12"
1.76"
4.47cm
1.51"
3.84cm
0.50"
1.27cm
sensing faces
B
A
0.99"
2.51cm
Actuator
C
0.99"
2.51cm
0.63"
1.6cm
0.75"
1.91cm
0.38"
0.97cm
GuardSwitch™ Series 100
Magnetic Door Position Switch
126-EY-01AX
126
126*-EY-03AX 126*-EY-06AX 126-EY-06X 126-3Y-01AX 126-4Y-01AX
Installation
The Model 126 is designed for use with tungsten filament bulbs of 150-watt rating or less at 120 volts.
• The switch and actuator must be within the listed sense range. See Ordering/ Electrical Specifications.
• The actuator must be aligned with the switch—labels facing the same direction. (See Figure 1.)
Important: When mounting in proximity to ferrous material (steel), the sense range can be reduced 50% minimum depending on the shape and type of material. Test the switch in specific applications to determine the actual sense range.
2. Determine location of switch on door jamb. To ensure proper operation and that the magnetic field not interfere with switching, do not locate closer than six inches from hinge side of door.
3. Locate switch (B) and magnet (A) locations on door jamb and door. (See Figure 2.) Drill a one-inch hole to accomodate these. (Do not hammer. This can damage the switch.) Misalignment of up to 1/2-inch can be tolerated, but not in a ferrous metal door. (To check if a door or jamb is ferrous hold a magnet to it. If it is attracted it is ferrous.)
4. Connect the black line conductor, see Figure 3, to the fuse and fuse holder that are provided. Connect the white neutral conductor to the load. Connect the flexible conduit to a NEMA Type I enclosure, see Figure 2.C, using a properly sized and acceptable 3/8 inch flexible conduit connector. If the switch is being used in a branch circuit, connect to a UL listed relay with minimum rating of 120VAC/15A.
5. The switch and actuator must move in one of the approved directions. See Figure 4.
126-7Y-01AX 126-8Y-01AX 126-8Y-06X 126-8Y-03AX 126-EY-03AX 126-__________
Note: Before making electrical connections be sure that power is off. Electrical
connections are black to line and white to load (bulb).
Figure 3
White
126 Switch
Black
Fuse & Holder
Customer Load
1
2
4
2 1
Relay SPST
Min 120VAC/15A
Neutral (White)
Line (Black)
3
UL rated relay recommended when used in a
branch circuit
Figure 4 Barrel Switch Mounting Configurations
End-to-End Side-by-Side
Perpendicular
“T”
General Specifications
Enclosure ABS Plastic with Protective PVC
Switch Sleeve
Temperature Range -40°F to 122°F (-40°C to 50°C)
NEMA Rating 1, 2, 3, 4, 4X, 5, 6, 12
Protection Class IP 67
Response Time 10 msec
Life Cycles 100,000 Under Full Load;
Up to 200,000,000 Under Dry Circuit
Lead Types/O.D. 12 AWG (AX)/0.13" (0.33cm)
Flex Conduit (X)/0.58" (1.5cm)
UL/CSA Certified All Models
OK OK NO
OK
Three configurations are appropriate for recessed interlock applications. Moving the actuator parallel to the switch can result in on/off/on signal if the actuator passes by
File E115761 LR89176 New York Calendar #40018
the switch rather than coming to rest in proximity to it. This is NOT a recommended configuration for interlock/position applications. "T" configuration results in non-actuation.
Ordering/Electrical Specifications
PART NUMBER CONTACT
1
LOAD RATING SWITCHING VOLTAGE SWITCHING CURRENT SENSE RANGE
CONFIG. AC/DC MAXIMUM, AC/DC MAXIMUM, AC/DC NOMINAL NOMINAL NOMINAL
126-EY-01AX
126*-EY-03AX
126*-EY-06AX
126-EY-06X
4
4
4
4
triac
N.C./ 150VA/NA 120V@1.25A NA 1.25A3@120V NA 1.0"(2.5cm) 1.5"(3.8cm) 1'(0.3m)
output triac
N.C./ 150VA/NA 120V@1.25A NA 1.25A3@120V NA 1.0"(2.5cm) 1.5"(3.8cm) 3'(0.9m)
output triac
N.C./ 150VA/NA 120V@1.25A NA 1.25A3@120V NA 1.0"(2.5cm) 1.5"(3.8cm) 6'(1.8m)
output
triac
N.C./ 150VA/NA 120V@1.25A NA 1.25A3@120V NA 1.0"(2.5cm) 1.5"(3.8cm) 6'(1.8m)
output
126-3Y-01AX N.C. 100VA/84W 120V@0.8A 28V@3.0A 3.0A@34V 3.0A@28V 0.5"(1.3cm) 1.0"(2.5cm) 1'(0.3m)
126-4Y-01AX SPDT 100VA/84W 120V@0.8A 28V@3.0A 3.0A@34V 3.0A@28V 0.5"(1.3cm) 1.0"(2.5cm) 1'(0.3m)
126-7Y-01AX N.0. 100VA/84W 120V@0.8A 28V@3.0A 3.0A@34V 3.0A@28V 0.5"(1.3cm) 1.0"(2.5cm) 1'(0.3m)
126-8Y-01AX
126-8Y-06X
126-8Y-03AX
126*-EY-03AX
4
4
4
4
triac
N.C./ 150VA/NA 120V@1.25A NA 1.25A3120V NA 0.5"(1.3cm) 1.0"(2.5cm) 1'(0.3m)
output triac
N.O./ 150VA/NA 120V@1.25A NA 1.25A3120V NA 1.0"(2.5cm) 1.5"(3.8cm) 6'(1.8m)
output
triac
N.O./ 150VA/NA 120V@1.25A NA 1.25A3120V NA 1.0"(2.5cm) 1.5"(3.8cm) 3'(0.9m)
output triac
N.C./ 150VA/NA 120V@1.25A NA 1.25A3120V NA 1.0"(2.5cm) 1.5"(3.8cm) 3'(0.9m)
output
126-Y Actuator Only Included with all switches unless otherwise noted.
Warning— Each electrical rating is an individual maximum and cannot be exceeded!
1
Configuration with actuator away from the switch
2
Proximity of ferrous materials usually reduces sense range — typically by 50%. The shape and type of material cause a wide diversity of effects. Testing is required to determine actual sense range for specific applications.
3
Can withstand inrush surge up to 4 Amps. Voltage Drop 1.5V. Minimum switch current 30mA.
4
Maximum 25 switches in series.
2
BREAK RANGE LEAD LENGTH
GE Security
Industrial
©2004 GE Security Industrial. GE Security Industrial reserves the right to change specifications without notice. I-3885-0404 11317 Rev E