GE Security GuardSwitch Series 100 114 Installation Guide

Warning! To avoid switch failure determine the actual load of the switch circuit and
take steps to protect the switch from voltage spikes, current inrush and line/load capacitance using the following recommendations.
• Surges from coils, motors, contactors, solenoids and tungsten filaments. Transient protection, such as back-to-back zener diodes (Transorb) or an RC network, is recommended for such loads toensure that maximum ratings of the switch are not exceeded.
• Line capacitance and load capacitance. An in-line resistor can be added in series immediately before the load to limit the inrush current. The resistor can only be added in series with the last wire just before the load. The voltage drop and the power rating of the resistor must also be calculated as follows:
Voltage drop = I • R
2
Watts = I ( I = maximum continuous current of the load)
To verify switch operation with an ohmmeter:
Set range at 20 mega ohms (switches with triac output, set ohm range at 20 kilo ohms). For a normally open switch, the meter will read a high impedance with the actuator away. It will read very high to infinity range (triac switches will read high kilo ohm to infinity range) with the actuator within sense range. You will see the opposite reading for a normally closed switch.
• R
GuardSwitch™ Series 100
Non-Contact Interlock/Position Switch
114
114-1N-08(J) 114-3Y-12(K) 114-4Y-06(K) 114-6N-06(K) 114-6Y-06(K)(J) 114-6Y-12(K) 114-7Y-06(K)
114-7Y-12(K) 114-8Y-06(K) 114-8Y-06(K)-SER25 114-8Y-12(K) 114-17N-06(V) 114-__________
Dimensions
0.41"
1.04cm
0.31"
0. 63"
0.79cm
1. 60cm
0.22"
0.56cm
0.75"
1.91cm
0.19"
0.48cm
Switch
Actuator
sensing face
sensing face
2.54"
6.45cm
1.73"
4.39cm
2.11"
5.36cm
Figure 1
0.18"
0.46cm dia.
Installation
Use non-removable screws, bolts, or nuts to mount the switch and actuator. Do not over-torque mounting hardware.
1. Using the following guidelines, determine a suitable mounting location:
• The switch and actuator must be within the listed sense range. See Ordering/ Electrical Specifications.
• The actuator must be aligned with the switch—labels facing the same direction. (See Figure 1.)
Important: When mounting in proximity to ferrous material (steel), the sense range can be reduced 50% minimum depending on the shape and type of material. Test the switch in specific applications to determine the actual sense range.
•When mounting on a ferrous material (steel), a 1/4" nonferrous (plastic or aluminum) spacer may be used under the actuator and switch to restore most of the lost gap.
•When mounting on a hinged gate or door, mount the switch and actuator at least 6" away from the hinges to achieve the maximum movement.
• The switch and actuator must move in one of the approved directions. See Figure 2.
• The actuator can be mounted at a 90° rotation to the switch.
•Do not mount for parallel actuation. An on-off-on signal may result when the actuator passes by the switch.
2. Mount the switch on the stationary frame of the machine and connect the electrical wiring. When mounting the switch on an ungrounded machine, connect the ground lead to one of the mounting screws.
3. Mount the actuator on the movable guard, door, or gate.
The interlock switch and actuator magnet should be mounted in only three configurations for actuation:
Figure 2
Perpendicular
Actuation
Best Best
Door
Actuation
Pivot Actuation
Good
Parallel Actuation
Not Recommended
Three configurations are appropriate for interlock applications. The parallel actuation can result in on/off/on signal if the actuator passes by the switch rather than coming to rest in proximity to it. This is NOT a recommended configuration for interlock applications.
Wire Color Code
Black COM
White N.O.
Red N.C.
File E 122942
LR89176
General Specifications
Enclosure ABS Plastic
Temperature Range -40°F to 180°F (-40°C to 80°C)
Environmental Hermetically Sealed Contact Switch
Sealed in Polyurethane
NEMA Rating 1, 2, 3, 4, 4X, 5, 6, 12
Protection Class IP 67
Response Time 1 msec, 10 msec (150VA)
Life Cycles 100,000 Under Full Load;
Up to 200,000,000 Under Dry Circuit
Lead Types/O.D. 18/2 SJTOW (K)/0.30" (0.76cm)
18/3 SJTOW (K)/0.33" (0.84cm)
18/2 or 18/3 Jacketed (J)/O.24" (0.62cm)
18-2 Flying Lead (V) AWG/0.05" (0.13cm)
22/2 Jacketed (J)/0.16" (0.41cm)
UL/CSA All Models
Ordering/Electrical Specifications
PART NUMBER CONTACT
114-1N-08(J) N.O. 15VA/15W 120V@0.11A 120V@0.11A 0.5A@30V 0.5A@30V Switch Only Switch Only 8'(2.4m)
114-3Y-12(K) N.C. 100VA/84W 120V@0.8A 28V@3.0A33.0A3@34V 3.0A3@28V 1.0 Ohms 0.7"(1.8cm) 1.2"(3.0cm) 12'(3.6m)
114-4Y-06(K) SPDT 100VA/84W 120V@0.8A 28V@3.0A
114-6N-06(K) N.O. 25VA/25W 120V@0.2A 120V@0.2A 0.7A@35V 1.0A@25V 1.0 Ohms Switch Only Switch Only 6"(1.8m)
114-6Y-06(K)(J) N.O. 25VA/25W 120V@0.2A 120V@0.2A 0.7A@35V 1.0A@25V 0.2 Ohms 1.0" (2.5cm) 2.0"(5.1cm) 6'(1.8m)
114-6Y-12(K) N.O. 25VA/25W 120V@0.2A 120V@0.2A 0.7A@35V 1.0A@25V 0.2 Ohms 1.0"(2.5cm) 2.0"(5.1cm) 12'(3.6m)
114-7Y-06(K) N.O. 100VA/84W 120V@0.8A 28V@3.0A33.0A3@34V 3.0A3@28V 1.0 Ohms 0.7"(1.8cm) 1.2"(3.0cm) 6'(1.8m)
114-7Y-12(K) N.O. 100VA/84W 120V@0.8A 28V@3.0A33.0A3@34V 3.0A3@28V 1.0 Ohms 0.7"(1.8cm) 1.2"(3.0cm) 12'(3.6m)
114-8Y-06(K)
114-8Y-12(K)
5
5
114-8Y-06(K)-SER255N.O./ 150VA/NA 120V@1.25A NA 1.25A@120V4NA NA 1.0"(2.5cm) 1.5"(3.8cm) 6'(1.8m)
114-17N-06(V) N.O. 100VA/100W 250V@0.4A 250V@0.4A 250V@0.4A 3.0A@35V Switch Only Switch Only 6'(1.8m)
114-Y Actuator Only Included with all switches unless otherwise noted.
Warning— Each electrical rating is an individual maximum and cannot be exceeded!
1
Configuration with actuator away from the switch
2
Proximity of ferrous materials usually reduces sense range — typically by 50%. The shape and type of material cause a wide diversity of effects. Testing is required to determine actual sense range for specific applications.
3
Rated at 3.0A for 6,000 cycles only. Other ratings are at 100,000 cycles.
4
Can withstand inrush surge up to 4 amps. Voltage Drop 1.5V. Minimum switch current 30mA.
5
Maximum 10 switches in series; SER25 – Maximum 25 switches in series.
1
LOAD RATING SWITCHING VOLTAGE SWITCHING CURRENT CONTACT SENSE RANGE2BREAK RANGE LEAD LENGTH
CONFIG. AC/DC MAXIMUM, AC/DC MAXIMUM, AC/DC RESISTANCE NOMINAL NOMINAL NOMINAL
3
3.0A3@34V 3.0A3@28V 1.0 Ohms 0.7"(1.8cm) 1.2"(3.0cm) 6'(1.8m)
triac
N.O./ 150VA/NA 120V@1.25A NA 1.25A@120V4NA NA 1.0"(2.5cm) 1.5"(3.8cm) 6'(1.8m)
output triac
N.O./ 150VA/NA 120V@1.25A NA 1.25A@120V4NA NA 1.0"(2.5cm) 1.5"(3.8cm) 12'(3.6m)
output triac output
GE Security
Industrial
©2004 GE Security Industrial. GE Security Industrial reserves the right to change specifications without notice. I-3900-0404 12520 Rev C