GE Security AP633A Installation

AP633A Passive Infrared Detector Installation Instructions

Description

The AP633A offers the detection of motion for infrared targets in selectable ranges extending 40 feet (12.2m), 80 feet (24.4m), and 200 feet (61.0m). The viewing angle selection allows the installer to select and delete any portion of the coverage pattern to customize the optical performance of the unit. The mounting plate of the unit is equipped with precise adjustment screws to allow the installer to alter the horizontal viewing point as much as 2 degrees to the left or right, up or down. Features include:
Step focus curtain
• Calibrated sensitivity
Coverage up to 200-foot (61.0m) max.
12 different protection patterns
Precision step focus mirror optics
Form C contacts

Mounting tips

Do not mount the unit outdoors.
Do not block the viewing angle of the unit.
Mount the unit so that would-be intruders cross the pattern of detection at a 90 degree angle.
Seal all openings and wire entries.
When mounting the unit on masonry surfaces, use an appropriate moisture barrier.
Use of the vertical screw adjustment may reduce the unit’s range.
Avoid these sources of disturbance:
Sunlight or vehicle headlights shining directly onto the unit.
Heat sources or mobiles in the field of view.
Strong air drafts blowing onto the unit.
Animals in the field of view.
Insects in the housing or on the face of the unit.
Rapid temperature changes in the field of view.
Very strong sources of RF energy and induction of electrical noise.

Installing the unit

1. Loosen the screw at the bottom of the unit; then remove the front housing (Figure 1 below).
Caution: You must be free of static electricity before handling
sensor circuit boards. Touch a grounded, bare metal surface before touching circuit boards or wear a grounding strap.
Figure 1: AP633A
2. Pull down on the plastic locking tab at the base of the circuit board to remove the mirror/circuit board assembly. See Figure 2 on page 2.
Remove the appropriate wiring knockouts and pull the
3. cable through the entries. See Figure 3 on page 2.
Level the backplate to the wall leaving a 1/2 inch
4. clearance space above the unit. For flat-wall mounting, use the four mounting holes. For corner mounting applications remove the mounting knockouts located in each corner. See Figure 3 on page 2. Insert 8-32 x 2 inch
ws. Tighten until secure, but be careful not to over-
scre tighten the backplate as you may need to adjust the viewing angle after walk testing.
5. Replace the mirror/circuit board assembly then make wire connections. See Figure 4 on page 2.
P/N 1036522 • REV C • 19JUN12 1
6. Set the sensitivity and test the zone locations. See Figure 5 below, “Setting the sensitivity” on page 3, and “Testing zone locations” on page 3.
Replace the front housing and tighten the screw located at
7. the unit base.
8. Conduct a final walktest by walking across the unit’s field of view - but not directly at the unit.
Figure 4: Terminals
1 2 3 4 5 6 7 8
NEG +12V
33ohm
Alarm
Tamper
Spare
Figure 2: Locking tab
Locking tab
Figure 3: Mounting and wiring
Surface Mount Wire Knockouts
Corner Mounting Knockout
Mounting Holes
Terminal AP633A
#1 (-) Negative
#2 (+) Positive
#3 Closed Loop Contact
#4 Common
#5 Open Loop Contact
#6 Tamper Closed Loop
#7 Tamper Closed Loop
#8 Spare (not used)

Aiming the unit

Corner Mounting Knockout
To ensure proper coverage, make subtle pattern adjustments using the three adjustment screws located inside the unit (see Figure 5 below):
The top screw adjusts the unit’s coverage pattern up or
• down.
The bottom two screws adjust the coverage pattern to the right or left.
Figure 5: Adjustments and jumpers
Primary Wire Entry Knockout
Wire Routing Knockouts
Optional Swivel Bracket Mount
Corner Mounting Knockout
Mounting Holes
Wire Routing Knockouts
Corner Mounting Knockout
Viewing Angle Adjustment
Jumper A (Sensitivity)
Jumper B (Test)
Terminals
A
B
C
2
Viewing Angle Adjustment
Jumper D (LED)
8
1046
Tamper

Setting the sensitivity

Select the sensitivity setting that best meets the needs of a given application by changing Jumper A (see Figure 5 on
2 AP633A Passive Infrared Detector Installation Instructions
Loading...
+ 2 hidden pages