gerkros Attack NST, Attack NSK Instructions For Use Manual

2
Puttingtheboilerintooperation
:
ATTACKNST,NSK-WALLGASBOILER
Theboilermustbeputintooperationbyaserviceworkertrainedbyproducer!
TheboilerissetbytheproducertonaturalgasG20,inletgaspressure2,0kPa.
Beforeinstallationandputtingtheboilerintooperationitisnecessarytoget acquaintedwiththeinstructionforuse.
TheNSKboilerisequippedwithawaste-gasthermostat(B11Bs)
Beforefirstputtingintooperationitisnecessarytotakefollowingsteps:
Checkwhethertheheatingsystemisfilledwithwaterandtheboilerisdeareatedproperly.
1.
Makesureifallthevalvesareopen.
2.
Openthegasvalvenexttotheboilerandtestthesealingofthegaspipingintheboiler
3.
Procedureofthefirstboilerburning:
Plugthefeedingflexintothe230V/50Hzsocket.
1.
Testthesocketwithanotherappliance.Themainswitchoftheboilermustbeintheoff position. Thebuttonforsettingtheheatingtemperatureandaroomthermostat(if
2.
settomaximum. Putthemodeswitchtotheposition.
3.winter
Checktheproperoperationofallthethermostatsandcontrolelements
4.
5.Settheboileroutputbytherequestofheatedplace.
connected)
ATTACKs.r.o.
Vrútky
2
Contents:
3Introduction 3Generaldescription 4Purposeofuse 4Conditionsofinstallation 5Conditionsofservice 5Technicaldescription 6Controlfrontboardoftheboiler 7Outsidedimensionsoftheboiler 8ThemainpartsoftheNSTboiler 9ThemainpartsoftheNSKboiler 10Connectingtheboilertowater,gas,electricity 10Supervisionoveroperation 11Waste-gasexhaust 11Spareparts 11Guarantee,reclamation 12Service 12Maintenance 12Wrapping,transport,storing 12Accessories,documentation
13Technicalparameters
14Installation,positioningandhangingoftheboiler 15Connectingtheboilertotheheatingsystem,tothehotwaterpipeline,gas
pipe-lineandpowernet 17Integratedsystemofboilercontrol 18Operation,hot-watermode,heatingmode,handlingthepumpand
circulation,antiblockingcapacityofthepump 19Anti-freezingcapacity,handlingtheventilatorandcontroloftheair
circulation,servicetestingfunctions,signallingofoperationalconditions 20Bertelliautomaticsfunctions 21Technicaldata 22Resistanceandtemperaturedependencechart
23Ignitionandionizationunit 24Technicaldataofignitionandionizationunit 25Defectsofignitionunit 26ThechartofNSTconnecting 27ThechartofNSKconnecting,pumpcharacteristics 28Settingminimumandmaximumoutput
29Notes 30Recordonputtingtheboilerintooperationandobligatoryserviceinspections
Introduction
Dearcustomer,
ThankyouforconfidenceexpressedbypurchasingourproductwallgasboilerATTACK withsmoothelectronicoutputregulation.Wewishyoulongandreliableoperation, thereforeyouneedtoreadthisinstructionforusecarefully.Themanualiswritteninthe waytorespecttherightoperationoftheboilerincentralheating. Theconditionsofrightoperationoftheboiler:
-choosetherighttypeandoutputoftheboiler
-impeccableputtingintooperation
-sensibleoperation
-regulartechnicalmaintenance
-reliableservice
Generaldescription
Thelatestproducedrangeofwallgasboilersisdesignedasanappliancewithmaximum effectivityandminimumemissionsintoatmosphere,savingenvironmentconsiderably.The outputisregulatedsmoothly,controlledbymicroprocessorinboththemodes(hotwater mode,heatingmode)inalltheoutputrangeofboilersandismodifiedtoabuildingby heatinglossandrequestforhotwater.Hightechnicallevelofboilersissupportedbyused topcomponentsfromworldproducers.
NOTICE:
Fortherightworkingoftheboileritisnecessarytokeepaminimumwaterpressureof1 bar(measuredwhenthewateriscold)intheheatedsystem.
DescriptionofATTACKNST,NSKboilersbrand:
Modulated boileroutput
8-24kWNST
Wallboiler
Withwaterheating
Turboversion
8-24kWNSK
Flueversion
Purposeofuse:
ThetyperangeofATTACKwallboilers(turboandflueversion)isproducedwith modulatedoutputof8-24kW.Theyareusedforheatingorcentralheatingoffamily houses,flats,shopsandsimilarplaceswherenaturalgasisusedasfuel.Theboilerisalso equippedwithadeviceforwaterheating. Astoinstallation,theboilerisbuilttooperatewithheatingwatertomaximumhydrostatic pressureof0,3Mpa(3bar)andoperatingtemperatureto85°Cwiththeconnectionto heatingsystemswithforcedflowofheatingwaterinaclosedsystem.Thewaterinthe heatingsystemmustsuittoSTN077401(itmustnotbesourinanycase,whichmeansthat thepH-valuemustbehigherthan7anditmusthaveminimumcarbonatehardness,max. 3,5mval/l).Fillingpressureincoldsystemisof11,5bar.Fillingmustbedoneslowlyto letairbubblesescapethroughproperdeareatingvalves.Foradjustingthewaterhardnessin theheatingsystemitisnecessarytouserecommendedagents.
therulesabove,thereisnoguaranteefordamagedcomponents.
Inthecaseofnotfollowing
Installationconditions:
Agasboilercanbeinstalledonlybyacompanyauthorizedtocarrythisworksonthebase ofapproveddocumentationofaprojectantwhilerespectingadviceandnotesinthis manual.Beforeinstallationtheinstallingcompanyisobligedtochecktherightchoiceof theboilertypewithregardtothefunctionalattributesandrequiredparametres.Theboiler hasacoveringofelectricpartsIP41thatisresistentagainstwaterdroppingvertically. Thereforeitcanbeinstalledinbathroomsinzone3(inthedistanceof60cmfromtheedge ofthebathorshowercorner).Theroomwheretheboilerislocatedmusthavethe temperatureintherangeof+5to+35°Cwithrelativehumidityto80%.
Itisnotallowedtoplacethingsclosetotheboiler,inthedistanceof:
-100mmthingsfromhardandmediuminflammablematerials
-200mmthingsfromeasy-inflammablematerials
Thefirstputtingintooperationandtrainingoftheboileroperatorsmustbedonebya contractservicepartneroftheproducerthatmakesregularmaintenanceaswellas guaranteeandpost-guaranteeserviceoftheboiler.Tothesupplygaspiping,ahandygas valvemustbeinstalledbeforetheboilerwhichmustbeapproachablebutisnotapartofthe boileraccessories.Connectingtheboilertotheheatingsystemisthroughscrewjoints G3/4“.HotwateraswellasgasinletisconnectedthroughscrewjointsG3/4“.Before installingtheboileritisnecessarytomakesurethatthechosenplacefitstorequirements forwastegasescapeandthatminimumdistancesbeforementionedarekept.Asthisboiler isfast-heating,equippedwithitsownpump,itispossibletoconnectitwithgravity circulationaswellastoanewsystemforforcedwatercircualtionintheheatingsystem.In thecaseofnewdistributionswerecommendtousesmall-volumeheatingbodiesand distributionsinthesmallestdimensionsbecauseoffastheatingofthesystemtothe temperatureaswellasbigflexibilityofthesystem.Connectingtheboilertotheheating systemandtothegasandhotwaterdistributionisnecessarytocarryoutsoasnottostrain
connectingoutletsoftheboiler.Beforeconnectingtheboilertotheheatingsystemitis necessarytoflushitthoroughlytoremovesmallimpuritiesandmud.
5
Theheatingsystemmustincludeaproperfilter.Toutilizethemaximumoutputofthe boileritisnecessarytoensureminimumpressureintheheatingsystemof1barforright functioningandlonglifetime.Abuiltinexpansiontankenablesconnectingtheboilerto closedheatingsystem.
magneticorelectromagneticwatertreatmentdevice.
gasof20mbarnominalpressureinthedistributionnet.Theboilerislocatedsoastoensure necessaryoperatingconditionswhetheritisanappliancewithopencombustionchamber (flue)orwithclosedcombustionchamber(turbo)andwithregardtothewaysof combustionairsupplyandwastegasexhaust.
Onhot-waterinlettotheboileritisnecessarytoinstalla
Theboileristooperateonnatural
Conditionsofservice:
Theserviceoftheboilermustbecarriedoutbytherulesdescribedinthismanual.Except serviceworks,theusermustnotcarryoutanyrepairsontheappliancenoradjustmentsor
dismountingandcleaningtheinsidepartsoftheboiler.Theboilercanbeoperatedonlyby anadult.Afterleavinghomeinwinter(onholiday...)asupervisionbyatrainedpersonis needed.Ifthereisadangerofapproachofinflammable(combustible)gasesorfumestothe boiler(e.g.whenlyingaPVCflooring),itmustbeputoutofactionearly.Theuseris obligedtotakecareofproperuseoftheboileraccordingtothisinstructionwhichisalsoa conditiontoacknowledgeguarantee.Whenputtingtheboilertooperation,theservice workermustinstructtheuseraboutboileroperating.
intheletterofguaranteeconfirmshavingbeeninstructedwiththeboileroperating.
Theuserwithhisorhersignature
Technicaldescription
Fast-heatingwallboilersATTACKNST,NSKareequippedwithcopperheat-exchangers protectedonsurfacewithsiliconecoatingonthebaseofaluminium,resistentto430°C. Theseareexchangerswithseparatedsystemstowarmuphotwaterandheatingwater.A bigadventageofthisexchangerisplaceandweightsaving.Maximumoperationpressure forheatingcircleis300kPa(3bar)by85°C,forhot-watercircle600kPa(6bar)by60°C. Minimumoperationpressureis100kPa(1bar).Theheat-exchangerislocatedintheupper partofcombustionchamberandisfittedwithanautomaticdeareatingvalve,whichleads overclosingchamber.Forminimumlosesduringheattransmissionitisnecessarytokeep thesurfaceofheat-exchangerlamellasclean. Thesourceofheatisagasburnerofmodernunit-builtdesignmadefromstainlesssteel.It islocatedinthebottompartofcombustionchamber.Therearetwoelectrodesintheburner. Oneofthemisasparkingitionelectrode,anotherisainonizationprobeforburning control.Combustionchamberismadefromaluminium-coatedsteelplatewithinside thermalinsulation.Overthecombustionchamber(NST)isawaste-gascollectorwithafan forwaste-gasdraw.Withthehelpofsiliconetubesisthefanconnectedtoaswitchof differentialpressure(manostat).Intheflueversion(NSK)thereisadrawbreakerwitha waste-gasthermostat.Intheupperpartoftheexchangertherearethermalprobesfor heatingandhot-watersystem.Theinsidewaterpipingintheboilerismadefromcopper pipes.Closingchamberoftheboiler(NST)ismadefromaluminium-coatedsteelplate. Openingsintheclosingchamberaresealedwithsiliconeseal.Onhotwaterinletthereisa water-passagesensorinstalled.Fast-heatingwallboilersATTACKNSTandNSKare equippedwithautomaticsandcontinuousregulationofoutput.
Thecontrolcentreforcontrollingboileroperationisamodulationelectronicboard equippedwithamicroprocessor.Sensorstateandvalueisscoredbysoftwarewhichalso givesorderstoactiveelementsgasvalve,ignitionelectronics,circulationpump.Onthe insidedistributionofheatingwateroutletthereisanemergencythermostat,pressureswitch andpressuregaugesignallingthepressureintheheatingpiping. Inthecasethetemperatureofoutgoingheatingwaterovercomes95°C,theemergency thermostatputstheboilerinemergencyconditionfollowingbyputtingitoutofoperation. Inthecasethepressureintheheatingsystemfallsunder1bar,thepressureswitchputsthe boileroutofoperation.Ininsidedistributionofheatingwaterinletthereisa3-bar-safety valveandacirculationpump.Inthebridgingofhotwaterinletandheatingwaterinlet thereisaballvalveservingforfillingtheheatingsystemfromthedistributionnet.Inthe rearpartoftheboilerthereisan8-literexpansiontankconnectedwiththepump.Outside caseistreatedwithdustpaintwiththermalenduranceupto180°C.
Controlfrontboardoftheboiler
Operation mode switch
Signallight Breakdown
Signallight On
Signallight Operation
Settingup heating
Hot-watermode
Thermometer
Settingsup hot-water temperature
Central-heatingandhot-watermode
Pressuregauge
Reset
O
Off
Service function
Thethermometerandpressuregaugetakethetemperatureandpressureintheheating system.Withabuttonforsettingtheheatingtemperature,ausercansetthetemperatureof waterintheheatingsystemintherangeof35-85°C.Therecommendedrangeis55­85°C.Withacontrolbuttonforsettinguphot-watertemperature,ausercansetrequested outlettemperatureofhotwaterintherangeof35-60°C.Signallightsignalsa
Breakdown
condition,whentheelectronicsdidnotmanagetoburntheboiler(e.g.becauseofgas deliveryfailure).Returntooperationconditioncanbemadebybriefturningtheoperation modeswitchintotherightextremeposition(reset)whencontrollingtheboileroperation. Thesignallightsignalsburningoftheboiler.Thesignallightservesto
OperationOn
signallingofstartingtheboilermode.Theoperationmodeswitchhasthesepositions: –theboileroff –summeroperation(hot-waterpreparationon,heatingoff) –winteroperation(hotwaterandheatingon) –unblockingtheboilerbreakdown(reset) –servicetestingfunction
Outsidedimensionsoftheboiler:
225NSK
183NST
Ventilator
Flue
700
60
140
355
50
110
D.H.W.
D.H.W.
445
290 380
Gas
C.H.
C.H.
MainpartsoftheNSTboiler:
.
Bar
3
MainpartsoftheNSKboiler
Bar
3
Connectingtheboilertowaterandgas:
D.H.W.inlet
1/2”
D,H.W.outlet
1/2”
Gasinlet
3/4”
C.H.outlet
3/4”
C.H.inlet
3/4”
Connectingtheboilertoelectricnet
Theboilerispluggedintotheelectricnetsocketwithasupplyleadwithaplug.Thesocket mustsuittoappropriatestandards,variousmultiplugsandlenghteningcablesarenot allowedtouse.Installationofthesocket,connectingthespacethermostatandserviceof electricpartsoftheboilercanbeonlyperformedbyapersonwithspecialelectric qualificationbythePublicNoticeNo.718/2002Z.z.Electricinstallationisreadyfor additionalconnectionofroomthermostat.
Operationcontrol
Duringtheoperationtheboilerissecuredagainstdangerousoperationconditions. However,thebreakdownsthecauseofwhichisnotincludedintheboilermechanism, cannotbeprotectedtoarise.Thereforeitisnecessaryafterputtingtheboilertooperationto examinetheboileronceinthreedaysandcheck: –whetherthesystemisfilledwithwaterandthereisnodischarge –whetherwastegasesorgascannotbesmelled
Foundbreakdownsmustbereportedtotheserviceworkerwhoputtheboilerto operation.Ifthereisagasdischarge,thegassupplymustbeclosed.Foundbreakdowns mustberemovedimmediately.
Service
Waste-gasexhaust
WASTE-GAS
BEND COLLAR
EXTERNALWALL
COAXIALPIPE
1000mm
MIN.150mm
VENTILATORMANOSTAT
Waste-gasexhaustandcombustionaircomethroughdoublepiping(turboversion)
deliveredbytheboilerproducerwhichcanbeorderedinrequiredamountbytheproject
(horizontalorverticalexhaust)includingsealingcollars,roofreducingpieceandsoon.
Conditionsofwaste-gasexhaustoutletthroughtheexternalwall:
–theoutletmustprotrude150mmminimallyfromtheexternalwallofabuilding
–minimumheightoverthegroundtoaspacepubliclyinapproachableis1m
–minimumheightoverthegroundtoaspacepubliclyapproachableis2m
–theoutletmustnotleadtoanexplosiveandinflammablespace
–ifintheupdirectiontherearesomeinflammablematerialsonthebuilding,itisnecessary
tokeepverticaldistanceof1,5mfromtheoutlet
Maximumlengthofdoublewaste-gasexhaustpermittedbytheproducer:
–horizontalpipingof3mmeasuredfromthebendontheboilertotheoutletonthefacade
–verticalpipingof2,7mmeasuredfromtheboilertothebottomedgeofaroofreducing
piece
–each90°bendinsertedshortensthelengthin0.75manda45°bendshortensitin0.5m
Spareparts
Theproducerkeepssinglepartsofboilersassparepartswhichareprovidedforguarantee
andpostguaranteeserviceonlytocontractpartnersonthebaseoforderorreclamation.
Guarantee,reclamation
Theexactreadingofguaranteeandguaranteeconditionsandhintsforreclamationare
includedintheletterofguarantee.Repairsintheguaranteetimeareperformedonlyby
contractservices.
Attention!
Torespecttheconditionsofguarantee,theproducerdoesnotpermitperforminganyrepairs
byacompanyotherthanacontractorserviceintheguaranteetime.
Service
Aftereachyearoftheoperationduringtheguaranteetimeitisnecessarytogettheboiler examinedandadjustedbyacontractcompany.Untilthisisnotperformed,theguarantee willnotbeadmitted.Evenafterfinishingtheguaranteetimetheproducerrecommendsany
interventionsaimingtorepairstobemadeonlybyacontractservicepartner.Theactivities oftheboileruserinthepostguaranteetimearedeterminedinthepart„Maintenance“.
Maintenance
Regularmaintenanceisimportantforreliableworkingoftheboiler,longlifetimeand combustioneffectivityoftheboiler.Theuserisrecommendedtocontactacontractservice organizationnearbyandensureregularannualexaminations(seeconditionsforguarantee). Aserviceworkercheckscontrolandsafetyelementsoftheboiler,gasandwater distributionsealingorcleanstheburnerandexchangerfromburntdustparticles.For faultlessoperationofheatingsystemitisnecessarytocheckregularlythepressureofwater inheatingsystem(min.1bar,measuredwhenthewateriscold).Inthecaseoflower pressureitisnecessarytorefillwaterintocoldheatingsystem.Theoutsidecoatofthe boilercanbecleanedwitharagsoakedinsoapywaterandthendriedwithadryone.
Wrapping,transport,storing
Boilersaretransportedinverticalposition.Topreventpossibledamage,theyareprotected byacartonwrapping.Thewrappingissecuredbyanadhesivetape.Theboilermustbe
storedinnon-aggressivespacewiththetemperatureof+5upto+50°Cinmaximum relativehumidityofairof75%,withoutpresenceoforganicsteams,gasesanddust.
Boileraccessoriesanddocumentation
ATTACKNST,NSKboilersaredeliveredcompletelyassembliedandtestedfunctionally. Thedeliveryincludesfollowingdocumentation: –instructionforusewithadocumentonboilertestingonthebacksideoftheinstruction –letterofguarantee,listofcontractpartners
Technicalparameters
Table
Max.min.outputofheating Max.min.outputofhotwater Gasconsumption-naturalgas
Effectivity Electricalsupply Controlofroomthermostat Min.max.pressureinheating Min.max.pressureofhotwater Expansiontankvolume Weight Passageofhotwaterheatedin25°C Passageofhotwaterheatedin35°C Outletheatingtemperatureregulation Outlethot-watertemperatureregulation Waste-gasexhaustingdiameter Forcedwaste-gasexhaustingdiameter Electricinput
Connectinggaspressure Electricstandard
Numberofnozzles NozzlediameterNST
NozzlediameterNSK Nox CO
Fuel
kW kW
3
m/hod
%
V/Hz
V
bar bar
l
kg l/min l/min
°C
°C
mm mm
W
mbar
-
pcs mm
mm ppm ppm
-
24-8 24-8
0,9-2,7
9092
230/50
24
0,8-3
1-6
8
40 13
9
30-85 30-60
130
100/60
130
20 IP41 13 1,15
1,25 20-50 7-14
Naturalgas
TECHNICALMANUALFOR
ASSEMBLYANDSERVICECOMPANIES
Installationofboilers
Aboilercanbeinstalledonlybyacompanywithanappropriatecertificateforassemblyof gasappliances.Connectingoftheboilermustalsosuittovalidstandards,rulesand
instructionforuse.
connecting.
Localizationofboilers
Localizationofboilersmustsuittoprojectdocumentation.Boilersaretobesituatedinthe waytoensurealltheoperationconditionsneededforanappliancewithopencombustion chamber(flue)aswellasforclosedcombustionchamber(turbo)withregardtothewayof combustionairsupplyandwastegasexhaust.Fromthesidesofboilerstheremustbefree accessofatleast0.2mandinfrontofboilersof1mforassemblyandservice.Boilers mustbeinstalledatleast0.1moverthefloor.Theflueversionhasanopencombustion chambersoittakesairforcombustiondirectlyfromtheroomwheretheboilerisplaced. Theroomcanbeventilatedthroughventilatingopeningsintosurroundingatmosphereor indirectlythroughneighbouringrooms.Theneighbouringroom,wheretheairissucked from,mustnotbeabedroomorapartofthehousewherethereisdangeroffiree.g.store ofinflammablematerialsoragarage.
Hangingboilersonthewall
Theproducerisnotresponsiblefordamagescausedbywrong
Mountingboilersonthewallmustbeperformedonthebaseofqualifiedassessmentofthe wallbearingcapacity(byaprojectworkerorassemblycompany)soastoguaranteesafe
andreliablehangingofboilers.Boilersarenecessarytomounttothewallwithasuitable connectingmaterial(e.g.screwsanddowels)regardingthequalityofthewall.
300
150150
580
50
Connectingboilerstoheatingsystem
ATTACKboilersserveforheatingsystemswithforcedcirculation.Rateofwaterflowcan besetbytheswitchonthepump.Beforefillingtheheatingsystemwithwater,itis necessarytocleanthesystemproperly.Heatersanddistributionmustbewashedseveral times.Forthoroughwashingandcleaningtheheatingsystemwerecommendtouse cleaningagents.Ontheinletfromheatingsystemandhotwatertoboilers,filtersmustbe mounted.Werecommendbrassfilterswithsidecleaning.Thefiltersmustbecleanedonce ayearminimally.Maintenanceoftheboileriseasierwhenontheinletaswellasonthe outletofheatingthereisavalve.Inthehot-watercircuit,thevalveisrecommendedto mountintheinlettotheboilerbeforethefilter.Filtersandballvalvesarenotdeliveredas boileraccessories.Cloggedfilterscancausehighernoisinessofboilers.Outletfromsafety valveisnecessarytoconnecttodischargepiping.
cloggingtheexchangerorpumpbyimpuritiesfromthesystem.
Thehardnessofwaterintheheatingsystemisnotrecommendedhigherthan3.5mval/l.In boilersthereisan8-litrepressureexpansiontankenablingconnectingtoaclosedheating system.Ifitisrequiredbythesizeoftheheatingsystem,itisnecessarytomountanother
pressureexpansiontank.Therecommendedtemperaturedifferencebetweenoutcomingand incomingheatingwaterfromaboileris15-20°C.Forreconstructionofheatingoranew systemwerecommendsmall-volumeheatersanddistributionsinthesmallestdimensions regardingtofastriseofthesystemtothetemperatureandquiteabigflexibilityofthe system.Processofwaterfilling:whenfillingwithwater,boilermustbedisconnectedfrom electricity,deareatingvalvesontheboilerandheatingsystemmustbeopen.Setthesystem tothepressureof1bar,thendeareateandsettothepressureagain(1.5barwhenitiscold).
Guaranteedoesnotapplytothecasesof
Connectingtowaterpiping
Maximumpermittedoverpressureofwaterfrompipingis6bar.Usersofboilersare remindedtopayhighattentiontothequalityofwaterusedtoheatingsystemandwater heating.Ontheinletofhotwatertoaboilertheremustbeamagneticorelectromagnetic watertreatmentdeviceinstalled.
Guaranteedoesnotapplytothecasesofincrustationoftheheatexchangerorpump.
Connectingboilerstogaspipeline
Beforeconnectingaboilertothegaspipeline,thepipelinemustbetestedandadjusted. Afterconnectingtoaboiler,allthegasconnectorsmustbetested,includingpipingand fittingsintheboiler.Boltedconnectionsofthegaspipelineaswellasthoseofthewater pipingandheatingwaterpipingmustnotbestressedbyanyadditionalforce.
Connectingaspatialthermostat(regulator)
Aspatialthermostatisnotapartofboileraccessoriesbutitcanbeconnectedintoaboiler bytherequestofacustomer.Voltageforswitchcontactsofthespatialthermostatis24V. Connectingofthespatialthermostatintotheboilerisillustratedontheconnectionchart.
Connectingterminalsforthethermostatare interconnectedbyajumper.Afterconnectingthespatialthermostattotheterminalsthe jumperistoberemoved.
Connectingtoaflue.NSKversion
ATTACKNSKboilersintheflueversionareconnectedtoafluewithanexhaustbranchof 130mmdiameter.Connectiontothefluemustbedonebytheappropriaterules.
Connectingofcoaxialpipe.NSTversion
Airinletforcombustionandfluegasexhaustiscarriedoutbypipeinpipeelbow90°and pipeinpipe1mlong.Additionalaccessories90°and45°albowsorpipes0,5and1mlong ispossibletopurchaseonrequest. coaxialwastegasexhaustis3mhorizontallyand2,7vertically,measuredfromtheboilerto theoutletonthefacadeortothebottomedgeoftheroofreducingpiece.Each90°bend shortensthelenghtin0.75manda45°bendin0.5m.Thewholepressurelossofthepiping mustnotbebiggerthan80Pa.Coaxialpipingmusthaveaslopeof3°fromtheboilerout.
Themaximumlenght,admittedbytheproducer,of
Puttingtheboilerintooperation
Puttingintooperation,checkingandsettingminimumandmaximumoutputoftheboileras wellastherepairscanbecarriedoutonlybyfirmsauthorizedtothisandtrainedbythe producer(listofthecontractservicepartnersisinthesupplement).
Dutiesofaserviceworkerwhenputtingtheboilerintooperation:
–checkwhethertheinstallationoftheboilerandaccessoriessuitstotheprojectandboiler
inspection.
–checkthedeaerationoftheboilerandheatingsystem(theboltontheautomaticdeaerator
mustbereleased) –checkthewaterpressureintheheatingsystem(minimumof11.5barinthecoldsystem) –checkifthesafetyvalveisworking –checktheconnectingtothegaspipelineaswellascontrolandsafetyelementsandtestthe
sealingofthegaspipelinefromthemainpipesealuptotheburnerintheboiler –checkelectricsocketconnectingandelectroinstallationinspection –checkthewastegasexhaust –checktheflueinspection –checktheminimumandmaximumoutputbymeasuringthepressureonburnernozzles –settheoutputoftheboilerbyathermallossoftheheatedplace
testtheregulationofheating
–checktheoperationofsummerandwintermode,regulationofhot-waterheating –setappropriatepumpspeedandpressureintheheatingsystem –testfunctionofballvalvesbeforetheboiler –getauseracquaintedwiththeboilerattendancewhichisconfirmedbytheuser´s
signatureintheletterofguarantee
–writedownputtingtheboilerintooperationtotheletterofguaranteeandinstructionsfor
use
IntegratedcontrolsystemofboileroftypeAM56IMS02code16562
Description: ControlautomaticsoftheAM56IMS02typeforhanginggasboilerswith instantaneouswaterheating,doubleheatexchangerandautomaticignition.
Controlfunctionsofautomaticsincludeignitionofflame,itscontrolandsmooth modulation.Automaticshastwofunctionalunits: –burnercontrolunit(ACCF) –flamecontrolandmodulationunit(CMF)
Generalproperties:
–signallingofworkingandbreakdownswiththehelpofLEDlightsontheboard –eliminationofdisturbingcausedbyignitionandcontactswitching –controlofacirculationpumpwitharun-outfunctionaftertherequestforheating –controlofaventilatorandairflowwitharun-outfunction
–earthingconnectorontheboard –2Afuseontheboard –connectingthephase,neutralconductorandearthingontheentrywiththehelpof
connectorontheboard –connectingthespatialthermostatwiththehelpofconnectorontheboard –connectingtheemergencythermostat –optionofoperationmodeandresetbyaswitchontheboard –stoppingtheburnerinthecaseofprimarythermalsensorfailure(breakdownorshort) –manualreset
Sectionofflamemodulation
–settingtheboilermodebyP1switchontheboard –settingstartingoutputwiththehelpofP5trimer –settingcentralheatingandhotwatertemperaturewithpotentiometersontheboard –controlofhotwatertemperaturewithathermalsensorontheoutlet –controlofheatingtemperaturewithathermalsensorontheoutlet –anti-fastcyclingfunctionintheheatingmodewhichcanbesetto180secondsor
cancelled(byinsertingajumper)withJP3ontheboard –settingtheburneroutputintheheatingmodewithP4trimerontheboard
Operation
Hot-watermode
Hot-watermodeisswitchedonbyaninformationfromthewaterpassagesensorwhenthe passageisbiggerthan3l/min.Afteropeninghotwater,thecirculationpumpoftheheating
circuitstops.Startingoutput(setupbyresistancetrimerP5)iskeptafterburningtheboilerin thetimeoftwoseconds.ThentheboileroutputiscontrolledbyPIDregulationbythe passageandtemperatureofhotwatertoreachthesettemperatureassoonaspossible.When thewaterpassagedropsunder2.5l/min,theoperationphaseofhotwatermodefinishes.If thesetuptemperatureintheheatingmodeisover55°Cbythepassageofhotwaterof3 l/min,thistemperaturewillbelimitedto50°Ctopreventincrustationintheheatexchanger. Iftheoutlettemperatureofhotwaterreaches70°C,theburnerisoff.Afterfinishingthe requestforhotwaterthepumpstartsworkingtolimitincrustation.Run-outtimeofthepump changesfrom0.4to2secondsdependingonthetemperatureintheheatingcircuitinthetime ofrequestforhotwater.Inthecaseofparallelrequeststhehotwatermodeispreferredto
heatingmode.IftheJ5jumperispositionedintheONposition,therun-outofthepumpat theendoftherequestforhotwaterisalways2seconds.
Heatingmode
Operationphaseintheheatingmodestartswhenaspatialthermostatputsarequestforheat andtheoperationswitch(P1potentiometerontheboard)isintheposition.Thepump andventilatorareactivatedandafterverifyingairflow,theburnercontrolunitisactivated. Startingoutputiskeptinthetimeoftwosecondsafterburningtheboiler.Thentheboiler outputiscontrolledbyPIDregulationuntilthesettemperatureforcentralheatingisreached. Inthecasethewaterovercomesthesetvaluein5°C,theburnerisoff.Theburnerisreignited bythetemperature5°Clowerthansetvalueuntiltheanti-fastcyclingtimeisover.Theanti­fastcyclingfunctionisoveruntilthecontactsoftheroomthermostatarebrokenand switched.WhentheJP4jumperissettoONposition,therangeoftemperaturesisloweredto valuessuitableforfloorheating.
Note:Alwaysmustbeusedanappliancelimitinghightemperature(toprotectfloorheating)
winter
Pumpcontrolandcirculation
Thepumpstartsinthemomentoftherequestforheatingorhotwater.Attheendofeach requestforheatingthepumpkeepsworkingfor180smore.Ifafterworkingtimetheboiler
signalsafailureinheatingmode,thepumpworksonallthetimeasarun-outintheheating mode.
Anti-blocking-pumpfunction
After24hoursofnotworkingthepumpisactivatedto150s.Afterbreakingelectrical supply,thefirstcycleofanti-blocking-pumpfunctionstartsafter3hoursofnotworking.
Anti-freezingfunction
Ifathermalsensoroftheheatingcirculationfindsadecreaseoftemperatureofunder6°C, thepumpisactivatedandburnerstartswithminimumoutput.Thislastsuntilthe25°C temperatureisreachedandthentheanti-freezingfunctionstopsworking.Thisfunctionis activeevenwhentheoperationswitchisinSUMMERpositionandinemergencymode (stand-by).Ifthereisafailureintheboiler,onlypumpisactivated.
Controlofventilator,airflowandwastegas(NSTversion)
Ifthereisarequestforignition,burningautomaticsatfirstteststheconditionofmanostat. Ifitisinastillposition,burningautomaticsswitchesthewastegasexhaustventilator.Ifthe ventilatorisoperatingandtheexhaustisclear,themanostatswitchesintoworkingposition andtheboilerisburned.Differencepressuremustbeover80Pa. Aftereachblowingouttheventilatorkeepsworking20secondsmore.
Thetypewithopencombustionchamber.(NSKversion)
Inthisversion,ifthereisarequestforheat,theburnercontrolunitisactivatedafter activatingthepumpandverifyingthewaterpassage.Inthecaseoffailure(rising temperaturebecauseofwrongwastegasexhaust)thewastegasthermostatbreakscontacts, theburnerblowsoutandafailureissignalled.Reignitionisnotpossiblefor30minutes. Thistimeperiodcanbecleared(reset)withtheoperationswitch.
Servicetestingfunctions
Ifthisfunctionischosen,theboilerstartsworkingintheheatingmodetothemaximum outputoftheburnerandmaximumtemperatureoftheheatingwater(80°C).Theburneris offafterreachingthemaximumswitch-offtemperature(85°C).Ifthereisarequestforhot water,thisfunctionisinterruptedandtherequestispostponed.Thisfunctioncanlast15 minutesmaximallyandthenitisnecessarytoswitchtheoperationswitchtosomeofother functionsandthenbacktothisfunction.
Signalling
RedLEDGreenLED1GreenLED2 BoileroffXOFFX BoilerinemergencymodeOFFONOFF Breakdown-ignitionmodeONONOFF Breakdown-overheating Parasiticflame,errorinACCFunitONLONONL NowaterpressureONONOFF Lackofair­WastegasthermostatopenONLAONONLA SensordamagedOFFONONL FlamepresenceOFFONON
ON=lightingX=alltheerrorsignallingspossible ONL=flickering
ONLA=flickeringalternately OFF=nolighting
1919
FunctionsoftheBERTELLIautomaticsinMAXIMUSRZT,RZKboilers
Ifthespatialthermostatisnotconnected,
Ifthespatialthermostatisconnected,
during180seconds.
thepumpkeepsworkingeveniftheboilerisoff.
thepumpisinoperationafterswitchingofftheboiler
BrokenSwitched
naturalgasLPG
JP1 JP3
anti-cyclingfunction-waitingfor180s betweenswitchingoffandon
heatingwaterbysetup
JP4
Run-outofthepumpfor0,4-2sbythe
JP5
temperatureofheatingwater
Anti-cyclingfunction
Timeofanti-cyclingbeginswhenthetempearuteofheatingwaterovercomesthe temperaturesetupbytheboilerorspatialthermostatin2-3°C.Beforethat,theouputhas
beenmodifiedtominimumbymicroprocessorandthengasinletwasstopped.Duringthis timetheboilerisoffandmustnotbeswitchedondespitetheheatingwaterhavingbeen cooled.Anti-cyclingtimeintherangeof0to180secondsissetupbyJP3jumper.Normal burningbeginswhentheanti-cyclingtimeisover.Thisfunctionpreventstheboilerworking inasmallcircuit(e.g.closedheatingvalves)toburnandturnout.Ifthereisarequestfor hotwaterduringthistime,theimmediateburningonstarts.Short-circuitingofJP3jumper causesdisablingofthisfunction.Theboilerthenreactswithoutstopping,burnson immediatelyafterdroppingthetemperatureofheatingwater(ifthespatialthermostatison).
switchedonimmediatelyafterdroppingthe heatingwatertemperatureundersetuplevel
floorheatig-watchingthetemperatureof ofheatingwater-40°Cmaximally
run-outofthepumpafterhot-water heatingisalwaysfor2s
Run-outofthepump
Therun-outtimestartsinthemomentofswitchingofftheboilerbythethermostat.Atthe endofeachrequestforheating,thepumpstaysinoperationfor180secondsmore.Therun­outofthepumphas2importantfunctions:
–itcoolsheat-exchangertopreventoverheating –intherun-outtime,thetemperaturedifferencesonheatingbodiesareequalized
Therun-outofthepumpbytherequestforhotwaterissetupbyJP5jumper.Whenthe jumperisinOFFposition,therun-outis0.4-2seconds,inONpositiontherun-outis always2seconds.
20
22
Technicalparameters
Supply
Supplyvoltage Innerfuse Groundresistance
Contactloading
Outlettomainvalve Outlettopump Outlettoventilator
Functionalparamaters
Operationtemperaturerange Rangeofsetupofhot-watertemperature Startingtemperatureforfunctionoflimitinghot-waterheating Rangeofheatingtemperaturesetup Rangeoffloor-heatingtemperaturesetup Switching-offheatingtemperautre Switching-onheatingtemperature Operationthermostattemperature Timingfunctionagainstrepeatedstarting Switch-ontemperatureofanti-freezingfunction Switch-offtemperatureofanti-freezingfunction
Slow-ignitiontiming Supplytoamodulatornaturalgas SupplytoamodulatorLPG Powerregulationrangeforslowignition Powerregulationrangeformaximumheatingoutput
230V+10%-15% 2AF250VAC 10m
230V0,1AMAXcos0,4 230V0,4AMAXcos0,4 230V0,35AMAXcos0,4
-20°C/+60°C +35/+60°C 70°C +30°C/+80°C +20°C/+40°C +35°C/+85°C +25°C/+75°C 10K 0alebo180sek 6°C 25°C 2sek 45-220mA+-7,5% 65-310mA+-7,5% 0-80%Imax 0-100%Imax
Thermalprobes
Electricparameters
Resistanceby25°C B(2580°C) Insulationresistance
10k+-1% 3435+-1% 10mA500VDC
RRT=TOxe
RT-resistancebyrequestedtemperature RTO-resistanceby25°C T,TO-temperatureinK
1
x()B
TT10
1
22
Tableofrelationbetweenresistanceandtemperature
ResistanceTemperatureResistanceTemperatureResistanceTemperature
°Ck
°Ck
°Ck
-30
-29
-28
-27
-26
-25
-24
-23
-22
-21
-20
-19
-18
-17
-16
-15
-14
-13
-12
-11
-10
-9
-8
-7
-6
-5
-4
-3
-2
-1
10 11 12 13 14 15
111,3 105,7
100,5
95,52 90,84
86,43 82,26
78,33 74,61
71,10 87,77 64,51 61,64 58,68 55,97 53,41 50,98 48,68 46,50 44,43 42,47 40,57 38,77 37,06 35,44 34,48 32,96 31,52 30,16
28,85 0 1 2 3 4 5 6 7 8 9
27,62
26,44
25,32
24,25
23,23
22,27
21,34
20,46
19,63
18,83
18,07
17,34
16,65
15,98
15,35
14,75
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61
14,17 13,62
13,09 12,59 12,11 11,65 11,21 10,79 10,39 10,00
9,63 9,27 8,93 8,61 8,30 8,00 7,71 7,44 7,18 6,92 6,68 6,45 6,23 6,01 5,81 5,61 5,42 5,24 5,06 4,89 4,73 4,57 4,42 4,28 4,14 4,01 3,88 3,75 3,64 3,52 3,41 3,30 3,20 3,10 3,01 2,91
62 63
64 65
66 67
68 69
70 71 72
73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99
100
2,83 2,74 2,66 2,58 2,50 2,43 2,35 2,29 2,22 2,15 2,09 2,03 1,97 1,92 1,86 1,81 1,76 1,71 1,66 1,62 1,57 1,53 1,49 1,45 1,41 1,37 1,33 1,30 1,26 1,23 1,20 1,17 1,14 1,11 1,08 1,05 1,02 1,00 0,97
Ignitionandionizationunit(ACCF)
Definition
ElectronicalapplianceforcontrolofflamebytheES298,fordirectignitionoftheburner bydischargesparkandmonitoringpresenceofflamewithionizationelectrode.
Heating,timeschedule
t1=0,5stypically,t2=0,5to1stypically(dependsonheatingsystem, notthecontrolboardfunction) t3=run-outofthepump,t4=run-outoftheventilator
Technicalparameters
Flamedetection
Minimumionizationcurrent Maximumlengthofionizationcable Maximumparasiticcapacity
Minimumresistanceofionizationelectrodeandcabletoground Short-circuitcurrent
Thecircuitmeasuringamplifiersensitivity
M10
A
D
>1.2uA
1m 1nF 50m
>200uA
M11
Tableofvalues(230V~50Hz):
ŠtartONPrevádzkaONPrevádzkaOFF Ionizač nýprúd I(uA´)<0.6+-10%>1.2+-10%>0.9+-10%
OdporplameňaR(m)>140+-10%<70+-10%<95+-10%
Ignition
Ignitionvoltage Distanceofignitionelectrode
Frequencyofsparklerepeating Maximumlenghtofignitioncable Ignitiontransformer
Workingprogrammandtimes
Autotesttime Safetytime
Manufacturingtoleranceofsafetytime Reactiontimeofswitch-off
Basicfunctionalcharacteristics
–detection,polarity –interruptedrun(interruptionevery24hoursatleast) automaticreset
2,2s+15%/-10%A230V~25°C
8s+10%/-15%A230V~25°C
16kVcca(záťaž40pF)
R
4mm(max)
10Hz
1m
typb&p
10s
<1s
26
Workinginthecaseoffailure
-Ifthereisflamesimulation,ignitionisstopped
Note:
IfCMFunitfindsflamesimulation,itreportsanomalyandifthissituationlasts longerthan15seconds,therequestforheatisstopped(itisswitchedoffbyarelay).Anew tryforignitioncanoccuronlyafterresettingthesystemwiththeoperationmodeswitch.
Repeatedcyclinginthecaseofflamefailureduringoperation
Thefailurethatcanberemediedbyswitchingoffandonthemainsupplyofpowerif
theflameisnotpresent
Note:
TheCMFunitcanresolvethebreakdowncausedbyignitionfailurebecauseof switchingoff,whenthehighesttemperaturewasovercome.Theunitinducesappropriate anomalyandswitchessofftherelayrequestsforheating.Anewattemptforignitioncan startafterresettingthesystembytheoperationmodeswitch.
Functionalfailure:Overheating
26
CHARTOF“ATTACKNST”CONNECTING
+
ELECTRIC
SUPPLY
PHASENEUTRALCONDUCTOR
JP1
P2 P3P1
P4
P6
BLUE
BROWN
P5
JP4
JP5
JP3
EMERGENCY THERMOSTAT
GASFITTINGS
P1OperationmodeswitchJP1Fuelsetting P2HeatingtemperaturesettingJP2 P3WatertemperaturesettingJP3Anti-fastcyclingtimer P4Max.outputtoheatingsystemJP4Settingtofloorheating P5StartingoutputJP5Pumprun-outsetting P6NotusedJP6
BROWN
BLUE
BLUE
BROWN
IONIZATION ELECTRODE
PUMP
VENTILATOR
IGNITION ELECTRODE
CHARTOF“ATTACKNSK”CONNECTING
+
JP1
ELECTRIC
SUPPLY
NEUTRALCONDUCTOR
PHASE
BROWN
BLUE
IONIZATION ELECTRODE
PUMP
P2
P4
P6
P5
JP4 JP3
JP5
PUMPCHARACTERISTICS
Wilo RS15/6-3PPN10
CondenserMOTORrevolutionsP1CurrentThreatWeightPitch
uFlevelsrev/minWAkgmm
11450460,2
2,621900670,32,00130
32200930,4
MODRÝ
HNEDÝ
EMERGENCY THERMOSTAT
P3P1
GASFITTINGS
3/4”
IGNITION ELECTRODE
27
Settingminimumandmaximumboileroutputintoheating
Modulationregulatoronthegasfittingsissetfromproductiontominimumandmaximum pressureonnozzlesthatsuitstominimum(8kW)andmaximum(24kW)boileroutput. Whenputtingboilertooperation,itisnecessarytocheckminimumandmaximumgas pressureonthenozzles.
Instructionforcheckingandsettingup
–releasetheboltintheprobeformeasuringinletgaspressure,connectmanometerand
readthemeasuredvalue(2mbar).Screwintheboltintheprobeformeasuringinletgas pressure.
–releasetheboltintheprobeformeasuringgaspressureonburnernozzles,connect
manometerandreadthemeasuredvaluebythechartofpressuresetting.
–inthecaseofsettingminimumandmaximumpressureonnozzles,followingactionsare
tobedone: a)removethecoverofmodulationregulator b)setthemodeswitchonthecontrolboardtotheheatingandhot-watermodeandtheP4
trimerlocatedontheelectricboardsettotherightextremeposition(minimumoutputto
heating)andwiththehelpofmanometertakeoutletpressureonnozzles c)ifnecessary,setminimumpressureonnozzleswithnutonthemodulationregulator d)turntheP4trimertowardstheleftextremepositionwherebyraisetheboileroutputto
heating,readthemeasuredvalueofoutletpressureonnozzlesandcomparethevalue
withthechartofrelationshipbetweentheboileroutputandgaspressureonnozzles e)maximumoutputof24kWcanbesetbyturningthenutonthemodulationregulator f)disconnectthemanometerandclosetheprobebyscrewingthebolt g)attachbackthecoverofmodulationcoil h)checkrightoperationoftheboiler
B
A
Chartofsettingpressureonnozzles
25 20 15
OutputkW
10
5
12534678910
B
wrenchNo.5)
A
wrenchNo.8)
Modulation
regulator
Measuringgas pressureonnozzles
Inletgaspressure measuring
12
11
13140
Naturalgas(mBar)
SettingMINandMAXoutput onthe"NST"boiler,1,15nozzle
SettingMINandMAXoutput onthe"NSK"boiler,1,25nozzle
Notes:
RECORDONPUTTINGTHEBOILERTOOPERATION
Boilertype:
Boileroutput:
ProductionNo.
Dateofputtingtooperation:
Servicecompany:
....................................................................................
................................................................................
...............................................................................
........................................................
..........................................................................
Stamp,signature
Obligatoryserviceexaminationafterthe1styearofoperation
Date: .......................................................
Stamp,signature
Obligatoryserviceexaminationafterthe2ndyearofoperation
Date: .......................................................
Stamp,signature
Obligatoryserviceexaminationafterthe3rdyearofoperation
Date: .......................................................
Stamp,signature
DOCUMENTontestingandcompletness
ofATTACKgasboiler
NSTNSK
Boileroutput:8-24kW
BoilerproductionNo.:
.
Theproductdeliveredwiththiscertificatesuitstotechnical standardsandtechnicalconditions. Theproductwasmanufacturedbyitsdrawingdesigninrequested qualityandisapprovedbyTECHNICALTESTINGFACILITY SKTC104inPiešťanyundertheNo.ofcertificate00846/104/2/2002, 00847/104/2/2002
Technicalinspection
N
Vrútky,date:.....................................................................................
Stampandsignatureofthefinalinspection:.....................................
Producer:
TERMOGAS DielenskáKružná5 03861Vrútky SLOVAKIA
Exporter:
ATTACKs.r.o. DielenskáKružná5 03861Vrútky SLOVAKIA
Tel:00421434003103 Fax:00421434003106
E-mail: export@attack-sro.sk http: www.attack-sro.sk
www.termogas.sk
