Copyright 2016 GE Reuter-Stokes. All rights reserved
NOTICE
All content and material in this Manual (including, without limitation, text, design, graphics, logos, icons,
images, code and software, as well as the selection and arrangement thereof) is confidential and
proprietary, the exclusive property of and owned by Reuter-Stokes, Inc. and is protected by copyright,
trademark and other applicable laws. Any use of content and material in this Manual, including but not
limited to the modification, distribution, transmission, performance, broadcast, publication, uploading,
licensing, reverse engineering, transfer or sale of, or the creation of derivative works from, any material,
information, software, products or services obtained from the content and material in this Manual, or use
thereof for purposes competitive to Reuter-Stokes, Inc., is expressly prohibited.
WHILE EVERY ATTEMPT HAS BEEN MADE TO ASSURE THE COMPLETENESS, ACCURACY AND
TIMELINESS OF THE CONTENT AND MATERIAL IN THIS MANUAL, IT IS PROVIDED ON AN "AS IS" AND
"AS AVAILABLE" BASIS. REUTER-STOKES, INC. EXPRESSLY DISCLAIMS ALL WARRANTIES OF ANY
KIND, WHETHER EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES
OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND ANY WARRANTIES THAT THE
CONTENT AND MATERIAL IN THIS MANUAL IS NONINFRINGING, AS WELL AS WARRANTIES IMPLIED
FROM A COURSE OF PERFORMANCE OR COURSE OF DEALING; THE MATERIALS IN THIS MANUAL
WILL BE ERROR-FREE; OR THAT THE MATERIALS IN THIS MANUAL WILL BE COMPLETE, ACCURATE
OR TIMELY. NO ADVICE OR INFORMATION, OBTAINED BY YOU FROM REUTER-STOKES, INC. OR
THROUGH THE CONTENT AND MATERIAL IN THIS MANUAL SHALL CREATE ANY WARRANTY OF ANY
KIND. REUTER-STOKES, INC. DOES NOT MAKE ANY WARRANTIES OR REPRESENTATIONS REGARDING
THE USE OF THE CONTENT AND MATERIAL IN THIS MANUAL IN TERMS OF THEIR COMPLETENESS,
CORRECTNESS, ACCURACY, ADEQUACY, USEFULNESS, TIMELINESS, RELIABILITY OR OTHERWISE.
YOU ACKNOWLEDGE AND AGREE THAT YOU ASSUME FULL RESPONSIBILITY FOR YOUR USE OF THE
CONTENT AND MATERIAL IN THIS MANUAL. YOU ACKNOWLEDGE AND AGREE THAT YOUR USE OF
THE CONTENT AND MATERIAL IN THIS MANUAL IS AT YOUR OWN RISK. YOU ACKNOWLEDGE AND
AGREE THAT, TO THE FULLEST EXTENT PERMITTED BY APPLICABLE LAW, REUTER-STOKES, INC.
WILL NOT BE LIABLE FOR ANY DIRECT, INDIRECT, PUNITIVE, EXEMPLARY, INCIDENTAL, SPECIAL,
CONSEQUENTIAL OR OTHER DAMAGES ARISING OUT OF OR IN ANY WAY RELATED TO THE CONTENT
AND MATERIAL IN THIS MANUAL, WHETHER BASED ON CONTRACT, TORT, STRICT LIABILITY OR
OTHERWISE. THIS DISCLAIMER APPLIES, WITHOUT LIMITATION, TO ANY DAMAGES OR INJURY
ARISING FROM ANY FAILURE OF PERFORMANCE, ERROR, OMISSION, YOUR LOSS OF PROFITS,
DESTRUCTION, AND ANY OTHER TANGIBLE OR INTANGIBLE LOSS.
Copyright 2016 GE Reuter-Stokes. All rights reserved
FS-9001OM – REV M
Revision History
REV#: G
DATE:
10/2006
ECN#:
7233394
WRTR:
K. Schmidt
REV#: G
DATE:
6/16/2009
ECN#:
27755661
WRTR:
L. Lombardo
REV#: H
DATE:
10/12/2009
ECN#:
31496139
WRTR:
L. Lombardo
REV#: J
DATE:
06/25/10
ECN#:
40293054
WRTR:
R. Martin
REV#: K
DATE:
04/24/13
ECN#:
77469075
WRTR:
J. Hashmi
REV#: L
DATE:
12/18/15
ECN#:
500000157848
WRTR:
J. Hashmi
REV#: M
DATE:
02/22/16
ECN#:
500000204318
WRTR:
J. Hashmi
ii
Copyright 2016 GE Reuter-Stokes. All rights reserved
FS-9001OM – REV M
Certification Information
0359
II 3 G
Ex nA IIC T3 Gc
ATTENTION! The RS-FS-9001 Flame Tracker sensor complies with the following standards:
ETL
Control Number 9900287
Class 1, Div. 2, Grp A,B,C,D T3
Class 1, Zone 2 AEx nA IIC T3 Gc
ATEX / IECEx
Temperature Range
-40ºC ≤ Ta ≤ 150ºC; T3
-40ºC ≤ Ta ≤ 235ºC; T2 ; with cooling coil
These certifications are based on the use of approved interconnecting cables only. Currently available approved
interconnecting cables are GE Reuter Stokes RS-E2-0285PXXX and GE 362A1053PXXX. See Section 1.1.2 for
details.
Certifications are based on the use of approved cables only. Currently available approved cables are GE ReuterStokes RS-E2-0285 and GE 362A1053.
Do not attempt to disassemble the sensor. Sensor is not repairable. Breaching the seal of the sensor will cause
lose of the inert fill gas and render the sensor unusable.
Do not remove the sensor by wrenching on the body. Always use the 1 3/8 inch mounting nut. Wrenching on the
body may breach the seal. Breaching the seal of the sensor will cause lose of the inert fill gas and render the
sensor unusable. Once the seal has been broken it cannot be resealed by reassembly.
Do not install a sensor that has a cracked window, damaged threads or one that has been disassembled.
The operating temperature range of the Flame Sensor is -40°C to 150°C. Do not attempt to work on the Flame
Sensor until it has reached a safe handling temperature.
WARNING
CAUTION
iii
Copyright 2016 GE Reuter-Stokes. All rights reserved
1.3 GENERAL DESCRIPTION .................................................................................................................................4
MIL-C-38999 series III, shell size 15, 5 #16 pins (only 3
pins are used)
Operating
Voltage (max)
300 vrms
Temperature (max)
482F (250C)
Copyright 2016 GE Reuter-Stokes. All rights reserved
2
FS-9001OM – REV M
1.2 REFERENCE
3
Copyright 2016 GE Reuter-Stokes. All rights reserved
FS-9001OM – REV M
1.3 GENERAL DESCRIPTION
On Liquid Dry Low Nox Applications, as well as those applications with significant levels of water and steam
injection, the ultra-violet light sensed by the Geiger Mueller tube based flame detectors is absorbed by the fog
of fuel, steam or water. GE’s research center invented a silicon carbide (SiC) photodiode that is significantly
more sensitive to the longer wavelength components of the UV light generated by the flame. This longer
wavelength light does penetrate the fog of oil quite well and therefore the SiC based sensor is significantly
more sensitive to the presence of flame. A flame sensor utilizing the SiC photodiode is being produced by GE
Reuter Stokes, and has been successfully operated on a number of GE gas turbine installations.
2 SENSOR
Figure 1 is a block diagram of the SiC Flame Sensor. The sensor has a sapphire window that is transparent
to UV light and can withstand the compressor discharge temperature and pressure. It has a lens inside that
focuses the light on a silicon carbide photodiode in a hermetic package. The photodiode is wired to a
MOSFET input amplifier. The amplifier has a high initial gain, which automatically shifts to a lower gain in
order to accommodate a wide range of input light level without saturating. The sensor regulates the supply
current in proportion to the amount of UV light present. Both power and signal are transmitted on the same two
wires. The sensor can be powered from a dc voltage between 12 and 30 volts. The whole transducer is
sealed and filled with dry argon.
4
Copyright 2016 GE Reuter-Stokes. All rights reserved
FS-9001OM – REV M
FIGURE 1 - SiC FLAME SENSOR WIRING DIAGRAM
5
Copyright 2016 GE Reuter-Stokes. All rights reserved
FS-9001OM – REV M
3 INSTALLATION
3.1 MECHANICAL
The maximum operating temperature for the flame sensor is 302 F (150 C). If the peak ambient
temperature at the location of the sensor exceeds this then cooling will be required. There are three methods
available for cooling: Water-cooling, air-cooling with ambient air, and air-cooling with pressurized air.
Water cooling requires the use of a water cooling coil Part Number sp-566, GE Part Number
353B3490G001. The water-cooling coil requires water at a temperature of 50 F to 135 F (10 C to 57 C) at
a flow rate of 1.0 gpm (3.8 lpm) per sensor. When using water-cooling the flame sensor can be operated to
an ambient temperature of (455F) 235C.
Air-cooling with ambient air can be used in installations where the enclosure is cooled with forced air. This
would be typical of LM2500 and LM6000 aircraft engine applications. The air velocity at the sensor must be 5
ft/sec (1.5 m/sec), or greater, at a temperature of 50 F (10 C), or less, above outside ambient. Under these
conditions the sensors will operate at outside ambient temperatures up to 140 F (60 C).
Air-cooling with pressurized air requires the use of Air-Cooling Can. GE Reuter-Stokes Part Number RS-E20259 (GE Part Number 07482SOCNL44821P01). The Air-Cooing Can is installed in the same manner as the
water-cooling coil. The Air-Cooling Can requires 25-psi (170 kPa) minimum at 120 F (49 C) maximum.
Do not complete step 2 in the “FLAME SENSOR AND WATER COOLING JACKET INSTALLATION
INSTRUCTIONS” on the next page. Leave the sensors installed hand tight until after the sensor checkout
described in Section 3.3.
6
Copyright 2016 GE Reuter-Stokes. All rights reserved
FS-9001OM – REV M
Note: 50 - 60 in. lbs = 5.6 - 6.8 Nm. When installing the Water Cooling Coil, ensure that the edge of the
1. Apply a small amount of Never-Seez PN NG-165 (GE PN 248A9779P001) to threads, prior
to reinstalling the Flame Sensor
2. Inspect the window and clean with Isopropanol soaked swab. If required install hand tight
(3-4 Full turns) tighten with a wrench approximately 2.5 turns. Tighten further as required to
align keys on cable connector with slots in sensor connector
3. Slide cooling coil over Flame Sensor major diameter and orient tubes on the coil as required
for assembly. Tighten clamps 50-60 in. lbs. Install Swagelok fittings re-torque clamps to 5060 in. lbs. after first shut down
Sheet Metal Band is not in contact with the cooling tubes. This will ensure that no rubbing or fretting of the
cooling tubes by the band’s edge will occur during turbine operation.
7
Copyright 2016 GE Reuter-Stokes. All rights reserved
FS-9001OM – REV M
3.2 ELECTRICAL
The sensors are connected to the turbine junction box with connector cable RS-E2-0285 or equivalent. The
RS-E2-0285 consists of black, white and green wires twisted and shielded. All wiring must be in grounded
conduit. The green wire must be connected to earth ground at the junction box. Do not connect the shields to
each other or to earth ground at any location. The shields should be individually jumped through all junction
boxes and connected to the proper ground terminal at the Controller. The polarity of the cable is as follows;
white is positive and black is negative/signal return. Reverse polarity will not damage the sensor. Signal cable
from the junction box to the Controller should be 18 gauge (1.02 mm) twisted shielded pair. The extension
cable from the junction box to the Controller is the customer’s responsibility.
8
Copyright 2016 GE Reuter-Stokes. All rights reserved
FS-9001OM – REV M
The Flame Tracker™ is connected to the controller as a typical two wire current transmitter. It can be
CONNECTOR LEGEND
PIN
CIRCUIT DESIGNATION
A - B + C
Ground
D
Not Used
E
Not Used
operated from any well-filtered dc supply from 12 volts to 30 volts. The supply should be capable of supplying
100 milliamps.
The power supply must be protected to prevent the supply voltage from exceeding 30 volts in normal use
and more than 42 volts under transient conditions. The sensor is protected against reverse polarity. The
maximum value for the sense resistor plus the wire resistance is dependent on the supply voltage. At 24 volts
this value is 560 ohms. Resistance values for other voltages can be determined from the chart in Figure 2.
Figure 1 shows the preferred wiring for the sensor with the R
of the controller in the return line of the
sense
sensor. This configuration can be used with controllers that have single ended inputs (one side of the input
grounded) or differential inputs (neither side of the input grounded). For pin outs and cable color code see
Figure 1.
3.3 CONNECTOR PINOUT
The pinout for the power connector is as follows:
3.4 SENSOR CHECKOUT
Disconnect the sensors and unscrew them from the turbine. Plug the sensor cables back in to each of the
sensors. Apply power to the sensors. Check the current values at the controller for each of the sensors. The
sensors are sensitive to light, and may have some reading, depending on the ambient light level. Test each
sensor by covering the port to see the zero flame intensity signals, and with a flashlight to see a positive
reading. With no light the reading should be 3.7 to 4.1 milliamps, while with most flashlights the reading should
be above 8 milliamps. An LED flashlight may not work for this application. Variations in flashlight type,
strength, or battery voltage may cause variation in signal output. The flashlight test is intended as a field test
for general functionality only and is not a controlled or quantitative test. If a sensor is outside these rough
check limits see Section 5.0.
Disconnect the sensor cables, and reinstall the sensors according to the instruction in Section 3.1. At this
time step 2 of Section 3.1 should be completed and the sensor cables reconnected. Make sure that the
sapphire window is clean; if it needs cleaning, do this according to the maintenance instructions in Section 4.0.
Check that all sensors are reading between 3.7 to 4.1 milliamps.
3.5 CONTROLLER SETUP
The Flame Sensor provides a minimum output of 5 milliamps when exposed to the minimum flame intensity
specified in GE specification number 362A1052. The set point for flame off should be set to 6.25%, which
equals 5 milliamps. The set point for flame on should be 10%, which equals 5.6 milliamps. If the intensity
levels are to low for these settings their may be other problems. Low intensity levels may be a sign of other
problems. Refer to Section 5.0 - Troubleshooting.
9
Copyright 2016 GE Reuter-Stokes. All rights reserved
FS-9001OM – REV M
4 MAINTENANCE
PROBLEM
CAUSE
SOLUTION
No current flows
Reversed polarity
Open wire
Change polarity
Check connections
Low sensitivity during checkout or
operation
Dirty lens
Grounded cable
Clean lens (Section 4.0)
Check cable for grounds
Low flame intensity signal during
operation
Misalignment of the sensor mount
Check the squareness of all flanges
and pipes of the sensor mount. Verify
that the sensors have a clear view of
the flame.
Periodic low reading on secondaries
of DLN1 turbines
Condensation on the lens that can
occur under high humidity
situations.
A shorter mount tube (PN# E10058P002), is available from GE
Reuter Stokes and may improve this
condition. Please contact GE Reuter
Stokes for further information.
4.1 WARNING
Do not disconnect connector while circuit is energized (or live), unless area is known to be non-hazardous.
4.2 CAUTION
The operating temperature range of the Flame Sensor is -40°C to 150°C. Do not attempt to work on the
Flame Sensor or the cable until they have reached a safe handling temperature.
The Flame Sensor output will deteriorate as the lens becomes dirty. It is recommended, when initially
installed, that the signal level be recorded during normal operation. During subsequent running, the signal
level should be compared with the initial values. If a significant reduction in the signal level is noticed, then it is
recommended that the lens be cleaned at the next opportunity (with the turbine shut down and cold). Clean the
lens with isopropyl alcohol or other residue free solvent compatible with Sapphire. In order to reduce the risk of
galling, an anti seize compound should be applied to the mounting thread prior to reinstallation of the sensor.
5 TROUBLESHOOTING
5.1 WARNING
Do not disconnect connector while circuit is energized (or live), unless area is known to be non-hazardous.
5.2 CAUTION
The operating temperature range of the Flame Sensor is -40°C to 150°C. Do not attempt to work on the
Flame Sensor or the cable until they have cooled to a safe handling temperature.