Find a contact near you by visiting www.gewater.com and clicking on “Contact Us”. 
* Trademark of General Electric Company; may be registered in one or more countries. 
©2013, General Electric Company. All rights reserved. 
FSsmAG_LF_EN.docx Nov-13 
Thin-film membrane (TFM*) 
Average 
permeate 
flow gpd 
(m3/day)
1,2
Average NaCl 
rejection
1,2
Minimum NaCl 
rejection
1,2
Typical Operating Pressure 
Maximum Operating Pressure 
Continuous operation: 122°F (50°C)  
Clean-In-Place (CIP): 122°F (50°C) 
Optimum rejection: 7.0-7.5,  
Continuous operation 4.0-11.0,  
Clean-In-Place (CIP): 2.0-11.5 
Over an element: 12 psi (83 kPa)  
Per housing: 50 psi (345 kPa) 
1,000+ ppm-hours,  
dechlorination recommended 
AG LF Series 
Low Fouling Brackish Water Reverse Osmosis Elements 
The A-Series LF proprietary thin-film reverse osmosis (RO) membrane elements are characterized by 
high flow, high sodium chloride rejection and low 
fouling surface properties.  AG LF brackish water 
elements are selected when high rejection and operating pressures as low as 200 psi (1,379 kPa) are 
desired. These elements are recommended for 
brackish water with salt concentration (TDS) levels 
between 1,000 and 10,000mg/l or when very high 
salt rejection of monovalent ions is required. 
AG LF high rejection brackish water elements feature a Fiberglass outer wrap. 
Table 1: Element Specification 
Figure 2: Element Dimensions Diagram – AG4040F LF, WET 
Table 2: Dimensions and Weight 
1
 Average salt rejection after 24 hours operation. Individual flow rate may vary 
+25%/-15%. 
2
 Testing conditions: 2,000ppm NaCl solution at 225psi (1,550kPa) operating 
pressure, 77°F, pH7 and 15% recovery. 
Figure 1: Element Dimensions Diagram - AG8040F 400 LF, 
WET 
1 
These elements are bagged wet (WT) before shipping. 
² Internal diameter unless specified OD (outside diameter). 
Table 3: Operating and CIP parameters