6.0 Declaration of conformity ...................10
1.0 General safety precautions
1.3 Technical data
G L E F-180-3
Fan Designation
No. of phases on motor
Size of impeller in mm.
Flange motor B5
Backward curved impeller
RPMs: M=2800 L=1400 rpm
EEX-e protected version
Fan
Name plate
Motor
Name plate
IMPORTANT - Please study all the instructions before
mounting and commissioning.
This instruction manual is valid for MEF/LEFfans.
LEF/MEF is standard motor where an external
frequency inverter can be connected. More specic
data regarding frequency inverters can be found in the
specic manual for the inverter.
Please keep these instructions in a safe place and
instruct all users in the function and operation of the
product.
Do not dismantle any factory-mounted parts, as it
impedes the commissioning of the equipment.
All electrical installations must be carried out by an
authorised electrician
1.1 Danger
Explosive media – The fan is not suitable for the extrac-
tion of aluminium dust, our, textile dust nor for sawdust
or other media, which are connected with danger of
explosion, without specic approval from Geovent A/S.
Removing the protection net on the fan whilst in operation involves a risk of mutilation.
Temperature extracted air Max 80°C
Temperature surroundings Max 40°C
If the temperature of the extracted air exceeds 80°C,
special bearings must be used. Please contact your
dealer.
The sound level depends on various factors under
various circumstances. For instance, where in the room
the Fan has been installed, the size of the room, the
temperature in the room, the sound of the room and
also the connection (hose><pipe) of the Fan inuences
the sound level of the fan.
As a main rule, a sound box will reduce the actual
sound level to only half the level without a sound box.
The actual ampere consumption and the kW of the
motor are shown on the metal sign on the fan.
1.4 Construction
Always switch o the current when mounting something
on the Fan or when servicing it.
1.2 Field of application
The GEOVENT fan LEF is typically used for general
ventilation as well as for smaller process extraction
jobs, where a high pressure is not required. The fan
MEF is applied for process extraction within the industry for the extraction of welding smoke, exhaust gasses,
grinding dust and vapours.
The fan is neither suitable for the extraction of alumin-
ium dust, our, textile dust nor for sawdust or other
media, which are connected with danger of explosion,
without prior, written approval from Geovent A/S.
3
Fan housing: 100% galvanized steel for optimal corrosion resistance. Brackets are standard on all fans as well
as inlet nozzle with safety net.
Impeller: Backward curved B-impeller in painted Domex
sheet metal.
Motor: B5 ange motor, directly driven IEC/DIN B5
EFF2 quality motor in painted die cast aluminium in
protection class IP-55. Other motor types available on
request.
Console:
5.5kW motors and above or heavy custom motors
come with a supporting console to carry the weight.
Fan, mounted on the roof with
roof bracket, supporting angles
with vibration dampers and
outlet ange
Fan, mounted on the
side by means of a wall
bracket, supporting
angles with vibration
dampers and outlet
ange
Fan, mounted on the
bottom by means of a wall
bracket, supporting angles
eith vibration dampers and
outlet ange
Console
Motors of less than 5,5 Kw do not have a console to
support the weight of the motor.
2.0 Installation
The Fan is supplied assembled and ready for
connection to piping and to the mains.
Before mounting the fan, please make sure that the
optimum installation area is selected.
Is there space enough for carrying out satisfactory
installation/service of the fan? What about optimum
connection possibilities for piping and automatics?
If at all possible, please avoid bends just before the
intake and after the outlet, since since this may reduce
the eectivity of the fan.
For outdoor mounting, any noise nuisances for neighbours should be taken into account and also ensure
that the motor is kept out of heavy showers.
Drill holes in motor housing and remove drain plugs
from the motor.
Procedure:
1. The fan is solidly xed to the roof/oor or to a
ceiling bracket or wall bracket (see gure 1). The
fan is xed by attaching the vibration dampers with
4 o M8 bolts. The Fan is to be mounted in one
of the shown ways. Do not install the Fan with the
intake in vertical direction.
2. The piping is connected to the fan. On the inlet
side, the pipe may be fastened by means of self
cutting screws. Remember to seal the connection
with ller!
3 On the outlet side, the pressure connecting piece
(optional equipment) is attached to the fan by means of the supplied clamps. Remember to seal the
connection with ller!
4. The pressure connecting piece is then attached to
the piping on the outlet side by means of self-cut-
ting screws. Remember to seal the connection!
2.1 Connection of fan to the mains
- standard motor
1. The fan should only be connected to the mains by
a certied electrician and a motor protection switch
should always be used.
2. Our 3-phase motors may be congured to both
3x230V and 3x400V. From the factory, the motor
has not been congured and the enclosed metal
cover plates are to be mounted in such a way in
the terminal box that they t the voltage.
4
2.3 Installation of optional equipment
Mounting of sound box
From the factory, the fan will be installed in the sound
box (optional equipment). The box must be mounted
on horizontal surfaces and may only be mounted with
vertical outlet.
Mounting of frequency converter
Our standard 3-phase motors are particularly suitable
for frequency converter operation.
Suggested application – frequency inverter
Always double check the metal sign on the motor
and on the inner side of the cover for current
congurations (diagram).
From 4,0 kW motors and up:
∆ 400… 460V 50/60Hz
Y 690 50Hz
Our 3 phased motors at 4,0 kW and larger are
congurable for both 3x400, 440V and 3x690V.
By default the motor is not congured and the jumper
bars must be installed in the terminal box according to
voltage.
Double check the metal sign on the motor and the
inside of the lid for current conguration.
2.2 Connection of fan to the mains
- Motors with integrated
frequency inverter.
Installation of frequency inverter
Our standard 3-phased LEF/MEF fans are highly
suitable for operation with frequency inverter allowing
for pressure control and speed control.
Draft of installation with frequency inverter:
Channel – spiro duc
Suction tube
Terminal box
3x400V + PE
Multi
box
1x230VAC
Frequency inverter
3x400V
3-conductort
0-10DC
Switch
Draft of installation with
pressure guard and motor guard:
3.Connection diagram 1-phase motor
(Not suitable for regulation) up to 2,2 kW
Draft of installation with potentionmeter:
5
2.4 Trial run – exact adjustment
4.1 Trouble-shooting
After the installation has been completed, please check
whether there are any vibrations in the fan.
We recommend checking whether the fan supplies the
correct volume of air, for which the equipment has been
dimensioned. I.e. control the volume of air and make
sure that it does not exceed the ampere capacity of the
motor.
3.0 User instruction – application
When extracting large quantities of air, containing dust,
the fan wheel may get out of balance due to dirt on the
wheel. In order to avoid this, we recommend using a
lter.
In many cases, the fan is started by pushing the green
button on the motor protection switch (if automatics are
not used).
The fan will not work as intended if:
• unauthorised parts have been mounted on the fan
(e.g. unauthorised wheel).
• the wheel runs in the wrong direction. It will still
work, but the capacity will be reduced to a third of
the normal capacity.
• no motor protection switch is used.
4.0 Maintenance
Periodic maintenance
In principle, the motor is maintenance-free because
of the factory-mounted, completely closed special ball
bearings, which do not require any maintenance.
Replacement of worn bearings should only be handled
by an electrician.
The wheel and the fan housing should be cleaned
every year or according to requirement. The wheel and
the housing may be cleaned by means of a soft brush
and detergent. Remember to disconnect the power
before the washing and to wipe the parts afterwards
with a dry cloth. This operation results in a longer life of
the fan.
Access to the inside of the fan housing and the impel-
ler, can be gained by screwing o the umbracko screws
on the back of the fan.
Remember to always cut the power.
Remember to always use a
motor protection switch!
Always use adjustment damper!
In case of problems with the fan, the following items
may be reviewed in order to check whether:
The volume of air or the pressure is too low:
• Wrong direction of operation of the wheel.
May be due to wrong electrical installation.
Please double-check the direction of rotation.
Change two phases, if necessary.
• Leaky channel system.
• Poor inlet/outlet possibilities near the Fan may
reduce the yield (e.g. 90° bend before the inlet).
• Damaged wheel.
• The rotation speed has been set lower.
• If the temperature deviates substantially from the
lab measurements, where the temperature was
20°C with an atmospheric pressure of 101.4 kPa.
• The dampers have not been correctly adjusted.
• The central lid on the sound box is turned the
wrong way and thus blocks the air.
• The suction net has been blocked by cotton waste,
a cloth or the like.
Vibrations and noise
• The base is not even/stable.
• Foreign objects are stuck in the fan.
• Damaged wheel or motor.
• The wheel is loose.
• The wheel may have become unstable, for instance
as a result of dirt on the impellers.
• The wheel is rotating in the wrong direction.
• The fan supplies more air than for which the
equipment has been dimensioned.
Use adjustment damper.
• Loose bolts or screws.
The motor is overtaxed
• The cabling of the motor is not correct.
• The shaft has been bent.
• The fan has over-capacity in relation to the
resistance in the system.
Use adjustment damper.
• The speed of the motor is too high.
• Defective motor – please contact your dealer!
Soundbox - optional
6
J
E
A
L
G
C
F
H
B
K
ø
D
M
I
1
4
6 x M6
M8
5 x M8
ød
ø9
4
8
N
4.2 Table of dimensions
Table LEF/MEF 250 - 630 (LEX/MEX)
Type250315355400450500560630
A410510570648715758907989
B500700700800800800800800
C500600680756850871 1070 1175
øD250315400400500500630630
ød************************
E215260284308340345425446
F230290329370408421523563
G210240272304340362440467
H460660660760760760760760
I****************
J170210234260290295375400
K320400450500560510709800
M637720797965 1045 1065 1340 1340
N185225250275305263380425
VÆGT38*43*48*56*71*81*125* 135*
* The weight depends on which size motor
** Depending on the motor size
*** Depending on which size pressuretub
4.3 Pressure drop
Fan designation
[Pa]Fan LEF / MEF-355
2400
2100
1800
1500
1350
1200
1050
900
750
600
450
300
150
(2p - 57Hz)
n=2860
(2p - 50Hz)
n=2507
(2p - 44Hz)
n=2240
(2p - 39Hz)
n=1460
(4p - 50Hz)
(2p - 25Hz)
►
500
1000 1500 2000 2500 3000 3500 4000 4500 5000 5500
RPM. & resulting frequency
Example: A pressure controlled fan with frequency inverter, is
connected to 4 extraction arms. If all arms are in use, is the
extracted air ow 4.200 m3/h at 1.200 Pa. If the air ew is reduced
to tow extraction arms at the same time, the air ow will regulate
to 2.000 m3/h & the power consumption will be reduced by 50%
Geovent A/S grants a warranty for products, which are
defective, when it can be proved that the defects are
due to poor manufacture or materials
on the part of Geovent A/S. The warranty comprises
remedial action (reparation or exchange) until one year
after date of shipment. No claims can be made against
Geovent A/S in relation to loss of earnings or
consequential loss as a result of defects on products
from Geovent A/S.
Wear parts like fan impellers are not included in the
warranty.
User liability
In order for Geovent A/S to be capable of granting the
declared warranty, the user/tter must follow this
manual in all respects.
Under no circumstances may the products be changed
in any way, without prior written agreement with
Geovent A/S.
6.0 Declaration of conformity
has been manufactured in compliance with the
directions of the Directive Council 2006/42/EEC,
regarding machine safety, changes of directive
95/16/EEC and following standards:
UNE-EN ISO 12100: 2012