Geostar GAH022, GAH030, GAH026, GAH036, GAH042 Installation Manual

...
INSTALLATION MANUAL
AFFORDABLE RENEWABLE CLEAN
GEOTHERMAL HEAT PUMPS
ASTON SERIES AIR HANDLER
Table of Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Hydronic Models. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-13
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14-15
Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-18
ECM Blower Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Blower Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21-24
Unit Startup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Replacement Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Service Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Revision Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Model Nomenclature
1-3 4-6 7 8-9 10 11 12
GAH 036 * 00 0 1 R
Model
GAH – G Series Air Handler
Unit Capacity Refrigeration (DX) Models with Nominal CFM
022 MBTUH 800 026 MBTUH 925 030 MBTUH 980 036 MBTUH 1225 042 MBTUH 1425 048 MBTUH 1625 060 MBTUH 1760
Hydronic Models with Nominal CFM
026 MBTUH 925 036 MBTUH 1225 048 MBTUH 1625 060 MBTUH 1760
Vintage
* = Factory Use Only
NOTE: To field convert the GAH042-060 to bottomflow air discharge, the NAHBC kit must be ordered.
Air Coil
R – Refrigerant H - Hydronic
Motor
1 – ECM 208-230/60/1
Disconnect
0 – No Breaker Installed
(only on 5kW & 10kW Heaters)
1 – Breaker Installed
(only on 15kW & 20kW Heaters)
Electric Heat
00 – None 05 – 5kW (022 – 036 only) 10 – 10kW (030 – 060 only) 15 – 15kW (042 – 060 only) 20 – 20kW (060 only)
Rev.: 08 April 2013D
Initial Inspection
When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question
should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.
4
Physical Data
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Air Handler Model Number (Refrigerant)
Evaporator
Coil
Refrigerant R-410a Nominal cooling capacity - tons [kW] 1.8 [6.44] 2.1 [7.59] 2.5 [8.79] 3 [10.55] 3.5 [12.30] 4 [14.06] 5 [17.58] Condensate drain connection - (O.D.) in. [mm] Blower Wheel Size (Dia x W), in. [mm] Blower motor type/speeds Blower motor output - hp [W] Filter Standard - 1" [51mm] MERV3 disposable, in. [mm] Electrical characteristics (60hz) Shipping weight - lbs. [kg] Operating weight - lbs. [kg]
Air Handler Model Number (Hydronic)
Hydronic
Coil
Nominal cooling capacity - tons [kW] 2.1 [7.59] 3 [10.55] 4 [14.06] 5 [17.58] Condensate drain connection - (O.D) in. [mm] Blower Wheel Size (Dia x W), in. [mm] Blower motor type/speeds Blower motor output - hp [W] Filter Standard - 1" [51mm] MERV3 disposable, in. [mm] Electrical characteristics (60hz) Shipping weight - lbs. [kg] Operating weight - lbs. [kg]
Note: Water connection dimensions are O.D.
Air Coil Total Face Area, ft2 [m2] Tube outside diameter - in. [mm] Number of rows Fins per inch Suction line connection - in. [mm] sweat Liquid line connection - in. [mm] sweat
Air Coil Total Face Area, ft2 [m2] Tube outside diameter - in. [mm] Number of rows Fins per inch Water In connection - in. [mm] sweat Water Out connection - in. [mm] sweat
GAH022 GAH026 GAH030 GAH036 GAH042 GAH048 GAH060
5.83 [0.54] 3/8 [9.52]
23
12
5/8 [15.87] 7/8 [22.22]
3/8 [9.52]
3/4 [19.05]
11 x 10 [279 x 254]
ECM variable speed
1/2 [373] 1 [746]
20 x 24 [508 x 635]
208/230 - 1ph
215 [97.52] 220 [99.79]
195 [88.45] 200 [90.71]
GAH026 GAH036 GAH048 GAH060
6.94 [0.64] 3/8 [9.52]
3
13 7/8 [22.22] 7/8 [22.22]
3/4 [19.05]
11 x 10 [279 x 254]
ECM variable speed
1/2 [373] 1 [746]
20 x 24 [508 x 635]
208/230 - 1ph
220 [99.79] 200 [90.71]
8/15/14
4/28/14
General Installation Information
Safety Considerations
Warning: Before performing service or maintenance operations on a system, turn off main power switches to the equipment. Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fire extinguisher available.
Note: Local codes and regulations take precedent over any recommendations by the manufacturer. In addition to conforming to manufacturer’s and local municipal building codes, the equipment should also be installed in accordance with the National Electric Code and National Fire Protection Agency recommendations.
5
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
General Installation Information cont.
Air Handler Sizing Selection
The Aston Series Air Handlers are designed for R410a refrigerant and should be matched with Aston indoor and outdoor series compressor section according to the table below.
Air Handler
GAH022B***1R 103*022 - 800 5 GAH026B***1R - 103*026 104*026 925 5 GAH030B***1R 103*030 - - 980 5, 10 GAH036B***1R 103*036 - - 1225 5, 10 GAH036B***1R - 103*038 104*038 1225 5, 10 GAH042B***1R 103*042 - - 1425 10, 15 GAH048B***1R 103*048 - - 1625 10, 15 GAH048B***1R - 103*049 104*049 1625 10, 15 GAH060B***1R 103*060 - - 1760 10, 15, 20 GAH060B***1R - 103*064 104*064 1760 10, 15, 20 GAH060B***1R 103*070 - - 1760 10, 15, 20 GAH060B***1R - 103*072 104*072 1760 10, 15, 20
Indoor Split Model
(Single)
Moving and Storage
If the equipment is not needed for immediate installation it should be left in its shipping carton and stored in a clean, dry area. Units must only be stored or moved in the normal “up” orientation.
Unit Location
Locate the unit in an indoor area that allows for easy removal of the filter and access panels (the air handler units are not approved for outdoor installation). Location should have enough space for service personnel to perform maintenance or repair. Provide sufficient room to make refrigerant, electrical and duct connections. If the unit is located in a confined space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. The air handler section may be installed on any level surface strong enough to support its weight. When installed in a closet or on a stand, it should be mounted on vibration absorbing material slightly larger than the base to minimize vibration transmission to the building structure.
When installed in an attic or above a drop ceiling, the installation must conform to all local codes. If the unit is suspended and installed in the horizontal position, the entire length of the unit should be supported. If the application requires the air handler to be installed on the attic floor then the unit should be set in a full size secondary drain pan. In this case the secondary drain pan should be set on top of a vibration absorbing mesh. The secondary drain pan is usually placed on a plywood base. A secondary drain pan should be used when equipment is installed over a finished living area to provide protection from water damage in case of plugging of the air handler primary drain line. The secondary drain line should terminate somewhere that is easily visible by the homeowner. Be certain to show the homeowner the termination location of the secondary drain line and to explain its purpose.
Indoor Split Model
(Dual Capacity)
Outdoor Split Model
(Dual Capacity)
Airfl ow(CFM) Electric Heat (kW)
Duct System
The duct system should be sized to handle the design airflow quietly and efficiently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fiberglass or constructed of ductboard for the first few feet. On systems employing a metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airflow is a problem, the blower speed can be changed. Application of the unit to un-insulated metal ductwork in an unconditioned space will cause poor unit performance and allow condensation to form on the duct and possibly cause damage to the structure.
If the unit is connected to existing ductwork, check the duct system to ensure that it has the capacity to accommodate the air required for the unit application. If the duct is too small, as in the replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repaired as necessary.
Condensate Drain
To facilitate condensate removal, the air handler should be pitched 1/4” towards the drain in both directions. The drain line contains cold water and should be insulated in unconditioned spaces to avoid drain line condensation from dripping on ceiling, etc. The drain pan has a primary and auxiliary drain connection. The 21S521A03 condensate hose assembly kit is provided to connect the drain pan's primary stainless steel tube to the PVC coupling The air handler drain connections must be connected to a drain line and pitched away from the unit a minimum of 1/8” per foot to allow the condensate to flow away from the air handler. A trap must be installed in the drain line below the bottom of the drain pan to ensure free condensate flow (units are not internally trapped).
6/9/08
6
General Installation Information cont.
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
The primary condensate drain must be terminated to an open drain or sump. Do not connect the condensate drain to a closed waste system. An open vertical air vent should be installed to overcome line length, friction and static pressure. It is recommended that the auxiliary drain be connected to a drain line for all units. The auxiliary drain should be run to an area where the homeowner will notice it draining. The drain line should not be smaller than the drain connection at the condensate pan. If the air handler is located in an unconditioned space, water in the trap may freeze. It is recommended that the trap material be of a type that will allow for expansion of water when it freezes. Drain lines must be in conformance with local codes.
Air Handler Configuration
The air handler is factory configured for upflow and horizontal left hand air discharge installation (Figure 1). For bottomflow or horizontal right hand discharge, certain field modifications are required.
Warning: Do not lift or reposition the ‘A’ coil by grasping the copper tube header or distributor. This could cause a tubing fracture resulting in a refrigerant leak.
Vent 3/4" PVC Coupling
3/4" PVC
1/8" per foot
3.0"
1.5"
Figure 1 - Factory configuration is top discharge and horizontal left hand air discharge.
7
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
General Installation Information cont.
Bottomflow Application
To convert the air handler for bottomflow applications follow the steps shown below:
1. Remove all access panels. Disconnect the blower harnesses from the motor and loosen ground wire from blower. Remove the blower by removing 2 screws from the blower mounting bracket, and slide the blower assembly out the front. Remove the stiffener bracket in front of coil, 'A' coil/pan assembly and the horizontal drain pan. This will lighten the cabinet and make it easier to maneuver.
2. Rotate the cabinet 180° from the upright position so that the discharge air opening is located at the bottom and the return air opening is at the top.
3. Install the blower assembly into the blower discharge opening at the bottom of the cabinet by sliding the blower mounting bracket under the discharge support bracket and secure in place with 2 screws. The blower harness and motor ground wire should be reattached before sliding the blower into place.
4. On the 042-060 install the NAHBC bottomflow conversion kit per instructions in the kit. Failure to install this kit will result in condensate blow-off from the 'A' coil into the cabinet and ductwork.
5. Install the 'A' coil into the upper section of the cabinet as pictured in Figure 2. Attach the stiffener bracket into the two holes provided in the cabinet so that the bracket is in front of the coil. The horizontal drain pan is not needed and must be discarded. Plug the 2 drain hole openings in the access panel with the plugs provided.
6. Replace the access panels.
7. Bottom air discharge units require the supply air opening to be cut at least a 1/2” larger than the unit’s air outlet.
8. When installed on combustible flooring, protect the edges of the floor opening with sheet metal over wrap or
other non-combustible material.
9. Bottom air discharge units should be sealed well to the floor to prevent air leakage.
Figure 2 - Bottomflow Air Handler
Horizontal Right Air Discharge Application
To convert air handler for horizontal right air discharge applications follow the steps shown below
1. Remove all access panels. Remove the stiffener bracket in front of the coil, ‘A’ coil assembly and the horizontal drain pan.
2. From the vertical upflow position, rotate the top of the cabinet 90° to the right and set in place.
3. Remove the support bracket mounted to the top plate of the ‘A’ coil. Rotate the ‘A’ coil support bracket 180° from its original position and re-attach into existing holes in the top plate of the coil. This must be done to prevent the ‘A’ coil from falling into the drain pan (Figure 3).
4. Move the horizontal drain pan from the left side of the ‘A’ coil to the right hand side of the ‘A’ coil. Place the ‘A’ coil and horizontal drain pan assembly into the cabinet so that the support bracket is resting in the horizontal drain pan as shown in Figure 3. Attach the stiffener bracket into the two holes provided in the cabinet so that the bracket is in front of the coil.
5. Remove the 2 drain plugs from the upper right of the access panel and install them on the lower left of the access panel. Replace the access panels.
6. If the unit is suspended, the entire length of the cabinet should be supported.
Figure 3 - Horizontal Right Hand Air Discharge
Rotate the coil support bracket to this position
Important: When removing the coil, there is possible danger of equipment damage and personal injury. Be careful when removing the coil assembly from the unit.
8
General Installation Information cont.
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Air Handler Installation
The air handler is attached to the shipping pallet with screws. Prior to setting the unit in place remove the shipping screws located in the front base right behind the air filter access panel. Also remove the external shipping brackets at the rear of the cabinet.
An air filter must always be installed upstream of the air coil on the return air side of the air handler. An air filter is provided with the air handler. If there is limited access to the filter rack for normal maintenance, it is suggested that a return air filter grille be installed. In this instance the filter supplied with the air handler should be removed. Be sure that the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the filter and plugging the air coil.
The cabinet should be sealed so that unconditioned warm air can not enter the cabinet. Warm air will introduce moisture into the cabinet which could result in water blow-off problems, especially when installed in an unconditioned space. Make sure that the liquid line, suction line and drain line entry points into the cabinet are well sealed. Use the butyl tape supplied with the air handler to seal around the copper lines entering the cabinet.
All wall penetrations should be sealed properly. The line set should not come into direct contact with water pipes, floor joists, wall studs, duct work, floors, walls and brick. The line set should not be suspended from joists or studs with a rigid wire or strap which comes into direct contact with the tubing. Wide hanger straps which conform to the shape of the tubing are recommended. All line sets should be insulated with a minimum of 3/8” closed cell insulation. The line set insulation should be pliable, and should completely surround the refrigerant line. As in all R-410a equipment, a reversible liquid line filter drier is required to insure all moisture is removed from the system. This drier is factory installed in the series compressor section. This drier should be replaced whenever “breaking into” the system for service. All exterior insulation should be painted with UV resistant paint or covering to insure long insulation life.
Connection to the Coil
Connect the refrigerant line set to the ‘A’ coil tubes. Nitrogen should be bled through the system at 2 to 3 PSI to prevent oxidation inside the refrigerant tubing. Use a low silver phos­copper braze alloy on all brazed connections. The air handler TXV bulb is secured to the ‘A’ coil for shipping. The indoor and outdoor compressor section is shipped with a factory charge and the service valves are not to be opened until the line set and air handler have been leak tested, purged and evacuated. A damp towel or heat sink should be used on the service valves to prevent damage caused by excessive heat.
Refer to the Refrigerant Line Sizing table to determine the proper line set configuration for the system being installed. Line sets over 60 feet in length are not recommended. If the line set is kinked or deformed and cannot be reformed, the bad section of pipe should
be replaced. A restricted line set will affect unit performance. Line sets should be routed as directly as possible, avoiding any unnecessary bends and turns.
Important Note: The bulb will need to be attached to the suction line on the outside of the cabinet once the refrigerant line connections have been made.
Leak Testing
The refrigeration line set must be pressurized and checked for leaks before purging and charging the unit. To pressurize the line set, attach refrigerant gauges to the service ports and add an inert gas (nitrogen or dry carbon dioxide) until pressure reaches 60 to 90 PSIG. Never use oxygen or acetylene to pressure test the system. Use an electronic leak detector or a good quality bubble solution to detect leaks on all connections made in the field. Be sure to check the service valve ports and stems for leaks. If a leak is found, repair it and repeat the above steps. For safety reasons do not pressurize the system above 150 PSIG. Purge pressure from the line set slowly when the pressure test is complete. The system is now ready for evacuation.
System Evacuation
Ensure that the line set and air coil are evacuated before opening service valves. The line set and air coil must be evacuated to 250 microns with a good quality vacuum pump and use a vacuum gauge to ensure that air and moisture are removed. With the system shut off from the vacuum pump a sufficient system vacuum is achieved when a 500 micron vacuum can be held for 30 minutes. A fast rise to atmospheric pressure indicates a leak, while a slower rise to around 1500 microns indicates moisture is still present in the system and further evacuation is required.
Refrigeration
The GAH series air handlers are supplied with an expansion device. Once the line set has been brazed into the air handler the txv bulb must be attached to the suction line outside of the cabinet and insulated with foam tape. Be careful not to crush the txv bulb by over-tightening the clamp. The txv supplied has an internal check valve so no external check valve is necessary. The
9
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
General Installation Information cont.
air handler TXV should be adjusted initially per TXV Superheat Adjustments table. Check sub-cooling and superheat, refrigerant charge and TXV may require further adjustment.
Charging the System
Refer to the unit Installation Manual for charging the system, checking sub-cooling/superheat and unit operating parameters. Refer to the Refrigerant Line Sizing table for initial refrigerant
TXV Superheat Adjustment Procedure (see figure 4)
charge amounts used with the compression section.
TXV’s may require adjustment for a specific application.
1. Remove the seal cap from the bottom of the valve.
2. Turn the adjustment screw counterclockwise to increase superheat and clockwise to decrease superheat. One complete 360° turn changes the superheat approximately 3-4°F. You may need to allow as much as 30 minutes after the adjustment is made for the system to stabilize.
3. Once the proper superheat setting has been achieved replace and tighten the seal cap. Warning – There are 8 total (360°) turns on the superheat adjustment stem from wide open to fully closed. When adjusting the superheat stem counterclockwise (superheat increase) and the stop is reached, any further counterclockwise turning adjustment will damage the valve.
NOTE: The air handler is factory supplied with a holding charge of dry nitrogen.
TXV Superheat Adjustments
Part
Number
33P609-01 factory set 33P609-03 factory set 33P609-05 factory set open 2 turns 33P609-06 open 2 turns
GAH022, GAH026,
GAH030
GAH036 GAH042 GAH048 GAH060
Note: When installing these air handlers, follow the table for initial txv setting.
Check sub-cooling and superheat to verify final setting.
Refrigerant Line Sizing
Unit Size
022 GAH022 5/8” OD 3/8” OD 5/8” OD 3/8” OD 3/4” OD 3/8” OD 56 78 030 GAH030 5/8” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 3/8” OD 56 78 036 GAH036 5/8” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 56 86 042 GAH042 3/4” OD 3/8” OD 3/4” OD 3/8” OD 7/8” OD 1/2” OD 74 99 048 GAH048 3/4” OD 3/8” OD 7/8” OD 3/8” OD 7/8” OD 1/2” OD 90 115 060 GAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 92 112 070 GAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 108 132 026 GAH026 5/8” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 52 74 038 GAH036 3/4” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 56 86 049 GAH048 3/4” OD 3/8” OD 7/8” OD 3/8” OD 7/8” OD 1/2” OD 90 115 064 GAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 92 112 072 GAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 104 132
NOTES: * The "Charge Amount with GAH Air Handler" column is based on the charge amount for a GAH Air Handler+Compressor Section/Split.
Additional charge will have to be added accordingly for line set length. After Charge is added adjustments can be made to get appropriate subcooling and superheat. Additional charge for R-410A is 0.50 oz. per ft. for 3/8 in. and 1.0 oz. per ft. for 1/2 in. tube. Longer line sets will significantly reduce capacity and efficiency of the system as well as adversely effect the system reliability due to poor oil return.
Air
Handler
20 feet 40 feet 60 feet
Suction Liquid Suction Liquid Suction Liquid
10
Factory
Charge (oz.)
*Charge Amount
with GAH Air Handler (oz.)
4/6/10
General Installation Information cont.
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Figure 4: Decrease Superheat: Open Valve Increase Superheat: Close Valve
11
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Hydronic Models
The water heater and hydronic air handler must be located indoors and not subject to freezing temperatures. The water heater must be installed in accordance to local codes and its own installation instructions. The piping between the water heater and air handler should be kept to a minimum. Piping should be sized to allow for water velocities of 2’-4’ per second. At average water velocities, air bubbles should be carried along the piping to an air separator where they can be discharged from the system. Water velocities greater than 4’ per second could cause flow noise and should be avoided. If water lines pass through an unconditioned space they should be protected to prevent them from freezing. Valves should be installed to allow system isolation. All closed loop hydronic systems must be equipped with an expansion tank to allow room for the heated liquid to expand. A system is considered closed when a check valve or backflow prevention valve is installed in the cold water pipe upstream of the water heater.
Once piping is complete all air must be purged from the water lines. There is a dole valve at the top of the hydronic coil header that can be opened to purge air from the coil. There is also a plug at the bottom of the hydronic coil header for draining the coil.
Dole valve for air purging
Plug for coil drainage.
Typical Installation. See the Hydronic Application Guide for other applications
30 PSI
RELIEF VALVE
Back Flow Preventer /
Pressure Relief Valve
Dielectric
Unions
Dielectric
Unions
Pressure
Gauge
GEO
STORAGE
TANK
Ý
FPT
Vent
Expansion
Tank
Air
Air
Separator
LOAD PUMP
TO
DSH
P/T Ports
G Series
HYDRONIC AIR HANDLER
FROM
DSH
Source OUT
P/T PortsP/T Ports
*NOTE: A 30 PSI pressure relief valve (Part No: SRV30) should be used in hydronic applications.
Ball Valve
Source IN
G Series
HYDRONIC UNIT
12
Hydronic Models cont.
Water Presure Drop - Hydronic Coil
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Flow gpm
3.0 0.5 0.5 0.5 0.4 0.4 0.4 0.4
4.5 0.9 0.9 0.9 0.8 0.8 0.8 0.8
6.0 1.4 1.4 1.4 1.2 1.2 1.2 1.2
9.0 2.8 2.6 2.5 2.4 2.4 2.4 2.3
12.0 4.6 4.4 4.2 4.0 4.0 4.0 3.9
15.0 7.0 6.8 6.6 6.0 6.0 5.9 5.8
40°F 50°F 60°F 100°F 110°F 120°F 130°F
Pressure Drop (PSI)
Coil Capacity vs. Entering Water Temperature
Entering Water Temperature °F
EAT °F 100 110 120 130 140 150
65 44% 56% 69% 81% 94% 106% 70 37% 50% 63% 75% 87% 100%
13
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Electrical Data
All field wiring must comply with local and national fire, safety and electrical codes. Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Refer to the unit Electrical Data table for fuse and circuit breaker sizing. The thermostat should be connected to the air handler and to the compressor section. Line voltage power should be supplied to the breakers on air handlers with 15kW and 20kW heater kits (see the electric heat control section picture).
15kW and 20kW Wiring Instructions
If two separate circuits are used to supply power to the auxiliary heat kit, the installer will need to verify that each leg of the auxil­iary circuit breakers are wired from the power supply correctly in order for the electric heat kit to operate properly. This can be done by measuring the supply side voltage of the auxiliary heat circuit breakers. Put a voltmenter on the L2 side of Circuit Breaker One and on the L2 side of Circuit Breaker Two. The voltmeter should read approximately 0 volts. If the meter reads high voltage, the aux­iliary heat breakers need to be rewired so that breakers in the aux­iliary heat kit match the wiring of the Disconnect Panel breakers. Meaning, L1 and L2 from one breaker in the disconnect panel must connect to L1 and L2 at one of the auxiliary heat circuit breakers and L1 and L2 from the other breaker in the disconnect panel must connect to L1 and L2 of the other auxiliary heat circuit breaker, making sure that the L1 and L2 from each disconnect breaker matches the L1 and L2 at each of the auxiliary heat breakers.
Air Handler Control Section: Power should be supplied to PB on air handlers with no electric heat and 5kW or 10kW heaters.
On air handlers with no electric heat installed, or with 5kW and 10kW heater kits the power should be supplied to L1 and L2 lugs on PB (see air handler control section picture).
Electric Heat Control Section: Power should be supplied to the breakers on air handlers with 15kW and 20kW heaters.
14
Electrical Data cont.
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Model
022
026
030
036
042
048
060
Rated Voltage of 208/230/60/1 HACR circuit breaker in USA only
Electric Heat Capacity
KW BTUH
240v 240v 208v 240v
00 -
4.8 16,382 single 740 4.0 17.3 20.0 21.3 24.0 26.6 30.0 30 30 0 0 - 4.0 - - 4.0 4.0 5.0 5.0 10 10
4.8 16,382 single 740 4.0 17.3 20.0 21.3 24.0 26.6 30.0 30 30 0 0 - 4.0 - - 4.0 4.0 5.0 5.0 10 10
4.8 16,382 single 740 4.0 17.3 20.0 21.3 24.0 26.6 30.0 30 30
9.6 32,765 single 900 4.0 34.7 40.0 38.7 44.0 48.4 55.0 50 60 0 0 - 4.0 - - 4.0 4.0 5.0 5.0 10 10
4.8 16,382 single 740 4.0 17.3 20.0 21.3 24.0 26.6 30.0 30 30
9.6 32,765 single 900 4.0 34.7 40.0 38.7 44.0 48.4 55.0 50 60 0 0 - 7.0 - - 7.0 7.0 8.8 8.8 15 15
9.6 32,765 single 900 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
14.4 49,147 single
14.4 49,147 0 0 - 7.0 - - 7.0 7.0 8.8 8.8 15 15
9.6 32,765 single 900 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
14.4 49,147 single
14.4 49,147 0 0 - 7.0 - - 7.0 7.0 8.8 8.8 15 15
9.6 32,765 single 900 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60
14.4 49,147 single
14.4 49,147
19.2 65,530 single
19.2 65,530
Supply Circuit
L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60 L3/L4 - 17.3 20.0 17.3 20.0 21.6 25.0 25 25
L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60 L3/L4 - 17.3 20.0 17.3 20.0 21.6 25.0 25 25
L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60 L3/L4 - 17.3 20.0 17.3 20.0 21.6 25.0 25 25
L1/L2 7.0 34.7 40.0 41.7 47.0 52.1 58.8 60 60 L3/L4 - 34.7 40.0 34.7 40.0 43.4 50.0 50 50
Aux. Heat
Minimum
CFM
1,275
1,275
1,275
1,700
Rated Voltage
208-230/60/1 197/253
Voltage Min/
Max
Motor FLA
Heater Ampacity Total Unit FLA
Blower
4.0 - - 4.0 4.0 5.0 5.0 10 10
7.0 52.0 60.0 59.0 67.0 73.8 83.8 80 90
7.0 52.0 60.0 59.0 67.0 73.8 83.8 80 90
7.0 52.0 60.0 59.0 67.0 73.8 83.8 80 90
7.0 69.3 80.0 76.3 87.0 95.4 108.8 100 110
208v 240v 208v 240v 208v 240v
Minimum Circuit
Ampacity
Maximum Fuse/
HACR
7/11/08
Low Voltage Point to Point Wiring
T o Air
Handler
From
Thermostat
To Compressor
Section CC C RR R
GG
OO O Y1 Y1 Y1 Y2 Y2 Y2
W2 W
LL
Air Handler transformer must be 75VA. 5/29/08
15
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Wiring Schematics
Air Handler Wiring Schematic - 208-230/60/1 97P787-02
Legend
Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Internal junction Quick connect terminal
TS
Thermal Limit Switch
Field wire lug
L1
Ground
N.O., N.C.
ER1 to ER4 - Aux heat stage relays
1 – To operate in 208V mode replace the blue transformer wire connected to PB-L2 with red transformer wire.
2 – Jumper wires are Factory Installed, and are needed for
electric heat operation.
3 – Dip switches are used to select the air flow.
Notes:
4 – Use manufacturer’s part number 19P592-01 (jumper bar assembly) when single source power is required.
5 – Low voltage wiring CLASS 2.
P
G
EHC
EHC
1 2 3
PB -
SW1 -
HE -
Light emitting diode - Green
208-230V Relay coil
Electric Heat Contactor
Polarized connector
Power block DIP package 10 position
Heater element
Breaker
Dual Power Supply Connections
If two separate circuits are used to supply power to the auxiliary heat kit, the Installer will need to verify that each leg of the auxiliary heat circuit breakers are wired from the power supply correctly in order for the electric heat kit to operate properly. This can be done by measuring the supply side voltage of the auxiliary heat circuit breakers. Put a voltmeter on the L2 side of Circuit Breaker One and on the L2 side of Circuit Breaker Two. The voltmeter should read approxi If the meter reads high voltage, the auxiliary heat breakers need to be rewired so that breakers in the auxiliary heat kit match the wiring of the Disconnect Panel breakers. Meaning, L1 and L2 from one breaker in the disconnect panel must connect to L1 and L2 at one of the auxiliary heat circuit breakers and L1 and L2 from the other breaker in the disconnect panel must connect to L1 and L2 of the other auxiliary heat circuit breaker, making sure that the L1 and L2 from each d
isconnect breaker matches the L1 and L2 at each
of the auxiliary heat breakers.
mately 0 v
olts.
Yel
Grn/Yel(1)
Thermostat
C
R
Y1 Y2
G
O
W
208-230/60/1
Transformer
24V
Blk/Wh
C
XFRM SEC
R
P3
ODD
Y1 Y2
O/B
W1
W2
G
Black
Red
NOTE 1
Blue
Note 3
C R
SW1
G
W1
PB
L2L1
P4
8
LED
1 2 3 4 5 6 7 8 9
10
On
W2
3
1 16 12
5
7 11
4 10
6 14
15
9
2 13
13
Black (16) Black (12)
Black (11)
Black (10)
Black (14) Black (15)
Black (13)
Air Handler No Electric Heat
Black (8) Black (3)
Black (1)
Black (5) Black (7)
Black (4)
Black (6)
Black (9) Black (2)
Brown
Orange
16 12
11
10
14 15
13
8 3 1
5 7
4
6
9 2
Grn
2 3 4 51
RPM grnd C2 C1 RPM
R COOL
ADJUST
HEAT
DELAY BK
Y1 Y /Y2
On/Off
O W / W1
EM / W2
ECM Blower Motor
16
Wiring Schematics cont.
208-230/60/1
G
PB
L2L1
LED
16 12
1 2 3
11
4 5
10
6 7 8
14
9
10
15
13
W2
Grn(9)
Yel
Grn/Yel(1)
Thermostat
C R
Y1 Y2
G O
W
Transformer
24V
Blk/Wh
C
XFRM SEC
R
ODD
O/B
Black
Red
NOTE 1
Blue
Note 3
P3
C R
On
SW1
Y1 Y2 G
W1
W2
W1
Air Handler 5kW Electric Heat
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Gry(12)
Gry(13)
Gry(6)
HE1
TS1
Gry(4)
Brown Orange
Grn
P4
8
Black (8)
3
Black (3)
1
Black (1) Black (16) Black (12)
5
Black (5)
7
Black (7) Black (11)
4
Black (4) Black (10)
6
Black (6) Black (14) Black (15)
9
Black (9)
2
Black (2) Black (13)
2 3 4 51
8
RPM grnd
3
C2
1
C1
16
RPM
12
R
5
COOL
7
ADJUST
11
HEAT
4
DELAY
10
BK Y1
6
14
Y /Y2
15
On/Off
O
9 2
W / W1
EM / W2
13
ECM Blower Motor
Wht(28)
NOTE 2
P1
C 1 2 3 4
C1234
Grn(9)
ER1
Gray
NO
ER2
NO
ER3
NO
ER4
NO
P2
Electric Heat
Grn(9)
208-230/60/1
G
PB
L2L1
P4
Black (8)
8 3
LED
1 2 3 4 5 6 7 8 9
10
W2
Black (3)
1
Black (1)
16
Black (16)
12
Black (12)
5
Black (5)
7
Black (7)
11
Black (11)
4
Black (4)
10
Black (10)
6
Black (6)
14
Black (14)
15
Black (15)
9
Black (9)
2
Black (2)
Black (13)
13
Yel
Grn/Yel(1)
Thermostat
C R
Y1 Y2
G O
W
Transformer
24V
Blk/Wh
C
XFRM SEC
R
ODD
O/B
Black
Red
NOTE 1
Blue
Note 3
P3 C
R
On
SW1
Y1 Y2
G
W1
W2
W1
Air Handler 10kW Electric Heat
Brown Orange
Yel(7)
Gry(12)
Yel(16)
Gry(13)
Yel(15)
Gry(6)
HE1
HE3
Electric Heat
TS1
TS3
Gry(4)
Yel(5)
Grn
2 3 4 51
8
RPM grnd
3
C2
1
C1
16
RPM
12
R
5
COOL
7
ADJUST
11
HEAT
4
DELAY
10
BK Y1
6
14
Y /Y2
15
On/Off
O
9 2
W / W1 EM / W2
13
ECM Blower Motor
Wht(8)
Grn(9)
NOTE 2
P1
C 1 2 3 4
C1234
TDR
Wht(10)
Blu(11)
Gray
ER1
NO
ER2
NO
ER3
NO
ER4
NO
P2
17
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Wiring Schematics cont.
Grn(9)
PB
L2L1
P4
Black (8)
8
3
LED
1 2 3 4 5 6 7 8 9
10
W2
Black (3)
1
Black (1)
16
Black (16)
12
Black (12)
Black (5)
5
7
Black (7)
11
Black (11)
4
Black (4)
10
Black (10)
6
Black (6)
Black (14)
14 15
Black (15)
9
Black (9)
2
Black (2)
Black (13)
13
Yel
Grn/Yel(1)
Thermostat
C R
Y1 Y2
G O
W
Transformer
24V
Blk/Wh
C
XFRM SEC
R
ODD
Black
Red
NOTE 1
Blue
Note 3
P3
C R
On
SW1
Y1 Y2
G
O/B
W1 W2
W1
Air Handler w/ 15kW Electric Heat
Brown Orange
14
8 3
1 16 12
5
7 11
4 10
6
15
9
2 13
Red (2)
Black(3)
Grn
2 3 4 51
RPM grnd C2 C1 RPM R COOL ADJUST HEAT
DELAY
BK Y1
Y /Y2 On/Off O
W / W1 EM / W2
ECM Blower Motor
Wht(8)
Grn(9)
208-230/60/1
Circuit 2
G
P1
C 1 2 3 4
NOTE 2
L1L2
BRK2
Blk(25)
Yel(26)
C1234
Wht(10)
TDR
208-230/60/1
Gry(24) ER1
Gray
ER2
ER3
ER4
Blu(11)
Circuit 1
BRK1
NO
NO
NO
NO P2
L1L2
Gry(20)
Gry(12)
Blk(14)
Yel(16)
Blk(21)
Yel(22)
EHC
G
Blu
Blu
Note 4
EHC
HE1
TS1
HE2
TS2
HE3
TS3
Electric Heat
Gry(13)
Blk(18)
Yel(17)
Grn(9)
PB
L2L1
P4
Black (8)
8 3
LED
1 2 3 4 5 6 7 8 9
10
W2
Black (3)
1
Black (1)
16
Black (16)
12
Black (12) Black (5)
5 7
Black (7)
11
Black (11)
4
Black (4)
10
Black (10)
6
Black (6) Black (14)
14 15
Black (15)
9
Black (9)
2
Black (2) Black (13)
13
Yel
Grn/Yel(1)
Thermostat
C R
Y1 Y2
G O
W
Transformer
24V
Blk/Wh
C
XFRM SEC
R
ODD
Black
Red
NOTE 1
Blue
Note 3
P3 C
R
On
SW1
Y1 Y2
G
O/B
W1
W2
W1
Air Handler w/ 20kW Electric Heat
Brown Orange
3
1 16 12
5
7 11
4 10
6 14
15
9
2 13
Red (2)
Black(3)
Grn
8
2 3 4 51
RPM grnd C2 C1 RPM R COOL ADJUST HEAT
DELAY
BK Y1
Y /Y2 On/Off O
W / W1 EM / W2
ECM Blower Motor
Wht(8)
Grn(9)
208-230/60/1
Circuit 2
G
P1
C 1 2 3 4
NOTE 2
L1L2
BRK2
Blk(25)
Yel(26)
Pnk(27)
C1234
Wht(10)
TDR
208-230/60/1
Gry(24)
ER1
Gray
ER2
ER3
ER4
Blu(11)
Circuit 1
BRK1
NO
NO
NO
NO P2
L1L2
Gry(20)
Pnk(23)
Gry(12)
Blk(14)
Yel(16)
Blk(21)
Yel(22)
EHC
Pnk(18)
G
Blu
Blu
Note 4
EHC
HE1
TS1
HE2
TS2
HE3
TS3
HE4
TS4
Electric Heat
Gry(13)
Blk(15)
Yel(17)
PNK(19)
18
ECM Blower Control
The ECM blower motor is controlled by an interface board installed in the air handler and allows field selectable CFM settings. The interface board receives inputs from the thermostat and converts them to signals used by the ECM motor. There are four different airflow settings that are field selectable via DIP switches (see Blower Performance table).
Cooling/Heating settings
The cooling/heating CFM settings determine the normal cooling/ heating CFM when the unit is not in dehumidification mode or auxiliary heat mode. DIP switches 1 and 2 ‘off’ is the lowest CFM setting while with DIP switches 1 and 2 ‘on’ is the highest CFM setting. To prevent air coil freeze up, the lowest CFM setting can not be used when dehumidification mode is selected. DIP 9 must be ‘on’ to enable normal airflow settings.
Dehumidification Mode settings
This setting provides for field selection of humidity control (via setting DIP 9 ‘off’). The cooling airflow settings are determined by the Cooling/Heating DIP switch settings above. Dehumidification mode reduces the selected normal cooling CFM by 15%-20% which increases the moisture removing capability of the heat pump. To prevent air coil freeze up, the lowest CFM setting can not be used when dehumidification mode is selected.
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Dehumidification Mode (Continuous) – This mode is selected via setting DIP 9 ‘off’ on the ECM interface board and will be engaged whenever an ‘O’ input is present. In this mode any time the unit is operating in cooling mode, it will run at a CFM level 15%-20% lower than the selected normal cooling CFM.
NOTE: Do not select dehumidification mode if the lowest Cooling/ Heating airflow level is selected (DIPS 1 & 2 off).
Auxiliary Heat settings - DIP 5 & 6 on the ECM interface board are used to select the desired CFM in auxiliary/emergency heat mode. Whenever auxiliary or emergency electric heat is energized this air flow setting will be used.
19
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Blower Performance
Blower Performance Variable Speed ECM
Max
Model
022
026
030
036
042
048
060
Factory CFM settings are in boldface
CFM is controlled within 5% up to maximum ESP Maximum ESP includes allowance for wet coil and standard fi lter DIP switch 9 must be 'OFF' to select dehumidifi cation mode
Blower ESP (wg)
0.50 1/2 On On 900 700 450 Off 775 600 450 On On 1000
0.50 1/2 Off On 800 625 400 Off 680 530 400 Off On 800
0.50 1/2 On Off 700 540 375 Off 600 450 375 On Off 775
0.50 1/2 Off Off 640 480 350 Off Off 740
0.50 1/2 On On 1050 800 525 Off 850 700 525 On On 1150
0.50 1/2 Off On 925 725 475 Off 760 620 475 Off On 950
0.50 1/2 On Off 800 625 425 Off 670 540 425 On Off 925
0.50 1/2 Off Off 740 575 400 Off Off 825
0.50 1/2 On On 1150 950 600 Off 975 775 600 On On 1250
0.50 1/2 Off On 980 780 500 Off 825 640 500 Off On 1000
0.50 1/2 On Off 900 700 440 Off 750 580 440 On Off 975
0.50 1/2 Off Off 800 630 425 Off Off 900
0.50 1/2 On On 1300 1025 760 Off 1105 871 760 On On 1300
0.50 1/2 Off On 1225 950 685 Off 1041 808 685 Off On 1250
0.50 1/2 On Off 1150 850 620 Off 940 690 620 On Off 1225
0.50 1/2 Off Off 1075 800 550 Off Off 1200
0.75 1 On On 1500 1100 750 Off 1250 900 750 On On 1550
0.75 1 Off On 1425 1010 650 Off 1180 840 650 Off On 1450
0.75 1 On Off 1300 975 635 Off 1080 800 635 On Off 1400
0.75 1 Off Off 1150 850 625 Off Off 1275
0.75 1 On On 1700 1300 975 Off 1400 1080 975 On On 1700
0.75 1 Off On 1625 1240 875 Off 1350 1025 875 Off On 1550
0.75 1 On Off 1450 1100 750 Off 1200 900 750 On Off 1525
0.75 1 Off Off 1300 1000 675 Off Off 1400
0.75 1 On On 1850 1750 1175 Off 1540 1450 1175 On On 1850
0.75 1 Off On 1760 1625 1050 Off 1460 1350 1050 Off On 1760
0.75 1 On Off 1720 1575 1015 Off 1425 1300 1015 On Off 1725
0.75 1 Off Off 1680 1525 975 1428 Off Off 1700
Motor
(hp)
HP CFM Setting Normal Mode Htg & Clg Dehumidification Mode Clg Aux CFM Setting Aux
S1 S2 Stg 2 Stg 1 Blower S9 Stg 2 Stg 1 Blower S5 S6
Emerg
Mode
2/3/10
DIPS Switch Description
Air Handler DIP
Switches
1 2 3 4 5 6 7 8 9 Used to set dehumidification CFM
10 Not used
Used to set normal CFM
Not used
Used to set aux./emergency heat CFM
Not used
20
Dimensional Data - DX Air Handler
Top Flow/Horizontal Unit Configuration
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
TOP VIEW
DD CC
EE
FF
GG
HH
BOTTOM VIEW
JJ
LL MM
FRONT VIEW
D
II
J
K
L
AA
BB
P
Q
R
S
T U
V
A
M
O
N
RIGHT SIDE VIEW
W
G
C
E
F
B
H I
Topflow/ Overall Cabinet
Horizontal
Configuration
026-060
DEF
AB C
Width Depth Height
3/4" cond 1/2" cond Return
Power
Supply
in. 21.0 26.1 57.3 54.0 52.3 0.7 58.1 27.4 28.3 26.8 24.3 16.0 9.8 4.0 3.1 0.8 1.5 10.5 15.5
cm. 53.4 66.3 145.6 137.2 132.7 1.8 147.4 69.6 71.8 68.1 61.7 40.6 24.9 10.2 7.9 2.0 3.9 26.7 39.4
STUVW
15.5 18.0 19.5 20.1 59.5 15.1 53.1 51.3 7.8 5.2 1.5 18.0 1.5 18.0 2.0 2.0 2.0 22.1 2.0 16.9
39.4 45.8 49.5 51.0 151.1 38.4 134.9 130.2 19.8 13.2 3.8 45.7 3.8 45.7 5.1 5.1 5.1 56.2 5.0 42.9 5.0
Condensate is stainless steel 3/4" O.D. tube Discharge flange is field installed and extends 1" (25.4 mm) from cabinet
Low
Voltage
Air Duct
Flange
XYZAABB CC DD EE FF
21
GHI JK L M NOPQRS
Refrigerant/Water
Connections
Suction /
Water Out
Liquid /
Water In
GG HH II
1" cond
Power
Supply
1/2" cond
Low
Voltage
JJ
KK LL MM
1.96
Rev: 4/28/14
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Dimensional Data DX Air Handler
Bottom Flow Unit Configuration
TOP VIEW
JJ
KK
LL
MM
FRONT VIEW
A
X
W
V
U
T S R
RIGHT SIDE VIEW
I
B
0.71 F
H
Y
G
C
BOTTOM VIEW
DD
EE
FF
CC
J
K
L
AA
BB
P
M
N
O
D
E
GG
Bottomflow
Configuration
026-060
HH II
Z
Overall Cabinet
DEF
ABC
Width Depth Height
3/4" cond 1" cond Return
Low
Voltage
Power
Supply
Air Duct
Flange
GH I JK L M NOPQR
Q
Refrigerant/Water
Connections
Suction /
Water Out
Liquid /
Water In
in. 21.0 26.1 57.3 5.1 3.3 0.7 58.1 27.4 28.3 51.9 49.4 41.2 34.9 29.2 28.2 6.1 4.2 0.9
cm. 53.4 66.3 145.6 12.9 8.5 1.8 147.4 69.6 71.8 131.8 125.5 104.7 88.7 74.2 71.6 15.4 10.8 2.4
CC DD
STUVW
XYZAA
BB
1" cond
Power
Supply
1.5 10.5 15.5 18.0 19.5 20.1 59.1 15.1 32.9 30.4 2.0 2.0 2.0 18.0 1.5 18.0 1.5 22.1 2.0 16.9
EE
1/2" cond
Low Voltage
FF GG
HH
II JJ
KK LL MM
1.96
3.9 26.7 39.4 45.8 49.5 51.0 150.0 38.4 83.6 77.2 5.1 5.1 5.1 45.7 3.8 45.7 3.8 56.2 5.0 42.9 5.0
Condensate is stainless steel 3/4" O.D. tube
Rev: 4/28/14
Discharge flange is field installed and extends 1" (25.4 mm) from cabinet
22
Dimensional Data - Hydronic Air Handler
Top Flow/Horizontal Unit Configuration
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
TOP VIEW
DD CC
EE
FF
GG
HH
BOTTOM VIEW
JJ
LL MM
FRONT VIEW
D
II
J
K
L
AA
BB
P
Q
R
S
T U
V
A
M
O
N
RIGHT SIDE VIEW
W
G
C
E
F
B
H I
Topflow/ Overall Cabinet
Horizontal
Configuration
026-060
DEF
AB C
Width Depth Height
3/4" cond 1/2" cond Return
Power Supply
in. 21.0 26.1 57.3 54.0 52.3 0.7 58.1 27.4 28.3 26.8 24.3 15.9 9.5 4.0 3.1 0.8 1.5 10.5 15.5
cm. 53.4 66.3 145.6 137.2 132.7 1.8 147.4 69.6 71.8 68.1 61.7 40.4 24.0 10.2 7.9 2.0 3.9 26.7 39.4
STUVW
15.5 18.0 19.5 20.1 59.5 15.1 53.1 51.3 7.8 4.9 1.5 18.0 1.5 18.0 2.0 2.0 2.0 22.1 2.0 16.9
39.4 45.8 49.5 51.0 151.1 38.4 134.9 130.2 19.8 12.5 3.8 45.7 3.8 45.7 5.1 5.1 5.1 56.2 5.0 42.9 5.0
Condensate is stainless steel 3/4" O.D Discharge flange is field installed and extends 1" (25.4 mm) from cabinet
Low
Air Duct
Voltage
Flange
XYZAABB CC DD EE FF
23
GHI JK L M NOPQRS
Refrigerant/Water
Connections
Suction /
Water Out
Liquid /
Water In
GG HH II
1" cond
Power
Supply
1/2" cond
Low
Voltage
JJ
KK LL MM
1.96
Rev: 8/15/14
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Dimensional Data - Hydronic `Air Handler
Bottom Flow Unit Configuration
TOP VIEW
JJ
KK
LL
MM
FRONT VIEW
A
X
W
V
U
T S R
RIGHT SIDE VIEW
I
B
0.71 F
H
Y
G
C
BOTTOM VIEW
DD
EE
FF
CC
J
K
L
AA
BB
P
M
N
O
D
E
GG
Bottomflow
Configuration
026-060
HH II
Z
Overall Cabinet
DEF
ABC
Width Depth Height
3/4" cond 1" cond Return
Low
Voltage
Power Supply
Air Duct
Flange
GH I JK L M NOPQR
Q
Refrigerant/Water
Connections
Suction /
Water Out
Liquid /
Water In
in. 21.0 26.1 57.3 5.1 3.3 0.7 58.1 27.4 28.3 51.9 49.4 41.2 34.6 29.2 28.6 6.1 4.2 0.9
cm. 53.4 66.3 145.6 12.9 8.5 1.8 147.4 69.6 71.8 131.8 125.5 104.7 87.9 74.2 72.7 15.4 10.8 2.4
CC DD
STUVW
XYZAA
BB
1" cond
Power
Supply
1.5 10.5 15.5 18.0 19.5 20.1 59.1 15.1 32.9 30.4 2.0 2.0 2.0 18.0 1.5 18.0 1.5 22.1 2.0 16.9
EE
1/2" cond
Low Voltage
FF GG
HH
II JJ
KK LL MM
1.96
3.9 26.7 39.4 45.8 49.5 51.0 150.0 38.4 83.6 77.2 5.1 5.1 5.1 45.7 3.8 45.7 3.8 56.2 5.0 42.9 5.0
Condensate is stainless steel 3/4" O.D
Rev: 8/15/14
Discharge flange is field installed and extends 1" (25.4 mm) from cabinet
24
Unit Start Up
• Check that supply voltage matches nameplate data.
• Fuses, breakers and wire size are correct.
• Confirm that the 15kW or 20kW auxiliary heat kit is wired correctly (see "Electrical Data" section if applicable).
• Low voltage wiring is complete.
• Piping is complete and water system is cleaned and flushed.
• Air is purged from the closed loop system.
• Isolation valves are open, water control valves or pumps are wired.
• Condensate line is open and correctly pitched.
• Transformer switched to 208v if applicable.
• DIP switches are set correctly.
• Blower rotates freely.
• Blower speed is correct.
• Air filter/cleaner is clean and in position.
• Service/access panels are in place.
• Return air temperature is between 50-80°F heating and 60-95° cooling.
• Check air coil cleanliness to insure optimum performance. Clean as needed according to maintenance guidelines. To obtain maximum performance the air coil should be cleaned before startup. A 10 percent solution of dishwasher detergent and water is recommended for both sides of coil. A thorough water rinse should follow.
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Maintenance Filters
Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating conditions and be replaced when necessary. Units should never be operated without a filter. Always replace the filter with the same type as originally furnished.
Condensate Drain
In areas where airborne bacteria produce slime in the drain pan, it may be necessary to treat chemically to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty filters.
Blower Motors
The ECM motor is equipped with sealed ball bearings and requires no periodic lubrication.
Air Coil
The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum clean. Care must be taken not to damage the aluminum fins while cleaning.
Caution: Fin edges are sharp.
25
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Replacement Procedures
Obtaining Parts
When ordering service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an explanation of the malfunctions and a description of the replacement parts required.
In Warranty Material Return
Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor for warranty return authorization and assistance.
Service Parts
Part Description
Air Coil 61S641-02 61S640-02 61S642-02
TXV 33P609-01 33P609-03 33P609-05 33P609-06 N/A
Refrigeration
Blower Assembly 54S555-01 54S555-02 54S555-03 54S555-04 54S556-01 54S556-02 54S556-03 54S555-01 54S555-02 54S556-02 54S556-03
ECM Blower Housing 53P501B01 53P501B01
ECM Motor 208-230/60/1
ECM Power Harness 11P585B01 11P585B01
ECM Motor & Blower
ECM Control Harness 11P598-01 11P598-01
Control board 17P551-01 17P551-01
Transformer 15P501B01 15P501B01
Electrical
Power Block 12P501A02 12P501A02
Ground Lug 12P004A 12P004A
022****R 026****R 030****R 036****R 042****R 048****R 060****R 026****H 036****H 048****H 060****H
14S555-01 14S555-02 14S555-03 14S555-04 14S556-01 14S556-02 14S556-03 14S555-02 14S555-04 14S556-02 14S556-03
DX Refrigerant Models Hydronic Models
Air Filter 20” x 24” x 1”
Filter
59P020B14 59P020B14
08/14/14
26
ASTON SERIES AIR HANDLER INSTALLATION MANUAL
Revision Guide
Pages: Description: Date: By:
16-19, 26 Updated Wiring Schematics, Unit Start Up 01 April 2015 MA
5-7, 22-24 Updated Hydronic Data 15 Aug 2014 MA
4-6,19,20 Updated Drain Pan 20 May 2014 DS/MA
All Updated Dimensional Data for New Vertical Condensate Drain 02 May 2014 DS All Updated Nomenclature For New ECM Motor 20 Feb 2013 DS 22 Added Service Parts List 20 Feb 2013 DS 23 Added Revision Guide 20 Feb 2013 DS
27
©2015 The manufacturer has a policy of continual product research and development and reserves the right to change design and specifi cations without notice.
Product: Aston Series Air Handler Type: Hydronic or R-410A Size: 2 - 5 Tons
Document Type: Installation Manual Part Number: IM1008HG Release Date: 07/15
Loading...