0 – No HWG, No GeoStart
1 – HWG with Factory Installed Pump, No GeoStart
3 – No HWG, GeoStart
4 – HWG with Factory Installed Pump, GeoStart
*049AA10AC013015A160
®
10111214
17
Future Option
0 - Standard
Controls
A – Aurora
Future Option
0 – Standard
Future Option
0 – Standard
Coax Option
C – Copper
N – CuproNickel
Future Option
A – None
Rev.: 08 October 2013D
TM
Base Control
4
Page 5
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
General Installation Information
Safety ConsiderationsDuct System
WARNING: Before performing service or maintenance
operations on a system, turn off main power switches
to the indoor unit. If applicable, turn off the accessory
heater power switch. Electrical shock could cause
personal injury.
Installing and servicing heating and air conditioning equipment can
be hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, repair or
service heating and air conditioning equipment. Untrained personnel
can perform the basic maintenance functions of cleaning coils
and cleaning and replacing filters. All other operations should be
performed by trained service personnel. When working on heating
and air conditioning equipment, observe precautions in the literature,
tags and labels attached to the unit and other safety precautions that
may apply, such as the following safety measures:
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use a quenching cloth for brazing operations.
• Have a fire extinguisher available for all brazing operations.
Moving and Storage
Move units in the normal “up” orientation. Units may be moved and
stored per the information on the packaging. Do not stack more
than three units in total height. Do not attempt to move units while
stacked. When the equipment is received, all items should be
carefully checked against the bill of lading to be sure all crates and
cartons have been received. Examine units for shipping damage,
removing the units from the packaging if necessary. Units in
question should also be internally inspected. If any damage is noted,
the carrier should make the proper notation on the delivery receipt,
acknowledging the damage.
Unit Location
NOTE: Prior to setting the unit in place, remove and discard the
compressor shipping bolt located at the front of the compressor
mounting bracket.
Locate the unit in an indoor area that allows for easy removal of
the access panels. Location should have enough space for service
personnel to perform maintenance or repair. Provide sufficient room
to make water, electrical and refrigerant line connections. Any
access panel screws that would be difficult to remove after the unit
is installed should be removed prior to setting the unit. Care should
be taken when units are located in unconditioned spaces to prevent
damage from frozen water lines and excessive heat that could
damage electrical components.
Air Coil Location
Refer to the air handler manufacturer’s instructions for the blower coil
unit for details on installing the air handling portion of the system.
Condensate Drain
Follow the blower coil manufacturer’s instructions.
All blower coil units/air coils must be installed as specified by the
manufacturer’s installation instructions; however, the following
recommendations should be considered to minimize noise and
service problems.
An air filter must always be installed upstream of the air coil on
the return air side of the air handler or furnace. If there is limited
access to the filter rack for normal maintenance, it is suggested
that a return air filter grill be installed. Be sure that the return duct
is properly installed and free of leaks to prevent dirt and debris
from bypassing the filter and plugging the air coil.
In applications using galvanized metal ductwork, a flexible duct
connector is recommended on both the supply and return air
plenums to minimize vibration from the blower. To maximize sound
attenuation of the unit blower, the supply and return plenums
should include an internal duct liner of 1-inch thick glass fiber or
be constructed of ductboard. Insulation is usually not installed in
the supply branch ducts. Ducts in unconditioned areas should be
wrapped with a minimum of 1-inch duct insulation. Application of
the unit to uninsulated ductwork in an unconditioned space is not
recommended as the unit’s performance will be adversely affected.
If the air handler is connected to existing ductwork, a previous
check should have been made to assure that the duct system has
the capacity to handle the air required for the unit application. If
ducting is too small, as in replacement of heating only systems,
larger ductwork should be installed. All existing ductwork should be
checked for leaks and repairs made accordingly. The duct systems
and diffusers should be sized to handle the design airflow quietly.
If air noise or excessive airflow is a problem, the blower speed can
be changed to a lower speed to reduce airflow. This will reduce the
performance of the unit slightly in heating; however, it will increase
the temperature rise across the air coil. Airflow must still meet
minimum requirements.
Equipment Selection
The following guidelines should be used when mating a indoor split
to an air handler/coil.
• Select R-410A components only .
• Select 13 SEER or higher air handler/coil.
• Match the air handler to the air handler coil data table.
• Indoor matching adjustable TXV should be used with any air
handler/coil. Fixed orifice or cap tube systems should not be used.
Utilizing Existing Coil or Air Handler
It is recommended that a new R-410A air handler be installed with a
indoor split considering the long term benefits of reliability, warranty,
etc. versus the short term installation cost savings. However, the
existing air handler may be retained provided the following:
• Coil currently is R-410A rated
• Coil uses a TXV. No capillary or fixed orifice systems should
be used
• A life expectancy of more than 7 years remaining for the air
handler and components
• Flush air coil and line set
5
Page 6
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
General Installation Information cont.
When utilizing the existing air coil or line set, only flushing
compounds that vaporize should be used; which means they are
packaged in a pressurized disposable cylinder. It is preferable
to use a flushing agent that removes oil, water, and acid, plus, is
biodegradeable and non-toxic. The flushing agent should be safe to
use with both HCFC and HFC refrigerants. Once a flushing agent
has been selected, follow the instructions provided with the product.
The first step should be purging the lines or air coil with nitrogen.
Purging with nitrogen first will remove some of the particulate and
residual oil which will allow the flushing agent to work better. Never
blow the flushing agent through a compressor, filter drier, or txv as it
will cause the components to fail.
When flushing is complete and the final system is assembled, an
acid check should be preformed on the system. Acid test kits are
available from most HVACR distributors.
Connection to Air Coil
Figures 1 and 2 illustrate typical indoor split installations. Reference
the Line Set Sizes table for typical line set diameters and maximum
length. Line sets over 60 feet are not recommended. Longer line
sets will significantly reduce capacity and efficiency of the system
as well as adversely effect the system reliability due to poor oil
return. If the line set is kinked or deformed and cannot be reformed,
the bad section of pipe should be replaced. A restricted line set will
affect unit performance. As in all R-410A equipment, a reversible
liquid line filter drier is required to insure all moisture is removed
from the system. This drier should be replaced whenever “breaking
into” the system for service. All line sets should be insulated with
a minimum of 1/2 in. closed cell insulation. All exterior insulation
should be painted with UV resistant paint or covering to ensure long
insulation life.
Air Handler Installation
Air handlers used with dual capacity units must be capable
of operating with a minimum of 2 blower speeds. Refer to the
manufacturer’s instructions for the blower coil unit for details on
installing the air handling portion of the system. All blower coil
units/air coils must be installed as specified by the manufacturer’s
installations instructions. However, the following recommendations
should be considered to minimize noise and service problems.
An air filter must always be installed upstream of the air coil on the
return air side of the air handler or furnace. If there is limited access
to the filter rack for normal maintenance, it is suggested that a return
air filter grille be installed. Be sure that the return duct is properly
installed and free of leaks to prevent dirt and debris from bypassing
the filter and plugging the air coil.
Ensure that the line set size is appropriate to the capacity of the
unit (refer to Line Set Sizes table). Line sets should be routed as
directly as possible, avoiding unnecessary bends or turns. All wall
penetrations should be sealed properly. Line set should not come
into direct contact with water pipes, floor joists, wall studs, duct
work, floors, walls and brick. Line set should not be suspended
from joists or studs with a rigid wire or strap which comes into direct
contact with the tubing. Wide hanger strips which conform to the
shape of the tubing are recommended. Isolate hanger straps from
line set insulation by using metal sleeves bent to conform to the
shape of insulation. Line set insulation should be pliable, and should
completely surround the refrigerant line.
NOTES: Improper installation of equipment may result in
undesirable noise levels in the living areas.
Figure 1: Typical Split System Application with Remote Blower Coil
Thermostat Wire
From Air Handler
Disconnect
Insulated Suction Line
Lineset To Air Handler
DHW Out
DHW In
P/T Plugs
Water Out
Water In
Vibration Absorbing Pad or Air Pad
Supply
Duct
Wire To
Thermostat
Remote Air Handler
(Maximum Recommended Distance is
60' Between Units)
6
Return
Duct
To D r a in
Condensate Drain
(must be trapped)
Page 7
General Installation Information cont.
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Dual Fuel Systems
Indoor split units can be connected to fossil fuel furnaces that
include an A-coil or slab coil. Dual fuel installations utilize the
geothermal heat pump for heating until the point that auxiliary
heat is called for on the thermostat. At that point, the furnace will
be enabled and the heat pump will be disabled. The geothermal
heat pump provides air conditioning through the furnace’s
refrigerant coils.
In add-on indoor split applications, the coil should be located in
the supply side of the furnace to avoid condensation damage
to the furnace heat exchanger. A high temperature limit should
be installed upstream of the coil to de-energize the compressor
whenever the furnace is operating. Without this switch, the
indoor split will trip out on high pressure. A dual fuel thermostat
can remove the Y1 and Y2 calls when a W call is energized to
allow gas furnace backup on a indoor split application. Refer to
thermostat wiring diagram for details.
Refer to the furnace manufacturer’s installation manual for
the furnace installation, wiring and coil insertion. A Dual Fuel
thermostat, a field-installed SPST relay or dual capacity
auxiliary heat relay is required. See Figure 2 for typical Dual
Fuel application.
Air Temperature Limit Switch to prevent compressor operation
when entering air is greater than
90°F.
Condensate
Drain
(must be trapped)
DHW Out
DHW In
Return
P/T Plugs
Duct
Water Out
Water In
Vibration Absorbing Pad or Air Pad
Up-Flow
Fossil Fuel
Furnace
7
Page 8
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
General Installation Information cont.
Water Piping
The proper water flow must be provided to each unit whenever the
unit operates. To assure proper flow, use pressure/temperature
ports to determine the flow rate. These ports should be located at
the supply and return water connections on the unit. The proper
flow rate cannot be accurately set without measuring the water
pressure drop through the refrigerant-to-water heat exchanger.
All source water connections on residential units are swivel piping
fittings (see Figure 3) that accept 1 in. male pipe threads (MPT).
The swivel connector has a rubber gasket seal similar to a rubber
hose gasket, which when mated to the flush end of any 1 in.
threaded pipe provides a leak-free seal without the need for thread
sealing tape or compound. Check to ensure that the rubber seal
is in the swivel connector prior to attempting any connection. The
rubber seals are shipped attached to the waterline. To make the
connection to a ground loop system, mate the brass connector
(supplied in CK4L connector kit) against the rubber gasket in the
swivel connector and thread the female locking ring onto the pipe
threads, while maintaining the brass connector in the desired
direction. Tighten the connectors by hand, then gently snug the
fitting with pliers to provide a leak-proof joint. When connecting to
an open loop (ground water) system, thread the 1 in. MPT fitting
(SCH80 PVC or copper) into the swivel connector and tighten in
the same manner as noted above. The open and closed loop piping
system should include pressure/temperature taps for serviceability.
Never use flexible hoses smaller than 1 in. inside diameter on the
unit. Limit hose length to 10 ft. per connection. Check carefully for
water leaks.
Figure 3: Swivel Connections
(Residential Units)
Stainless
Steel
Snap Ring
Gasket
Material
Locking
Ring
Gasket
Support
Sleeve
8
Page 9
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
General Installation Information cont.
Water Quality
In ground water situations where scaling could be heavy or where
biological growth such as iron bacteria will be present, a closed
loop system is recommended. The heat exchanger coils in ground
water systems may, over a period of time, lose heat exchange
capabilities due to a buildup of mineral deposits inside. These
can be cleaned, but only by a qualified service mechanic, as
special solutions and pumping equipment are required. Hot water
generator coils can likewise become scaled and possibly plugged.
In areas with extremely hard water, the owner should be informed
that the heat exchanger may require occasional flushing.
AmmoniaLess than 2 ppmLess than 2 ppmLess than 20 ppm
Ammonia ChlorideLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Ammonia NitrateLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Ammonia HydroxideLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Ammonia SulfateLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Total Dissolved Solids (TDS)Less than 1000 ppm1000 - 1500 ppm1000 - 1500 ppm
LSI Index+0.5 to -0.5+0.5 to -0.5+0.5 to -0.5
2
Iron, FE
Bacterial Iron Potential
+ (Ferrous)
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
(Total Hardness)
less than 350 ppm
Less than 0.5 ppm (rotten egg
smell appears at 0.5 ppm)
< 0.2 ppm< 0.2 ppm< 0.2 ppm
Less than 1 ppm, above this level
deposition will occur
Less than 10 ppm and filtered for
max. of 600 micron size
< 6 ft/sec< 6 ft/sec< 6 ft/sec
Units with cupronickel heat exchangers are recommended for
open loop applications due to the increased resistance to build-up
and corrosion, along with reduced wear caused by acid cleaning.
Failure to adhere to the guidelines in the water quality table could
result in the loss of warranty.
(Total Hardness)
less than 350 ppm
10 - 50 ppmLess than 1 ppm
Less than 1 ppm, above this level
deposition will occur
Less than 10 ppm and filtered for
max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this level
deposition will occur
Less than 10 ppm and filtered for
max. of 600 micron size
2/22/12
Low Water Coil Limit
Set the freeze sensing switch SW2-1 on the Aurora Base Control
(ABC) printed circuit board for applications using a closed loop
antifreeze solution to “LOOP” (15°F). On applications using an
open loop/ground water system (or closed loop no antifreeze), set
this dip switch to “WELL” (30°F), the factory default setting. (Refer
to the DIP Switch Settings table in the Aurora Control section.)
9
Page 10
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Closed Loop - Ground Source Systems
NOTE: For closed loop systems with antifreeze protection, set
SW2-1 to the “LOOP” (15°F) position. (Refer to the DIP Switch Settings table in the Aurora Control section.)
Once piping is completed between the unit, pumps and the ground
loop (see figure below), final purging and charging of the loop is
required. A flush cart (or a 1.5 HP pump minimum) is needed to
achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas
to prevent freezing. Flush the system adequately to remove as
much air as possible then pressurize the loop to a static pressure of
40-50 psi (summer) or 50-75 psi (winter). This is normally adequate
for good system operation. Loop static pressure will fluctuate with
the seasons. Pressures will be higher in the winter months than
during the cooling season. This fluctuation is normal and should be
considered when initially charging the system.
After pressurization, be sure to turn the venting (burping) screw in
the center of the pump two (2) turns open (water will drip out), wait
until all air is purged from the pump, then tighten the plug. Ensure
that the loop pumps provide adequate flow through the unit(s) by
checking the pressure drop across the heat exchanger and comparing it to the unit capacity data in this catalog. 2.5 to 3 gpm of flow per
ton of cooling capacity is recommended in earth loop applications.
Multiple Units on One Flow Center
When two units are connected to one loop pumping system, pump
control is achieved by following Figure 5. Installer will be required to
supply fuses, two relays, and wiring.
NOTE: Additional information can be found in Flow Center
installation manual and Flush Cart manual.
10
Page 11
Open Loop - Well Water Systems
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Typical open loop piping is shown below. Always maintain
water pressure in the heat exchanger by placing water control
valves at the outlet of the unit to prevent mineral precipitation.
Use a closed, bladder-type expansion tank to minimize mineral
formation due to air exposure. Ensure proper water flow through
the unit by checking pressure drop across the heat exchanger
and comparing it to the figures in unit capacity data tables in the
specification catalog. 1.5-2 gpm of flow per ton of cooling capacity
is recommended in open loop applications.
Discharge water from the unit is not contaminated in any manner
and can be disposed of in various ways, depending on local codes,
Figure 6: Typical Split System Application Open Loop Well Water
Thermostat Wire
From Air Handler
Disconnect
Vibration Absorbing Pad or Air Pad
Lineset
T o Air Handler
Boiler Drains for
System Flushing
P/T Plugs
Rubber Bladder
Pressure Tank
Water Solenoid
Control Valve
Flow
Regulator
Shut-Off Valves
Water Out
Water In
From W ell
Figure 7a: Open Loop Solenoid Valve Connection Option
Typical quick operating external 24V water solenoid valve
(type PPV100 or BPV100) wiring.
i.e. recharge well, storm sewer, drain field, adjacent stream or
pond, etc. Most local codes forbid the use of sanitary sewer for
disposal. Consult your local building and zoning departments to
assure compliance in your area.
NOTE: For open loop/groundwater systems or systems that do not
contain an antifreeze solution, set SW2-Switch #1 to the “WELL”
(30°F) position. (Refer to the DIP Switch Settings table in the
Aurora Control section.) Slow opening/closing solenoid valves
(type V or VM) are recommended to eliminate water hammer.
Figure 7b: Open Loop Solenoid Valve Connection Option
NOTE: SW2-4 and SW2-5 should be “OFF” to cycle with
the compressor.
P2
R
VM Valve
Acc Com
ACC NC
Acc NO
ABC Board
NOTE: SW2-4 should be “ON” and SW2-5 should be “OFF” when
using a slow opening (V or VM) water valve.
11
Page 12
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Hot Water Generator Connections
The heat reclaiming hot water generator coil is vented double-wall
copper construction and is suitable for potable water. To maximize
the benefits of the hot water generator a minimum 50-gallon water
heater is recommended. For higher demand applications, use an
80-gallon water heater or two 50-gallon water heaters connected
in a series as shown below. A geo storage tank should not be used
in this application unless it is plumbed in a series with an electric
water heater. The geo storage tank is equipped with a single 4500
Watt element and will not be able to provide adequate water heating
if used as a standalone water heater. Electric water heaters are
recommended. Make sure all local electrical and plumbing codes
are followed when installing a hot water generator. Residential units
with hot water generators contain an internal circulator and fittings. A
water softener is recommended for hard water applications (greater
than 10 grains or 170 ppm total hardness).
Water Tank Preparation
To install a unit with hot water generator, follow these
installation guidelines.
1. Turn off the power to the water heater.
2. Attach a water hose to the water tank drain connection and
run the other end of the hose to an open drain or outdoors.
3. Close the cold water inlet valve to the water heater tank.
4. Drain the tank by opening the valve on the bottom of the tank,
then open the pressure relief valve or hot water faucet.
Figure 8: Typical Hot Water Generator Installation
Ý[Ý[ÝWHH
Venting Waste Valve
or Vent Coupling
HWG
Water Out
Cold
Water In
P/T Relief
Water Out
Valv e
Hot
5. Flush the tank by opening the cold water inlet valve to the
water heater to free the tank of sediments. Close when
draining water is clear.
6. Disconnect the garden hose and remove the drain valve from
the water heater.
7. Refer to Plumbing Installation and Hot Water
Generator Startup.
CAUTION: Elements will burn out if energized dry.
Figure 9: Hot Water Generator Installation in Preheat Tank
Hot
Water Out
P/T Relief
Valve
Venting W a ste Valve
or Vent Coupling
Ý[Ý[ÝWHH
HWG
Water Out
Cold
Water In
P/T Relief
Valve
HWG
Water In
Drain Valve
In
HWG
Water In
Drain Valve Drain Valve
In
12
Page 13
Hot Water Generator Connections cont.
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Plumbing Installation
1. Inspect the dip tube in the water heater cold inlet for a check
valve. If a check valve is present it must be removed or
damage to the hot water generator circulator will occur.
2. Remove drain valve and fitting.
3. Thread the 3/4-inch NPT x 3-1/2-inch brass nipple into the
water heater drain port.
4. Attach the center port of the 3/4-inch FPT tee to the opposite
end of the brass nipple.
5. Attach the 1/2-inch copper to 3/4-inch NPT adaptor to the side
of the tee closest to the unit.
6. Install the drain valve on the tee opposite the adaptor.
7. Run interconnecting tubing from the tee to hot water generator
water out.
8. Cut the cold water “IN” line going to the water heater.
9.
Insert the reducing solder tee in line with cold water “IN” line
as shown.
10.
Run interconnecting copper tubing between the unit hot water
generator water “IN” and the tee (1/2-inch nominal). The
recommended maximum distance is 50 feet.
11.
To prevent air entrapment in the system, install a vent coupling
at the highest point of the interconnecting lines.
12. Insulate all exposed surfaces of both connecting water lines
with 3/8-inch wall closed cell insulation.
NOTE: All plumbing and piping connections must comply with local
plumbing codes.
Hot Water Generator Switch
The hot water generator switch is taped in the disabled position
at the factory.
Hot Water Generator Startup
1. Turn the hot water generator switch to the “ON” position. The hot
water generator switch will allow the hot water generator pump to
be enabled or disabled by the service technician or homeowner.
2. Close the drain valve to the water heater.
3. Open the cold water supply to the tank.
4. Open a hot water faucet in the building to bleed air from the
system. Close when full.
5. Open the pressure relief valve to bleed any remaining air from
the tank, then close.
6. If so equipped, turn the venting (burping) screw in the center
of the pump two (2) turns open (water will drip out), wait until
all air is purged from the pump, then tighten the plug. Use vent
couplings to bleed air from the lines.
7. Carefully inspect all plumbing for water leaks and correct
as required.
8. Before restoring electrical supply to the water heater, adjust the
temperature setting on the tank.
• On tanks with both upper and lower elements, the
lower element should be turned down to the lowest
setting, approximately 100°F. The upper element
should be adjusted to 120°F to 130°F. Depending upon
the specific needs of the customer, you may want to
adjust the upper element differently.
• On tanks with a single element, lower the thermostat
setting to 120°F.
9. After the thermostat(s) is adjusted, replace the access cover
and restore electrical supply to the water heater.
10. Make sure that any valves in the hot water generator water
circulating circuit are open.
11. Turn on the unit to first stage heating.
12. The hot water generator pump should be running. When
the pump is first started, turn the venting (burping) screw (if
equipped) in the center of the pump two (2) turns open until
water dribbles out, then replace. Allow the pump to run for at
least five minutes to ensure that water has filled the circulator
properly. Be sure the switch for the hot water generator pump
switch is “ON”.
13. The temperature difference between the water entering and
leaving the hot water generator should be 5°F to 15°F. The water
flow should be approximately 0.4 gpm per ton of nominal cooling.
14. Allow the unit to heat water for 15 to 20 minutes to be sure
operation is normal.
CAUTION: Never operate the HWG circulating pump
while dry. If the unit is placed in operation before
the hot water generator piping is connected, be sure
that the pump switch is set to the OFF position.
13
Page 14
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Electrical Connections
General
Be sure the available power is the same voltage and phase as that
shown on the unit serial plate. Line and low voltage wiring must be
done in accordance with local codes or the National Electric Code,
whichever is applicable.
Unit Power Connection
Connect the incoming line voltage wires to L1 and L2 of the
contactor as shown in Figure 10B for single-phase unit. Consult
the Unit Electrical Data in this manual for correct fuse sizes.
Open front access panel. Insert power wires through knockouts
on the left side of cabinet (Figure 10A). Route wires through left
side of control box and connect to contactor and ground (Figure
10B). Close control box and replace grounding fastener before unit
start-up.
Accessory Relay
A set of “dry” contacts has been provided to control accessory
devices, such as water solenoid valves on open loop installations,
electronic air cleaners, humidifiers, etc. This relay contact should
be used only with 24 volt signals and not line voltage power. The
relay has both normally open and normally closed contacts and
can operate with either the fan or the compressor. Use DIP switch
SW2-4 and 5 to cycle the relay with blower, compressor, or control
a slow opening water valve. The relay contacts are available on
terminals #2 and #3 of P2.
When powering high VA draw components such as electronic air
cleaners or VM type open loop water valves, R should be taken
‘pre-fuse’ from the ‘R’ quick connect on the ABC board and not the
‘post-fuse’ ‘R’ terminal on the thermostat connection. If not, blown
ABC fuses might result.
208 Volt Operation
All 208/230 units are factory wired for 230 volt operation. For
208 volt operation, the red and blue transformer wires must be
switched on terminal strip PB2.
Figure 10A:
Wire access
Figure 10B:
Line Voltage 208-230/60/1 control box
1
PB1
2
L2
L1
T1T2
Wire Insert
Location
14
Page 15
Electrical Connections cont.
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Pump Power Wiring
See Figure 11 for electrical connections from control box
to pumps.
FC1/FC2 style flow centers with fixed speed pumps connect to
PB1 in the control box.
Figure 11: Pump Wiring 208-230/60/1
PB1
External
Loop Pump(s)
208-230/60/1
1/2 hp Max
CB
Electronic Thermostat Installation
Position the thermostat subbase against the wall so that it is
level and the thermostat wires protrude through the middle of
the subbase. Mark the position of the subbase mounting holes
and drill holes with a 3/16-inch bit. Install supplied anchors and
secure base to the wall. Thermostat wire must be 8-conductor
(4 or 5 counductor for communicating thermostats), 20-AWG
(minimum) wire. Strip the wires back 1/4-inch (longer strip
lengths may cause shorts) and insert the thermostat wires into
the connector as shown. Tighten the screws to ensure secure
connections. The thermostat has the same type connectors,
requiring the same wiring. See instructions enclosed in the
thermostat for detailed installation and operation information.
NOTE: Aurora Base Control (ABC) DIP switch SW2-7 is
required to be in the “OFF” position for the control to operate
with FaultFlash or ComforTalk thermostats. SW2-7 in the
“ON” position configures the control to operate with typical
thermostats (continuous lockout signal). There must be a
wire connecting Y2 on the Aurora controller to 2nd stage
compressor on the thermostat for proper operation.
Dimensions are in inches.
Decorative molding and water connections extend 1.2 in. [30.5 mm] beyond the front of the cabinet.
P
N
HWGInHWG
Out
Low
Voltage
External
Pump
Line
Voltage
Knock
Out
Knock
Out
17
Page 18
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Physical Data
Model02203003604204806007002603804906472
Compressor (1 each)Single Speed ScrollDual Capacity Scroll
Factory Charge R410a, oz [kg]
Coax and Water Piping
Water Connections Size - Swivel- in [mm]1 [25.4]1 [25.4]
HWG Connection Size - Female Sweat
(I.D.) - in [mm]
Brass Service Valve - Liquid Line - in [mm]
Brass Service Valve - Suction Line - in [mm]
Coax and Piping Water Volume - gal [l]
Weight - Operating, lb [kg]
Weight - Packaged, lb [kg]
NOTES: All units have TXV expansion devices, and 1/2 in. [12.2 mm] and 3/4 in. [19.1 mm] electrical knockouts.
Brass service valves are sweat type valves.
56
[1.59]
0.7
[2.6]
164
[74]
184
[83]
56
[1.59]
[9.525]
5/8
[15.875]
1.0
[3.8]
174
[79]
194
[88]
56
74
90
92
[22.225]
1.6
251
271
108
[3.06]
1/2
[12.7]
7/8
2.3
[8.7]
292
[132]
312
[142]
[1.59]
[4.9]
[105]
[2.1]
[2.55]
[2.61]
1/2 [12.7]1/2 [12.7]
3/8
3/4
[19.05]
1.3
1.3
213
[97]
233
1.6
[6.1]
246
[112]
266
[121]
[6.1]
[114]
[123]
[4.9]
212
[96]
232
[106]
52
[1.47]
5/8
[15.875]
0.7
[2.6]
189
[186]
209
[95]
[1.59]
[9.525]
3/4 [19.05]
56
90
[2.55]
3/8
1.3
[4.9]
236
[107]
256
[116]
1.6
[6.1]
250
[113]
270
[122]
92
[2.61]
1.6
[6.1]
271
[123]
291
[132]
104 [2.95]
1/2
[12.7]
7/8
[22.225]
2.3
[8.7]
290
[132]
310
[141]
6/27/11
18
Page 19
Model Nomenclature - Air Handler
A
A
1-34-678-9101112
GAH 036*0001R
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Model
GAH – G Series Air Handler
Unit Capacity
Refrigeration (DX) Models with Nominal CFM
The Aurora ‘Base’ Control
(ABC) System is a complete
residential and commercial
comfort system that brings all
aspects of the HVAC system
into one cohesive module
network. The ABC features
microprocessor control and HP,
LP, and freeze detection, over/
under voltage faults, along with
communicating thermostat capability for complete fault detection
text at the thermostat.
urora uses the Modbus communication protocol to communicate
between modules. Each module contains the logic to control all
features that are connected to the module. The Aurora ‘Base’
Control (ABC) has two Modbus channels. The first channel is
configured as a master for connecting to devices such as a
communicating thermostat, expansion board, or other slave
devices. The second channel is configured as a slave for
connecting the Aurora Interface Diagnostics Tool (AID Tool).
Service DeviceDescriptionAurora ‘Base’
Allows setup, monitoring and troubleshooting of any
Aurora Control.
NOTE: Although the ABC has basic compatibility with all Aurora, new
product features may not be available on older AID Tools. To simplify
Aurora Interface and Diagnostics
Add On Thermostats and ZoningDescriptionAurora ‘Base’
TP32U03GSR/04GSR - MonoChrome
Traditional Y1, Y2 Thermostat
Traditional Y1, Y2 Thermostat
IntelliZone
(AID) Tool
TP32S01GSR/02GSR -
®
Zoning Compatibility
the basic compatibility ensure the version of AID is at least the same
or greater than the ABC software version.
Elite Stat with full English fault codes and alerts, traditional Y1, Y2
thermostat
Traditional Y1, Y2 thermostatOptional
IntelliZone® is a non-communicating zoning system requiring Y1, Y2
signals and controls the ECM blower motor directly.
For Service
(Ver. 1.xx or greater)
Optional
Optional
(ECM Preferred)
21
Page 22
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
The Aurora Control System cont.
Aurora ‘Base’ Control
NOTE: Refer to the Aurora Base Control Application and
Troubleshooting Guide and the Instruction Guide: Aurora Interface and
Diagnostics (AID) Tool for additional information.
Control Features
Software ABC Standard Version 2.0
Single or Dual Capacity Compressors
Either single or dual capacity compressors can be operated.
Other Control Features
• Random start at power up
• Anti-short cycle protection
• High and low pressure cutouts
• Loss of charge
• Water coil freeze detection
• Over/under voltage protection
• Load shed
• Emergency shutdown
• Hot gas reheat operation (where applicable)
• Diagnostic LED
• Test mode push button switch
• Two auxiliary electric heat outputs
• Alarm output
• Accessory output with N.O. and N.C.
• Modbus communication (master)
• Modbus communication (slave)
Field Selectable Options via Hardware
DIP Switch (SW1) – Test/Configuration Button (See SW1
Operation Table)
Reset Configuration Mode
The control is placed in reset configuration mode by holding the
push button switch SW1 for 50 to 60 seconds. This will reset
all configuration settings and the EEPROM back to the factory
default settings. LED3 (green) will turn off when entering reset
configuration mode. Once LED3 (green) turns off, release SW1
and the control will reset.
DIP Switch (SW2)
SW2-1 FP1 Selection – Low water coil temperature limit setting
for freeze detection. On = 30°F; Off = 15°F.
SW2-2 FP2 Selection – On = 30°F; Off = N/A
SW2-3 RV – O/B - thermostat type. Heat pump thermostats
with “O” output in cooling or “B” output in Heating can be
selected. On = O; Off = B.
SW2-4 Access Relay Operation (P2)
and 2-5
Access Relay OperationSW2-4SW2-5
Cycle with BlowerONON
Cycle with CompressorOFFOFF
Water Valve Slow OpeningONOFF
Cycle with Comm. T-stat Hum CmdOFFON
Cycle with Blower - The accessory relay will cycle with the
blower output.
Cycle with Compressor - The accessory relay will cycle with the
compressor output.
Water Valve Slow Opening - The accessory relay will cycle and
delay both the blower and compressor output for 90 seconds.
SW2-6 CC Operation – selection of single or dual capacity
compressor. On = Single Stage; Off = Dual Capacity
SW2-7 Lockout and Alarm Outputs (P2) – selection of a
continuous or pulsed output for both the LO and ALM
Outputs. On = Continuous; Off = Pulsed
SW2-8 Future Use
Alarm Jumper Clip Selection
From the factory, ALM is connected to 24 VAC via JW2. By cutting
JW2, ALM becomes a dry contact connected to ALG.
Test Mode
The control is placed in the test mode by holding the push button
switch SW1 for 2 - 5 seconds. In test mode most of the control
timings will be shortened by a factor of sixteen (16). LED3 (green)
will flash at 1 second on and 1 second off. Additionally, when
entering test mode LED1 (red) will flash the last lockout one
time. Test mode will automatically time out after 30 minutes. Test
mode can be exited by pressing and holding the SW1 button for
2 to 5 seconds or by cycling the power. NOTE: Test mode will
automatically be exited after 30 minutes.
22
Page 23
The Aurora ‘Base’ Control System cont.
A
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Safety Features
The following safety features are provided to protect the
compressor, heat exchangers, wiring and other components from
damage caused by operation outside of design conditions.
Fuse – a 3 amp automotive type plug-in fuse provides protection
against short circuit or overload conditions.
Random Start – 5 to 80 second random start upon power up.
Fault Retry – in the fault condition, the control will stage off the
outputs and then “try again” to satisfy the thermostat Y input
call. Once the thermostat input calls are satisfied, the control will
continue on as if no fault occurred. If 3 consecutive faults occur
without satisfying the thermostat Y input call, then the control will
go to Lockout mode.
Lockout – when locked out, the blower will operate continuously,
and PSC blower motor output will remain on. The Alarm output
(ALM) and Lockout output (L) will be turned on. The fault type
identification display LED1 (Red) shall flash the fault code. To reset
lockout conditions with SW2-8 On, thermostat inputs “Y1”, “Y2”,
and “W” must be removed for at least 3 seconds. To reset lockout
conditions with SW2-8 Off, thermostat inputs “Y1”, “Y2”, “W”, and
“DH” must be removed for at least 3 seconds. Lockout may also be
reset by turning power off for at least 30 seconds or by enabling the
emergency shutdown input for at least 3 seconds.
High Pressure – fault is recognized when the Normally Closed
High Pressure Switch, P4-9/10 opens, no matter how momentarily.
The High Pressure Switch is electrically in series with the
Compressor Contactor and serves as a hard-wired limit switch if
an overpressure condition should occur.
Low Pressure - fault is recognized when the Normally Closed
Low Pressure Switch, P4-7/8 is continuously open for 30 seconds.
Closure of the LPS any time during the 30 second recognition
time restarts the 30 second continuous open requirement. A
continuously open LPS shall not be recognized during the 2 minute
startup bypass time.
Loss of Charge – fault is recognized when the Normally Closed Low
Pressure Switch, P4-7/8 is open prior to the compressor starting.
Freeze Detection (Coax) - set points shall be either 30°F or 15°F.
When the thermistor temperature drops below the selected set
point, the control shall begin counting down the 30 seconds delay.
If the thermistor value rises above the selected set point, then the
count should reset. The resistance value must remain below the
selected set point for the entire length of the appropriate delay to
be recognized as a fault. This fault will be ignored for the initial 2
minutes of the compressor run time.
Over/Under Voltage Shutdown - An over/under voltage condition
exists when the control voltage is outside the range of 18 VAC to
30 VAC. If the over/under voltage shutdown lasts for 15 minutes,
the lockout and alarm relay will be energized. Over/under voltage
shutdown is self-resetting in that if the voltage comes back within
range of 18 VAC to 30 VAC for at least 0.5 seconds, then normal
operation is restored.
Operation Description
Power Up - The unit will not operate until all the inputs and safety
controls are checked for normal conditions. The unit has a 5 to 80
second random start delay at power up. Then the compressor has
a 4 minute anti-short cycle delay after the random start delay.
Standby In standby mode, Y1, Y2, W, DH, and G are not active.
Input O may be active. The blower and compressor will be off.
Heating Operation
Heating, 1st Stage (Y1) - The blower is started immediately and the
compressor is energized 10 seconds after the Y1 input is received.
Heating, 2nd Stage (Y1, Y2) - The compressor will be staged to
full capacity 20 seconds after Y2 input is received. The ECM blower
will shift to high speed.
Heating, 3rd Stage (Y1, Y2, W) - The hot water pump is deenergized and the first stage of electric heat is energized 10
seconds after the W command is received. If the demand
continues the second stage of electric heat will be energized after
5 minutes.
Emergency Heat (W Only) - When the unit is matched with an air
handler listed in the Air Handler Compatibility table, the thermostat
will send the "W" input to the air handler's control board. The blower
is started on high speed, and the first stage of resistance heat is
energized 10 seconds after the "W" input. Continuing demand will
engage the additional stages of resistance heat 90 seconds after
the first stage.
Cooling Operation
In all cooling operations, the reversing valve directly tracks the O
input. Thus, anytime the O input is present, the reversing valve will
be energized.
Cooling, 1st Stage (Y1, O) - The blower is started immediately and
the compressor is energized 10 seconds after the Y1 input is received.
Cooling, 2nd Stage (Y1, Y2, O) - The compressor will be staged to
full capacity 20 seconds after Y2 input is received. The ECM blower
will shift to high speed.
Blower (G) - The blower will start immediately upon receiving a
thermostat G command. If there are no other commands from the
thermostat the ECM will run on “G” speed until the G command is
removed. Regardless of blower input (G) from the thermostat, the
blower will remain on for 30 seconds at the end of each heating,
cooling, and emergency heat cycle.
23
Page 24
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
1
2
The Aurora ‘Base’ Control System cont.
Emergency Shutdown - Four (4) seconds after a valid ES input,
P2-7 is present, all control outputs will be turned off and remain
off until the emergency shutdown input is no longer present. The
first time that the compressor is started after the control exits
the emergency shutdown mode, there will be an anti-short cycle
delay followed by a random start delay. Input must be tied to
common to activate.
Load Shed -
The LS input disables all outputs with the exception
of the blower output. When the LS input has been cleared, the antishort cycle timer and random start timer will be initiated. Input must
be tied to common to activate.
Aurora ‘Base’ Control LED Displays
These three LEDs display the status, configuration, and fault
codes for the control. These can also be read in plain English via
the Aurora AID Tool.
Status LED (LED3, Green)
Description of OperationFault LED, Green
Normal ModeON
Control is Non-functionalOFF
Test ModeSlow Flash
Lockout ActiveFast Flash
Dehumidification ModeFlash Code 2
(Future Use)Flash Code 3
(Future Use)Flash Code 4
Load ShedFlash Code 5
ESDFlash Code 6
(Future Use)Flash Code 7
Configuration LED (LED2, Yellow)
Description of OperationConfiguration LED, Yellow
No Software OverwrittenFlashing ECM Setting
DIP Switch was OverwrittenSlow Flash
ECM Configuration ModeFast Flash
Fault LED (LED1, Red)
Red Fault LED
Normal - No FaultsOFF–
Fault - Input1NoAuto
Fault - High Pressure2YesHard or Soft
Fault - Low Pressure3YesHard or Soft
Fault - Freeze Detection FP24YesHard or Soft
Fault - Freeze Detection FP15YesHard or Soft
Fault - Condensate Overflow7YesHard or Soft
NOTE: All codes >11 use long flash for tens digit and short flash for the ones digit. 20,
30, 40, 50, etc. are skipped.
LED Flash
Code*
Lockout Reset/Remove
Aurora Interface and Diagnostics (AID) T ool
The Aurora Interface and
Diagnostics (AID) Tool is a
device that is a member of
the Aurora network. The AID
Tool is used to troubleshoot
equipment which uses the
Aurora control via Modbus
RTU communication. The AID
Tool provides diagnostics,
fault management,
ECM setup, and system
configuration capabilities to the Aurora family of controls. An AID
Tool is recommended, although not required, for ECM airflow
settings. The AID Tool simply plugs into the exterior of the cabinet
in the AID Tool port.
ABC Control Board Layout
5.0 in.
On
o
F/30oF
FP1 – 15
o
F/30oF
FP2 – 15
RV – B/O
ACC – Dip
ACC – Dip
Reheat/Normal
Control
C
G
O/B
Field ConnectionsField Connections
C
G
O/B
Off
LED 2
1
2
YR
3
Config
4
5
6
7
8
SW2
Com1
Com2
W
Y1
Y2
DH
W
Y1
Y2
DH
LED 5
LED 4
3A-Fuse
P6
G
G
RR
EH1
P3
Factory
RS485
P7
RS 485
P8
RS485 NET
EH2
C
EH1
C
CO
N/A
(+)
(-)
R
Exp
C
(+)
(-)
R
C
CC
C
6.25 in.
C
CFM
PWM
HP
HP
LP
LP
FP2
FP2
FP1
FP1
REV
REV
CC2
G
LO
CC2
HI
CCG
CC
FG
F
R
F
CC
G
Y1
P4
Factory
P5
Factory
JW2 - Alarm
P2
LS
ES
P13
ALM
ECM PWM
SW1 Test
RV – K1
CC – K2
CC Hi – K3
Fan – K4
Alarm – K5
Acc – K6
ALG
ACC c
ACC no
ACC nc
LED 1
Fault
LED 3
CC – Dual/Single
G
L – Pulse/Continuous
Status
AuroraTM Base
Factory Use
P11
P9
Factory Fan Connection
R
LO
P1
R
LO
5.5 in.
5.75 in.
24
Page 25
Reference Calculations
Heating Calculations:Cooling Calculations:
LWT = EWT -
HE
gpm x 500
LWT = EWT +
gpm x 500
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
HR
LAT = EAT +
TH = HC + HW
HC
cfm x 1.08
LAT (DB) = EAT (DB) -
LC = TC - SC
SC
S/T =
TC
cfm x 1.08
Legend
Abbreviations and Definitions
cfm = airflow, cubic feet/minute
EWT = entering water temperature, Fahrenheit
gpm = water flow in gallons/minute
WPD = water pressure drop, psi and feet of water
EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb)
HC = air heating capacity, MBtu/h
TC = total cooling capacity, MBtu/h
SC = sensible cooling capacity, MBtu/h
kW = total power unit input, kilowatts
HR = total heat of rejection, MBtu/h
HE = total heat of extraction, MBtu/h
SC
HWC = hot water generator capacity, MBtu/h
EER = Energy Efficient Ratio
= Btu output/Watt input
COP = Coefficient of Performance
= Btu output/Btu input
LWT = leaving water temperature, °F
LAT = leaving air temperature, °F
TH = total heating capacity, MBtu/h
LC = latent cooling capacity, MBtu/h
S/T = sensible to total cooling ratio
25
Page 26
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Wiring Schematics
Split Wiring Schematic - 208-230/60/1
C
CFM
PWM
HP
ECM PWM
P4
HP
P13
LP
LP
FP2
FP2
FP1
Factory
SW1 Test
FP1
REV
REV
CC2
LO
CC2
HI
CCG
CC
FG
F
CC
G
Y1
G
F
R
JW2 - Alarm
RV – K1
CC – K2
P5
CC Hi – K3
Fan – K4
Factory
Alarm – K5
Acc – K6
P2
LS
ES
ALG
ALM
ACC c
ACC nc
ACC no
Water Solenoid
(see Open Loop
Groundwater Systems
section)
1 second on and 1 second off
Slow Flash
100 milliseconds on and 100 milliseconds off
Fast Flash
100 millisec o n ds on and 400 m illise c onds off with a 2 second pause before repeating
Flash Code
Random Start Delay (Alternating Colors)
Status LED (LED1, Green)
Configuration LED (LED2, Yellow)
Fault LED (LED3, Red)
Fault LED (LED1, Red)
Normal Mode
Input Fault Lockout
High Pressure Lockout
Low Pressure Lockout
Futu re U s e
Freeze Detection – FP1
Reserved
Condensate Overflow Lockout
Over/Under Voltage Shutdown
Futu re U s e
Futu re U s e
FP1 and FP2 Sensor Error
1 – Field inst alled SPST relay required f or duel fuel applications
Cap
Circuit Breaker
5A
Black(2)
5A
Circuit Breaker
Black(3)
Unit Power Supply
208-230/60/1
G
EH1
P2
ES
LS
ALM
ALG
ACC COM
ACC NO
ACC NC
LO
R
C
O/B
G
Y1
Y2
W
DH
P1
R
CC2
K5-Alarm
Relay
C
Green(11)
1st Stage Compressor
2nd Stage Compressor
Reversing Valve
Fault Signal
24 VAC
Auxilia r y
Heat Relay
S
Blue
Tan(6)
CCFC
K6-Acc
Relay
RS485 NET
= chassis
R
Red
T2T1
CC
P9
Com2
LED5
P8
Compressor
C
Black
L1L2
G
Split
Y1
Y2
O
P1
LO
C
R
P2
ES
Violet(14)
JW2
RFFGCCCCG
K4-Fan Relay
Com1
LED5
RS485 NET
R-+
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Junction
Quick connect terminal
Wire nut
Field wire lug
L1
Ground
Relay Contacts-
N.O., N.C.
Fuse
Breaker
Com p re s so r C o n ta cto r
CC -
Condensate overflow sensor
CO -
DHW pum p relay
K5 -
Loop pump relay
K6 -
PSC Fan Speed Relay
CR3 -
PSC Fan Power Rel ay
CR4 CS -Compressor Solenoid
Fuses
F1 and F2 -
Heater element
HE -
High pressure switch
HP FP1 -
Freeze protection sensor
Low pressure switch
LP -
Event
Random Start Delay
Compressor On Delay
Compress or Minimum On Ti me
Compressor Short Cycle Delay
Blower Off Delay
Fault Recognition Delay – High Pressure
Start-Up Bypass – Low Pressure
Fault Recognition Delay – Low Pressure
Start-Up Bypass – Low Water Coil Limit
Fault Recognition Delay – Low Water Coil Limit
Fault Recognition Delay – Condensate Overflow
Thermostat Call Recognition Time
Water Valve Slow Open Delay
Cycle with BlowerONON
Cycle with CompressorOFFOFF
Water Valve Slow OpeningONOFF
Cycle with Comm. T-stat Hum CmdOFFON
RV
Orange
RV
Orange
REVREV FP1 FP1 FP2 FP2 LPS LPS HPS HPS
K1-RV Relay
SW1
Test Mode
CO
P6
EH2CEH1
C
P3
Polarized connector
Current Transducer (CT)
Power blocks
PB1, PB2 -
Pow e r strip
PS -
Reversing Valve coil
RV -
DIP package 5 position AXB
SW1 -
TEST MODE ABC Board
SW1 -
DIP package 8 position ABC Board
SW2 -
The r mal lim it s witch
TS HWL -
Hot water lim it s e n so r
SC -
Start Contactor
Start Relay
SR -
Water Coil Limit Sensor
WCL -
Normal Mode
5 to 80 seconds1 second
5 seconds< 1 second
2 minutes5 seconds
4 minutes15 seconds
30 seconds2 seconds
Less than 1 second
ABC SW2 Accessory Relay
DESCRIPTIONSW2-4 SW 2-5
FP1
Yellow
Less than 1 second
2 minutes
30 seconds30 seconds
2 minutes
30 seconds
30 seconds
2 seconds2 seconds
90 seconds90 seconds
HP
LP
Black
Blue
T
Yellow
Status
LED3
G
Black
Blue
Fault
LED1
R
FP1 – 15°F/30° F
FP2 – 15°F/30° F
RV – B/O
Acc – Dip 4
Acc – Dip 5
CC – Dual/Single
L Output Type
Futu re U s e
Config
LED2
Y
CCGY1
Test Mode
30 seconds
30 seconds
30 seconds
30 seconds
P4
F1-3A
Off
SW2
4/3/1397P840-21
PWM
CFM
C
R
F
C
P13
On
1
2
3
4
5
6
7
8
AID Tool
26
Page 27
Wiring Schematics cont.
Split Wiring Schematic with GeoStart - 208-230/60/1
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
C
CFM
PWM
HP
ECM PWM
P4
HP
P13
LP
LP
FP2
FP2
FP1
Factory
SW1 Test
FP1
REV
REV
CC2
LO
CC2
HI
CCG
CC
FG
F
CC
G
Y1
G
F
R
JW2 - Alarm
P2
RV – K1
CC – K2
P5
CC Hi – K3
Fan – K4
Factory
Alarm – K5
Acc – K6
LS
ES
ALG
ALM
ACC c
ACC nc
ACC no
Water Solenoid
(see Open Loop
Groundwater Systems
section)
Ext Pump
1/2 hp Total
208-230/60/1
Pump
Pump
G
Hot Water
Limit Switch
130°F
DHW
Pump
Blue
Optional Internal
Hot Water Generation Pump
1 second on and 1 second off
Slow Flash
100 millisec o n ds on and 100 m illise c o n d s o f f
Fast Flash
100 millisec o n ds on a n d 4 00 m illis e c o n ds off with a 2 s e c ond pause before repeating
Flash Code
Random Start Delay (Alternating Colors)
Status LED (LED1, Green)
Configuration LED (LED2, Yellow)
Fault LED (LED3, Red)
Fault LED (LED1, Red)
Normal Mode
Input Fault Lockout
High Pressure Lockout
Low Pressure Lockout
Futu re U s e
Freeze Detection – FP1
Reserved
Condensate Overflow Lockout
Over/Under Voltage Shutdown
Futu re U s e
Futu re U s e
FP1 and FP2 Sensor Error
CC CO K5 K6 CR3 CR4 CS -Compressor Solenoid
F1 and F2 HE HP FP1 -
LP -
GeoStart
Dual Capacity
Units Only
CC
RCP
Black(15)
Violet(14)
Blue(16)
CC2HICC2LOCC2
K4-Fan Rel ay
K2-CC Relay
K3
-CC2 Rel ay
Aurora Base Control
(ABC)
Com1
LED5
G
RS485 EXP
C
R-+C
P7
Legend
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Junction
Quick connect terminal
Wir e n ut
Field wire lug
Ground
Relay ContactsN.O., N.C.
Fuse
Breaker
Compressor Contactor
Condensate overflow sensor
DHW pum p relay
Loop pump relay
PSC Fan Speed Relay
PSC Fan Power Relay
Fuses
Heater element
High pressure switch
Freeze protection sensor
Low pressure switch
Event
Random Start Delay
Compressor On Delay
Compressor Minimum On Ti me
Compressor Short Cycle Delay
Blower Off Delay
Fault Recognition Delay – High Pressure
Start-Up Bypass – Low Pressure
Fault Recognition Delay – Low Pressure
Start-Up Bypass – Low Water Coil Limit
Fault Recognition Delay – Low Water Coil Limit
Fault Recognition Delay – Condensate Overflow
The r mosta t Call R e c o g n it io n T ime
Water Valve Slow Open Delay
UltraTech
CS
Blue(18)
P5
G
CO
P6
P
Cycle with Blowe rONON
Cycle with CompressorOFFOFF
Water Valve Slow OpeningONOFF
Cycle with Comm. T-stat Hum CmdOFFON
TEST MODE ABC Board
DIP package 8 position ABC Board
SW2 -
The rmal limit swit c h
TS HWL -
Hot water limit sensor
SC -
Start Contactor
Start Relay
SR -
Water Coil Limit Sensor
WCL -
Aurora T im ing E v en ts
Normal Mode
5 to 80 seconds1 second
5 seconds< 1 second
2 minutes5 seconds
4 minutes15 seconds
30 seconds2 seconds
Less than 1 second
ABC SW2 Accessory Relay
DESCRIPTIONSW2-4 SW 2-5
FP1
Yellow
Less than 1 second
2 minutes
30 seconds30 seconds
2 minutes
30 seconds
30 seconds
2 seconds2 seconds
HP
LP
Black
Blue
T
Yellow
Status
LED3
G
P3
Blue
FP1 – 15°F/30° F
FP2 – 15°F/30° F
CC – Dual/Single
L Output Type
CCGY1
Black
Fault
LED1
RV – B/O
Acc – Dip 4
Acc – Dip 5
Future Use
Confi g
LED2
Y
R
Test Mode
30 seconds
30 seconds
30 seconds
30 seconds
90 seconds90 seconds
P4
Off
F1-3A
4/3/1397P840-23
C
R
F
PWM
CFM
C
P13
On
1
2
3
4
5
6
7
8
SW2
Thermostat
Y1
1st Stage Compressor
Y2
2nd Stage Compressor
O
Reversing Valve
L
Fault Signal
C
R
24 VAC
G
Auxiliary
Heat Relay
W
Notes
Blue
CC2
Black
K5-Alarm
Relay
C
Green(11)
Red
PinkBlack
CCFC
K6-Acc
Relay
RS485 NET
C
CC
L1L2
EH1
AID Tool
27
Page 28
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Refrigeration
The indoor split series comes with a holding charge. The charge
must be adjusted in the field based on performance. Refrigeration
piping on the split consists of installing a brazed copper line
set between the blower coil unit and the unit’s split compressor
section. To select the proper tube diameters for the installation,
refer to the Line Set Sizes table. Line sets over 60 feet long are not
recommended because of oil return and pressure drop problems.
The suction line must always be insulated. Handle and route the
line sets carefully to avoid kinking or bending the tubes. If the line
set is kinked or distorted and it cannot be formed back into its
original shape, the bad portion of the pipe should be replaced. A
restricted line set will affect the performance of the system.
Fasten the copper line set to the blower coil unit as instructed
by the coil installation instructions shown in Figure 14. Nitrogen
should be bled through the system at 2 to 3 PSI to prevent
oxidation inside the refrigerant tubing. Use a low silver phoscopper braze alloy on all brazed connections.
Figure 13: Typical Split System Refrigerant Line Connections
Service ports for
attaching refrigerant
gauges
Insulated
Suction Line
The indoor split service valves are recessed in the unit’s corner post
and protected by a cover. Remove the protective cover and braze
the line set to the service valve stubs as shown in Figure 13. Care
should be used when brazing the service valves as to not scorch the
paint. Nitrogen should be bled through the system at 2 to 3 psi to
prevent oxidation contamination. Use a low silver phos-copper braze
alloy on all brazed connections. Indoor split units are shipped with a
factory charge and service valves are not to be opened until the line
set has been leak tested, purged, and evacuated. Schrader cores
should be removed before brazing, and replaced after the valves
have cooled. A heat sink should be used on the service valve and
TXV to prevent damage caused by excessive heat. When brazing is
completed, reinstall the protective cover.
Figure 14: Attaching the Air Coil
TXV ("IN" toward condensing unit)
Equalizer
Bulb
Suction
Liquid
ccw
ccw
Braze
Connection
Liquid
Line
Replace caps after
opening system
PositionDescriptionSystem
CW - Full In Shipping PositionClosedOpen
CCW - Full Out 1/2 turn CW Service PositionOpenOpen
CCW - Full Out Operation PositionOpenClosed
TXV has internal check valve
Service
Port
28
Page 29
Refrigeration cont.
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Leak Testing
The refrigeration line set must be pressurized and checked for
leaks before purging and charging the unit. To pressurize the line
set, attach refrigerant gauges to the service ports and add an inert
gas (nitrogen or dry carbon dioxide) until pressure reaches 60 to
90 PSIG. Never use oxygen or acetylene to pressure test. Use an
electronic leak detector or a good quality bubble solution to detect
leaks on all connections made in the field. Check the service
valve ports and stem for leaks and all connections made in the
field. If a leak is found, repair it and repeat the above steps. For
safety reasons do not pressurize the system above 150 psi. Purge
pressure from line set. The system is now ready for evacuating
and charging.
System Evacuation
Ensure that the line set and air coil are evacuated before opening
service valves to the split unit. The line set must be evacuated to at
least 200 microns to remove the moisture and air that may still be
in the line set and coil. Evacuate the system through both service
ports to prevent false readings on the gauge because of pressure
drop through service ports.
Charge Amount When Using GAH Air Handler
The Aston Series Split is shipped with a factory pre-charge.
This volume of refrigerant is not sufficient to run the system and
additional refrigerant must be added. If using an GAH Air Handler
please refer to the Line Set Sizes table for charge amounts to
be added. The “Factory Charge” column is the charge amount
the compressor section/split is shipped with from the factory. The
“Charge Amount with GAH Air Handler” column is the total amount
of charge for the GAH Air Handler + Compressor section/split. This
column does not factor in additional refrigerant needed for the line
set. The installer of the system must add charge appropriately for
the specific length of the line set. A 3/8 in. liquid line is calculated
at 0.50 oz. of charge per linear foot, and a 1/2 in. liquid line
is calculated at 1.0 oz. of charge per linear foot using R-410A
refrigerant. The suction line will not hold “liquid” and should be
ignored for the charge calculation.
Example: 103*036/GAH036 with 20 ft. of 3/8 in. liquid line.
Remember that when using the GAH Air Handler, the
column “Charge Amount with GAH Air Handler” will be
used. Now calculate for the additional 20 ft. line set.
Additional refrigerant to be added = (20 ft. x 0.5 oz.)
= 10 oz.
Solution: 10 oz. should be added to the recommended charge
of 86 oz. found in the “Charge Amount with GAH Air
Handler” column for a total charge of 96 oz.
After initial charge, the system should be operated and the
system subcooling and superheat verified to the Unit Operating
Parameters table.
If an air handler manufactured by others is used then refrigerant
should be added to the Aston Series Split factory pre-charge.
Refrigerant should be added for liquid line length. This should
result in a slightly under-charged system exhibiting low subcooling
and high superheat. As charge is added, the subcooling should
rise and the superheat should fall.
Charging the System
Charge Method – After purging and evacuating the line set, fully
open the service valves counterclockwise. Add R-410A (liquid)
into the liquid line service port until the pressure in the system
reaches approximately 200 PSIG. Never add liquid refrigerant
into the suction side of a compressor. Start the unit and measure
superheat and subcooling. Keep adding refrigerant until the unit
meets the superheat and subcooling values on the Operating
Parameters tables.
Checking Superheat and Subcooling
Determining Superheat
1. Measure the temperature of the suction line at the point where
the expansion valve bulb is clamped.
2. Determine the suction pressure in the suction line by
attaching refrigeration gauges to the Schrader connection on
the suction side of the compressor.
3. Convert the pressure obtained in Step 2 to the saturation
temperature by using the R-410A Pressure/Temperature
Conversion Chart.
4. Subtract the temperature obtained in Step 3 from Step 1. The
difference is the amount of superheat for the unit. Refer to the
Operating Parameters tables for superheat ranges at specific
entering water conditions.
Superheat Adjustment
TXVs are factory set to a specific superheat; however, the
superheat should be adjusted for the application. To adjust the
TXV to other superheat settings:
1. Remove the seal cap from the bottom of the valve.
2. Turn the adjustment screw clockwise to increase superheat
and counterclockwise to decrease superheat. One complete
360° turn changes the superheat approximately 3-4°F,
regardless of refrigerant type. You may need to allow as much
as 30 minutes after the adjustment is made for the system to
stabilize.
3. Once the proper superheat setting has been achieved,
replace and tighten the seal cap.
WARNING: There are 8 total (360°) turns on the
superheat adjustment stem from wide open to
fully closed. When adjusting the superheat stem
clockwise (superheat increase) and the stop is
reached, any further clockwise turning adjustment
will damage the valve.
29
Page 30
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Refrigeration cont.
Determining Subcooling
1. Measure the temperature of the liquid line on the small refrigerant
line (liquid line) just outside the split cabinet. This location
will be adequate for measurement in both modes unless a
significant temperature drop in the liquid line is anticipated.
2. Measure the liquid line pressure by attaching refrigerant
gauges to the Schrader connection on the liquid line service
valve.
3. Convert the pressure obtained in Step 2 to the saturation
temperature by using the R-410A Pressure/Temperature
Conversion Chart.
4. Subtract the temperature in Step 1 from the temperature in
Step 3. The difference will be the subcooling value for that
unit. Refer to the Operating Parameters tables for subcooling
ranges at specific enter water conditions.
NOTES: * The "Charge Amount with GAH Air Handler" column is based on the charge amount for a GAH Air Handler+Compressor Section/Split.
Additional charge will have to be added accordingly for line set length.
After Charge is added adjustments can be made to get appropriate subcooling and superheat.
Additional charge for R-410A is 0.50 oz. per ft. for 3/8 in. and 1.0 oz. per ft. for 1/2 in. tube.
NOTE: Remove and discard the compressor hold down shipping
bolt located at the front of the compressor mounting bracket.
• High voltage is correct and matches nameplate.
• Fuses, breakers and wire size correct.
• Low voltage wiring complete.
• Piping completed and water system cleaned and flushed.
• Air is purged from closed loop system.
• Isolation valves are open, water control valves or loop
pumps wired.
• Condensate line open and correctly pitched.
• Transformer switched to 208V if applicable.
• Dip switches are set correctly.
• Hot water generator pump switch is “OFF” unless piping is
completed and air has been purged.
• Blower rotates freely.
• Blower speed is correct.
• Air filter/cleaner is clean and in position.
• Service/access panels are in place.
• Return air temperature is between 50-80°F heating and
60-95°F cooling.
• Check air coil cleanliness to ensure optimum performance.
Clean as needed according to maintenance guidelines. To
obtain maximum performance the air coil should be cleaned
before startup. A 10% solution of dishwasher detergent and
water is recommended for both sides of coil, a thorough water
rinse should follow.
Startup Steps
NOTE: Complete the Equipment Start-Up/Commissioning Check
Sheet during this procedure. Refer to thermostat operating
instructions and complete the startup procedure. Verify that the
compressor shipping bolt has been removed.
1. Initiate a control signal to energize the blower motor.
2. Initiate a control signal to place the unit in the
cooling mode. Cooling setpoint must be set below
room temperature.
3. First stage cooling will energize after a time delay.
4. Be sure that the compressor and water control valve or loop
pump(s) are activated.
5. Verify that the water flow rate is correct by measuring the
pressure drop through the heat exchanger using the P/T plugs
and comparing to unit performance data in catalog.
6. Check the temperature of both the supply and discharge water
(see the Unit Operating Parameters tables).
7. Check for an air temperature drop of 15°F to 25°F across
the air coil, depending on the fan speed and entering water
temperature.
8. Decrease the cooling set point several degrees and verify high-
speed blower operation.
9. Adjust the cooling setpoint above the room temperature and verify
that the compressor and water valve or loop pumps deactivate.
10. Initiate a control signal to place the unit in the heating mode.
Heating set point must be set above room temperature.
11. First stage heating will energize after a time delay.
12. Check the temperature of both the supply and discharge water
(see the Unit Operating Parameters tables).
13. Check for an air temperature rise of 12°F to 35°F across the air
coil, depending on the fan speed and entering water temperature.
14. If auxiliary electric heaters are installed, increase the heating
setpoint until the electric heat banks are sequenced on. All
stages of the auxiliary heater should be sequenced on when the
thermostat is in the Emergency Heat mode. Check amperage of
each element.
15. Adjust the heating setpoint below room temperature and verify
that the compressor and water valve or loop pumps deactivate.
16. During all testing, check for excessive vibration, noise or water
leaks. Correct or repair as required.
17. Set system to desired normal operating mode and set
temperature to maintain desired comfort level.
18. Instruct the owner/operator in the proper operation of the
thermostat and system maintenance.
NOTES: Be certain to fill out and forward all warranty
registration papers.
Final Evaluation
After the initial check of superheat/subcooling values in the
heating mode, shut off the unit and allow it to sit 3 to 5 minutes
until pressures equalize. Restart the unit in the cooling mode
and check the values against those in the Operating Parameters
tables. If the unit performs satisfactorily, charging is complete. If
the unit does not perform to specifications, the charge may need
to be readjusted until the values are close. Adding refrigerant
will increase subcooling. Recovering some of the refrigerant will
decrease subcooling and increase superheat. If the superheat/
subcooling values are still not close to the specifications in the
Operating Parameters tables, analyze refrigerant circuit operation.
32
Page 33
Operating Parameters
Single Speed Models - 103*022 thru 103*070
(with GAH Series Air Handler)
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Entering Water
Temp °F
50
70
90
Entering Water
Temp °F
30
50
70
NOTES: Cooling performance based on entering air temperatures of 80°F DB, 67°F WB.
Heating performance based on entering air temperatures of 70°DB.
Water
Flow GPM/
Ton
1.5115-150205-245115-130205-24512-227-145-2218-24
3.0110-145200-235110-125200-23514-266-128-1218-24
1.5125-160260-300125-160275-3008-148-125-1918-22
3.0115-150265-295115-135265-2959-164-165-1218-22
1.5125-160320-370125-160330-3708-146-1314-2218-22
3.0120-150305-355120-150325-3659-164-165-1218-22
Water
Flow GPM/
Ton
1.565-85290-31065-85330-3607-132-217-1018-24
3.070-90265-33070-90335-3656-122-213-722-26
1.595-120320-34595-120395-4306-122-215-1121-34
3.0100-125280-365100-125375-4056-124-225-1124-33
1.5135-155315-380135-155435-4858-1410-208-1426-46
3.0135-156315-395135-155440-4908-1410-203-1025-48
103*022 thru 103*060103*070103*022 thru 103*070
Suction
Pressure PSIG
103*022 thru 103*060103*070103*022 thru 103*070
Suction
Pressure PSIG
Discharge
Pressure PSIG
Discharge
Pressure PSIG
Cooling -- No Hot Water Generator
Suction
Pressure PSIG
Heating -- No Hot Water Generator
Suction
Pressure PSIG
Discharge
Pressure PSIG
Discharge
Pressure PSIG
SuperheatSubcooling
SuperheatSubcooling
Water Temp
Rise °F
Water Temp
Drop °F
Air Temp Drop
°F DB
Air Temp Rise
°F DB
5/29/08
33
Page 34
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Operating Parameters cont.
103*026 thru 103*072 (with GAH Series Air Handler)
First Stage Operation
Cooling -- No Hot Water Generator
Suction
Pressure
PSIG
Heating -- No Hot Water Generator
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Discharge
Pressure
PSIG
Entering Water
Temp °F
50
70
90
Entering Water
Temp °F
30
50
70
Water Flow
GPM/Ton
1.5130-150193-230130-150200-2458-167-147-2018-24
3.0128-153190-230125-140205-2408-163-109-1418-25
1.5130-150238-282135-150240-2806-164-169-1818-25
3.0130-155238-262125-145245-2706-185-115-1018-24
1.5133-148308-340130-155300-3657-166-184-1119-25
3.0138-153303-333130-165305-3507-187-145-917-22
Water Flow
GPM/Ton
1.578-100275-32585-105325-3856-114-162-820-29
3.078-110285-32590-120335-3756-114-163-720-32
1.5105-120305-350100-130340-4005-124-165-1224-32
3.0110-125305-355110-125345-3959-152-144-920-34
1.5140-155305-355130-165370-4305-122-148-1224-39
3.0145-160330-360140-160375-4257-177-154-924-39
103*026 thru 103*064103*072103*026 thru 103*072
Suction
Pressure
PSIG
103*026 thru 103*064103*072103*026 thru 103*072
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Discharge
Pressure
PSIG
SuperheatSubcooling
SuperheatSubcooling
Water Temp
Rise °F
Water Temp
Drop °F
Air Temp Drop
°F DB
Air Temp Rise
°F DB
Second Stage Operation
Entering Water
Temp °F
50
70
90
Entering Water
Temp °F
30
50
70
NOTES: Cooling performance based on entering air temperatures of 80°F DB, 67°F WB.
Heating performance based on entering air temperatures of 70°DB.
Water Flow
GPM/Ton
1.5120-140200-245105-150210-2707-176-147-1619-26
3.0115-140195-290110-130215-2607-154-118-1220-24
1.5121-136265-310105-150280-3509-156-187-1519-25
3.0123-139265-310110-140285-32010-168-168-1218-24
1.5122-140310-360115-140325-3858-146-1810-1618-24
3.0123-139310-350120-135330-3558-147-158-1217-23
Water Flow
GPM/Ton
1.572-89295-35070-100320-3707-1810-204-1318-24
3.073-87305-33075-90315-3657-1810-204-1618-27
1.5100-120320-36595-130375-4306-146-184-1023-34
3.0105-120355-365100-125370-4206-146-184-920-37
1.5142-158360-380130-165400-4706-124-156-1528-38
3.0138-152365-390135-160405-4657-144-156-1224-42
103*026 thru 103*064103*072103*026 thru 103*072
Suction
Pressure
PSIG
103*026 thru 103*064103*072103*026 thru 103*072
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Discharge
Pressure
PSIG
Cooling -- No Hot Water Generator
Suction
Pressure
PSIG
Heating -- No Hot Water Generator
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Discharge
Pressure
PSIG
SuperheatSubcooling
Superheat Subcooling
Water Temp
Rise °F
Water Temp
Drop °F
Air Temp Drop
°F DB
Air Temp Rise
°F DB
5/29/08
34
Page 35
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Pressure Drop
Single SpeedDual Capacity
ModelGPM
3
022
030
036
042
048
060
070
4.5
6
8
4
6
8
10
5
7
9
12
5
8
11
14
6
9
12
16
9
12
15
20
12
15
18
24
Pressure Drop (PSI)
30°F50°F70°F90°F110°F
0.9
1.7
2.8
4.7
1.3
2.7
4.5
6.8
1.0
2.1
3.6
6.3
0.8
2.1
4.2
7.6
1.1
2.3
3.9
6.7
2.4
3.9
5.7
9.5
3.0
4.4
6.0
9.7
0.9
1.6
2.7
4.4
1.2
2.5
4.2
6.3
1.0
1.9
3.3
5.9
0.7
2.1
4.1
6.7
1.0
2.1
3.7
6.3
2.2
3.6
5.3
8.9
2.8
4.0
5.5
9.1
0.8
1.5
2.5
4.1
1.2
2.4
3.9
5.4
0.9
1.8
3.0
5.5
0.7
1.9
3.8
6.3
1.0
2.0
3.4
5.9
2.1
3.4
5.0
8.3
2.6
3.8
5.1
8.5
0.7
1.4
2.3
3.9
1.1
2.2
3.7
5.4
0.8
1.7
2.8
5.1
0.7
1.8
3.5
5.8
0.9
1.9
3.2
5.5
2.0
3.2
4.7
7.8
2.4
3.5
4.8
7.9
0.7
1.3
2.2
3.6
1.0
2.2
3.4
5.0
0.8
1.6
2.6
4.8
0.6
1.7
3.3
5.4
0.8
1.7
3.0
5.1
1.8
2.9
4.3
7.2
2.2
3.3
4.4
7.3
5/28/13
ModelGPM
026
full
load
026
part
load
038
full
load
038
part
load
049
full
load
049
part
load
064
full
load
064
part
load
072
full
load
072
part
load
4
6
8
10
3
5
7
9
5
7
9
11
4
6
8
10
6
9
12
15
5
8
11
14
8
12
16
20
6
10
14
18
12
15
18
21
10
13
16
19
Pressure Drop (psi)
30°F50°F70°F90°F110°F
1.4
2.8
4.7
7.0
0.8
2.0
3.6
5.8
1.2
2.2
3.4
4.9
0.9
1.7
2.8
4.2
1.2
2.4
3.9
5.7
0.9
2.0
3.4
5.0
1.8
3.8
6.5
9.7
1.0
2.6
5.0
8.1
3.2
4.5
6.0
7.8
2.3
3.6
5.0
6.5
1.3
2.6
4.4
6.6
0.7
1.8
3.4
5.5
1.2
2.1
3.2
4.6
0.8
1.6
2.6
3.9
1.2
2.2
3.6
5.3
0.9
1.8
3.1
4.7
1.7
3.5
6.0
9.1
0.9
2.5
4.7
7.6
3.0
4.2
5.7
7.3
2.1
3.3
4.6
6.2
1.2
2.4
4.1
6.2
0.7
1.7
3.2
5.1
1.1
1.9
3.0
4.3
0.8
1.5
2.5
3.7
1.1
2.1
3.4
5.0
0.8
1.7
2.9
4.4
1.6
3.3
5.6
8.5
0.9
2.3
4.4
7.1
2.8
4.0
5.3
6.8
2.0
3.0
4.3
5.8
1.1
2.3
3.8
5.8
0.7
1.6
3.0
4.8
1.0
1.8
2.8
4.0
0.7
1.4
2.3
3.4
1.0
2.0
3.2
4.7
0.8
1.6
2.8
4.1
1.4
3.0
5.2
8.0
0.8
2.1
4.1
6.6
2.6
3.7
4.9
6.4
1.9
2.8
4.0
5.4
1.0
2.1
3.5
5.3
0.6
1.5
2.8
4.4
1.0
1.7
2.6
3.7
0.7
1.3
2.1
3.2
1.0
1.8
2.9
4.3
0.7
1.5
2.5
3.8
1.3
2.8
4.8
7.4
0.8
2.0
3.8
6.1
2.4
3.4
4.6
5.9
1.7
2.6
3.7
5.0
5/30/06
35
Page 36
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Refrigerant Circuit Guideline
Symptom
Under Charged System (Possible Leak)LowLowLowHighLowLowLow
Over Charged SystemHighHighHighNormalHighNormal/LowNormal
Low Air Flow HeatingHighHighHighHigh/NormalLowHighLow
Low Air Flow CoolingLowLowLowLow/NormalHighHighLow
Low Water Flow HeatingLow/NormalLow/NormalLowLowHighLowHigh
Low Water Flow CoolingHighHighHighHighLowLowHigh
High Air Flow HeatingLowLowLowLowHighLowLow
High Air Flow CoolingLowHighNormalHighLowLowNormal
High Water Flow HeatingNormalLowNormalHighNormalNormalLow
High Water Flow CoolingLowLowLowLowHighNormalLow
Low Indoor Air Temperature HeatingLowLowLowNormalHighNormalNormal/High
Low Indoor Air Temperature CoolingLowLowLowNormal/LowHighLowLow
High Indoor Air Temperature HeatingHigh HighHighNormal/HighNormal/LowLowNormal
High Indoor Air Temperature CoolingHighHighHighHighLowLowHigh
Restricted TXV (Check Service Advisory)HighLowNormal/LowHighHighLowLow
Insufficient Compressor (Possible Bad Valves)LowHighLowHighNormal/HighLowLow
TXV - Bulb Loss of ChargeLowLowLowHighHighLowLow
Scaled Coaxial Heat Exchanger HeatingLowLowLowNormal/LowHighLowLow
Scaled Coaxial Heat Exchanger CoolingHighHighHighNormal/LowLowLowLow
Restricted Filter DrierCheck temperature difference (delta T) across filter drier.
Heat of Extraction/Rejection Data - Dual Capacity Units
ModelGPM
3.013.117.621.523.522.921.8
Part Load
026
Full Load
Part Load
038
Full Load
Part Load
049
Full Load
Part Load
064
Full Load
Part Load
072
Full Load
Note: operation not recommended in shaded areas.1/14/2011
5.09.413.818.622.621.723.623.021.720.2
7.09.614.118.923.021.923.723.121.720.2
4.017.823.428.531.031.230.0
6.013.418.824.729.929.931.131.329.928.1
8.013.619.325.130.530.131.231.329.928.1
4.017.923.328.132.531.830.0
6.012.818.724.529.829.832.732.030.128.2
8.013.919.725.229.830.333.132.430.428.5
5.025.131..536.144.845.142.8
7.018.726.233.238.641.845.245.743.641.0
9.019.126.934.340.042.045.546.043.841.1
5.024.029.533.744.946.144.0
8.019.226.432.637.540.645.045.843.440.5
11.019.827.534.339.940.044.946.144.341.5
6.033.340.646.160.260.256.4
9.026.034.742.849.156.060.260.857.452.9
12.026.535.744.250.956.160.461.157.653.2
6.031.039.246.156.355.452.1
10.021.631.440.949.752.456.255.552.449.4
14.022.632.641.749.852.256.255.652.649.7
8.040.852.764.773.775.770.3
12.031.943.855.165.866.874.176.170.566.2
16.032.244.756.868.667.274.576.570.966.3
10.036.446.554.763.463.058.9
13.025.236.748.559.157.763.263.059.255.1
16.026.738.249.459.157.363.263.359.555.4
12.048.362.769.081.883.077.8
15.037.251.665.470.973.682.183.378.071.9
18.037.652.767.573.574.182.683.878.472.2
Heat of Extraction (kBtuh)Heat of Rejection (kBtuh)
30°F50°F70°F90°F30°F50°F70°F90°F110°F
37
Page 38
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Heat of Extraction/Rejection Data - Single Speed Units
ModelGPM
3.013.618.022.025.6
022
030
036
042
048
060
070
Note: operation not recommended in shaded areas.5/29/2013
4.59.914.319.123.023.325.825.523.522.3
6.010.014.819.423.523.526.025.523.622.4
4.019.225.029.831.231.529.8
6.014.019.826.031.029.031.131.429.726.4
8.014.220.426.532.529.331.431.629.926.5
5.023.631.037.238.639.736.7
7.017.524.732.338.832.138.539.636.635.7
9.017.925.232.939.432.538.939.936.835.9
5.026.933.436.646.747.643.9
8.020.828.235.142.043.146.947.944.242.3
11.021.229.036.243.543.447.248.244.443.1
6.034.743.550.757.657.551.3
9.026.536.345.853.853.457.857.951.751.6
12.027.037.347.255.653.758.158.051.851.6
9.041.052.461.275.474.068.9
12.028.942.354.165.072.975.674.368.764.9
15.030.043.256.365.873.575.773.968.967.0
12.050.364.270.382.984.174.7
15.036.451.667.074.675.983.082.274.470.7
18.036.652.168.176.376.383.683.175.271.4
Heat of Extraction (kBtuh)Heat of Rejection (kBtuh)
30°F50°F70°F90°F30°F50°F70°F90°F110°F
25.423.5
38
Page 39
Troubleshooting
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Aurora Control System
NOTE: Refer to the Aurora Base Control Application and
Troubleshooting Guide and the Instruction Guide: Aurora Interface and
Diagnostics (AID) Tool for additional information.
To check the unit control board for proper operation:
1. Disconnect thermostat wires at the control board.
2. Jumper the desired test input (Y1, Y2, W, O or G) to the R
terminal to simulate a thermostat signal.
3. If control functions properly:
• Check for thermostat and field control wiring (use
the diagnostic inputs mode).
4. If control responds improperly:
• Ensure that component being controlled is functioning
(compressor, blower, reversing valve, etc.).
• Ensure that wiring from control to the component
is correct.
• Refer to the Aurora Base Control Application and
Troubleshooting Guide and the Instruction Guide: Aurora
Interface and Diagnostics (AID) Tool for additional information.
Refrigerant Systems
To maintain sealed circuit integrity, do not install service gauges
unless unit operation appears abnormal. Compare the change in
temperature on the air side as well as the water side to the Unit
Operating Parameters tables. If the unit’s performance is not
within the ranges listed, and the airflow and water flow are known
to be correct, gauges should then be installed and superheat and
subcooling numbers calculated. If superheat and subcooling are
outside recommended ranges, an adjustment to the refrigerant
charge may be necessary.
NOTE:
Refrigerant tests must be made with hot water generator
turned “OFF”.
before servicing the refrigerant circuit.
Verify that air and water flow rates are at proper levels
39
Page 40
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Unit Startup/Troubleshooting
Heating Cycle Analysis
Measure suction
temperature here
at TXV bulb in
cooling modes.
Air
Coil
ClgTXV
COOLING TXV - ACTIVE
RIGHT TO LEFT
filter/drier
Measure liquid line
temperature and
pressure here in
both heating and
cooling modes
Lineset
length
Bi-flow
Measure suction temperature
here at TXV bulb in heating modes.
Volts ____
Amps ____
HtgTXV
COAX
EWT ____
LWT ____
HEATING TXV - ACTIVE LEFT TO RIGHT
Suct PSI____
Suct sat temp____
Suct temp____
Super heat____
Suction
Comp
Discharge
Hot Water
Generator
Discharge PSI____
Disch. sat temp____
Liquid temp____
Sub cooling____
Note: DO NOT hook up pressure gauges unless there appears to be a performance problem.
Cooling Cycle Analysis
Measure suction
temperature here
at TXV bulb in
cooling modes.
Air
Coil
ClgTXV
COOLING TXV - ACTIVE
RIGHT TO LEFT
filter/drier
Measure liquid line
temperature and
pressure here in
both heating and
cooling modes
Lineset
length
Bi-flow
Measure suction temperature
here at TXV bulb in heating modes.
Volts ____
Amps ____
HtgTXV
COAX
EWT ____
LWT ____
HEATING TXV-ACTIVE LEFT TO RIGHT
Suct PSI ____
Suct sat temp ____
Suct temp ____
Super heat ____
Suction
Comp
Discharge
Hot Water
Generator
Discharge PSI ____
Disch. sat temp ____
Liquid temp ____
Sub cooling ____
40
Page 41
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Troubleshooting cont.
Single Speed/Dual Capacity Startup/Troubleshooting Form
1. Job Information
Model # Job Name: Loop: Open / Closed
Serial # Install Date: Hot Water Generator: Y / N
2. Flow Rate in gpmSOURCE COAXLOAD COAX (Water-to-Water)
HEATINGCOOLINGHEATINGCOOLING
WATER IN Pressure:
WATER OUT Pressure:
Pressure Drop: a - b
Look up flow rate in table:
3. Temp. Rise/Drop Across Coaxial Heat Exchanger
WATER IN Pressure:
WATER OUT Pressure:
Temperature Difference:
4. Temp. Rise/Drop Across Air CoilSOURCE COAXLOAD COAX (Water-to-Water)
SUPPLY AIR Temperature:
RETURN AIR Temperature:
Temperature Difference:
5. Heat of Rejection (HR)/Heat of Extraction (HE)
Brine Factor
2
:k.
HR/HE = d x g x k
STEPS 6-9 NEED ONLY BE COMPLETED IF A PROBLEM IS SUSPECTED.
6. WattsENERGY MONITOR
Volts:
Total Amps (Comp. + Blower)
3
:n. Amps n. Amps
Watts = m x n x 0.85:
7. Capacity
Cooling Capacity = l - (o x 3.413):
Heating Capacity = l + (o x 3.413):
8. Efficiency
Cooling EER = p / o:
Heating COP = p / (o x 3.413):
9. Superheat (S.H.)/Subcooling (S.C.)
Suction Pressure:
Suction Saturation Temperature:
Suction Line Temperature:
S.H. = t - s
Head Pressure:
High Pressure Saturation Temp:
4
Liquid Line Temperature
:x. °F x. °F
S.C. = w - x
1
NOTES:
2
Steps 3-9 should be conducted with the hot water generator disconnected.
Use 500 for pure water, 485 for methanol or Environol™. (This constant is derived by multiplying the weight of one gallon of water (8.34) times the minutes
in one hour (60) times the specific heat of the fluid. Water has a specific heat of 1.0.
3
4
If there is only one source of power for the compressor and blower, amp draw can be measured at the source wiring connection.
Liquid line is between the coax and the expansion device in the cooling mode; between the air coil and the expansion device in the heating mode.
a. psi a. psi a. psi a. psi
b. psi b. psi b. psi b. psi
c. psi c. psi c. psi c. psi
d. gpm d. gpm d. gpm d. gpm
1
HEATINGCOOLING
e. °F e. °F
f. °F f. °F
g. °F g. °F
HEATINGCOOLINGHEATINGCOOLING
h. °F h. °F h. °F h. °F
i. °F i. °F i. °F i. °F
j. °F j. °F j. °F j. °F
HEATINGCOOLING
l. Btu/h l. Btu/h
HEATINGCOOLING
m. Volts m. Volts
o. Watts o. Watts
HEATINGCOOLING
p. Btu/h p. Btu/h
HEATINGCOOLING
q. Btu/h q. Btu/h
HEATINGCOOLING
r. psi r. psi
s. °F s. °F
t. °F t. °F
u. °F u. °F
Software Version
ABC:
AXB:
IZ2:
T’STAT:
v. psi v. psi
w. °F w. °F
y. °F y. °F
41
Page 42
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Preventive Maintenance
Water Coil Maintenance
1. Keep all air out of the water. An open loop system should be
checked to ensure that the well head is not allowing air to
infiltrate the water line. Lines should always be airtight.
2. Keep the system under pressure at all times. It is
recommended in open loop systems that the water control
valve be placed in the discharge line to prevent loss of
pressure during off cycles. Closed loop systems must have
positive static pressure.
NOTE: On open loop systems, if the installation is in an area with
a known high mineral content (125 PPM or greater) in the water,
it is best to establish with the owner a periodic maintenance
schedule so the coil can be checked regularly. Should periodic
coil cleaning be necessary, use standard coil cleaning procedures
which are compatible with either the cupronickel or copper water
lines. Generally, the more water flowing through the unit the less
chance for scaling.
Other Maintenance
Filters
Filters must be clean to obtain maximum performance. They
should be inspected monthly under normal operating conditions
and be replaced when necessary. Units should never be operated
without a filter.
Condensate Drain
In areas where airborne bacteria produce a slime in the drain pan,
it may be necessary to treat chemically to minimize the problem.
The condensate drain can pick up lint and dirt, especially with dirty
filters. Inspect twice a year to avoid the possibility of overflow.
Blower Motors
ECM blower motors are equipped with sealed ball bearings and
require no periodic oiling.
Hot Water Generator Coil
See Water Coil Maintenance section above.
Air Coil
The air coil must be cleaned to obtain maximum performance.
Check once a year under normal operating conditions and, if dirty,
brush or vacuum (with a brush attachment) clean. Care must be
taken not to damage the aluminum fins while cleaning.
Replacement Procedures
Obtaining Parts
When ordering service or replacement parts, refer to the model
number and serial number of the unit as stamped on the serial
plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along
with an explanation of the malfunctions and a description of the
replacement parts required.
CAUTION: Fin edges are sharp.
In-Warranty Material Return
Material may not be returned except by permission of authorized
warranty personnel. Contact your local distributor for warranty
return authorization and assistance.
42
Page 43
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Service Parts List
Single Speed Split Units
022030036042048060070
Compressor34P581-0134P582-0134P583-0134P578-0134P579-0134P580-0134P646-01
Run Capacitor16P002-1816P002-2016P002-2116P002-2516P002-41
Compressor
Refrigeration
Components
Desuperheater
Electrical
Sensors & Safeties
Part numbers subject to change10/09/13
Sound Jacket92P504A0592P504A16
Power Harness11P781-01
Solenoid HarnessN / A
Accumulator36P509-0236P509-01
Coax62I594-0162I588-0162I542B0162I543B0162I555-01
TXV33P609-0133P609-0333P609-0533P609-06
Reversing Valve33P506-0433P503-0533P526-05
Filter Dryer36P500B0136P500B02
Desuperheater62P516-0562P516-03
Desuperheater Pump24P501-02
Contactor13P004A03
2 Pole Screw Term. Block12P500A01
ABC Board17X553-00
Freeze Protection Thermistor12P505-09
HWL Thermistor13P073B05
High Pressure SwitchSKHPE600
Low Pressure SwitchSKLPE40
43
Page 44
ASTON INDOOR SPLIT SERIES INSTALLATION MANUAL
Service Parts List cont.
Parts List
Compressor34P640-0134P641-0134P642-0134P643-0134P644-01
Run Capacitor16P002-1916P002-2016P002-1816P002-31