Georgia-Pacific Engineered Lumber Canada User Manual

GP LAM® LVL
installation Guide
WOOD I BEAM™ JOISTS
WHAT YOU DON’T
SEE MATTERS
canadian Installation Instructions
Storage, Handling & Safety Guidelines
Safety Tips
1. Walking on the joists should not be permitted until they are properly braced.
2. Lateral restraint, such as an existing deck or braced end wall, must be established at the ends of the bay. Alternatively, temporary or permanent sheathing may be nailed to the first 4 feet of the joists at the end of the bay.
3. All hangers, rim boards, rim joists and blocking at the supports of the joists must be installed and nailed properly.
4. During installation, a minimum 1x4 temporary brace at least 8 feet long is required. Temporary bracing members should be spaced at no further than 10*-0( o.c. and nailed to each joist with two 8d nails (10d box nails if bracing thickness exceeds 1(). Lap bracing ends and anchor them to temporary or permanent sheathing. Remove the temporary bracing as the permanent sheathing is attached.
5. The ends of cantilevers must be temporarily braced on both the top and bottom flanges.
6. Never overload sheathed joists with loads that exceed design loads.
7. Do not ship or install any damaged I-joists.
8. When stacking construction material, stack only over beams or walls, NOT on unsheathed joists.
Storage & Handling
1. CAUTION: Wrap and joists are slippery when icy or wet.
2. Store bundles upright on a smooth, level, well-drained and supportive surface to protect
from the weather (sun and precipitation). Keep covered and strapped until installed.
3. Keep bundles above ground to minimize the absorption of ground moisture and allow air
circulation.
4. Re-cover unused products with bundle wrap. Repair damage to bundle wrap with tape,
more bundle wrap, plastic or weatherproof covering.
5. Place 2x or LVL spacers (at a maximum of 10* apart) under bundles stacked on the
ground, and between bundles stored on top of one another.
6. All handling of joists with a forklift or crane should be done carefully by lifting from below
the bottom of the bundle.
7. Joists should remain upright (web vertical) during handling.
8. Avoid excessive bowing during all phases of handling and installation (i.e., measuring, sawing,
or placement).
9. Damage may result if the I-joist is twisted or a load is applied to it while it’s lying flat.
10. An MSDS is available at www.buildgp.com.
11. When handling I-joists with a crane on the job site (“picking”), take a few simple
precautions to prevent damage to the I-joists and injury to your work crew. Pick I-joists in bundles as shipped by the supplier. Orient the bundles so that the webs of the I-joists are vertical. Pick the bundles at the 5th points, using a spreader bar if necessary.
Align stickers
one above
the other
Hard, dry,
level surface
10* max.
10*-0(
max.
GeorGia-Pacific Wood Products
2
PaGe
JaN 2014
caNadiaN iNstallatioN iNstructioNs
Floor details
Some framing requirements such as erection bracing and blocking panels have been omitted for clarity.
1E
1D
Glulam or multiple Structural Composite Lumber (SCL) headers
1C1B
1G
Holes may be cut in web for plumbing, wiring and duct work.
NOTE: Never cut or notch flanges.
Glulam or multiple SCL headers
Use code approved hangers
1J
1N1A
Floor Installation Guidelines
1. Before laying out floor system components, verify that I-Joist flange widths match hanger widths. If not, contact your supplier.
2. Except for cutting to length, never cut, drill, or notch I-Joist flanges.
3. Install I-Joists so that top and bottom flanges are within
1
2" of true vertical alignment.
4. I-Joists must be anchored securely to supports before floor sheathing is attached, and supports for multiple­span joists must be level.
5. Minimum bearing lengths: 1
1
2” for intermediate bearings.
3
6. When using hangers, seat I-Joists firmly in hanger bottoms to minimize settlement.
1
7. Leave a
8. Concentrated loads greater than those that can
16” gap between the I-Joist end and a header.
normally be expected in residential construction should only be applied to the top surface of the top flange. Normal concentrated loads include track
3
4” for end bearings and
lighting fixtures, audio equipment and security cameras.
Never suspend unusual or heavy loads from the I-Joist’s bottom flange. Whenever possible, suspend all concentrated loads from the top of the I-Joist. Or, attach the load to blocking that has been securely fastened to the I-Joist webs.
9. Never install I-Joists where they will be permanently exposed to weather, or where they will remain in direct contact with concrete or masonry.
10. Restrain ends of floor joists to prevent rollover. Use rim board or equivalent, rim joists or I-Joist blocking panels.
11. For I-Joists installed over and beneath bearing walls, use full depth blocking panels, rim board, or squash blocks (cripple members) to transfer gravity loads through the floor system to the wall or foundation below.
12. Due to shrinkage, common framing lumber set on edge may never be used as blocking or rim boards. I-Joist blocking panels or other engineered wood products – such as rim board – must be cut to fit between the I-Joists, and an I-Joist compatible depth selected.
1F
13. Provide permanent lateral support of the bottom flange of all I-Joists at interior supports of multiple-span joists. Similarly, support the bottom flange of all cantilevered I-Joists at the end support next to the cantilever extension. In the completed structure, the gypsum wallboard ceiling provides this lateral support. Until the final finished ceiling is applied, temporary bracing or struts must be used.
14. If square-edge panels are used, edges must be supported between I-Joists with 2 x 4 blocking. Glue panels to blocking to minimize squeaks. Blocking is not required under structural finish flooring, such as wood strip flooring, or if a separate underlayment layer is installed.
15. Nail spacing:
• Space nails installed to the flange’s top face in
accordance with the applicable building code requirements or approved building plans.
• If nails must be installed into the sides of flanges,
spacing shall not be closer than 3 inches o.c. for 8d common nails, and 4 inches o.c. for 10d common nails.
1M1K1J1H
georgiA-pAcific Wood products
JAN 2014
cANAdiAN iNstAllAtioN iNstructioNs
pAge
3
Floor Details (continued)
All nails shown in the details below are assumed to be common nails unless otherwise noted. 10d box nails may be substituted for 8d common shown
in details. Individual components not shown to scale for clarity.
1
/
1
8" APA Rim
Board Plus
8090
1B
Blocking Panel
1A
or Rim Jost
Depth (in.)
up to 16
Maximum Factored
Uniform Vertical Load (plf)
WI 40
WI 60, WI 80
3340
8d nails @ 6" o.c. (when used for lateral
Attach I-Joist to top plate per 1B
shear transfer, nail to bearing plate with same nailing as required
for decking)
One 8d face nail at each side at bearing
To avoid splitting flange, start nails at least 1½"from end of I-Joist. Nails may be driven at an angle to avoid splitting of bearing plate
For APA Rim Board Plus,
1
1
/8" thick, up to 16" depth allowable factored vertical load transfer
= 8090 plf.
One 8d nail at top and bottom flange
Attach Rim Board to top plate using 8d box toe nails @ 6" o.c.
Rim joist vertical load transfer (see detail 1A for capacities)
1C
Attach I-Joist per 1B
Attach rim joist to top plate per 1A
For single I-Joist, see detail 1A for capacities. For double I-Joist,
1F
the table capacity may be doubled. Filler block is not required for this detail.
Provide backer for siding
Wall sheathing, as required
Rim Board may be used in lieu of I-Joists. Backer is not required when Rim Board is used.
attachment unless nailable sheathing is used.
Attach rim joist to floor joist with one nail at top and bottom. Nail must provide 1" min. penetration into floor joist. Toe nails may be used.
Min. 1 ¾" bearing required
1G
Joist attachment per detail 1B
Blocking panel see details 1A and 1B for vertical load capacities.
1D
Rim Board blocking panel per 1A
Squash block
Provide lateral bracing per 1A, 1B or 1C
Pair of Squash Blocks 2x Lumber
1
/
1
8
" APA Rim board, Rim Board
Plus, or Rated Sturd-I-Floor 48 o.c. 1" APA Rim Board or
Rated Sturd-I-Floor 32 o.c.
Load bearing wall above shall align vertically with the wall below. Other conditions such as offset walls are not covered by this detail.
Blocking required over all interior supports
under load-bearing walls or when floor
8d nails at 6" o.c. to top plate
Vertical load transfer capacity per
pair of squash blocks as shown:
vertical load per pair of
3½" wide 5½" wide
joists are not continuous over support.
In high seismic areas blocking is required at all intermediate supports.
1E
1
/
"
16
for lumber squash blocks
Transfer load from above to bearing below. Match bearing area of squash blocks in floor cavity to post above.
Maximum factored
squash blocks (lb)
5800
9500
4500
5800
4000 5800
Method 1: One 8d nail toe nailed at each side of top and bottom flange at each end of I-Joist blocking.
Caution: Effective toe nailing may be difficult to achieve due to limited access of pneumatic nailers. The builder shall evaluate installation for potential of nail squeak.
Notes: 1- I-Joists do not always need blocking (bridging) between supports. I-Joist blocking must be installed only where specified by the building designer.
2- Use of construction adhesive is recommended at wood-to-wood contact areas. 3- It shall be permitted to offset (stagger) I-Joist blocking up to the flange width. Nailing
thru the joist flange into the ends of the I-Joist blocking is not permitted.
Blocking panels or Rim Board are also required for uniform vertical and / or lateral load transfer. (See details 1A, 1B or 1C as applicable.)
Squash block
I-Joist blocking at mid-span (or at other locations between supports) may be used to reduce vibration. Two recommended methods
of attachment are shown. Other fastening methods are possible.
1Ga
Factored load (lbs.)
size (1) 2 x 42 900 (2) 2 x 45 800 (3) 2 x 48 700 (4) 2 x 4 11 600
Squash block
size (1) 2 x 64 750 (2) 2 x 69 500 (3) 2 x 6 14 250 (4) 2 x 6 19 000
Method 2: Minimum two 10d nails face nailed thru OSB web of I-Joist blocking into 2 x 6 vertical block and clinched (preferred) or nailed thru 2 x 6 and clinched on back face of OSB web of I-Joist blocking. In addition, nail thru OSB web of full-length joist into 2 x 6 with minimum two 10d nails. Repeat at opposite end of I-Joist blocking.
Factored load (lbs.)
GeorGia-Pacific Wood Products
4
PaGe
JaN 2014
caNadiaN iNstallatioN iNstructioNs
Floor Details (continued)
All nails shown in the details below are assumed to be common nails unless otherwise noted. 10d box nails may be substituted for 8d common shown
in details. Individual components not shown to scale for clarity.
Backer block (use if factored hanger load exceeds 360 lbs.) Before installing a backer block to a double I-joist, drive three additional 3 inch nails through the webs and filler block where the backer block will fit. Clinch. Install backer
1H
tight to top flange. Use twelve 3 inch nails, clinched when possible. Verify hanger capacity with manufacturer. Maximum factored resistance for hanger for this detail = 1620 pounds.
Backer blocks (Blocks must be long enough to permit required nailing without splitting)
Flange Width
2 "
½ 5½"
3 ½"
* Minimum grade for backer block material shall be Utility grade SPF (south) or better for solid sawn lumber and Rated Sheathing grade for wood structural panels. **For face-mount hangers use net joist depth minus 3¼".
1J
Material Thickness Required*
1"
1½"
7¼"
Glulam or multiple structural composite lumber (SCL) beams
Minimum Depth**
For nailing schedules for multiple SCL beams, see the manufacturer’s recommendations
Top - or face - mounted hanger Double I-Joist header
Note: Unless hanger sides laterally support the top flange, bearing stiffeners shall be used. Backer blocks are not required for top mount hangers with factored reactions less than 360 pounds.
Face-mount hangers shallower than the joist depth shall have full depth bearing web stiffenners and shall have side flanges at least 60% of the joist
Filler block
Backer block required (both sides for face-mounted hangers)
For hanger capacity see hanger manufacturer’s recommendations. Verify double I-Joist capacity to support concentrated loads.
1K
depth.
2x plate flush with inside face of wall or beam
Top - or face - mounted hanger installed per manufacturer’s recommendations
Note: Unless hanger sides laterally support the top flange, bearing stiffeners shall be used.
Install framing anchor per manufacturer’s
1M
recommendations (both sides of stringer)
Filler block
Maximum factored support = 1620 pounds
Multiple I-Joist header with full depth filler block shown. Glulam and multiple SCL headers may also be used. Verify double I-Joist capacity to support concentrated loads.
Backer block attach per 1H. Nail with twelve 10d nails, clinch when possible.
Top-mounted hanger installed per manufacturer’s recommendations
1N
Note: Blocking required at bearing for lateral support, not shown for clarity.
Note: Unless hanger sides laterally support the top flange, bearing stiffeners shall be used.
Do not bevel­cut joist beyond inside face of wall
Attach I-Joist per 1B
georgiA-pAcific Wood products
JAN 2014
cANAdiAN iNstAllAtioN iNstructioNs
pAge
5
Loading...
+ 11 hidden pages