1. Walking on the joists should not be permitted until they are properly braced.
2. Lateral restraint, such as an existing deck or braced end wall, must be established at the
ends of the bay. Alternatively, temporary or permanent sheathing may be nailed to the
first 4 feet of the joists at the end of the bay.
3. All hangers, rim boards, rim joists and blocking at the supports of the joists must be
installed and nailed properly.
4. During installation, a minimum 1x4 temporary brace at least 8 feet long is required.
Temporary bracing members should be spaced at no further than 10*-0( o.c. and nailed
to each joist with two 8d nails (10d box nails if bracing thickness exceeds 1().
Lap bracing ends and anchor them to temporary or permanent sheathing. Remove the
temporary bracing as the permanent sheathing is attached.
5. The ends of cantilevers must be temporarily braced on both the top and bottom flanges.
6. Never overload sheathed joists with loads that exceed design loads.
7. Do not ship or install any damaged I-joists.
8. When stacking construction material, stack only over beams or walls, NOT on
unsheathed joists.
Storage & Handling
1. CAUTION: Wrap and joists are slippery when icy or wet.
2. Store bundles upright on a smooth, level, well-drained and supportive surface to protect
from the weather (sun and precipitation). Keep covered and strapped until installed.
3. Keep bundles above ground to minimize the absorption of ground moisture and allow air
circulation.
4. Re-cover unused products with bundle wrap. Repair damage to bundle wrap with tape,
more bundle wrap, plastic or weatherproof covering.
5. Place 2x or LVL spacers (at a maximum of 10* apart) under bundles stacked on the
ground, and between bundles stored on top of one another.
6. All handling of joists with a forklift or crane should be done carefully by lifting from below
the bottom of the bundle.
7. Joists should remain upright (web vertical) during handling.
8. Avoid excessive bowing during all phases of handling and installation (i.e., measuring, sawing,
or placement).
9. Damage may result if the I-joist is twisted or a load is applied to it while it’s lying flat.
10. An MSDS is available at www.buildgp.com.
11. When handling I-joists with a crane on the job site (“picking”), take a few simple
precautions to prevent damage to the I-joists and injury to your work crew. Pick I-joists
in bundles as shipped by the supplier. Orient the bundles so that the webs of the I-joists
are vertical. Pick the bundles at the 5th points, using a spreader bar if necessary.
Align stickers
one above
the other
Hard, dry,
level surface
10* max.
10*-0(
max.
GeorGia-Pacific Wood Products
2
PaGe
JaN 2014
caNadiaN iNstallatioN iNstructioNs
Floor details
Some framing requirements such as
erection bracing and blocking panels
have been omitted
for clarity.
1E
1D
Glulam or multiple
Structural Composite
Lumber (SCL)
headers
1C1B
1G
Holes may be cut in web for
plumbing, wiring and duct work.
NOTE: Never cut or notch flanges.
Glulam or multiple
SCL headers
Use code approved hangers
1J
1N1A
Floor Installation Guidelines
1. Before laying out floor system components, verify that
I-Joist flange widths match hanger widths. If not, contact
your supplier.
2. Except for cutting to length, never cut, drill, or notch
I-Joist flanges.
3. Install I-Joists so that top and bottom flanges are within
1
⁄2" of true vertical alignment.
4. I-Joists must be anchored securely to supports before
floor sheathing is attached, and supports for multiplespan joists must be level.
5. Minimum bearing lengths: 1
1
⁄2” for intermediate bearings.
3
6. When using hangers, seat I-Joists firmly in hanger
bottoms to minimize settlement.
1
7. Leave a
8. Concentrated loads greater than those that can
⁄16” gap between the I-Joist end and a header.
normally be expected in residential construction should
only be applied to the top surface of the top flange.
Normal concentrated loads include track
3
⁄4” for end bearings and
lighting fixtures, audio equipment and security cameras.
Never suspend unusual or heavy loads from the
I-Joist’s bottom flange. Whenever possible, suspend
all concentrated loads from the top of the I-Joist. Or,
attach the load to blocking that has been securely
fastened to the I-Joist webs.
9. Never install I-Joists where they will be permanently
exposed to weather, or where they will remain in direct
contact with concrete or masonry.
10. Restrain ends of floor joists to prevent rollover. Use rim
board or equivalent, rim joists or I-Joist blocking panels.
11. For I-Joists installed over and beneath bearing walls, use
full depth blocking panels, rim board, or squash blocks
(cripple members) to transfer gravity loads through the
floor system to the wall or foundation below.
12. Due to shrinkage, common framing lumber set on edge
may never be used as blocking or rim boards. I-Joist
blocking panels or other engineered wood products
– such as rim board – must be cut to fit between the
I-Joists, and an I-Joist compatible depth selected.
1F
13. Provide permanent lateral support of the bottom flange
of all I-Joists at interior supports of multiple-span joists.
Similarly, support the bottom flange of all cantilevered
I-Joists at the end support next to the cantilever
extension. In the completed structure, the gypsum
wallboard ceiling provides this lateral support. Until the
final finished ceiling is applied, temporary bracing or
struts must be used.
14. If square-edge panels are used, edges must be supported
between I-Joists with 2 x 4 blocking. Glue panels to
blocking to minimize squeaks. Blocking is not required
under structural finish flooring, such as wood strip
flooring, or if a separate underlayment layer is installed.
15. Nail spacing:
• Space nails installed to the flange’s top face in
accordance with the applicable building code
requirements or approved building plans.
• If nails must be installed into the sides of flanges,
spacing shall not be closer than 3 inches o.c. for 8d
common nails, and 4 inches o.c. for 10d common nails.
1M1K1J1H
georgiA-pAcific Wood products
JAN 2014
cANAdiAN iNstAllAtioN iNstructioNs
pAge
3
Floor Details (continued)
All nails shown in the details below are assumed to be common nails unless otherwise noted. 10d box nails may be substituted for 8d common shown
in details. Individual components not shown to scale for clarity.
1
/
1
8" APA Rim
Board Plus
8090
1B
Blocking Panel
1A
or Rim Jost
Depth (in.)
up to 16
Maximum Factored
Uniform Vertical Load (plf)
WI 40
WI 60, WI 80
3340
8d nails @ 6" o.c.
(when used for lateral
Attach I-Joist to
top plate per 1B
shear transfer, nail to
bearing plate with same
nailing as required
for decking)
One 8d face
nail at each
side at bearing
To avoid splitting flange, start nails at least 1½"from end of I-Joist.
Nails may be driven at an angle to avoid splitting of bearing plate
For APA Rim Board Plus,
1
1
/8" thick, up to 16" depth
allowable factored vertical
load transfer
= 8090 plf.
One 8d nail at top and
bottom flange
Attach Rim Board to
top plate using 8d box
toe nails @ 6" o.c.
Rim joist vertical load transfer
(see detail 1A for capacities)
1C
Attach I-Joist
per 1B
Attach rim joist to
top plate per 1A
For single I-Joist, see detail 1A
for capacities. For double I-Joist,
1F
the table capacity may be doubled.
Filler block is not required
for this detail.
Provide backer
for siding
Wall
sheathing,
as required
Rim Board may be used in lieu of I-Joists.
Backer is not required when Rim Board is used.
attachment
unless nailable
sheathing is used.
Attach rim
joist to floor
joist with one
nail at top and
bottom. Nail
must provide
1" min.
penetration into
floor joist. Toe nails
may be used.
Min. 1 ¾"
bearing
required
1G
Joist attachment
per detail 1B
Blocking panel
see details 1A and 1B
for vertical load capacities.
1D
Rim Board blocking
panel per 1A
Squash block
Provide lateral bracing
per 1A, 1B or 1C
Pair of Squash Blocks
2x Lumber
1
/
1
8
" APA Rim board, Rim Board
Plus, or Rated Sturd-I-Floor 48 o.c.
1" APA Rim Board or
Rated Sturd-I-Floor 32 o.c.
Load bearing wall above shall align vertically
with the wall below. Other conditions such as
offset walls are not covered by this detail.
Blocking required over all interior supports
under load-bearing walls or when floor
8d nails
at 6" o.c.
to top plate
Vertical load transfer capacity per
pair of squash blocks as shown:
vertical load per pair of
3½" wide 5½" wide
joists are not continuous over support.
In high seismic areas blocking
is required at all intermediate
supports.
1E
1
/
"
16
for lumber
squash
blocks
Transfer load
from above to
bearing below.
Match bearing
area of squash
blocks in floor
cavity to post above.
Maximum factored
squash blocks (lb)
5800
9500
4500
5800
40005800
Method 1:
One 8d nail toe nailed at each
side of top and bottom flange
at each end of I-Joist blocking.
Caution: Effective toe nailing
may be difficult to achieve due to limited access of pneumatic nailers.
The builder shall evaluate installation for potential of nail squeak.
Notes:
1- I-Joists do not always need blocking (bridging) between supports. I-Joist blocking must be installed
only where specified by the building designer.
2- Use of construction adhesive is recommended at wood-to-wood contact areas.
3- It shall be permitted to offset (stagger) I-Joist blocking up to the flange width. Nailing
thru the joist flange into the ends of the I-Joist blocking is not permitted.
Blocking panels or Rim Board are also required
for uniform vertical and / or lateral load transfer.
(See details 1A, 1B or 1C as applicable.)
Squash block
I-Joist blocking at mid-span (or at other locations between supports)
may be used to reduce vibration. Two recommended methods
of attachment are shown. Other fastening methods are possible.
1Ga
Factored
load (lbs.)
size
(1) 2 x 42 900
(2) 2 x 45 800
(3) 2 x 48 700
(4) 2 x 411 600
Squash block
size
(1) 2 x 64 750
(2) 2 x 69 500
(3) 2 x 614 250
(4) 2 x 619 000
Method 2:
Minimum two 10d nails face nailed
thru OSB web of I-Joist blocking
into 2 x 6 vertical block and clinched
(preferred) or nailed thru 2 x 6 and
clinched on back face of OSB web
of I-Joist
blocking. In
addition, nail
thru OSB web
of full-length
joist into 2 x 6
with minimum
two 10d nails.
Repeat at opposite
end of I-Joist
blocking.
Factored
load (lbs.)
GeorGia-Pacific Wood Products
4
PaGe
JaN 2014
caNadiaN iNstallatioN iNstructioNs
Floor Details (continued)
All nails shown in the details below are assumed to be common nails unless otherwise noted. 10d box nails may be substituted for 8d common shown
in details. Individual components not shown to scale for clarity.
Backer block (use if factored hanger load exceeds 360 lbs.) Before installing a
backer block to a double I-joist, drive three additional 3 inch nails through the
webs and filler block where the backer block will fit. Clinch. Install backer
1H
tight to top flange. Use twelve 3 inch nails, clinched when possible. Verify
hanger capacity with manufacturer. Maximum factored resistance for
hanger for this detail = 1620 pounds.
Backer blocks (Blocks must be long enough to permit required nailing without splitting)
Flange Width
2 "
½ 5½"
3 ½"
* Minimum grade for backer block material shall be Utility grade SPF (south) or better
for solid sawn lumber and Rated Sheathing grade for wood structural panels.
**For face-mount hangers use net joist depth minus 3¼".
1J
Material Thickness Required*
1"
1½"
7¼"
Glulam or multiple structural composite
lumber (SCL) beams
Minimum Depth**
For nailing schedules
for multiple SCL beams,
see the manufacturer’s
recommendations
Top - or face - mounted hangerDouble I-Joist header
Note: Unless hanger sides laterally
support the top flange, bearing
stiffeners shall be used. Backer blocks
are not required for top mount hangers
with factored reactions less than
360 pounds.
Face-mount hangers shallower
than the joist depth shall
have full depth bearing
web stiffenners and
shall have
side flanges
at least 60%
of the joist
Filler block
Backer block required
(both sides for face-mounted hangers)
For hanger capacity see hanger manufacturer’s recommendations.
Verify double I-Joist capacity to support concentrated loads.
1K
depth.
2x plate flush with
inside face of wall
or beam
Top - or face - mounted hanger installed
per manufacturer’s recommendations
Note: Unless hanger sides laterally support the top flange,
bearing stiffeners shall be used.
Install framing anchor
per manufacturer’s
1M
recommendations
(both sides of stringer)
Filler block
Maximum factored support = 1620 pounds
Multiple I-Joist header with
full depth filler block shown.
Glulam and multiple SCL
headers may also be used.
Verify double I-Joist capacity to
support concentrated loads.
Backer block attach per 1H.
Nail with twelve 10d nails,
clinch when possible.
Top-mounted hanger installed
per manufacturer’s recommendations
1N
Note: Blocking required at
bearing for lateral support,
not shown for clarity.
Note: Unless hanger
sides laterally support
the top flange, bearing
stiffeners shall be used.
Do not bevelcut joist beyond
inside face
of wall
Attach
I-Joist
per 1B
georgiA-pAcific Wood products
JAN 2014
cANAdiAN iNstAllAtioN iNstructioNs
pAge
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.