Building codes require that walls resist wind pressures caused by the design wind speeds, resist wall-racking forces
and provide weather protection. This section provides details on how wood structural panels can be used to meet these
fundamental requirements.
APA Sturd-I-Wall
®
The APA Sturd-I-Wall system consists of APA RATED SIDING (panel or lap) applied direct to studs or over nonstructural fiberboard, gypsum or rigid foam insulation sheathing*. Nonstructural sheathing is defined as sheathing not
recognized by building codes for meeting both bending and racking strength requirements.
* Where panel siding is applied over foam sheathing, see APA publication APA Rated Siding Panels over Rigid Foam Insulation Sheathing, Form C465.
TABLE 19
FASTENING APA RATED SIDING (PANEL) APPLIED DIRECT-TO-STUDS OR OVER NONSTRUCTURAL
SHEATHING
APA Rated
Panel Siding
3/8 Performance
Category
APA MDO
GENER AL
APA Rated Siding
APA Rated Siding
(a) Table is based on wind pressures acting toward and away from
building surfaces, at 30-ft height in wall Zone 5 (corners) with
smallest effective area, per Section 6.4.2.2 of ASCE 7-05 and
Section R301.2 of the 2009 IRC. Stud specific gravity = 0.42.
(b) Recommendations of siding manufacturer may vary.
(c) For use as wood structural panel wall bracing, the minimum
fastener spacing of 6" o.c. at panel edges and 12" o.c. at interme-
diate supports shall be sufficient except:
(1) For braced wall section with Performance Categor y 3/8 panel
(a)(b)(c)(d)(e)
Minimum Nail
Shank
Diameter
(in.)
(f)
Penetration
in Framing
(in.)
Wall Stud
Spacing
(in. o.c.)
166
1.5
246
0.113
16 oc
166
2.0
24 oc
siding applied horizontally over studs 24" o.c., space nails
3" o.c. along panel edges.
246
Panel Nail SpacingMaximum Wind Speed (mph)
Edges
(in. o.c.)
(g)
Intermediate
Supports
(in. o.c.)
Wind Exposure Category
BCD
121109090
6140120110
1290
NPNP
6130110100
1212510590
6140120110
1210085
NP
6140120110
(d) Hot-dip galvanized nails are recommended for most siding
applications, see Siding Fasteners section on page 48 for more
information.
(e) Maximum stud spacing shall be in accordance with Table 21A.
(f) See Table 5, page 14, for nail dimensions.
(g) Supported panel joints shall occur approximately along the center-
line of framing with a minimum bearing of 1/2". Fasteners shall
be located 3/8" from panel edges. Siding installed over two or
APA RATED LAP SIDING APPLIED DIRECT-TO-STUDS OR OVER NONSTRUCTURAL SHEATHING
Minimum Nail
Shank Diameter
(in.)
(f)
Penetration in
Framing (in.)
Minimum
Performance
Category (in.)
Wall Stud
Spacing
(in. o.c.)
Lap Siding
Width (in.)
Maximum Wind Speed (mph)
Wind Exposure Category
6140120110
3/816
8140120110
1212010090
6140120110
0.1131.5
7/1616
8140120110
1212010090
6140120110
7/1624
812010090
1290NPNP
(a) Table is based on wind pressures acting toward and away from
building surfaces, at 30-ft height in wall Zone 5 (corners) with
smallest effective area, per Section 6.4.2.2 of ASCE 7-05 and
Section R301.2 of the 2009 IRC, Stud specific gravity = 0.42.
(b) Recommendations of siding manufacturer may vary.
(c) APA Rated lap siding rated 16 oc and 24 oc shall be used with
a maximum stud spacing of 16" o.c. and 24" o.c., respectively.
(d) Hot-dip galvanized nails are recommended for most siding applica-
tions, see Siding Fasteners section of page 48 for more information.
(e) Supported panel joints shall occur approximately along the center-
line of framing with a minimum bearing of 1/2". Fasteners shall
be located 3/8" from panel edges. Siding installed over two or
more spans.
(f) See Table 5, page 14, for nail dimensions.
(a)(b)(c)(d)(e)
BCD
TABLE 21A
MAXIMUM STUD SPACING: APA RATED SIDING (PANEL) APPLIED DIRECT-TO-STUDS OR STRUCTURAL SHEATHING
Minimum Performance
Category or
Siding Description
APA MDO GENERAL
APA Rated Siding
(a) Stud spacing may be 24" o.c. for veneer-faced siding panels.
Span Rating
3/81624
15/322424
16 oc1616
24 oc2424
Maximum Stud Spacing (in.) for Vertical Rows of Nails
Parallel to SupportsPerpendicular to Supports
(a)
TABLE 21B
APA RATED SIDING (PANEL) APPLIED TO STRUCTURAL SHEATHING
Minimum Nail
(f)(g)
Panel Nail SpacingMaximum Wind Speed (mph)
Wall Stud
APA Rated
Panel Siding
Shank Diameter
(in.)
3/8 Performance Category
APA MDO GENERAL
APA Rated Siding
0.120 ring shank
16 oc or 24 oc
(a) Table is based on wind pressures acting toward and away from
building surfaces, at 30-ft height in wall Zone 5 (corners) with
smallest effective area, per Section 6.4.2.2 of ASCE 7-05 and
Section R301.2 of the 2009 IRC, Stud specific gravity = 0.42.
(b) Recommendations of siding manufacturer may vary.
(c) For use as wood structural panel wall bracing, the minimum fas-
tener spacing of 6" o.c. at panel edges and 12" o.c. at intermediate
supports shall be sufficient.
Spacing
(in. o.c.)
166
246
Edges
(in. o.c.)
(d) Hot-dip galvanized nails are recommended for most siding applica-
(e) Maximum stud spacing shall be in accordance with Table 21A.
(f) Ring shank nail shall be used.
(g) See Table 5, page 14, for nail dimensions.
(h) Supported panel joints shall occur approximately along the center-
(a)(b)(c)(d)(e)
Intermediate
(h)
Supports
(in. o.c.)
12110
Wind Exposure Category
BCD
9085
612510590
12
90NPNP
6110 9085
tions, see Siding Fasteners section on page 48 for more information.
line of framing with a minimum bearing of 1/2". Fasteners shall be
located 3/8" from panel edges.
Panel siding meets code
requirements for wall bracing
1/8" spacing is recommended
at all edge and end joints unless
otherwise indicated by panel manufacturer
Building paper or coderecognized weather-resistive
barrier required behind siding
APA RATED SIDING panels.
All edges supported by framing
or blocking.
FIGURE 8
APA STURD-I-WALL (Vertical Panel Installation)
6" minimum clearance,
siding to grade
A single layer of wood structural panel siding, since it is strong and rack resistant, eliminates the cost of installing separate
structural sheathing or diagonal wall bracing. Panel sidings are normally installed vertically, but may also be placed horizontally (long dimension across supports) if horizontal joints are blocked. Maximum stud spacings for both applications are
given in Tables 19, 20 and 21.
When installing panel or lap siding over rigid foam insulation sheathing, drive the nails flush with the siding surface,
but avoid over-driving, which can result in dimpling of the siding due to the compressible nature of foam sheathing.
Sidings are occasionally treated with water repellents or wood preservatives to improve finishing characteristics or moisture resistance for certain applications. If the siding has been treated, allowing the surface treatment to dry will avoid
solvent or chemical reaction with the foam sheathing.
When rigid foam insulation sheathing is used, building codes also generally require installation of 1/2-inch gypsum wallboard,
or other materials of the required thermal barrier rating, on the inside surface of the wall for fire protection.
See Figures 8 through 12 for panel and lap siding installation recommendations for the Sturd-I-Wall system or for siding
installed over nailable sheathing. See APA’s Build A Better Home: Walls, Form A530, for additional recommended details to
avoid moisture penetration in walls.
All panel siding edges in Sturd-I-Wall construction should be backed with framing or blocking. Use nonstaining, noncorrosive nails as described in Tables 19, 20 and 21 to prevent staining the siding.
Where siding is to be applied at an angle, install only over wood structural panel sheathing.
Note: Gluing of siding to framing is not recommended due to the increased potential for panel buckling.
Hot-dip galvanized nails are
recommended for most siding applic ations. For best
FIGURE 9
APA STURD-I-WALL (Horizontal Panel Siding Installation)
performance, stainless steel
or aluminum nails should
be considered. APA test s
Building paper
or other code-recognized
weather-resistive barrier
also show that electrically
or mechanically galvanized
steel nails appear satisfactory when plating meets or
exceeds thickness requirements of ASTM A641 Class 2
coatings, and is further protected by yellow chromate
coating. Note that galvanized
fasteners may react under wet
conditions with the natural
extractives of some wood species and may cause staining if
left unfinished. Such staining
can be minimized if the sid-
Battens at 4' or 8' o.c.
to conceal butt joints at
panel ends. Nails through
battens must penetrate
studs at least 1".
APA RATED SIDING
panels (nailing as required
for vertical installation)
1/8" spacing is
recommended at all
edge and end joints
unless otherwise
indicated by panel
manufacturer
6" minimum clearance,
siding to grade
ing is finished in accordance
with APA recommendations,
or if the roof overhang protects the siding from direct exposure to moisture and weathering.
See Tables 19, 20 and
21 for maximum
stud spacing
Panel siding meets
code requirements
for wall bracing
Seal panel edges
2x4 blocking at
horizontal joints
Wood Structural Panel Sheathing as a Nail Base for Siding
The recommendations in Tables 22 and 23 for panel and lap siding apply to siding installed over wood structural panel
sheathing. Unless otherwise indicated in the local building code, nailable sheathing includes:
1. Nominal 1-inch boards with studs 16 or 24 inches o.c.
2. APA RATED SHEATHING panels with roof Span Rating of 24 inches or greater installed with strength axis either
parallel or perpendicular to studs 16 or 24 inches o.c. (except 3-ply plywood panels must be applied with strength axis
across studs when studs are spaced 24 inches o.c.).
3. APA RATED SHEATHING panels with roof Span Rating less than 24 inches installed with strength axis either parallel or perpendicular to studs 16 inches o.c. (except plywood panels 3/8 Performance Category or less must be applied
with strength axis across studs).
Lap siding joints, if staggered, and panel siding joints may occur away from studs with wood structural panel sheathing.
Note: In addition to panel edge spacing and the use of straight studs, nailing sequence can also be a factor in maintaining a uniformly flat
appearance of the finished wall. Installation procedure: First, position the panel, maintaining recommended edge spacing, and lightly tack at
each corner. Install the first row of nails at the edge next to the preceding panel from top to bottom. Remove remaining tacking nails. Then nail
the row at the first intermediate stud. Continue by nailing at the second intermediate stud, and finally, at the edge opposite the preceding panel.
Complete the installation by fastening to the top and bottom plates.