Georg Fischer 9900-1BC Specifications

Page 1
T
Signet 9900-1BC Batch Controller System
Member of the SmartPro™ Family of Instruments
The Signet 9900-1BC Batch Controller system provides control capability and process fine­tuning in a familiar package. The programming interface uses a four-button keypad and an intuitive menu for adjusting a batching system to the best performance possible. Choose between simple or advanced modes. In simple mode, relay outputs can be used for batching, external counter, missing signal alarm and 4 to 20 mA output can be used to indicate batch status. In advanced mode relays can also be used for end of batch pulse, two-stage shutdown, overrun alarm, high flow detection, total volume or source volume alarm.
Features
• Store up to 10 batch sizes for batching or blending a variety of liquid volumes
• Customize 10 batch names for easy distinction between batches
• Modular Design - Can be purchased as a complete system or add a Batch Module and Relay Module to an existing 9900 Transmitter (Generation II)
• Remote control wiring with start, stop & resume terminals for remote batch control
• 3 programmable relays
• Two-stage control to prevent overfilling or to minimize water hammer
• Confirmation START/RESUME – Can prompt user prior to starting each batch with a Yes/No or password to prevent inadvertently starting a batch
• Enter 10 different K-Factors - one per batch for when different liquids are batched
MEASURING EQUIPMEN
77CJ
Designed for a variety of batch applications, the 9900-1BC can save up to 10 batch sizes for batching or blending a variety of liquid volumes. Customize batch names for easy distinction between batches. One K-Factor can be used for all batches, or use a different K-Factor for each batch for when different liquids are batched. User can choose to be prompted prior to starting a batch with a Yes/No or with a password to prevent inadvertently starting a batch.
The 9900-1BC operates on 10.8 to 35.2 VDC, regulated. Connect a remote start or stop switch for remote batch control. Use the end-of-batch pulse to trigger the next step in the process.
Applications
• Batch Process
Filter Backwash Initiation
• Chemical Addition
Canning and Bottling
U.S. Patent No.: D662,844 S Taiwan Patent No.: D147,150
Page 2
Specifications
General
Input Channels One Accuracy ±0.2% Terminal Blocks Pluggable screw type 14 AWG max wire gauge
Enclosure and Display
Case Material PBT Window Shatter-Resistant Glass Keypad 4 buttons, injection-molded silicone rubber seal Display Backlit, 7- and 14-segment Indicators Dial-type digital bar graph Update Rate 1 s LCD Contrast 5 settings Enclosure Size ¼ DIN Mounting Panel ¼ DIN, ribbed on four sides for use with mounting bracket for panel mount installations
Wall Large enclosure (sold as an accessory) that encases the panel mount transmitter
Environmental
Ambient Operating Temperature Backlit LCD -10 °C to 70 °C 14 °F to 158 °F Storage Temperature -15 °C to 70 °C 5 °F to 158 °F Operating Temperature -10 °C to 70 °C 14 °F to 158 °F Relative Humidity 0 to 100% condensing for front only; 0 to 95% non-condensing for back side Maximum Altitude 4,000 m (13,123 ft) Enclosure Rating Designed to meet NEMA 4X/IP65 (front face only)
Input Power
DC 24 VDC input; range: 10.8 to 35.2 VDC regulated 300 mA maximum Overvoltage Protection 48 Volt transient protection device Current limiting for circuit protection Reverse-Voltage Protection
Input Specifications
Digital (S Accuracy Determined by sensor Frequency
Power to Sensors
Power Supply
3
L) Serial ASCII, TTL level, 9600 bps
Sensitivity Range Accuracy
80 mV @ 5 Hz, mV threshold gradually increasing with frequency
0.5 Hz to 1500 Hz @ TTL level input for open collector ± 0.5% of reading max error @ 25 °C
Repeatability ± 0.2% of reading Resolution 1 μs Update Rate 150 ms nominal
Voltage +4.9 to 5.5 VDC
@ 25 °C, regulated
Current 20 mA max. Short Circuit Protected
Reverse Polarity Protected
www.gfsignet.com
Page 3
Specifications continued
Output Specifications Relay Specifications
Dry-Contact Relays (2) Open Collector (1) Type SPDT NPN Form C N/A Max. Voltage Rating 30 VDC or 250 VAC 30 VDC Max. Current Rating 5 A 50 mA
Hysteresis Adjustable (absolute in Engineering Units) Latch Reset in test screen or view mode Delay 9999.9 seconds (maximum) Test Mode Set On or Off Maximum Pulse Rate 400 pulses/minute Volumetric Pulse Width 0.1 s to 3200 s
4 to 20 mA
ANSI-ISA 50.00.01 Class H (passive)
Current Loop Output
Output 1 Span 3.8 to 21 mA Zero 4.0 mA factory set; user programmable from 3.8 to 4.2 mA Full Scale 20.00 mA factory set; user programmable 19.0 to 21.0 mA Accuracy
± 32 μA max. error @ 25 °C @ 24 VDC
Resolution 6 μA or better Temperature Drift ± 1 μA per °C Power Supply Rejection ± 1 μA per V Isolation
Low voltage (< 48 VAC/DC)
Voltage 10.8 to 35.2 VDC Max. Impedance
250 Ω @ 12 VDC 500 Ω @ 18 VDC 750 Ω @ 24 VDC
Update Rate 150 ms nominal Short circuit and reverse polarity protected Adjustable span Reversible Error Condition Selectable error condition 3.6 or 22 mA or NONE Actual update rate determined by sensor type Test Mode Increment to desired current (range 3.6 to 21.00 mA)
Shipping Weights
Base Unit 0.63 kg (1.38 lb) Batch Module 0.16 kg (0.35 lb) Relay Module 0.19 kg (0.41 lb)
Standards and Approvals
CE, UL, CUL, FCC
RoHS compliant, China RoHS
Manufactured under ISO 9001 for Quality, ISO 14001 for Environmental Management
and OHSAS 18001 for Occupational Health and Safety
Dimensions
99.06 mm (3.90 in.)
29.97 mm (1.18 in.)
www.gfsignet.com
99.06 mm (3.90 in.)
8.13 mm (0.32 in.)
91.44 mm (3.60 in.)
54.10 mm (2.13 in.)
Page 4
Signet Model 9900-1BC Batch Controller System
(Includes mounting bracket and panel gasket)
Signet Sensors - Flow
FLOW
System Overview
525
2000
515
2536
Panel Mount - Tank, Wall
Signet Model 9900-1BC Batch Controller System
with Wall Mount Accessory
2100
2507
2537
2540
+
3-9900.392
2551 2552
Signet Fittings - See individual sensor data sheets
Ordering Information
Mfr. Part No. Code Description
3-9900-1BC 159 001 770 Batch Controller System
3-9900-1P
159 001 695 9900 Panel Mount Transmitter
3-9900.393 159 001 698 Relay Module - 2 DCR (dry-contact relays) 3-9900.397 159 310 163 Batch Module
Accessories and Replacement Parts
Mfr. Part No Code Description
6682-1102 159 001 710 DC Power Plug, 2 Pos, Right Angle 6682-1103 159 001 711 Relay Module Plug, 3 Pos, Right Angle 6682-1104 159 001 712 Loop Power Plug, 4 Pos, Right Angle
3
6682-3004 159 001 725 Freq/S 6682-3104 159 001 713 Freq/S 7300-7524 159 000 687 24 VDC power supply 7.5 W, 300 mA 7300-1524 159 000 688 24 VDC power supply 15 W, 600 mA 7300-3024 159 000 689 24 VDC power supply 30 W, 1.3 A 7300-5024 159 000 690 24 VDC power supply 50 W, 2.1 A 7300-1024 159 000 691 24 VDC power supply 100 W, 4.2 A 3-9900.390 159 001 714 Standard Connector Kit, Right Angle 3-9900.391 159 001 715 Connector Kit, In-Line 3-9900.392 159 001 700 Wall Mount Accessory 3-9000.392-1 159 000 839 Liquid Tight Connector Kit, NPT (1 pc.)
L Plug, 4 Pos, In-Line
3
L Plug, 4 Pos, Right Angle
All sold separately
3-9900-1BC.099 Rev A (02/13)
© Georg Fischer Signet LLC 3401 Aero Jet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057 • www.gfsignet.com • e-mail: signet.ps@georgfischer.com Specifications subject to change without notice. All rights reserved. All corporate names and trademarks stated herein are the property of their respective companies.
Loading...