Georg Fischer 9900 Operating Manual

Signet 9900 Transmitter
*3-9900.090*
3-9900.090 Rev. H 08/17
Quick Start
Look for the Quick Start icon to quickly set up your new 9900.
English
Operating Instructions
Your new Signet 9900 Transmitter needs to be calibrated and the sensor needs to be initialized prior to use. The following steps outline the recommended procedure to start up a new system.
1. Module Installation (page 3)
2. Installation (page 7)
3. Wiring (page 8)
4. Sensor Wiring (page 11)
5. Power Wiring (page 17)
6. Relay and Open Collector Wiring (page 18)
7. Relay Functions (page 19)
8. Operation (page 23)
9. Menu System (page 25)
Panel Mount
Field Mount
English
Deutsch
Français
Español
Italiano
中文
Description
The 9900 Transmitter, a member of Signet's line of SmartPro® instruments, provides a single-channel interface for all Flow, pH/ORP, Conductivity/Resistivity, Salinity, Pressure, Temperature, Level, Dissolved Oxygen, Turbidity, Batch and other applications.
The 9900 is available in either Panel or Field Mount. Both versions run on
10.8 to 35.2 VDC power (24 VDC nominal), and can power certain sensors on loop power (see NOTE on page 11).
The 9900 Transmitter, also allows third-party 4 to 20 mA signals to be used as an input (optional Signet 8058 i-Go® Signal Converter required, sold separately).
Compatibility
The 9900 is compatible with all GF Signet products listed in the column to the right.
 pH and ORP electrodes require the
Signet 2750/2751 DryLoc® Sensor Electronics (sold separately).
 Conductivity/Resistivity or Salinity
measurement requires either the optional Direct Conductivity/Resistivity Module (part number 3-9900.394) or the Signet 2850 Conductivity/Resistivity Sensor Electronics (sold separately). NOTE: If using the 2850, use the one­channel Digital (S3L) models. The two­channel model 3-2850-63 may be used with only one channel connected. Do not use with both channels connected. The 4 to 20 mA models 3-2850-52 and 3-2850-62 are incompatible with the 9900.
 Turbidity measurement using Signet 4150
or Dissolved Oxygen measurement using Signet 2610-31 requires Signet 8058 i-Go Signal Converter (sold separately).
Flow
515*/8510*, 525*, 2000, 2100, 2507, 2536*/8512*, 2537, 2540*, 2551, 2552
pH/ORP
2724-2726 with 2750*/2751 2734-2736 with 2750*/2751 2756-WTx–2757-WTx with 3719 and 2750*/2751 2764-2767 with 2750*/2751 2774-2777 with 2750*/2751
Conductivity/Resistivity, Salinity
2819-2823 with 2850 or Cond/Res Module 2839-2842 with 2850 or Cond/Res Module
Level, Temperature, Pressure
2250*, 2350*, 2450*
Turbidity
4150 requires 8058
Dissolved Oxygen
2610-41 direct to 9900 2610-31 requires 8058
* Can be run on Loop Power (see NOTE on page 11)
Warranty Information Table of Contents
Refer to your local Georg Fischer Sales offi ce for the most current warranty statement.
All warranty and non-warranty repairs being returned must include a fully completed Service Form and goods must be returned to your local GF Sales offi ce or distributor. Product returned without a Service Form may not be warranty replaced or repaired.
Signet products with limited shelf-life (e.g. pH, ORP, chlorine electrodes, calibration solutions; e.g. pH buffers, turbidity standards or other solutions) are warranted out of box but not warranted against any damage, due to process or application failures (e.g. high temperature, chemical poisoning, dry-out) or mishandling (e.g. broken glass, damaged membrane, freezing and/or extreme temperatures).
Product Registration
Thank you for purchasing the Signet line of Georg Fischer measurement products.
If you would like to register your product(s), you can now register online in one of the following ways:
• Visit our website www.gfsignet.com. Under Service and Support click Product
Registration Form
• If this is a pdf manual (digital copy), click here
Safety Information
 Follow instructions carefully to avoid personal injury.  This unit is designed to be connected to equipment
which can be hazardous to persons and property if used incorrectly.
 Read and understand all associated equipment
manuals and safety warnings before using with this product.
 Remove power to unit before wiring connections.  Wiring connections to this product should only be
performed by qualifi ed personnel.
 Do not use unit if front panel is cracked or broken.
Warning / Caution / Danger
Indicates a potential hazard. Failure to follow all warnings may lead to equipment damage, injury, or death.
Electrostatic Discharge (ESD) / Electrocution Danger
Alerts user to risk of potential damage to product by ESD, and/or risk of potential of injury or death via electrocution.
Personal Protective Equipment (PPE)
Always utilize the most appropriate PPE during installation and service of Signet products.
NOTE / Technical Notes
Highlights additional information or detailed procedure.
General Information .........................................................2
Dimensions ......................................................................3
Module Installation ...........................................................3
Plug-In Modules .........................................................4
Relay Module .............................................................4
Direct Conductivity/Resistivity Module .......................5
H COMM Module .......................................................5
Batch Module .............................................................6
4 to 20 mA Output Module .........................................6
Installation ........................................................................7
Wiring ...............................................................................8
Signal Type: Frequency .............................................9
Signal Type: Digital (S
3
L) ...........................................9
Signal Type: 4 to 20 mA ...........................................10
Terminal Identifi cation ..............................................10
Sensor Wiring ...........................................................11
Power Wiring ............................................................17
Relay and Open Collector Wiring ............................18
Relay Functions .............................................................19
Relay and Open Collector Outputs ................................19
Operation .......................................................................23
Menu System .................................................................25
System Setup Menu .................................................25
Common Menus .............................................................27
LOOP Menu .............................................................27
RELAY Menu ............................................................28
OPTION Menu .........................................................30
Sensor-Specifi c Menus ..................................................31
Flow ..........................................................................31
pH .............................................................................33
ORP ..........................................................................35
Conductivity/Resistivity ............................................37
Pressure ...................................................................39
Level/Volume ............................................................40
Temperature .............................................................42
4 to 20 mA ................................................................43
Salinity ......................................................................45
Dissolved Oxygen ....................................................47
Troubleshooting .............................................................49
Appendix ........................................................................51
Averaging .................................................................51
LOG Current Loop Output .......................................51
Custom Measurements ............................................52
Calibration Procedures - pH.....................................56
Calibration Procedure - ORP ...................................58
Calibration Procedure - Conductivity/Resistivity ......60
Calibration Procedure - Flow ...................................61
Calibration Error Messages .....................................62
USP Limits ................................................................63
H COMM Module Overview .....................................64
H COMM Module Installation ...................................65
H COMM Module Wiring ..........................................65
H COMM Module Operation ....................................67
HART Commands ....................................................68
Unit Codes ...............................................................69
Specifi cations .................................................................70
Maintenance ...................................................................71
Ordering Information ......................................................72
2
9900 Transmitter
Dimensions Module Installation
Panel Mount
3-9900-1P
29.97 mm (1.18 in.)
8.13 mm (0.32 in.)
99.06 mm (3.90 in.)
91.44 mm (3.60 in.)
99.06 mm (3.90 in.)
Top ViewSide View
54.10 mm (2.13 in.)
Base Unit
3-9900.393 Relay Module
5A 30 VDC
5A VAC
Rating:
׽׽
~
Relay Module (Panel Mount
Only)
H COM
Conductivity/
Resistivity
H COMM Module
DC Power
Loop Voltage
3-9900.394
Cond/Res Module
Module
If the 9900 Base Unit will be mounted in a panel, the plug-in modules may be installed either before or after the base unit is mounted. If the 9900 Base Unit will be mounted using the wall mount accessory kit (3-9900.392), install plug-in modules fi rst.
If installing both the Conductivity/Resistivity (Cond/Res) and the H COMM Modules, install the H COMM Module fi rst, then the Cond/Res Module on top of it (see illustration on page 5).
Field Mount
3-9900-1
107 mm
(4.21 in.)
88.90 mm (3.50 in.)
44.45 mm (1.75 in.)
24.13 mm (0.95 in.)
(3-8051-X shown)
NOTE: 3-8051-X Integral Mounting Kit sold separately.
3-9900.396 Angle Adjustment Adapter Kit
88.90 mm (3.50 in.)
25° Ref.
0.68 mm (0.27 in.)
CAUTION
Exercise care when installing modules. Do not bend connecting pins.
To install modules:
Remove power from the 9900. Carefully align pins and connectors (do not bend connecting pins) and push module fi rmly into place, then attach with screw(s) (except H COMM Module).
CAUTION
LOOP as well as DC power MUST be removed BEFORE installing H COMM Module.
To remove modules:
Remove power from the 9900. For Relay, Cond/Res, and 4 to 20 mA Output Modules,
unplug connectors, remove screw(s), and carefully pull module straight out from the base unit. Do not bend the connecting pins.
For H COMM Module, squeeze the tabs on the bottom edge, grasp the module and pull straight out. Do not bend the connecting pins.
For Batch Module, remove the Relay module. Loosen bottom screw of Batch module. Carefully grip and squeeze the tabs at the top of the module to release. Pull module away from the unit. Do not bend the connecting pins.
88.90 mm
3.50
(3.50 in.)
WARNING
Relays may be connected to external high-voltage power sources or multiple power sources creating an electrocution hazard.
9900 Transmitter
3
Plug-In Modules
Optional modules and accessories are available for the 9900: a. Base Unit (required) b. Slot for optional H COMM Module c. Slot for optional Conductivity/Resistivity, Batch, or 4 to 20 mA Output Module d. Slot for optional Relay Module (not available on fi eld mount)
Each item is ordered separately. Modules are fi eld-replaceable at any time. See Module Installation (pg. 3) and Ordering Information (pg. 72) sections for more details.
3-9900.395
H COMM Module
DC Power
Loop Voltage
a.
9900 Module
H COMM* XXXX
Relay XXXX
Conductivity/
Resistivity
Batch XXX
4-20mA
Output*
9900 Generation
I II III IV
XXXX
XX
CAUTION
Avoid Electrostatic Discharge (ESD).
 Minimize handling of the plug-in modules to
reduce the possibility of damage due to ESD.
 Handle modules by the edges.
Never touch any exposed circuitry or contacts.
 Wear an anti-static wristband or stand on an
anti-static mat, or keep one hand touching a properly grounded pipe or other piece of properly grounded metal when handling modules.
*Able to run on Loop power
Relay Module
(Panel Mount installations only)
Mfr. Part No. Code Description
3-9900.393 159 001 698 Relay Module - Two dry-contact relays
In addition to the standard programmable Open Collector output in the base unit, the Panel Mount version of the 9900 has a slot for an optional Relay Module, which adds two programmable dry-contact relays. The Open Collector output in the base unit uses the Relay 1 setting in the menus. If the optional Relay Module is installed, these are assigned to relays 2 and 3 in the menus.
Dry-contact relays are electromechanical switches with a moving contact armature. They are suitable for many general-purpose applications, AC or DC, including AC loads up to 250 V. Install RC Filter Kits, 3-8050.396, on relays used to switch motor or inductive loads.
 Two (2) SPDT dry-contact relay (DCR) inputs  User programmable  250 V, 5 A maximum resistive loading (AC).  Can switch line voltage (typically 120 to 240 VAC)  Can switch DC voltage (< 30 VDC @ 5A)  Larger voltage and current ratings than Open Collector outputs.
For wiring information, refer to the Relay and Open Collector Wiring section, page 18.
d.
3-9900.393 Relay Module
5A 30 VDC
5A VAC
Rating:
׽׽
~
b.
c.
DC Power
Loop Voltage
NOTE: The Relay Module requires 10.8-35.2 VDC, 300 mA power connection to DC PWR Terminals. The Relay Module cannot be used with loop power.
 The two red Mechanical Relay Indicator LEDs on the front panel of the 9900 show the
status of relays 2 and 3. (Status of all relays and Open Collector is available at all times in a single screen in View mode.)
 Hysteresis and time delay are adjustable for each relay.
CAUTION
Switching active loads (usually inductive) can cause contact arcing suffi cient to damage the relays.
The RC Filter Kit or “snubber” (part number 3-8050.396) is available as an accessory to reduce or eliminate these damaging effects. Recommended for inductive loads greater than 50 VAC (remote relays, solenoids, pumps, etc.)
4
9900 Transmitter
CAUTION
DO NOT bundle Relay Module wiring with other wiring.
Doing so may cause injury and/or damage to 9900 Transmitter, Relay Module, and Batch Module.
Direct Conductivity/Resistivity Module
Mfr. Part No. Code Description
3-9900.394 159 001 699 Direct Conductivity/Resistivity Module
The Direct Conductivity/Resistivity (Cond/Res) Module interfaces Signet 2818-2823 and 2839-2842 Conductivity electrodes directly to the 9900. (Conductivity/Resistivity and Salinity measurements may also be performed via the 2850 Sensor Electronics connected through the 9900 Digital (S
 Provides fi ltering and conditioning.  Sensor cable length can be extended to 30 m (100 ft).  2839 - 2842 sensors come with a cell constant certifi cate to improve the accuracy of
the sensor measurements (see page 38).
Signet Conductivity Module cannot operate when using loop power and requires an external DC power supply to be used with the 9900 Transmitter (see Power Wiring, pg. 17).
3
L) input.)
Red
Black
White
Shield
SHIELD (SILVER)
ISO GND (BLK)
SIGNAL (RED)
TEMP (WHT)
DC Power
Loop Voltage
2818 Sanitary 2819-
2821
2822 2823 2839-
2842
H COMM Module
Mfr. Part No. Code Description
3-9900.395 159 001 697 H COMM Module
The H COMM Module enables communication between the 9900 and a HART®-enabled device. The HART (Highway Addressable Remote Transducer) Protocol superimposes digital signals on top of the 4 to 20 mA analog signal.
Refer to the 9900 H COMM Module Instruction Sheet 3-9900.094 for further details.
NOTE: With H COMM Module installed, a minimum of 24 V is required for loop-powered systems.
NOTE: The black rubber jumper adjacent to the power terminal should only be removed when both the H COMM Module is utilized and the required sensor cable length is over 304 m (1000 ft).
See Appendix for H COMM Module Overview, Installation, Wiring, Operation, HART Commands, and Unit Code information. (See page 64-69)
H COMM Module
DC Power
Loop Voltage
NOTE: The H COMM Module can run on Loop Power.
TEMP (WHT)
ISO GND (BLK)
SIGNAL (RED)
Cond/Res Module
3-9900.395
H COMM Module
SHIELD
HART® is a registered trademark of the HART Communication Foundation, Austin, Texas, USA. Any use of the term HART hereafter in this document implies the registered trademark.
9900 Transmitter
5
Batch Module
Mfr. Part No. Code Description
3-9900.397 159 310 163 Batch Module
Convert a 9900-1P Transmitter (Generation II** or later) into a Batch Controller system by utilizing a Batch Module (3-9900.397) and a Relay Module (3-9900.393).
Optional Module Wiring:
 Wire an external button or keypad (customer supplied) to stop, start or resume
a batch remotely.
 *Wire an external input that can inhibit a batch from starting.
Full 9900-1BC Batch Controller System manual available at www.gfsignet.com
3-9900.397
Batch Module
Stop/Inhibit
Resume
Common
Start
Common
Start
Stop
Inhibit*
Resume
4 to 20 mA Output Module
Mfr. Part No. Code Description
3-9900.398-1 159 001 784 4 to 20 mA Output Module
The optional 4 to 20 mA Output Module adds an additional 4 to 20 mA loop output to a Signet 9900 Transmitter (Panel or Field Mount). Requires the 9900 Generation III** or later.
Features:
 4 to 20 mA Output Module can be powered using Loop Power or DC Power in the
9900 base unit.
 Independent settings for the loop currents of the Output Module and 9900 base unit
(Error, Loop Adjustments, etc.).
 The Primary or Secondary (if applicable) measurement of a compatible sensor can
be selected as the loop source.
 The same source (Primary or Secondary measurement) can be used for Loop 1 in
the 9900 base unit and Loop 2 in the Output Module.
** NOTE:
Verify 9900 Transmitter generation in the OPTIONS Menu.
NOTE: The 4 to 20 mA Output,
PWR+ PWR–
Loop+ Loop–
Loop2+ Loop2–
Red
Black
Blue
+
+
Power Supply
10.8 to 35.2 VDC
PLC or Recorder
Loop 1 Input
4 to 20 mA
Direct Conductivity, and Batch Modules share the same installation site on the 9900 base units.
Only one of these modules can be used per 9900 Transmitter.
NOTE:
PLC or Recorder
Blue
+
Loop 2 Input
4 to 20 mA
6
9900 Transmitter
The Output Module can run on Loop Power.
Installation
System Start-up: Step 1
Prepare the transmitter installation location. If the back of the transmitter is diffi cult to access when installed, wire the removable terminal blocks fi rst, then install it completely.
Next step: Wiring (see page 8).
For future reference, for each installation, it is recommended to record the part number and serial number of each of the components listed here:
Facility Tag Number or System ID (user assigned):__________________
Base unit 3-9900-____ S/N ___________________ Relay Module 3-9900.393 S/N ___________________ Cond/Res Module 3-9900.394 S/N ___________________ H COMM Module 3-9900.395 S/N ___________________ Batch Module 3-9900.397 S/N ___________________ 4 to 20 mA
Panel Mount Installation
Tools and Equipment Required
 Fine-tooth fi le  ¼ DIN punch or jigsaw suitable for cutting panel opening to within 1 mm (0.04 in) tolerance.  ¼ DIN punches are available and recommended for creating clean, precise openings
quickly and easily in most instrument panels.
 If a punch is not available, a jigsaw or other cutting tool can be used.
An adhesive template is provided to help guide the cutting process. De-burr and smooth the opening with a fi le.
Output Module 3-9900.398-1 S/N ___________________
Do not mount in direct sunlight.
Panel Cutout
92 x 92 mm
_
(+ 0.8, - 0 mm)
3.6 x 3.6 in.
(+0.031, -0 in.)
Panel Cutout
92 x 92 mm
(+ 0.8, - 0 mm)
3.6 x 3.6 in.
(+0.031, -0 in.)
panel
Quick-clip
mounting
bracket
minimum
clearance
25 mm
(1 in.)
3-9900.395
H COMM Module
gasket on front side of panel
DC Power
Loop Voltage
Panel Cutout
92 x 92 mm
(+ 0.8, - 0 mm)
3.6 x 3.6 in.
(+0.031, -0 in.)
Panel Cutout
92 x 92 mm
(+ 0.8, - 0 mm)
3.6 x 3.6 in.
(+0.031, -0 in.)
terminal blocks
1. The panel mount transmitter is designed for installation using a ¼ DIN punch. Recommended clearance on all sides between instruments is 25 mm (1 in).
2. Place gasket on instrument, and install in panel.
3. Slide mounting bracket over back of instrument until bracket snaps into latches on sides of instrument.
To remove:
1. Secure instrument temporarily with tape from front or grip from rear of instrument. DO NOT RELEASE.
2. Press bracket clips outward and remove.
Field Mount Installation
Field mounting requires a separate mounting kit. The 3-8050 Universal Mount Kit, the 3-8051 or 3-8052 Integral Mount Kits, and the 3-9900.396 Angle Adjustment Adapter Kit enable the transmitter to be installed virtually anywhere. Detailed instructions for fi eld installation options are included with the 3-8050, 3-8051 and 3-8052 adapter kits (see Ordering Information section).
For Field Mount installations with a Cond/Res Module, the 3-9900.396 Angle Adjustment Adapter is required along with a 3-8050 or 3-8052 adapter kit to allow for suffi cient clearance for the wiring.
Field Mount with
3-8050 Universal Mount Kit
Field Mount with
3-8051 Integral Mount Kit
and Angle Adjustment Adapter
9900 Transmitter
7
Wiring
System Start-up: Step 2
Wire the transmitter for all connections with the power off. Keep any 4 to 20 mA and relay-actuated output devices that are connected to it offl ine at this time. Connect the sensors (page 11), power (page 17) and relay(s) (page 18).
Next step: Relay Functions (see page 19).
Wiring Tips:
 Do not route the sensor, DC power, or 4 to 20 mA cables in conduit containing
AC power wiring. Electrical noise may interfere with sensor signal.
 Routing the sensor cable in grounded metal conduit can help prevent electrical noise
and mechanical damage.
 Seal the cable entry points to prevent moisture damage.  Only one wire should be inserted into a terminal.  Splice double wires outside the terminal or use appropriate wire ferrule,
not to exceed 2 mm (0.08 in) diameter.
All wiring connections to the 9900 are made via removable terminals.
In general:
 The Power, Loop and Open Collector plugs and the Relay Module plug accept
12 to 28 AWG wire. The S3L/Freq plug and the Cond/Res Module plug accept 16 to 28 AWG wire.
 Strip 7 mm (0.28 in.) of insulation from wire tips and tin bare ends to eliminate fraying.  Insert wire tip or ferrule completely into the terminal and secure with the screw.  Do not allow any AC leads that may be connected to the internal relays to come in
contact with low voltage wiring.
Tools Required
 Phillips screwdriver  Flat-head screwdriver  Wire strippers
For Field Mount installations, refer to the wiring diagram inside the Field Mount housing.
CAUTION:
Avoid Electrostatic Discharge (ESD)
 Minimize handling of plug-in modules to reduce the
possibility of damage due to ESD.
 Handle modules by the edges. Never touch any exposed
circuitry or contacts.
 Wear an anti-static wristband or stand on an anti-static mat,
or keep one hand touching a properly grounded pipe or other properly grounded piece of metal when handling modules.
8
9900 Transmitter
Signal Type: Frequency
Signet fl ow sensors 515/8510, 525, 2000, 2100, 2507, 2536/8512 and 2540 provide a frequency output. (Flow sensors 2551 and 2552 can be confi gured with either Digital (S or Frequency outputs, see page 13.)
The maximum allowable cable length for sensors with frequency output is dependent upon the output signal strength of the sensors themselves, and the degree to which the signals are susceptible to EMI or "noise." This is largely a function of whether the sensors are self-powered (515/8510 and 525), or powered by an external source.
 The input terminals on the 9900 carry frequency data signals from the sensor.  Do not route sensor or output cables in conduit containing AC power wiring.
Electrical noise may interfere with sensor signal.
 Routing cable in grounded metal conduit will help prevent electrical noise and
mechanical damage.
 Seal cable entry points to prevent moisture damage.  Only one wire should be inserted into a terminal. Splice double wires outside the terminal.  In case of noise interference, ground the sensor SHIELD wire to a local earth ground
at a point near the sensor.
 Consult the sensor manual for additional wiring information.
3
L)
Signal Type: Digital (S3L)
 The input terminals on the 9900 carry Digital (S3L) serial data from the sensor.  Do not route sensor or output cables in conduit containing AC power wiring.
Electrical noise may interfere with sensor signal.
 Routing cable in grounded metal conduit will help prevent electrical noise and
mechanical damage.
 Seal cable entry points to prevent moisture damage.  Only one wire should be inserted into a terminal. Splice double wires outside the terminal.  The TOTAL cable length from I/O devices to the transmitter must not exceed 305 m (1000 ft).  In case of noise interference, ground the sensor SHIELD wire to a local earth ground
at a point near the sensor.
 Consult the sensor manual for additional wiring information.  The maximum cable length of the Digital (S3L) bus varies depending on the types
of sensors connected and the size of the conductors in the cable. For best results, determine the maximum cable length for the system before routing cables.
 There are several methods that can help route the digital cables and remain within the
distance limitations.
Flow sensor models with
Frequency
Output
515/8510 X
525 X
2000 X
2100 X
2507 X
2536/8512 X
2537 X
2540 X
2551 X
2552 X
In case of noise interference, connect the cable shield to earth ground.
Maximum total cable length of the Digital (S3L) Bus:
The quality of the cable used in the bus determines the maximum length of all branches combined. The maximum cable length may not exceed 305 m (1000 ft), regardless of current requirements.
Maximum
Cable Length
60 m
(200 ft)
305 m
(1000 ft)
9900 Transmitter
9
Signet 8058 i-Go™
4-20 mA to S
3
L Converter
+GF+
4-20 mA input S3L Output
Input
4-to-20 mA
Output
S
3
L
White
Shield
Shield
Black
Black
Red
Red
Signal Type: 4 to 20 mA
When connecting a non-Signet sensor to the 9900, the sensor’s 4 to 20 mA signal must be converted to Digital (S and converts it into Digital (S
1. Wire the 8058 between the 4 to 20 mA loop source and the 9900 Digital (S
3
L). The 8058 i-Go Signal Converter accepts any 4 to 20 mA signal
3
L).
3
L) input
terminals (see page 14).
2. In the 9900 INPUT TYPE menu (see System Setup Menu discussion, page 25),
specify 4 to 20 mA INPUT.
3. Set additional labels and abbreviations as described on pgs. 42-43.
X
A
M
C
1
2
D
V
5
+
3
3
1
p
1 -
o
p
o
o
4
L
o
/C
5
6
/C
Input
N
4-20 mA
L Converter
3
3
S L
Output
4-20mA to S
8058 i-Go™
+GF+
L
+
N
2
- p
2
o
p
o
o
L o L
C D
3
V
9 GND
8 S L
7 +5
8058-1
+
G
3 2 1
6 5 4
S ig
n
N/C
7 8 9
F
+
L o
o
p
1
P
W
R
L
o o
p
2
P
W
R
S
3
L
D
A
TA
e t 80
5
8
8058-2
Terminal Identifi cation
3-8058.610D
For the 8058-2, connect Channel 1 ONLY
The 9900 requires regulated 10.8 to 35.2 VDC (24 VDC nominal) from an external power supply (not supplied). Maximum current draw is:
200 mA = 9900 without Relay module 300 mA = 9900 with Relay module
Terminals 1-2: DC Power
Required by the instrument
 10.8 to 35.2 VDC input power to sensors, relays and the LCD backlight
Terminals 3-4: Loop Power (may also be used for system power)
 10.8 to 35.2 VDC
NOTE: Backlight, LEDs and optional Relay Module do not operate on
loop power. Any connected sensors or sensor electronics that cannot operate on loop power will also be inoperative.
Terminals 5-6: Open Collector
 Software selectable for Normally Open or Normally Closed.  May be disabled (Off) if not used.
Terminals 7-10: Digital (S
3
L)/Frequency Input
7: V+: +5 VDC out to sensor (black wire) 8: DATA: Input signal from sensor (red wire) 9: GND: Sensor ground (white wire) 10: SHLD: Cable shield
Power
1 2
3 4
5
OC- OC+
Digital (S3L)/Freq
SHLD
DATA
GND
V+
PWR+ PWR– Loop+ Loop–
6
10
9900 Transmitter
10978
Sensor Wiring
3-9900.395
H COMM Module
DC Power
Loop Voltage
Connect sensor wires here as shown in the following fi gures.
Connect power and open
collector wires here as
shown on pages 17 and 18.
Loop powered systems cannot power both an H COMM Module and pH sensor.
If using both an H COMM Module and pH sensor, DC power is required.
Sensor model
Freq
Output
Digital (S3L)
Output
Run on
Loop Power
9900 Generation
I II III IV
515/8510 X X XXXX
525 X X XXXX 2000 X XXXX 2100 X XXXX 2250 X X XXXX 2350 X X XXXX 2450 X X XXXX 2507 X XXXX
2536/8512 X X XXXX
2537-5 X XXXX
2540 X X XXXX 2551 X X XXXX
Loop Power can be used ONLY for the following sensors:
515/8510, 525, 2250, 2350, 2450, 2536/8512, 2540, 8058 and pH/ORP sensors with 2750; all other measurement sensors require DC power.
2552 X X XXXX
2610-41 XXX
2610 + 8058 X XXXX
2724-2726 X XXXX 2734-2736 X XXXX
2750 X X* XXXX 2751 X XXXX
2756-2757 X XXXX 2764-2767 X XXXX
Advanced 2751 features require Gen 4 or greater
2774-2777 X XXXX 2819-2823 X XXXX 2839-2842 X XXXX
2850 X XXXX
4150 + 8058 X XXXX
U1000 X XXXX
* A minimum of 24 VDC Loop Power is required for the 2750.
9900 Transmitter
11
Sensor Wiring
NOTE: Loop Power cannot be used to power Signet models 2000, 2100, 2507, 2537,
2551 or 2552 Flow sensors.
Wiring for:
515/8510
525 2536/8512 2540
FLOW
2000 2100 2507
Wiring for:
FLOW
Black
Red
Shield
Frequency
SHLD
DATA
GND
V+
No connection
Technical Notes:
• See corresponding product manuals for maximum cable length.
• Maintain cable shield through cable splice.
• Route sensor cable away from AC power lines.
• 515/8510 and 525 installations, connect the silver (shield) wire to earth ground in case of EMI noise interference.
2537-5
Technical Notes:
• Wiring terminals on the 2537
9900 S
V+
3
L Inputs
SHLD
DATA
GND
are rated for 16 to 22 AWG wires.
• The cable must be 7 mm to 10 mm in diameter (0.275 in. to 0.394 in.) to seal properly in the liquid-tight connector.
Blk Red Shld
S1
-
+
S2
• The conduit ports have ½-inch NPT threads. After routing the cables, seal the port with a liquid-
Black Red White
tight conduit connector (3-9000.392-1) or with conduit.
• The 2537 models can connect to the 9900 via a relay frequency signal or with a Digital (S3L) output. Signet recommends installing the Digital (S3L) output model (2537-5) because Digital
3
L) is more accurate.
(S
• See 2537 instruction manual for additional installation information.
12
9900 Transmitter
Sensor Wiring
Wiring for:
2551-XX-11
Blind Magmeter
Black
Red
White
Shield
V+
DATA
SHLD
GND
Frequency
3
S L
4
3
4
2551 Technical Notes:
• When the blue jumper illustrated here is placed over both pins, the 2551-XX-11 (Blind Magmeter) outputs an open collector frequency signal. When the jumper is removed (or placed over one pin for storage) the 2551-XX-11 outputs a digital
3
(S
L) signal (recommended).
3
Only in case of EMI interference. See Frequency Output Technical Notes (2551 & 2552) at right
Input Wiring for 2551 and 2552 sensors
• Either Frequency or Digital (S3L) may be used.
Signet recommends con guring these sensors with the Digital (S3L) output
because it is more accurate and will also display reverse fl ow (negative numbers).
• Input type is selected by choosing between “SENSOR FREQ” and "SENSOR S3L" in the FLOW sensor type INPUT menu (see page 32).
• Loop Power cannot be used to power these sensors.
Wiring for:
2552
Frequency9900 S3L Inputs
V+
DATA
SHLD
GND
V+
DATA
SHLD
GND
Frequency Output Technical Notes (2551 & 2552):
• The frequency output will be displayed as positive ow regardless of the fl ow direction.
• 5 VDC power required by the 2551 & 2552 is supplied by the 9900. No additional power is required.
• Connect the silver wire (shield) to earth ground in case of EMI noise interference.
• If EMI noise interference continues, disconnect silver wire (shield) from 9900
2552 Technical Notes:
• The 2552 outputs an open collector frequency signal that can be connected to the 9900.
Black
Brown
White
Blue
Shield
Black
Brown
White
Blue
Shield
No
X
connection
9900 Transmitter
13
Sensor Wiring
Wiring for:
2250 2350 2450
2551* 2750/2751 2850
* 2551-XX-21, -41 Display Magmeter
Wiring for:
9900 S
V+
Black
Red
White
Shield
NOTE: The 2850 has no SHIELD wire.
3
L Inputs
SHLD
DATA
GND
Technical Notes:
• Use three conductor shielded cable for sensor cable splices up to 305 m (1000 ft) max.
• Maintain cable shield through cable splice.
• Route sensor cable away from AC power lines.
• Connect the silver (shield) wire to earth ground in case of EMI noise interference.
Technical Notes:
• The 2850 has no SHIELD wire.
• To work correctly with the 9900, the 2850 must be set for the custom cell constant or the actual probe cell constant and the 9900 set for a 1.0 cell constant.
8058-1
8058-1 close-up
8058-2
4-to-20 mA
+GF
+
3 2 1 6 5 4
L
L Converter
o o
p
3
1
PWR
L
o op2
PWR
4-20mA to S
8058 i-Go™
S
3
L
DA
+GF+
Sign
TA
et 8058
N/C 7 8 9
+GF+
Input
4-20 mA to S
4-20 mA input S3L Output
Signet 8058 i-Go™
4-20 mA to S3L Converter
S3L Output
MAX
DC
V
35
Loop1 + 1
Loop1 - 2
N/C 3
Loop2+ 4
Loop2 - 5
Input
N/C 6
3-8058.610D
4-20 mA
3
9 GND
8 S L
7 +5VDC
3
S L
Output
Signet 8058 i-Go™
3
L Converter
L
3
S
Output
L
3
S
Output
8058-2 close-up
Black Red White
Shield
N/C
7 8 9
9900 S3L Inputs
9900 S
3
S L
DATA
WHITE
RED
BLACK
V+
V+
DATA
SHLD
DATA
GND
3
L Inputs
SHLD
GND
Technical Notes:
• The cable length from the 8058 to the 9900 must not exceed 60 m (200 ft).
• When using the 8058-2, connect the loop source to Channel 1 input ONLY.
• See the 8058 manual for more information.
14
9900 Transmitter
Sensor Wiring
Wiring for:
2610-41
24 VDC
Power Supply
7310-XXXX
2610-31 via 8058-1
24 VDC
Power Supply
7310-XXXX
V–
V+
V+
V-
RED
BLACK
SHIELD
BLACK
SHIELD
(no connection)
REDRED
4-20 mA
Input
RED
9900 S3L Inputs
DATA
GND
V+
WHITE
Blue Green Brown
3-2610-41
PWR+ PWR– LOOP+ LOOP–
+GF+
4-20 mA input S3L Output
Signet 8058 i-Go™
4-20 mA to S
8058-1
3
L Converter
SHLD
9900 Power Inputs
RED BLACK
No connection
L
3
S
Output
PWR+ PWR– LOOP+ LOOP–
BLACK RED
WHITE SHIELD
Technical Notes:
The wiring of the 3-2610-41 is non-standard:
• RED is 12 to 24 VDC
• WHITE is Data
• BLACK is VDC Ground
• A jumper MUST be installed between PWR- and S3L GND.
9900 S3L Inputs9900 Power Inputs
V+
DATA
GND
SHLD
Technical Notes:
• 3-2610-31 Dissolved Oxygen Sensor can be connected to the 9900 only via a 3-8058-1 or 3-8058-2 i-Go Signal Converter.
• Program the 9900 for the 2610 DO sensor via the 4 to 20 mA sensor settings on the 9900 (see page 44).
• See the 2610 manual for more information.
DO Sensor
3-2610-31
2610-31 via 8058-2
9900 Power Inputs
PWR+
PWR– LOOP+ LOOP–
RED
BLACK
BROWN
GREEN BLUE WHITE
DO
Sensor
1
3-2610-31
BROWN
No connection
Power Supply
7310-XXXX
No connection
3 2 1
6 5 4
+GF+ SIGNET
24 VDC
+
PWR
Loop1
-
Loop2
PWR
Technical Notes:
• The cable length from the 8058 to the 9900 must not exceed 60 m (200 ft).
9900 S3L Inputs
V+
DATA
GND
SHLD
Technical Notes:
• When using the 8058-2 with the 9900, connect the loop power supply to 8058-2 Loop 1 inputs ONLY as shown in the fi gure.
• See the 8058 manual for more information.
BLACK
WHITE
RED
3
S L
DATA
N/C
7 8 9
9900 Transmitter
15
Sensor Wiring
Wiring for: 4150
via 8058-1
+
EMCF1
RLY2
TB2
TB4
ISL 1
ALARM2 ALARM1
NC
COMNONC
+
24 VDC
+
COM
L5
L7
SHLD
RED
ORG
L3
BLK
Q2
R2
D2
R3
R4
TB1
TB3
NO
SHLD
+
BA
4-20mA/
RS-485
L7
L4
Q1
R1
RLY1
L2
WHT
BRN
GRN
YEL
9900
S3L Inputs
SHLD
DATA
GND
V+
+
D1
Black
Red
White
Shield
Signet Turbidimeter
ENTER
Connect 4 to 20 mA wires to
S
L
+
3
Output
terminal board TB3 as shown in the fi gure.
Refer to the latest revision of
L1
+
3
L Converter
3
Signet 8058 i-Go™
4-20 mA to S
+GF+
L Output
4-20 mA input S
Input
4-20 mA
the Signet 4150 Turbidimeter Manual (3-4150.090) for further information.
Power
Connection
via 8058-2
+
EMCF1
TB2
+
24 VDC
+
Power
Connection
RLY2
ISL 1
ALARM2 ALARM1
NC
COMNONC
TB4
COM
RED
L5
ORG
L3
BLK
L7
SHLD
Q2
R2
D2
R3
R4
TB1
TB3
NO
SHLD
+–
BA
4-20mA/
RS-485
L7
L4
Q1
R1
RLY1
L2
WHT
BRN
GRN
YEL
Black Shield
Red
Technical Notes:
• All of the electrical connections to the instrument are made through the terminal box. The connections are labeled within the terminal box and are self-descriptive.
Technical Notes:
+
D1
When using the 8058-2, connect the loop source to Channel 1 input ONLY.
• A plug is inserted into the RS-485 cable bulkhead when shipped to ensure a watertight seal. Remove and discard this plug when cabling to this connection.
• The bulkhead will accept cable diameters from
5.8 mm (0.23 in.) up to
+
10 mm (0.34 in.). The terminals are designed to
L1
+
+GF+ SIGNET
3 2 1 6 5 4
Loop1
PWR
Loop2
PWR
S L
DATA
9900
3
L Inputs
S
SHLD
DATA
3
GND
V+
accept wires in the range of 14-28 AWG. All wires should be stripped to a length of 6 mm (0.25 in.).
• Ensure that the watertight seal is maintained after the terminal box has been wired for operation. If any of the bulkheads are not tightened
N/C
7 8 9
properly around a cable or plug, the ratings of the instrument will be jeopardized and there is a possibility of
Black Red
White (Gnd)
Red (S3L)
Black (5 VDC)
creating a shock hazard.
• Do not run 4 to 20 mA cables in the same conduit as power.
16
9900 Transmitter
Power Wiring
CAUTION!
DO NOT connect your 9900 to AC power.
The 9900 MUST be powered by
10.8 to 35.2 VDC ONLY.
Stand-alone application, no current loop used
ProcessPro
(for reference only)
Transmitter
Terminals
System Pwr Loop -
System Pwr Loop +
AUX Power -
AUX Power +
4 3 2 1
Black
Red
Connection to a PLC/Recorder, separate supply
ProcessPro
(for reference only)
Transmitter
Terminals
4
System Pwr Loop -
System Pwr Loop +
AUX Power -
AUX Power +
4 3
3 2
2 1
1
AUX power required for all 8750-2 systems
Blue
Black
Red
+
Power
Supply
12 to 24 VDC
PLC or Recorder
+
Loop Input
4 to 20 mA
+
Power
Supply
12 to 24 VDC
PWR + PWR – Loop +
Loop –
PWR + PWR –
Loop + Loop –
9900
Terminals
9900
Terminals
9900
Red
Black
9900
Blue
Red
Black
+
+
+
Power Supply
10.8 to 35.2 VDC
Power Supply
10.8 to 35.2 VDC
PLC or Recorder
Loop Input
4 to 20 mA
System Pwr Loop ­System Pwr Loop +
AUX Power -
AUX Power +
ProcessPro
(for reference only)
Transmitter
Terminals
4 3 2 1
Black
Red
Loop Powered
+
+
Power
Supply
12 to 24 VDC
PLC or Recorder
Loop Input
4 to 20 mA
9900
9900
Terminals
PWR + PWR – Loop +
Loop –
NOTE: Loop Power cannot be used to power certain Signet sensors. See table on page 11.
Red
Black
+
Power Supply
10.8 to 35.2 VDC
PLC or Recorder
Loop Input
+
4 to 20 mA
9900 Transmitter
17
Relay and Open Collector Wiring
Open Collector wiring
NPN Style Wiring
Pull-Up Resistor
..ȍ:
PWR +
PWR – Loop + Loop –
OC –
OC+
If PLC needs 0 logic input when relay is not energized, set NORMAL to CLOSED in the RELAY menu when using the Open Collector (R1) with NPN style wiring.
9WR9
Gnd
Input
Gnd
Power
Supply
PLC
PNP Style Wiring
3:5 3:5±
Loop +
/RRS±
2&±
with NORMAL set to OPEN.
PWR + PWR –
Loop + Loop –
OC – OC+
OC+
Pull-Down Resistor
..ȍ:
Alarm
Input
PLC
Gnd
9WR9
Power
Supply
Gnd
V+
Gnd
Power
Supply
• The 9900 Open Collector (R1) output provides high-speed switching capability. Signal frequencies can reach 400 pulses per minute.
• The 9900 Open Collector (R1) output connection is dependent upon the type of circuit being controlled by the output.
• Most indicating instruments or control system inputs require a signal voltage of 0 to 5 V (TTL or CMOS logic levels) or 0 to 24 V. Therefore, the 9900 Open Collector output circuits must be equipped with a pull-up or pull-down resistor (not supplied), and a quality regulated 5 to 24 V (depending on the application) power supply (not supplied) is recommended to function properly.
Relay Module wiring
The alarm is OFF during normal operation, and will go ON when relay energizes according to 9900 Relay settings.
The valve is ON during normal operation, and will go OFF when relay energizes according to 9900 Relay settings.
RELAY 2RELAY 3
NO NC
NO
NC
ALARM!
C
AC or DC
power
C
AC or DC
power
18
NO = normally open (closes when energized) NC = normally closed (opens when energized)
9900 Transmitter
Valve
Flow
Relay Functions
System Start-up: Step 3
Set your relay functions to your own application requirements.
Next step: System Setup (see page 25).
Once a setting is saved it becomes immediately active.
1. Go to the Relay Menu (RELAY fl ashing on screen, press ENTER).
2. If prompted, select desired source.
3. Press  to relay MODE selection screen.
4. If necessary, press and then or to select R1 MODE LOW.
Press ENTER to confirm.
5. Press  to R1 SET LOW. Press  to enter GPM value of 5.5.
6. Press ENTER to save.
7. Scroll  to the R1 HYSTERESIS menu.
8. Press  to edit.
9. Set the hysteresis for this relay. This affects the turn off only: 2.5 gpm.
10. Press ENTER.
11. Scroll down  to the R1 ON DELAY menu.
12. Press  to edit.
13. Set the turn-on delay in seconds for the relay: 15.0.
14. Press ENTER.
15. Exit to View Mode.
 Relay function can be tested in the RELAY menu.
Example: Set a relay R1 to turn on at a low setpoint of 5.5 gpm with a time delay of 15 seconds and turn off at 8.0 gpm.
Remember,
SET LOW + hysteresis = OFF point:
5.5 + 2.5 = 8.0
Relay and Open Collector Outputs
RELAY HIGH and LOW Settings
Depending on the desired function of the circuit attached to the Open Collector (R1) output, it may be necessary to have the Open Collector turned “on” or “off” when the criteria for the activation of this output are met.
If the 9900 is set to operate in RELAY LOW mode, when the user-defi ned condition for the activation is met (e.g. exceeding an alarm limit) the Open Collector switch is turned “on.” If wired as standard “NPN-style” output (see previous page) the logic level of the attached control system or PLC input consequently becomes “low” logic level (when NORMAL is set to OPEN).
If a high input logic level is required for activation, it can be accomplished in one of three ways. In order of preference,
1. Change the Open Collector (Relay 1) output function to “high” in the instrument's RELAY menu, or
2. Wire the Open Collector (R1) output “PNP” style as described on the previous page, or
3. Set the Open Collector (R1) to NORMAL CLOSED in the RELAY menu.
Fail-Safe Behavior
No matter the setting, the Open Collector output turns off if the 9900 loses power. This must be taken into account when evaluating system failure consequences. If the system layout requires a “closed” or “on” condition for the output in case of power loss, a mechanical dry-contact relay (NC contacts) must be used instead of the Open Collector (R1) output.
Voltage and Current Limitation
The supply voltage in the Open Collector output circuit MUST be limited to the specifi ed maximum Open Collector voltage (see operating manual for specifi c instrument). The use of a quality 5 to 24 V (depending on the application) regulated power supply (not supplied) is recommended.
The current through the Open Collector switch also must be limited. Typical Open Collector outputs allow only for 10 to 50 mA switch current. Exceeding this current limit can burn out the Open Collector output components immediately.
Load and Pull-Up/Down Resistor Considerations
By utilizing basic arithmetic and Ohm’s Law, the safe limits of load resistance can be determined. When the Open Collector switch is closed, almost the entire supply voltage is applied to the load (e.g., the pull-up or pull-down resistor, the alarm horn input, a potential power relay coil or annunciator lamp).The resulting current through the load and through the Open Collector switch, as well, can be calculated as:
(Current)
= (Supply Voltage) / (Load Resistance)
9900 Transmitter
19
Hysteresis
Time
Low Setpoint
Process
Hysteresis
Time
High Setpoint
Process
Relay energized
Relay de-energized
Relay Outputs
The 9900 open collector and relays are selectable and confi gurable and can be used as switches that respond when the process value moves above or below a user-defi ned setpoint or it can be used to generate a pulse at a rate proportional to the process value. They can be used for Low Alarm, High Alarm or Proportional Pulse triggering related to the process value. All relay functions are set up in the RELAY menus.
Open Collector Output
 Longer life than a mechanical relay  No moving parts  Faster ON/OFF switching capabilities than mechanical relays  Can switch DC voltage only (< 30 VDC)  Not recommended for use with inductive loads.
Low Setpoint:
Relay is on when the measured value is less than the setpoint.
High Setpoint:
Relay is on when the measured value is higher than the setpoint.
Cycle Time
Process
High Setpoint
Hysteresis
Relay energized
Relay de-energized
CAUTION!
If power is lost to the 9900 Transmitter during a cycle, the Cycle Time will reset. If the condition still exists after power is restored, the relay will be energized for the complete Cycle Time.
Time
Cycle High/Low:
The relay can stay energized for a set length of time after the process value goes above (or below) the setpoint. The relay will stay on for the CYCLE TIME and then turn off, even if the process value is still above (or below) the setpoint. The cycle will not repeat until the process value goes below (or above) the setpoint minus the hysteresis after the relay times out.
In FLOW, Cycle High activates the relay each time the volume reaches the SET VOLUME setpoint (see page 28).
NOTE: To reset the timer (or volume in Flow): in the RELAY menu, select TEST RELAY function. The timer will reset to 0 if the condition no longer exists when the TEST is performed. The timer will restart if the condition still exists.
20
9900 Transmitter
Time
High Limit
Hysteresis
Low Limit
Process
Window
10
5
Open Collector Output Rate:
0 to 100 Pulses/min.
Pulse rate
0 pulses
100 puls
Relay energized
Relay de-energized
Time
High Limit
Hysteresis
Low Limit
Process
Window
Hysteresis
Relay Outputs
Window In/Out:
Relay is on when the value is higher or lower than the high or low setpoint. WINDow IN = relay on if measurement is inside the window of two setpoints. Measurement inside the two setpoints is abnormal condition. WINDow OUT = relay on if measurement is outside the window of two setpoints.
Window IN example
Proportional Pulse Operation:
The transmitter can output a pulse at the rate defi ned by the settings in the CAL menu and the sensor input. The maximum pulse output from the relays is 300 pulses per minute. Example usage would be to control solenoid-operated dosing pumps.
For example: As the process value drops below the setpoint, the output will start pulsing in relation to the process value, the maximum pulse endpoint and the programmed pulses/minute. The pulse rate will change as the process value changes and approaches the programmed endpoint. This functionality can be used to precisely control the process.
The starting point, endpoint and maximum pulse rate are select able in the RELAY menus.
NOTE: Relay LEDs are not lit in PULSE mode.
Window OUT example
100 pulses
Starting point Endpoint
In the example:
• The output will be 0 pulses/min. when value is less than 5.
• The output will be 50 pulses/min. when value is 7.5.
• The output will be 100 pulses/min. when value is greater than 10.
9900 Transmitter
21
y
Relay Outputs
100%
80%
60%
40%
Relay Pulse Width
20%
(as a % of Relay period)
0%
alwa
Relay is
s OFF
PWM Minimum
PWM Maximum Range
Process value
Relay is
always ON
• Pulse Width Modulation
PWM automatically varies the ratio of ON time to OFF time proportional to minimum and maximum range settings.
The relay period is the sum of the time a relay is ON and the time it is OFF.
Relay pulse width is the time the relay is ON.
The 9900 must be programmed with the relay period, and with the low and high setpoints.
NOTE: The PWM mode is not used for Pressure applications.
NOTE: Relay LEDs are not lit in PWM mode.
Example:
• The pulse width will be 0% of the relay period (relay always OFF) when the process value is less than the minimum range.
• The pulse width will be 100% of the relay period (relay always ON) when the process value is greater than the maximum range.
• The pulse width will be 60% of the relay period when the process value is at 60% of the span between the minimum and maximum range.
• Volumetric Pulse
A pulse is generated each time a specifi ed volume of fl uid is registered. For fl ow inputs only.
NOTE: Relay LEDs are not lit in VOLUMETRIC PULSE mode.
• Totalizer Volume
Relay activates and latches when a specifi ed volume of fl uid is registered. For Flow inputs only.
Total Volume mode counts the TOTALIZER Units until the setpoint volume is reached, then turns on the relay until the resettable totalizer is reset.
If the Resettable Totalizer reading is greater than the setpoint, the relay will be turned on immediately. The relay will be off when the totalizer is reset to zero.
This mode is useful to trigger a reminder when a process is due, as for a backwash cycle or fi lter change.
22
9900 Transmitter
Loading...
+ 50 hidden pages