Signet 8059 External Relay Modules
Description
Signet 8059 External Relay Modules supplement the output capabilities of certain host instruments such as the Signet 8900 Multi-Parameter Control­ler. AC-powered versions accept uni­versal line voltage, and also provide 24 VDC output that can be used to power the host instrument or other device(s).
System Overview
The host instrument controls relay operation by way of a single digital
3
L) connection. The compact plastic
(S housing is DIN rail mountable and includes LED annunciators for each relay, plus one each for power-on and data transfer or test mode.
Features
• External relays controlled by host instrument
• AC and DC powered versions
• DC power output (AC versions)
• DC power pass­through (DC ver­sions) to simplify wiring
3
• Digital (S through to simplify sensor wiring
• Red LED annuncia­tors for each relay
• Green LED indica­tors for power and digitial (S transfer
• Relays may be tested locally, and also via the host instrument
L) pass-
3
L) data
Signet 8059 External Relay Module
Signet 8900 Multi-Parameter Controller
(sold separately)
Signet digital (S3L) or frequency sensor
(sold separately)
SIGNET
515
2536
525
2517 2540 2750 2850
2000
OW L F
2100
7000
+GF+
XX DN XX X
XX
2537 2551
2507 2350
2450
2552
Pipe, Tank, Wall MountPanel Mount
Signet 8250 Level Transmitter
(sold separately)
Signet Pressure and Level sensors
(sold separately)
24502250
C
E171559
US
156
www.gfsignet.com
Page 2
Dimensions Specifications
General
Input: Digital (S3L) via host instrument Type: DIN rail mountable Terminals: Standard screw-type
89 mm (3.5 in.)
Side View
NC C NO
RELAY A
Signet 3-8059 Relay Module
LISTED
®
E171559
INPUT
+
S3L
-
NC C NO
RELAY B
COM
POWER
PASS-THRU
+
100 - 240 V 50/60 Hz, 20 VA
57 mm (2.5 in.)
Test A
Test B
®
S3L
-
OUTPUT 24VDC
+ -
Material
Enclosure: Noryl
Electrical
Power Requirements:
• 8059-2AC, -4AC: 100-240 VAC ± 10%, 50/60 Hz, 20VA
• 8059-2, -4: 12 to 24 VDC DC output
• 8059-2AC, -4AC: 24 VDC regulated, 300 mA
• 8059-2: Pass-through: DC input minus 0.7 volts
(12VDC in =11.3 VDC out)
Relay A
Relay B
AC INPUT
L N
®
UL 94 V-O
Electrical (continued)
Isolation: > 5,000 Vrms Relays:
• Type: SPDT 250VAC/30VDC/5A
• Resolution: 2 ms (in pulse mode)
• Response Time: < 100 ms
• Annunciators: Red LED, 1 per relay
Environmental
Operating Temperature:
-10°C to 55°C (14°F to 131°F) Storage Temperature:
-20°C to 85°C (-4°F to 185°F) Relative Humidity: 0 to 90% (non-condensing) Maximum Altitude: 2,000 m (6,561 ft.)
Shipping Weight: 0.37 kg (0.8 lb.)
Standards and approvals
• CE, UL listed
• Manufactured under ISO 9001:2000 for Quality and ISO 14001:2004 for Environmental Management
Choosing
Products
Instrument
Multi-Pa-
rameter
Flow
pH/ORP
Conductivity/
Resistivity
Pressure, Level
Temperature,
108 mm (4.25 in.)
Face View (3-8059-2 shown)
Model 8059 Ordering Information:
1) Use an RC filter kit to protect relays from voltage spikes
2) DIN railing and clips are available for mounting a relay module.
3) The -AC version will supply enough volt­age to power the 8900 when using the 12-24 VDC power module.
Please refer to Wiring, Installation and Accessories sections for more information.
Ordering Information
Part Number 3-8059 External Relay Module
Relay Options - Choose one
-2 2 Relay module
-4 4 Relay module
Power input and output options - Choose one
- 12 to 24 VDC with pass-through DC output (minus 0.7 volts)
-AC 100 to 240 VAC with 24 VDC output
3-8059 -2 - Example Part Number
Mfr. Part No. Code
3-8059-2 159 000 770 3-8059-2AC 159 000 771
Mfr. Part No. Code
3-8059-4 159 000 772 3-8059-4AC 159 000 773
Accessories and Replacement Parts
Mfr. Part No. Code Description
3-8050.396 159 000 617 RC Filter Kit for relay use (2 per kit) 6205-0002 159 000 858 DIN Rail, 1 meter 6205-0003 159 000 859 End Clip, DIN Rail
Products
Other
Installation
Wiring &
Reference
Technical
Temperature/
Pressure
Graphs
of Terms
Glossary
Reference
Part No.
Index
www.gfsignet.com
Noryl® is a registered trademark of GE Plastics
157
Loading...