SERVICE AND MAINTENANCE
each of the brass brackets on either side of the motor
laminations.
5.4.2 CLEANING THE AIR FILTER.
To maintain proper cooling efficiency, the air
filter should be cleaned periodically. Local air conditions determine how often this
is
necessary. To clean,
release the air filter from its
holder,rap gently to remove
excess dirt, flush from the dirty side with hot soapy
water, rinse, and let dry. Commercially available prep-
arations to increase the filtering efficiency may be
applied but are not necessary.
5.5
TROUBLE-SHOOTING NOTES.
5.5.1 GENERAL.
If the pulse generator
is
inoperative, make the
following simple checks before proceeding further:
a. Check the power line voltage and frequency to
make sure they are as required by the power supply.
b. Check line cord, fuses, and power supply voltage.
If the voltage from pin
3 of V501 to ground
is
not
150 volts or if the voltage from pin
2 of V504 is not
-150 volts, refer to paragraph 5.5.2.
c. See if theprepulse is present at the SYNC binding
posts. If this pulse is present and the main pulse is
defective,refer to paragraph 5.5.2. If the prepulse
is
present and there is no main pulse, refer toparagraph
5.5.3.
If
neither prepulse nor main pulse
is
present,
refer to paragraph 5.5.4. If prepulse
is
absent and
the main pulse is present, refer to paragraph
5.5.7.
5.5.2 INOPERATIVE POWER SUPPLY.
Incorrect voltage.
If
the positive supply voltage
at pin
3 of V501
is regulated but not +I50 volts with
respect to ground, first see if the negative supply volt-
age at pin 4 of
V504 is -150 volts. If this voltage is
regulated but not correct, adjust
R512 so that an ac-
curate voltmeter indicates
+I50 volts from pin 3 of
V501 to ground. If the positive supply voltage adjustment drifts, but the negative supply voltage does not,
replace either
R504, R506, or R505. If the negative
supply voltage adjustment drifts, replace
R511, R513,
R510, R512, or V504.
If the voltage drops only at full load, replace
V501, and check the voltage at pins 2 and 5 of V501.
If either of thesevoltages
is
less than 210 volts, check
the corresponding capacitors and diodes.
Unregulated voltage.
The most probable cause of
this trouble is a defectivetube. Remove
V502 and V503
test them, and replace any defective tube. Measure the
voltage at pin 2 of
V503 with respect to ground. If this
is not within
5% of
-66
volts, regardless of the output
load, replace
V504. Measure the resistances to ground
from pin 2, pin 3, pin 5, and pin
6
of V501 and compare
the results with the values in Table
5-1. Replace any
defective resistors or capacitors thus found.
No output supply
voltage.
Check V501. Measure
the regulator input voltage across
C501 and C502.
If
either of these voltages
is
zero, check for a shorted
rectifier diode,
C501, C502, and a blown fuse in the
primary of
T501. If the input voltage
is
normal, check
V502 and V503 for an internal short. Check V504 for a
short. Measure the voltages at key points with a vacuum
tube voltmeter, comparing them with those given in
Table
5-1.
Incorrect
heater
voltage.
If the dc voltage at pin 4
of V103, V105, or VlO6 or pin 3 of V503 is not within
10% of -70 volts, check for a cathode-heater short in
one of those tubes. Check the resistance to ground from
pin
2 of V504 against the value in Table 5-1. Replace
any defective resistors. Check for a short in
C504 or
c505.
5.5.3 DEFECTIVE MAIN PULSE.
Overshoot.
Under normal conditions, with a high
impedance load, overshoot is not possible on any transition. Therefore, check the oscilloscope for overshoot
first.
If
overshoot occurs with a low-impedance terminated system, check the system for proper grounding
and make sure that all wiring
is
as short as possible.
Note that some overshoot may be present on negative
pulse transitions as shown in Figure 3.6.
Large imbalance in pulse amplitudes
or
slowly
falling negative-going edge of positive pulse.
These
defects can be caused by weakening of one of the output tubes.
Output pulse occasionally fails, and
starts
only
when RANGE switch setting
is
changed.
There are two
possible causes of this difficulty: (1) The ionization
voltage of V107 has drifted sufficiently so that the
automatic restarting circuit no longer functions, or (2)
a tube has developed heater-to-cathode leakage. First
check the voltage from the negative side of
V107 to
ground, using an electronic voltmeter of at least
100
megohms input impedance. The proper voltage is -65
t5 volts behind 5 megohms.
IF
this voltage is correct,
the trouble
is
a defectiveV107, and a newNE-96 should
be installed.
If
the voltage measured is not correct,
check all tubes for heater-to-cathode leakage.
Pulse-duration
errors.
An error indication on only,
one setting of the RANGE switch is an indication that
a time-determining component for that range has drifted
or failed.