General Filters
Incorporated
14 | P a g e
3.6.1 Connect the GFX3 Humidistat for ON/OFF Operation (Figure 3.w.)
1. Remove the humidistat from the base, squeeze the louvered base at the top and bottom.
To remove the humidistat from the wall, lift up on the humidistat and pivot top away from wall.
2. Before wall mounting, remove the black foam gasket.
3. Before return air duct mounting, remove the breakout piece.
4. If return air duct mounting, route wires between humidistat and base.
5. Mount the sensor outside the house. Do not mount on south side of the house or in direct
sunlight. Place at least 4 feet away from any exhaust vent. If in air intake, place 1 foot or
closer to outside wall. Place at least 6” higher than possible snow. Do not route sensor wire
near high voltage wires.
6. Connect the GND-IN terminals on the humidifier to the HUM terminals on the GFX3
Humidistat.
Connect the GND-24V terminals to the ACL-ACN terminals on the GFX3 Humidistat
(See Figure 3.w.).
3.6.2 Modulating Operation
Connect an external 0 to 10 VDC modulating input between terminals IN-GND. Connect any
Safety Switches (high-limit, air flow switch, remote ON/OFF) in series to terminals AB-AB. If no
safety switches are used, then a jumper must be installed between AB-AB.
DO NOT apply any voltage to AB-AB.
3.6.3 Connect the GFX50 Humidistat for Modulating Operation (Figure 3.x.)
To select signal modulating (See Figure 3.x.) Connect the power supply to the GFX50 G and G O
terminals, using the terminal GND and 24V on the Elite Steam. Note MODULATING OPERATION
requires a change in signal type. (See section 5.1.1 page 17.) Connect an external signal to the
GFX50 using the terminal IN from the Elite Steam and AOUT in GFX50. (See Figure 3.x.)
3.6.4 Safety and High Limit Switches (Field Supplied) (Figure 3.v)
Highly Recommended. Remove the jumper between terminals AB-AB and connect any simple
high-limits air flow switch (suggest part HC-201; GFI #7520 or similar); a pressure switch (suggest
part 12500; GFI #7021 or similar), and remote contacts in series to terminals AB-AB; otherwise, if
no such dry contacts are available, the jumper must remain in place between terminals AB-AB. DO
NOT apply any voltage to AB-AB. thread the control wiring through the bottom of the unit, and
the strain relief (see photo at top of previous page), and then up the side of the control module to
the top right wiring terminal blocks. Connect the control wiring to the control wiring terminal blocks
found at the top right side of the control module. (See Figure 3.v.)
3.6.5 Furnace Blower Operation / Air Conditioner Relay Interlock (Figure 3.y.)
Auxiliary DPDT safety relay: Use this method in the following situations:
1. To prevent the air conditioner from running when there is a call for humidity. The DPDT relay
will open the “Y” circuit and close the “G” circuit for operation while a call for humidity is
present (See Figure 3.y.). The demand for humidity will override the call for cooling.
2. In systems using a thermostat where G and Y are a single circuit, the DPDT relay will allow blower operation to occur without
back-feeding the compressor. DO NOT use this method when simultaneous
humidification and cooling will be desired. Use a high limit humidistat in to avoid
condensation in ductwork. The humidistat should be set to OFF during the air conditioning
season if humidification is not desired.
3. For homes without an air conditioner, see Figure 3.z.
4. For variable speed or DC systems, consult the furnace manufacturer.