General Electric PV970NSS Installation Manual

Chimney Vent Hoods
Profile
49-80549 12-08 JR
Safety Instructions . . . . . . . . 2, 3

Operating Instructions

Light Controls . . . . . . . . . . . . . . . . . . . .4
Vent Controls . . . . . . . . . . . . . . . . . . . . .4

Care and Cleaning

Hood Lights . . . . . . . . . . . . . . . . . . . . . .6
Stainless Steel Surfaces . . . . . . . . . . .6

Installation Instructions

Vented to the Outside . . . . . . . .14-17
Recirculating . . . . . . . . . . . . . . . . .18-22
Troubleshooting Tips . . . .23, 24

Consumer Support

Consumer Support . . . . . . . . . . . . . 26
Warranty . . . . . . . . . . . . . . . . . . . . . . . 25
Write the model and serial numbers here:
Model # ________________ Serial #
________________
You can find them on a label on the inside of the hood.
PV970 PV976
Owner’s Manual
and Installation
Instructions
ge.com
SAFETY PRECAUTIONS
IMPORTANT SAFETY INFORMATION. READ ALL INSTRUCTIONS BEFORE USING.
WARNING – TO REDUCE THE RISK
OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Use this unit only in the manner intended
by the manufacturer. If you have questions, contact the manufacturer.
B. Before servicing or cleaning unit, switch
power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
C. Do not use this unit with any solid-state speed
control device.
D. This unit must be grounded.
CAUTION – For general ventilating use
only. Do not use to exhaust hazardous or explosive materials and vapors.
CAUTION – To reduce risk of fire
and to properly exhaust air, be sure to duct air outside. Do not vent exhaust air into spaces within walls or ceilings or into attics, crawl spaces or garages.
WARNING – TO REDUCE
THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING*:
A. SMOTHER FLAMES with a close-fitting lid, cookie
sheet or metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS. If the flames do not go out immediately, EVACUATE AND CALL THE FIRE DEPARTMENT.
B. NEVER PICK UP A FLAMING PAN—You may
be burned.
C. DO NOT USE WATER, including wet dishcloths
or towels—a violent steam explosion will result.
D. Use an extinguisher ONLY if:
1. You know you have a Class ABC extinguisher,
and you already know how to operate it.
2. The fire is small and contained in the area
where it started.
3. The fire department is being called.
4. You can fight the fire with your back
to an exit.
* Based on “Kitchen Fire Safety Tips
” published
by NFPA.

Consumer Support Troubleshooting Tips Operating Instructions Safety Instructions

Care and Cleaning
2
Consumer Support
Troubleshooting TipsOperating Instructions
Safety Instructions
Care and Cleaning
READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY.
READ AND SAVE THESE INSTRUCTIONS
SAFETY PRECAUTIONS
ge.com
WARNING – TO REDUCE THE RISK
OF A RANGE TOP GREASE FIRE:
A. Never leave surface units unattended at high
settings. Boil overs cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.
B.
Always turn hood ON when cooking on high heat or when flambéing food (i.e. Crepes Suzette, Cherries Jubilee, Peppercorn Beef Flambé).
C. Clean ventilating fans frequently. Grease should
not be allowed to accumulate on fan or filter.
D. Use proper pan size. Always use cookware
appropriate for the size of the surface element.
WARNING – TO REDUCE
THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
A. Installation work and electrical wiring must
be done by qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction.
B. Sufficient air is needed for proper
combustion and exhausting of gases through the flue (chimney) of fuel burning equipment to prevent back drafting. Follow the heating equipment manufacturer’s guidelines and safety standards such as those published by the National Fire Protection Association (NFPA), the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) and the local code authorities.
C. When cutting or drilling into wall or ceiling,
do not damage electrical wiring and other hidden utilities.
D. Ducted fans must always be vented
to the outdoors.
WARNING – TO REDUCE THE RISK
OF FIRE, USE ONLY METAL DUCTWORK.
Do not attempt to repair or replace any
part of your hood unless it is specifically recommended in this manual. All other servicing should be referred to a qualified technician.
3
Using the hood controls.
Consumer Support
Troubleshooting Tips Operating Instructions Safety InstructionsCare and Cleaning
4
MEMORY/OFF. To set the memory: A. Press the MEMORY/OFF button. B. Set your desired fan and light settings. C. Press the MEMORY/OFF button again to save
these settings.
With your desired settings in memory, press the MEMORY/OFF button to restore the fan and light levels to their saved settings. These settings will remain in memory until they are changed or loss of power occurs.
To turn off the hood, press the MEMORY/OFF button.
LIGHT. Press + or – to increase or decrease light level to desired setting. There are 2 light levels (LOW, HIGH) and OFF. If you continue to press the + or – buttons, the light will cycle back through the settings.
NOTE: Please check the lamps to ensure only 20W lamps (maximum) are installed.
FAN. Press + or – to increase or decrease fan level to your desired setting. There are 4 fan levels (LOW, MED, HIGH, BOOST) and OFF. If you continue to press the + or – buttons, the fan will cycle back through the settings.
NOTE: There is an audible “beep” each time a button is pressed. This is normal.
NOTE: The collars around the buttons will illuminate when pressed. This is normal. The collars will automatically turn off if the hood is turned off.
HEAT SENSOR:
This hood is equipped with a heat sensor that will turn on the fan if excessive temperatures are detected (over 70 ˚C/158 ˚F) above the cooking surface. The hood will return to its normal operation once the heat sensor detects temperatures below 60 ˚C/140 ˚F.
NOTE: If the hood is OFF or on LOW fan speed, the temperatures above 70 ˚C/158 ˚F are detected; then the fan will automatically adjust to MED speed. You may adjust the fan speed to HIGH or BOOST, but you will not be able to adjust the fan speed to LOW or OFF until temperatures below 60 ˚C/140 ˚F are detected.
NOTE: The collars around the buttons may not illuminate if the heat sensor is activated. This is normal.
Care and cleaning of the vent hood. ge.com
Be sure electrical power is off and all surfaces are cool before cleaning or servicing any part of the vent hood.
The metal filter traps grease released by foods from the cooktop. The filter also helps prevent flames (from food, grease) from damaging the inside of the hood.
For this reason, the filter must ALWAYS be in place when the hood is in use. The grease filter is dishwasher-safe and should be cleaned every 6 months, or as needed.
To remove:
Pull downward on the filter lock to release the filter.
To replace:
Fit the tabs at the end of the filter into the slots in the left side of the filter opening. Lift up the right side of the filter and push gently until the filter locks into place. Make sure the filter lock is in the closed position to secure the filter.
To clean, swish the filter in hot soapy water and rinse in clean water or wash it in the dishwasher. Do not use abrasive cleansers.
NOTE: Some discoloration will occur in the dishwasher.
Metal Grease Filter
Consumer Support
Troubleshooting Tips
Operating InstructionsSafety Instructions Care and Cleaning
5
If the model is not vented to the outside, the air will be recirculated through a disposable charcoal filter that helps remove smoke and odors.
The charcoal filter should be replaced when it is noticeably dirty or discolored (usually after 6 to 12 months, depending on hood usage).
NOTE: DO NOT rinse, or put charcoal filter in an automatic dishwasher.
The charcoal filter cannot be cleaned. It must be replaced.
Order Charcoal Filter WB02X11348.
To inquire about purchasing replacement charcoal filters or to find the location of a dealer nearest you, please call our toll-free number:
National Parts Center
800.626.2002
To remove:
1. Remove the metal filter—see Metal
grease filter section.
2. Remove the charcoal filter by
pushing in on both locking tab handles to release.
To replace:
1. Insert the charcoal filter into the
opening. Push the locking tab handles toward the center and release to engage the locking tabs.
2. Replace the metal filter—see Metal
grease filter section.
Charcoal Filter (for recirculating installation only)
Locking tab handle
Locking tab handle
Consumer Support Troubleshooting Tips Operating Instructions Safety InstructionsCare and Cleaning
6
Care and cleaning of the vent hood.
Be sure electrical power is off and all surfaces are cool before cleaning or servicing any part of the vent hood.
Do not use a steel wool pad; it will scratch the surface.
To clean the stainless steel surface, use warm sudsy water or a stainless steel cleaner or polish. Always wipe the surface in the direction of the grain. Follow the cleaner instructions for cleaning the stainless steel surface.
To inquire about purchasing stainless steel appliance cleaner or polish, or to find the location of a dealer nearest you, please call our toll-free number:
National Parts Center
800.626.2002 ge.com

Stainless Steel Surfaces

Light Bulbs
CAUTION:
Allow bulbs to cool before touching.
To change the light bulbs:
1. Remove the lamp lens cover by
inserting a small flat blade screwdriver into each of the three slots and gently prying it free.
NOTE: Do not remove the outer trim ring (lamp assembly).
2. Wear gloves. Do not touch the bulb with your bare fingers. Skin oils can cause early lamp failure.
3. Grasp the bulb and pull it straight out.
4. Replace with the same wattage. Early
bulb failure and damage to or failure of the transformer may occur if wattage is too high.
These 12-volt, 20-watt halogen bulbs with a G4 base are available at specialty lighting stores and home building centers.
To order replacement bulb no. WB01X10239, contact the GE National Parts Center at 1.800.626.2002 or purchase from your local retailer.
5. Replace lamp lens cover by inserting the three retaining tabs into the three slots and pressing firmly in place.
Use a small flat blade screwdriver to remove the lamp lens cover.
Outer trim ring (lamp assembly)
Do not remove
Bulb
Removable inner lamp lens cover
NOTE: Make sure the tabs are inserted into the slots.
Tab
7
Questions? Call 800.GE.CARES (800.432.2737) or Visit our Website at: ge.com
Installation
Chimney Vent
Hoods
Instructions
BEFORE YOU BEGIN
Read these instructions completely and carefully.
IMPORTANT — Save these instructions
for local inspector’s use.
IMPORTANT — Observe all governing
codes and ordinances.
Note to Installer – Be sure to leave these
instructions with the Consumer.
Note to Consumer – Keep these instructions
for future reference.
Skill level – Installation of this vent hood requires
basic mechanical and electrical skills.
Completion time –
Approximately 1 to 3 hours
• Proper installation is the responsibility of the installer.
• Product failure due to improper installation is not covered under the Warranty.
PRODUCT DIMENSIONS
FOR YOUR SAFETY:
WARNING Before beginning the
installation, switch power off at service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag, to the service panel.
CAUTION — Due to the weight
and size of these vent hoods and to reduce the risk of personal injury or damage to the product, TWO PEOPLE ARE REQUIRED
FOR PROPER INSTALLATION.
30" Models Require a 30" Wide Opening
*Height
to
Ceiling
19-3/4"
29-7/8"
2-1/2"
13-1/8"
10-7/8"
*Height
to
Ceiling
19-3/4"
35-7/8"
3-1/8"
13-1/8"
10-7/8"
36" Models Require a 36" Wide Opening
2-1/4"
* For supplied duct cover ceiling heights for vented installation
and recirculating installation, refer to the table on page 13.
17-1/2"
Allow 1" overlap of duct.
2-3/8"
8
Installation Preparation
PREPARE TO INSTALL THE HOOD
INSTALLATION CLEARANCES
These vent hoods are designed to be installed onto a wall. They may be installed beneath a soffit or cabinet.
• Install these hoods 24" Min. to 30" Max. above
the cooking surface.
The vent hood must be installed 24" min. and 30" max. above the cooking surface. The hood installation height above the cooking surface depends upon ceiling height and duct cover limitations. The telescopic duct cover conceals the ductwork running from the top of the hood to the ceiling. For supplied duct cover ceiling heights, see table on page 13.
Recirculation Kit: Kit includes 1 air deflector and 1 charcoal filter and is included with the hood.
NOTE: Installation height should be measured from the cooking surface to the lowest part of the hood. This hood may be installed onto a wall and vented to the outdoors, or it can be installed for recirculating operation. For recirculation operation, a Recirculating Kit (included) is required.
24” Min.
30” Max.
ADVANCE PLANNING
Ductwork Planning
• This hood is designed to be vented vertically through the ceiling. A duct transition piece is supplied for vertical exhaust. Use locally supplied elbows to vent horizontally through the rear wall. See page 10.
• Determine the exact location of the vent hood.
• Plan the route for venting exhaust to the outdoors.
• Use the shortest and straightest duct route possible. For satisfactory performance, duct run should not exceed 100' equivalent length for any duct configurations.
• Refer to “Duct Fittings” chart to compute the maximum permissible length for duct runs to the outdoors.
• Use metal ductwork only.
• A transition piece for 8" round duct is supplied. Use 8" round duct.
• Install a wall cap or roof cap with damper at the exterior opening. Order the wall or roof cap and any transition and length of duct needed in advance.
Wall Framing for Adequate Support
• This vent hood is heavy. Adequate structural support must be provided. The hood must be secured to vertical studs in the wall. See page 14.
• We strongly recommend that the vent hood with duct cover be on site before final framing and wall finishing. This will also help to accurately locate the ductwork and electrical service.
9
Installation Preparation
POWER SUPPLY
IMPORTANT – (Please read carefully)
WARNING:
FOR PERSONAL SAFETY, THIS APPLIANCE MUST BE PROPERLY GROUNDED.
Remove house fuse or open circuit breaker before beginning installation.
Do not use an extension cord or adapter plug with this appliance. Follow National Electrical Codes or prevailing local codes and ordinances.
Electrical supply
These vent hoods must be supplied with 120V, 60Hz, and connected to an individual, properly grounded branch circuit, and protected by a 15 or 20 amp circuit breaker or time delay fuse.
• Wiring must be 2 wire with ground.
• If the electrical supply does not meet the above requirements, call a licensed electrician before proceeding.
• Route house wiring as close to the installation location as possible in the ceiling or wall. See page 14 for details.
• Connect the wiring to the house wiring in accordance with local codes.
Grounding instructions
The grounding conductor must be connected to a ground metal, permanent wiring system, or an equipment-grounding terminal or lead on the hood.
WARNING: The improper connection
of the equipment-grounding conductor can result in a risk of electric shock. Check with a qualified electrician or service representative if you are in doubt whether the appliance is properly grounded.
DUCT FITTINGS
This Hood Must Use an
8" Round Duct. It Can
Transition to a
3-1/4" x 12" Duct.
Use this chart to compute maximum permissible lengths for duct runs to outdoors.
NOTE: Do not exceed maximum permissible equivalent lengths!
Maximum duct length: 100 feet.
Flexible ducting:
If flexible metal ducting is used, all the equivalent feet values in the table should be doubled. The flexible metal duct should be straight and smooth and extended as much as possible.
DO NOT use flexible plastic ducting.
NOTE: Any home ventilation system, such as a ventilation hood, may interrupt the proper flow of combustion air and exhaust required by fireplaces, gas furnaces, gas water heaters and other naturally vented systems. To minimize the chance of interruption of such naturally vented systems, follow the heating equipment manufacturer’s guidelines and safety standards such as those published by NFPA and ASHRAE.
Total
Equivalent Quantity Equivalent
Duct Piece Dimensions Length* Used Length
8" Round, 1 ft. straight (per foot
length)
3-1/4" x 12" 1 ft. straight (per foot
length)
8" 90° elbow
17 ft.
8" 45° elbow
10 ft.
3-1⁄4" x 12" 90° elbow 43 ft.
3-1/4" x 12" 45° elbow 26 ft.
3-1/4" x 12" 90° flat elbow 102 ft.
8" round to 3-1/4" x 12" transition 2 ft.
3-1/4" x 12" to 7" round transition 5 ft.
8" round to 3-1/4" x 12" transition 90° elbow 6 ft.
3-1/4" x 12" to 8" round round transition 90° elbow 13 ft.
8" Round wall cap with damper 32 ft.
3-1/4" x 12" wall cap with damper 75 ft.
8" Round roof cap 44 ft.
Round roof vent 24 ft.
Installation Preparation
Total Duct Run
*Actual length of straight duct plus duct fitting
equivalent. Equivalent length of duct pieces are based on actual tests conducted by GE Evaluation Engineering and reflect requirements for good venting performance with any ventilation hood.
10
Installation Preparation
REMOVE THE PACKAGING
CAUTION: Wear gloves to protect
against sharp edges.
Remove the duct covers.
Remove the hardware bag, literature package
and other boxed parts.
Remove and properly discard the protective
plastic wrapping and other packaging materials.
Remove packing foam from behind the blower.
11
TOOLS AND MATERIALS REQUIRED
(NOT SUPPLIED)
Pencil and tape measure
Pliers
Wire cutter/stripper
Metal snips
Spirit level
Aluminized Duct tape
Safety glasses
120V 60Hz. 15 or 20 Amp, 2-wire with ground, properly grounded branch circuit
Step ladder
Saber saw or Key Hole saw
Phillips screwdriver
Strain relief for junction box
8" round metal duct, length to suit installation
Hammer
Electric drill with 3/16" bits, #2 Phillips and flat head
Flashlight
UL listed wire nuts
RECIRCULATING KIT (Included)
CHECK INSTALLATION HARDWARE
Locate the hardware package packed with the hood and check contents.
Installation Preparation
Stainless steel filter
Duct cover bracket
HARDWARE PACKAGE
Locate and count
screws
6 wood screws
(#10 1-3/4" long)
4 wall fasteners
(5/16")
(screw with
wall anchor)
8 duct cover
and air deflector
screws
(#8 thread forming
screw 3/8" long)
Charcoal filter
2-piece decorative
duct cover
Wall mount template
12
Air deflector
WALLVENT IS27-3/4" MIN. ABOVE THEINSTALLATION HEIGHT
11-7/16"
2"
Horizontal Line
DRILL 2 (TWO) 3/16"PILOT HOLESTHROUGH STUDSOR REARWALL SUPPORT
10-1/8"
Ver ti
cal C
e nterline
MOUNTING TEMPLATE
C
L
DRILL 2 (TWO) 3/16"PILOT HOLESTHROUGH STUDSOR REARWALL SUPPORT
12-1/2"
InstallationHeight
REAR WALL
ALIGN BOTTOMEDGE
WITH PENCILLINE
INDICATINGBOT TOM
OF THEHOOD
12-08JR
31-14772Printed inMexico
13
DETERMINE INSTALLATION HEIGHT
Telescopic duct covers are provided to conceal
the ductwork running to the ceiling.
This hood can be installed for recirculating
operation. Recirculating Kit included with hood.
NOTE: Installation height should be measured from the cooking surface to the straight portion of the hood.
The vent hood must be installed 24" min. and 30" max. above the cooking surface. The hood installation height, from the cooking surface to the bottom of the hood, depends upon ceiling height and duct cover limitations.
Installation Preparation
24" Min.
30" Max.
36" Min.
*Based on 36" countertop height
PV970, PV976 Upper Duct Cover 25.81 Lower Duct Cover 27.56
Counter to Hood Height
Actual *Possible Ceiling *Possible VENTED RECIRCULATING Height Installation Height Installation Height
7' 11" 24" to 30" 24"
8' 0" 24" to 30" 24" to 25" 8' 1" 24" to 30" 24" to 26" 8' 2" 24" to 30" 24" to 27" 8' 3" 24" to 30" 24" to 28" 8' 4" 24" to 30" 24" to 29" 8' 5" 24" to 30" 24" to 30" 8' 6" 24" to 30" 24" to 30" 8' 7" 24" to 30" 24" to 30" 8' 8" 24" to 30" 24" to 30"
8' 9" 24" to 30" 24" to 30" 8' 10" 24" to 30" 24" to 30" 8' 11" 24" to 30" 24" to 30"
9' 0" 24" to 30" 24" to 30"
9' 1" 24" to 30" 24" to 30"
9' 2" 25" to 30" 24" to 30"
9' 3" 26" to 30" 24" to 30"
9' 4" 27" to 30" 24" to 30"
9' 5" 28" to 30" 24" to 30"
9' 6" 29" to 30" 24" to 30"
9' 7" 30" 25" to 30"
9' 8" 26" to 30"
9' 9" 27" to 30" 9' 10" 28" to 30" 9' 11" 29" to 30" 10' 0" 30" 10' 1" 10' 2" 10' 3"
14
INSTALL FRAMING FOR HOOD SUPPORT
IMPORTANTFraming must be capable
of supporting 100 lbs.
If drywall is present, mark the screw hole locations for the top mounting brackets. Remove the template.
Cut away enough drywall to expose 2 vertical studs
at the bracket location indicated on the template.
Install a horizontal support at least 1" x 12"
between two wall studs at the mounting screw location. The horizontal support must be flush with the room side of the studs. Use cleats behind both sides of the support to secure to wall studs.
NOTE: 2 horizontal supports will be needed if there is a stud located between the horizontal screw locations (see figure).
IMPORTANT: Reinstall drywall for an even mounting surface.
1
Installation Instructions
Centerline of
installation
space
View from
rear cleats
1" x 12" min.
mounting
support
DUCTWORK, WIRING LOCATIONS
Determine the exact location of the vent hood.
Locate the template packed with the literature.
– Measure 36" from the floor to the top of the cooking
surface. Add hood installation height determined on pages 8 and 13. Mark that location.
Use a level to draw a straight pencil line on the wall. – Tape the template in position along the penciled
line. CHECK TO BE SURE THE TEMPLATE IS LEVEL.
Ceiling ducting:
If ductwork will vent straight up to the ceiling:
Use a level to draw a line straight up, from
the centerline on the template to the ceiling.
Measure 5" from the back wall to the centerline
of an 8-1/2" hole on the ceiling.
NOTE: If drywall is not present, add drywall thickness to the 5" dimension.
Wall Ducting:
If ductwork will vent to the rear:
Use a level to draw a line straight up from
the centerline on the template.
Measure at least 27-3/4" above the pencil line
that indicates the bottom installation height, to the centerline of an 8-1/2" dia. duct hole. (Hole may be elongated for duct elbow.)
HOUSE WIRING LOCATION:
The junction box is located on the top left side
of the hood.
Wiring should enter the back wall at least 18" above
the bottom of the hood and within 5" of the left side of the centerline.
INSTALLATION—VENTED TO THE OUTSIDE
8-1/2" min. opening for ductwork
Ceiling
House Wiring
Location
C
L
5"
18"
Min.
Wall vent
27-3/4" min.
above
installation
height
5" c enterline to wall
WALLVENT IS27-3/4" MIN. ABOVETHE INSTALLATION HEIGHT
11-7/16"
DRILL2 (TWO)3/16" PILOTHOLESTHROUGH STUDSOR REARWALLSUPPORT
DRILL2 (TWO)3/16" PILOTHOLESTHROUGH STUDSOR REARWALLSUPPORT
2"
HorizontalLine
10-1/8"
Ver ti
calC
e nterline
REAR WALL
MOUNTING TEMPLATE
C L
ALIGN BOTTOMEDGE
WITH PENCILLINE
INDICATINGBOTTOM
12-1/2"
InstallationHeight
OF THEHOOD
31-14772Printed inMexico
12-08JR
Installation Instructions
INSTALL DUCT BRACKET
The duct bracket should be installed against the back wall and flush with the ceiling; the point where the ceiling meets the wall should be level for the bracket and duct cover to fit flush. This bracket will hold the duct cover in place at the top.
Secure the bracket to the wall:
Align the diamond centerline cutout on the bracket
with the penciled centerline on the wall.
Mark 2 screw hole locations in the wall.
Drill 1/8" pilot holes in the marked locations.
If pilot holes do not enter wood studs, enlarge the holes
to 3/8" and install metal wall fastener anchors (provided).
If mounting directly to a masonry wall, obtain appropriate
#10 masonry screw anchors. Drill and install per the fastener supplier’s instructions.
Drive screws, by hand, into the fasteners to allow anchors
to expand. Remove the screws.
Secure the bracket to the wall with wood screws and/or
fasteners.
3
INSTALL HOOD MOUNTING SCREWS
The two upper mounting screws must enter the horizontal support or wall studs.
With the template taped in place, use a punch to mark
mounting bracket screw locations.
Drill 1/8" pilot holes in 4 of the punched locations
in the lower bracket. If the bottom 2 pilot holes do not enter wood, enlarge the holes to 3/8” and install metal wall fastener anchors (provided).
Remove the template.
Install the 2 top mounting screws, leave 1/4" gap between
the screw head and the wall. This will allow the keyhole slot on the hood frame to engage the screw head.
IMPORTANT:Use the mounting screws provided. DO NOT USE DRYWALL SCREWS.
Check to be sure the mounting screws are horizontally level.
2
Centerline cutout
MOUNT THE HOOD
WARNING: 2 people are required to lift
and position the hood onto the mounting screws.
Lift the hood onto the mounting screws.
If using a wall fastener, make sure the washer is in front
of the flange and not behind it. Check with a level before tightening the screws.
Install lower screws to pull the hood tight against the wall.
4
Tighten
screws
Install
screws
15
Bottom
screw
location
WALLVENT IS27-3/4" MIN. ABOVE THEINSTALLATION HEIGHT
11-7/16"
2"
DRILL 2 (TWO) 3/16"PILOT HOLESTHROUGH STUDSOR REARWALL SUPPORT
Ver ti
cal C
e nterline
C
L
DRILL 2 (TWO) 3/16"PILOT HOLESTHROUGH STUDSOR REARWALL SUPPORT
Horizontal Line
10-1/8"
MOUNTING TEMPLATE
12-1/2"
InstallationHeight
REAR WALL
ALIGN BOTTOMEDGE
WITH PENCILLINE
INDICATINGBOT TOM
OF THEHOOD
31-14772Printed inMexico
12-08JR
16
Installation Instructions
INSTALLATION—VENTED TO THE OUTSIDE
CONNECT DUCTWORK
Remove shipping tape from the damper.
Install ductwork, making connections
in the direction of airflow as illustrated.
Push duct over the exhaust outlet and damper.
Secure joints in ductwork with sheet metal screws.
Wrap all duct joints and the flange connections
with aluminized duct tape for an airtight seal.
CAUTION:Do not use sheet metal
screws at the hood flange connection. Doing so will prevent proper damper operation. Seal connection with tape only.
5
Duct tape over seam and screw
Screw
Airflow
CONNECT ELECTRICAL
Verify that power is turned off at the source.
WARNING: If house wiring is not 2-wire
with a ground wire, a ground must be provided by the installer. When house wiring is aluminum, be sure to use U.L. approved anti-oxidant compound and aluminum-to-copper connectors.
Remove the 6 screws on the junction box cover
and the knockout on the top left side.
Secure the house wiring to the junction box with
a strain relief (not provided).
Connect the white lead to the branch circuit white lead.
Connect the black lead to the branch circuit black lead.
Connect the green/yellow lead to the branch
circuit green lead or bare ground lead.
Secure all the connections with wire nuts on each
electrical connector.
Push the wires into the junction box and replace
the cover. Be sure the wires are not pinched.
Secure the junction box cover with the 6 original
screws.
6
Junction
box cover
Knockout
Loading...
+ 36 hidden pages