The information contained herein is intended to assist truck users and dealers in the servicing of SCR controls furnished
by the General Electric Company. It does not purport to cover all variations in equipment nor to provide for every possible
contingency to be met with installation, operation or maintenance.
Should further information be desired or should particular problems arise which are not covered sufficiently for the
purchaser's purpose, the matter should be referred to the truck manufacturer through his normal service channels, not directly
to the General Electric Company.
The control circuit is energized by closing the key switch, seat switch, and moving the forward or reverse lever to either position, and then depressing the accelerator closing the start switch.
This applies power to the control card turning on the PMT driver , which will close the selected
directional contactor and complete the circuits to the drive motor. (See elementary drawings.)
The control card then supplies a gate pulse to 2REC turning it on to a conducting state,
allowing current to flow from the battery through lC, lX, 2REC, motor field, motor armature, sensor,
and back to the battery. After lC charges, 2REC shuts off due to lack of holding current. The control card checks that lC is charged and unlocks the gate to lREC and 5REC.
The control card then supplies a gate pulse to lREC turning it on to a conducting state, allowing current to flow from the battery through lREC, motor field, motor armature, sensor, and back to
the battery. 5REC turns on and allows current to flow T4-T3, lC, lREC, 5REC to T4-T3. This
current charges the bottom of lC positive with respect to the battery positive bus. This charging cycle
occurs in less than l millisecond (.00l sec.) and 5REC shuts off. This charge is now stored on the
capacitor until it is time to turn off lREC.
Current continues to flow in lREC until the control card fires 2REC. When 2REC conducts,
capacitor lC discharges around the circuit composed of lC, 1X, 2REC, and lREC. This discharge
current opposes the battery current through lREC so that the resultant current is zero. With reverse
voltage across lREC, lREC is turned off. Current continues to flow in the 2REC, lC, motor and
battery loop until the capacitor (card terminal l4) is fully charged negative. This charge exceeds
battery voltage by an amount which is a function of peak motor current, and 2REC turns off. Figure l
illustrates the pulsing of current from the battery.
Figure lFigure 2
During the off time, the energy stored in the motor, by virtue of the motors inductance, will
cause current to circulate through the motor around the loop formed by 3REC. Thus, providing MD=J
15
Page 16
is called flyback current. Figure 2 shows the nature of the motor current which is composed of
both battery current and the inductive flyback current. It should be noted that the average motor
current measured will be greater than the average battery current. The SCR control, in effect, converts battery current at battery volts into a higher motor current and a lower motor volts.
The time for the next ON and OFF cycle to start is determined by the time that the control
card takes to oscillate. This frequency of oscillation is controlled by the potentiometer in the accelerator and automatic circuitry in the card. Slow speed is obtained by having maximum ohms in the
potentiometer. As the resistance in the potentiometer decreases, the speed of the motor increases.
The SCR circuit is capable of delivering approximately 95% speed. For full speed operation, the lA
contactor is closed to apply full battery voltage across the motor.
CONTROL FEATURES
OSCILLATOR - the oscillator section of the card has two adjustable features and one fixed feature.
With the accelerator potentiometer at maximum ohms, the creep speed can be adjusted by the
handset unit. Top speed is fixed by card and is
obtained with the accelerator potentiometer at
minimum ohms. The % ON time has a range of
approximately 5 to 95 percent. The center
operating condition of the oscillator is at 50
percent ON time with a nominal l.8 milliseconds
ON time and l.8 millisecond OFF time. This
corresponds to a maximum operating frequency
of about 300 hertz. At creep the ON time will
decrease to approximately 0.8 milliseconds while
OFF time will become in the order of 20 milliseconds. At full SCR operation, this condition
will be reversed (short OFF time, long ON time).
This variation of ON and OFF time of the
Figure 3
oscillator produces the optimum frequencies
through the SCR range. The frequency curve of
the oscillator is shown in Figure 3.
The rate at which the oscillator may increase its percent ON time is limited by Controlled
Acceleration. The minimum time required to go from creep speed to 80-85% on time point may be
varied by the C/A trimpot on the card, adjustable from approximately 0.1 seconds to 22.0 seconds.
CURRENT LIMIT - This circuit monitors motor current by utilizing a sensor in series with the
armature. The information detected across the sensor is fed back to the card so current may be
limited to a pre-set value. If heavy load currents are detected, this circuit overrides the oscillator and
limits the average current to a value set by function 4 of the handset. The C/L setting is based on the
maximum thermal rating of lREC and the peak voltage on the capacitor. Because of the flyback
current through 3REC, the motor current usually runs 2 to 3 times battery current. See current limit
curves for available current and adjustment range.
16
Page 17
PLUGGING - Slow down is accomplished when reversing by providing a small amount of retarding
torque for deceleration. If the vehicle is moving and the directional lever is moved from one direction
to the other, the motor field is reversed. The plug signal is initiated by the fact that the directional
switch has moved from one direction to the other. The motor armature, driven by the inertia of the
vehicle, acts as generator. This generated current passes through 4REC and the sensor. The oscillator circuit regulates at a plug current limit level as set by the Handset this controls the pulse rate of
lREC to regulate the generated motor current and bring the truck to a smooth stop and reversal. With
the accelerator potentiometer at minimum resistance, function 5 will enable adjustment of plugging
current from max to min. current level for plug current limit.
PEDAL POSITION PLUG - This feature will allow for plugging distance based on pedal position.
Pedal position will reduce the plugging current to the current value set by this function as the accelerator is returned to the creep speed position. Maximum plug current is obtained with the accelerator
in the top speed position. This feature is adjustable by using function 16 on the handset.
RAMP START - This feature provides full SCR torque to restart a vehicle on an incline. The
memory for this function is the directional switch. When stopping on an incline, the directional
switch must be left in its original or neutral position to allow the control to assure full power when
restarted. The accelerator potentiometer input will modulate ramp start current.
FULL POWER TRANSITION - this built-in feature provides smooth transition from SCR to lA
bypass. This is accomplished by the SCR continuing to pulse until the lA contactor power tips close.
CONTROL ACCELERATION AND 1A TIME - This feature allows for adjustment of the rate of
time it takes for the control to accelerate to 96% applied battery voltage to the motor on hard acceleration. The 1A contactor will automatically close .2 seconds after the controlled acceleration stops
and the accelerator input is less than .5 volts or less than 50 ohms. C/A is adjusted by function 3 from
.1 to 22 seconds.
1A CURRENT DROP OUT - This adjustable feature can be set to open the 1A contactor if the
traction motor is subject to excessive currents. The dropout is adjustable with function 6 of the
handset. Once the control has dropped out the 1A contactor due to excess current, the directional or
accelerator switch must be returned to neutral to unlock the dropout circuit to allow the control to
pick up the 1A contactor again. Using this feature will reduce the 1A contactor tip life, thus it should
be used only where needed to protect the motor.
STATIC RETURN TO OFF - This built-in feature of the control is set up to make the driver return
the directional lever to neutral anytime he leaves the vehicle and returns. If the seat switch or key
switch is opened, the control will shut off and cannot be restarted until directional lever is returned to
neutral. A time delay of approximately .75 seconds is built into the seat switch input to allow momentary opening of the seat switch if a bump is encountered.
ACCELERATOR VOLTS HOLD-OFF This feature checks the voltage level at the accelerator
input when ever the key switch or seat switch is activated. If the voltage is less than 2.5 volts the
control will not start. This is to assure that the control is calling for low speed operation at start-up.
17
Page 18
COIL DRIVER MODULES - these drivers are internal to the control card. They are the power
devices that operate F, R, lA, D, FW, RB, and PS contactor coils. These drivers open or close these
coils on command from the control card. All modules are equipped with reverse battery protection in
that if the battery is connected incorrectly, none of the contactors controlled can be closed electrically.
lA THERMAL HOLD OFF - this feature prevents the lA contactor from closing when the truck is
in severe thermal cutback to avoid torque jumps. When the control goes into severe cutback, the
must pulse to time will inhibit the lA timer.
MUST PULSE TO TIME - this feature prevents the lA timer from timing if the oscillation pulse rate
has not reached a particular level of operation.
PULSE MONITOR TRIP ( PMT ) - This feature contains three features which shuts down or locks
out control operation if fault conditions exist that would allow uncontrolled ( run away ) speed of the
vehicle:
Look ahead
Look again
Automatic look again and reset
The PMT circuit will not allow the control to start under the following conditions:
1. If 1REC is shorted or if 1A contactor is welded, the control will not allow the F or R
contactor to close.
2. Will not allow the control to operate if F and R internal coil drivers are shorted or if
3REC diode is shorted.
The PMT circuit will shut down operation of the control ( opening of the F or R contactor ) under the
following conditions:
If 1REC fails to commutate ( shut off ), or if 1A power tips remain closed when they should be open.
After opening the F or R contactor the PMT circuit will check for a fault and if none is found will
reclose the directional contactor. If the fault still exist, the directional contactor will open and remain
open.
If 1A closes before a second commutation failure, the look again counter will automatically reset.
This eliminates the inconvenience of resetting the PMT with the key switch if the trip is due to random noise.
When the PMT circuit prevents F or R contactors from closing, the PMT circuit can be reset only by
opening the key switch.
THERMAL PROTECTOR - (TP) - this temperature sensitive device is mounted on the lREC heat
sink. If the lREC temperature begins to exceed the design limits, the thermal protector will lower the
18
Page 19
maximum current limit and not allow lREC to exceed its temperature limits. Even at a reduced
current limit, the vehicle will normally be able to reach sufficient speed for full lA operation, thereby
allowing the panel to cool. As the panel cools, the thermal protector will automatically return the
control to full power.
LOW VOLTAGE- batteries under load, particularly if undersized or more than 80 percent discharged, will produce low voltages at the SCR control terminals. The EV-l00 control is designed for
use down to 50 percent of a nominal battery volts of 36-84 V, and 75 percent of a nominal battery
volts of 24 V. Lower battery volts may cause the control to not operate correctly; however the PMT
should open the F or R contactor in the event of a commutation failure.
FIELD WEAKENING - if the vehicle is supplied with a field weakening circuit, the FW PU and
FW DO (function 7 and 8) can be adjusted from the handset unit. Field weakening is a method of
attaining higher running speed for the vehicle in level operation. The normal settings for this feature
are: pickup of FW contactor from l25 to l50 percent of normal full-load running current (lA), and
dropout of FW contactor from 275 to 300 percent current. The dropout puts the motor back to the
lA range to climb ramps and inclines.
REGENERATIVE BRAKING if the vehicle is moving and the directional lever is moved from one
direction to the other, this initiates a plugging signal by reversing the motor field. During the standard motoring mode and the plugging mode, the RB contactor remains picked up. In the plugging
mode, the motor armature acts as generator. Once the generated current reaches a particular current
level, the plugging mode transitions to regenerative braking mode.
Transitioning to regenerative braking mode, opens the RB contactor, disconnecting the motor armature from battery negative and inserting 7REC and REGEN SENSOR-2 in the regen circuit. During
the lREC on time, the field and armature current is increased. During the 1REC off time, the energy
stored in the field and armature generates the regenerative current, which passes through 7REC, #2
sensor, battery, 3REC/4REC and back to motor field and armature.
The control will remain in regenerative mode as long as the regen current can maintain regenerative
current limit. When the regenerative current cannot be maintained and drops below the level set by
the regenerative current limit trimpot (RB C/L), the regenerative braking mode transitions back to
plugging mode. During the transition back to plugging mode, the RB contactor will reclose enabling
the control to function in plugging mode, regulating plugging currents to bring the vehicle to a
smooth stop and reversal. The accelerator potentiometer input will modulate plugging as well as
regenerative braking current. The major advantage of regen is longer motor life due to reduced motor
heating. This feature has two adjustable functions, regen current limit (function 9) and regen start
(function 10).
DUAL MOTOR OPERATION - This function is used to connect the motor armatures of a dual
motor vehicle system in parallel during a plug if both motors are in operation at the time of the
plug cycle. This prevents the fields from building flux in the opposite directions and prohibits the
motors from acting as a series generator thereby causing uncontrollable plugging torques. This circuit
require the addition of an armature shorting contactor ( D contactor ) and an additional 4REC diode (
4REC-B). The D contactor only closes when both motors are energized during a plugging cycle.
19
Page 20
DUAL MOTOR IN-BOARD WHEEL REVERSAL - This feature allows for the control of the inboard traction motor while in a sharper turning condition. The in-board motor is controlled by inputs
from limit switches located on the rear steering wheel which connect card input points to negative.
Logic for turn switch operation is shown below:
LEFT TURN- L1 and L2 open- motor energized.
- L1 closed and L2 open- motor disabled.
- L1 and L2 closed- motor reversed from normal direction.
RIGHT TURN- R1 and R2 open- motor energized.
- R1 closed and R2 open- motor disabled.
- R1 and R2 closed- motor reversed from normal direction.
DUAL MOTOR SHARP TURN SPEED LIMIT - This handset adjustable feature allows for the
limiting of top speed when either the R1 and R2 or the L1 and L2 switches are both closed.
TOP SPEED ( MOTOR VOLTS ) LIMIT - This feature provides a means to limit motor volts to
three adjustable limits by limit switch opening between input points on the control card and negative.
The lower motor volt limit always takes priority when more than one switch input is closed. This
motor volt limit effects top speed of the SCR, but actual truck speed will vary at any set point depending on the loading of the vehicle. Each speed limit is adjustable by the handset, function 11, 12,
and 13, for speed limits 1, 2, and 3.
STEER PUMP CONTACTOR TIME DELAY - This feature provides two options for SP time
delay option 1 provides a .5 to 63 second time delayed drop out of the steer pump contactor when the
Forward or Reverse directional switch is opened. This is overridden by a 1.5 second time delayed
drop-out whenever the seat switch is opened. Option 2 provides a .5 to 63 second time delayed drop
out of the SP contactor when the seat switch is opened.
CONSTANT CURRENT COIL DRIVERS AND INTERNAL COIL SUPPRESSION - This
feature allows the use of 24 volt contactor coils on through the entire voltage range of the EV100 (
24 volts to 84 volts ) for the F,R,1A,SP,RG,D,and FW contactors.
This feature also allows the above contactors to operate cooler due to less current being applied to
the coil after pick-up.
HOUR METER READINGS - This feature will display the recorded hours of use of the traction
control and pump control to the dash display each time the key switch is turned off.
INTERNAL RESISTANCE COMPENSATION - This feature is used when the Battery Discharge
Indicator is present. Adjustment of this function will improve the accuracy of the BDI.
TRUCK MANAGEMENT MODULE (TMM1) - is a multi-function accessory card that provides
the OEM the ability to provide status codes or operator warning codes that will be displayed on the
dash display whenever a normally open switch or sensor wire provides a negative signal to the card.
Typically the TMM1A can be used to display over temperature of motors, hydraulic systems or any
other switch that closes at the desired temperature. The TMM1A can also be used to monitor and
display motor brush wear warnings when the motor brushes require replacement.
20
Page 21
TRUCK MANAGEMENT MODULE (TMM2) - is a multi-function accessory card that provides a
horn alarm circuit which blows the horn when the truck is left unattended without the park brake
being set, and also provides a dash board located controlled acceleration adjustment for use by the
operator.
STORED STATUS CODE - This feature furnishes a function register functional that contains the
last fault that shut down vehicle operation (PMT type fault that is reset by cycling the key switch).
This status code will be over written each time a new status code occurs and can be cleared from
memory by adjusting the value to zero.
ON-BOARD DIAGNOSTICS - The logic card detects the systems current operating status which
can be displayed to either the Dash Display or the Handset. There are currently over 75 status codes
that are available with systems using Traction and Pump SCR controls and Truck Management
Module (TMM). Along with the status code display from the TMM, the logic card is capable of
reducing the current to the control to alert the operator of a critical fault condition.
BATTERY DISCHARGE INDICATION - This feature uses the latest in microprocessor technology to provide accurate battery state of charge information and supplies passive and active warning
signals to the vehicle operator.
Features and functions:
Displays 100 to 0 percent charge
Display blinks with 20% charge
Disables pump circuit with 10% charge
Auto ranging for 36/48 volt operation
Adjustable for use on 24 to 80 volts
HANDSET - This is a multi-functional tool to be used with the EV100 LX and LXT SCR controls.
The Handset consist of a Light Emitting Diode (LED) display and a keyboard for data entry.
Features and functions:
Monitor existing system status code for both traction and pump SCR systems
Monitor intermittent random status code
Monitor battery state of charge on LXT systems
Monitor hourmeter reading on traction and pump SCR systems
Monitor or adjust the control functions.
21
Page 22
HYDRAULIC SCR CONTROL ( EV100P ) - This hydraulic controller consist of the following
features:
Three speeds adjustable from 0 volts to full motor volts.
Fixed speeds actuated by switch closure to negative.
1A bypass contactor ( if required )
Variable resistor input (5K-0 ohms).
PMT functions available with use of line contactor.
Current limit and controlled acceleration adjustable.
Battery Discharge Indicator interrupt compatible.
On-board TMM1A functions
Operation of voltage regulator card:
This card provides the basic functions required for controlling the EV100 hydraulic control and
optional contactors and PMT functions. Battery positive is applied through a main control fuse to the
key switch, energizing the control card power supply input to TB4.
When the line contactor is used, PMT operation is the same as outlined for the EV100 traction
controllers.
The four speed ( motor volts ) reference points TB2, TB3, TB5, and TB6 are selected by connecting
these points independently to battery negative.
The first speed is obtained by closing speed point 1, TB2, to SCR control negative. Speed point 1 is
adjustable by function 11 to adjust motor voltage from 0 to full motor volts. The specified motor
volts will be regulated, however, the magnitude of motor current will vary depending on the loading
of the vehicle.
The second speed is obtained by closing speed point 2, TB3, to SCR control negative. Speed point 2
is adjustable by function 12 to adjust motor voltage form 0 to full motor volts.
The third speed is obtained by closing speed point 3, TB5, to SCR control negative. Speed point 3 is
adjustable by function 13 to adjust motor voltage form 0 to full motor volts.
The fourth speed is obtained by closing speed point 4, TB6, to SCR control negative. Speed point 4 is
non-adjustable and provides full control motor volts. Speed input 4 must be activated to enable the
optional 1A contactor.
If more than one speed input is activated, the selected speed with the highest motor volts will override the low motor volt speed.
The 1A contactor is activated by closing the speed input switch connected to TB6 and SCR negative.
This starts the time delay circuit of the 1A contactor. This time is trimpot adjustable from 1 to 4
seconds. A clockwise rotation of the trimpot will increase the time delay.
22
Page 23
The current limit circuit is adjustable and operates the same as the traction SCR current limit. See
current limit curves for limits and range.
The controlled acceleration circuit is adjustable and operates the same as the traction SCR circuit.
Adjustment range is from .45 to 4.0 seconds.
The variable resistor input will override the fixed motor volt limits set by the three adjustable speed
inputs. It will vary motor volts above the set limits up to full motor volts, as resistance is decreased.
The Battery Discharge Indicator ( BDI ) interrupt will disable the hydraulic controller if the connection between PB3 and PB6 is opened. If a BDI circuit is not used, a jumper must be placed between
PB3 and PB6 to allow the hydraulic control to operate.
The following are the input/output terminals for the pump control.
PA1-93 Status Code Input
PA2-93 Status Code Input
PA3-90 Status Code Input
PA4-94 Status Code Input
PA5-94 Status Code Input
PA6-91 Status Code Input
PB1-95 Status Code Input
PB2-95 Status Code Input
PB3-BDI Enable Signal
PB4-PMT Driver
PB5-1A Driver
PB6-92 Status Code Input
PY10-Input to Traction PY10
PY11-Input to Traction PY9
PY12-Input to Traction PY8
23
Page 24
GENERAL MAINTENANCE INSTRUCTIONS
The SCR control, like all electrical apparatus, does have some thermal losses. The semiconductor
junctions have finite temperature limits above which these devices may be damaged. For these reasons, normal maintenance should guard against any action which will expose the components to
excessive heat, such as steam cleaning; or which will reduce heat dissipating ability of the control,
such as restricting air flow.
The following DOS and DONTS should be observed:
Any controls that will be used in ambients of 100 F (40 C) or over should be brought to the
attention of the truck manufacturer.
All external components having inductive coils must be filtered. Refer to vehicle manufacturer for specifications.
The control should not be steam cleaned. In dusty areas, use low-pressure air to blow off the
control. In oily or greasy areas, a mild solution of detergent or denatured alcohol can be used
to wash off the control and then blow completely dry with low-pressure air. The control can
also be cleaned with Freon TF degreaser.
For the SCR panel to be most effective, it must be mounted against the frame of the truck.
The truck frame, acting as an additional heat sink, will give improved truck performance by
keeping the SCR control package cooler. The use of a heat-transfer grease (Dow Corning
340) is recommended.
Terminal boards and other exposed SCR control parts should be kept free of dirt and paint
that might change the effective resistance between points.
CAUTION: The truck should not be plugged when the truck is jacked up and the drive
wheels are in a free wheeling position. The higher motor speeds can create excessive
voltages that can be harmful to the control.
Do not hipot (or megger) the control. Unless the terminals of each semiconductor and card
are connected together, the control may be damaged. Refer to control manufacturer before
hipotting.
Use a lead-acid battery with the voltage and ampere hour rating specified for the vehicle.
Follow normal battery maintenance procedures, recharging before 80 percent discharged and
with periodic equalizing charges.
24
Page 25
TROUBLE-SHOOTING INSTRUCTIONS
Trouble-shooting the EV100/200 LX/LXT control should be quick and easy by following the instruction outlined in the following status code instruction sheets.
If mis-operation of the vehicle occurs, a status code will be displayed on the Dash Display for vehicle
equipped with a Dash Display or by plugging a Handset into logic card's plug "Y" location and then
reading the status code.
With the status code number, follow the procedures outlined in the status code instruction sheets to
determine the problem.
Checking and replacement of components are also outlined in sections of this instruction book. Please
refer to these section as needed.
Important Note: Due to the interaction of the logic card with all vehicle functions, almost any status
code or control fail could be caused by the logic card. After all other status code procedures have
been followed and no problem is found the logic card should then be replaced as the last option to
correct problem.
The same device designations have been maintained on different controls but the wire numbers may
vary. Refer to the elementary and wiring diagrams for your specific control. The wire numbers
shown on the elementary diagram will have identical numbers on the corresponding wiring diagrams
for a specific truck, but these numbers may be different from the numbers referenced in this publication.
WARNING: Before trouble-shooting, jack up wheels, disconnect the battery and
discharge capacitor 1C. Reconnect the battery as needed for the specific check.
If capacitor 1C terminals are not accessible, discharge capacitor by connecting from SCR POS terminal to 2 REC anode. Check resistance on Rx1000 scale from frame to SCR power and control
terminals. A resistance of less than 20,000 ohms can cause misleading symptoms. Resistance less
than 1000 ohms should be corrected first.
Before proceeding, visually check for loose wiring, maladjusted linkage to the accelerator switch,
signs of overheating of components, etc.
Tools and test equipment required are: (a) 6-volt lamp, 6-volt battery, two A14 diodes (1 Amp
400V), clip leads, volt-ohm meter (20,000 ohms per volt) and general hand tools.
25
Page 26
Reactor/Choke
Disconnect all leads to the reactor.
Remove the two mounting bolts and lift out.
Set new reactor on SCR base and start screws back into base. Be sure to use the original
screws and washers. run screws in to base finger tight.
Check that the bottom of the reactor is flat against the base.
Alternately tighten the two screws by 1/4 turn until firm.
Replace all connections removed in step 1.
26
Page 27
GEH-5722GEH-5722
GEH-5722
GEH-5722GEH-5722
GE Electric Vehicle
Systems
INSTRUCTIONS
STATUS CODES
The information contained herein is intended to assist truck users and dealers in the servicing of Solid-State controls
furnished by the General Electric Company. It does not purport to cover all variations in equipment nor to provide for every
possible contingency to be met with installation, operation or maintenance.
Should further information be desired or should particular problems arise which are not covered sufficiently for the
purchaser's purpose, the matter should be referred to the vehicle manufacturer through his normal service channels, not
directly to the General Electric Company.
September 1993
27
Page 28
STATUS CODE
BLANK
Segments do not illuminate on Dash Display or Handset
DESCRIPTION
DISPLAY
SYMPTOM
Display screen on Dash Display or Handset is blank.
POSSIBLE CAUSE
Positive or negative control voltage is missing.
Insure that the key switch is closed and voltage is
present between PZ7 and PZ3 control negative , and
that voltage is present between TB4 and PZ3 control
negative.
Open circuit between logic card plug "Y" and Dash Display
or Handset.
Check for a loose connection or open wire between
logic card plug "Y" and Dash Display or Handset.
MEMORY
RECALL
CONTROL
TYPE
No
Traction
and Pump
Defective Dash Display or Handset
Replace Dash Display or Handset.
STATUS CODE
No seat/deadman switch input.
-01
SYMPTOM
Forward or reverse contactor will not pick up.
POSSIBLE CAUSE
Mis-adjusted or defective seat switch.
Check seat switch to insure proper closure.
Open circuit between battery positive TB3.
Check for loose connections or broken wire
between seat switch and TB3 and between key
switch and positive side of the seat switch and seat
switch to TB4.
This indicates a lack of input voltage to the logic card
and/or display unit.
DESCRIPTION
Figure 1
STATUS INDICATION CRITERIA
MEMORY
RECALL
CONTROL
TYPE
No
Traction
On vehicles without seat switch, check for loose
connections or broken wire from TB4 to TB3.
28
Figure 1
STATUS INDICATION CRITERIA
This status code will be displayed when TB3 is less
than 50% battery volts.
Page 29
STATUS CODE
Forward directional switch is closed on initial power up.
DESCRIPTION
-02
SYMPTOM
Forward contactor will not close because of Static Return to
Off (SRO) lock out.
POSSIBLE CAUSE
Forward directional switch is closed on initial start up (i.e.
closure of battery, key switch or seat/deadman switch).
Return directional switch lever to neutral and then
return lever to forward position.
Forward directional switch is welded closed or mis-adjusted
to be held closed.
Replace or adjust directional switch to insure that it
opens when the directional switch is returned to
neutral.
Short circuit between TB2 and TB5.
Disconnect the wire from TB5 and check for a short
circuit between TB2 and the wire.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code will be displayed when TB5 is greater
than 60% of battery volts on initial start up.
No
Traction
Defective logic card.
Disconnect wire at TB5; Measure voltage at TB5,
should be less than 60% of battery volts.
STATUS CODE
Reverse directional switch is closed on initial power up.
DESCRIPTION
-03
SYMPTOM
Reverse contactor will not close because of Static Return to
Off (SRO) lock out.
POSSIBLE CAUSE
Reverse directional switch is closed on initial start up (i.e.
closure of battery, key switch or seat/deadman switch).
Return directional switch lever to neutral and then
return lever to reverse position.
Reverse directional switch is welded closed or mis-adjusted
to be held closed.
Replace or adjust directional switch to insure that it
opens when the directional switch is returned to
neutral.
Short circuit between TB2 and TB6.
Disconnect the wire from TB6 and check for a short
circuit between TB2 and the wire.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code will be displayed when TB6 is greater
than 60% of battery volts on initial start up.
No
Traction
Defective logic card.
Disconnect wire at TB6; Measure voltage at TB6,
should be less than 60% of battery volts.
29
Page 30
STATUS CODE
Start switch input low after initial start up
DESCRIPTION
-04
SYMPTOM
Forward or reverse contactor will not pick-up.
POSSIBLE CAUSE
Forward or reverse directional switch closed on initial start
up.
Depress accelerator to close start switch. Status code
will change to 03 if reverse directional switch or to
02 if forward directional switch is closed. If either of
these codes appear, return directional switch to
neutral and then select the desired direction.
Excessive leakage from TB2 to battery negative.
Check voltage at TB2 with key and seat switches
closed and directional switch in neutral. Voltage
should be greater than 60% of battery voltage.
If less than 60% battery voltage. Remove wire and
measure ohmic value from wire to SCR negative.
Value should be less than 22k ohms.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when TB2 voltage is less
than 60% of battery volts at initial start-up (seat switch
closure).
No
Traction
STATUS CODE
Start switch or brake switch fails to close.
DESCRIPTION
-05
SYMPTOM
Forward or reverse contactor will not pick up.
POSSIBLE CAUSE
Defective brake switch circuit.
Check brake switch to insure closure with brake
pedal released.
Check for open circuit or loose connections in
wiring from brake switch to seat switch and TB3,
and from brake switch to start switch.
Defective start switch circuit.
Check start switch to insure closure when accelerator
is depressed.
Check for open circuit or loose connections in
wiring from brake switch to start switch and from
TB2 to start switch.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is when TB1 is less than 2.5 volts and
TB2 is less than 60% battery volts.
No
Traction
30
Page 31
STATUS CODE
Accelerator depressed with no direction selected.
DESCRIPTION
-06
SYMPTOM
Forward or reverse contactor will not pick up.
POSSIBLE CAUSE
Accelerator pedal is depressed before closing forward or
reverse directional switch.
Status code will disappear when directional switch
isclosed or when accelerator pedal is
released.
Defective directional switch
Check forward or reverse switch to insure closure
when direction is selected.
Open circuit between directional switch(s) and battery
positive or between directional switch(s) and TB5 or TB6.
Check all control wires and connections shown in
Figure 1.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code will be displayed when TB5 and TB6
are less than 60% of the battery volts, and TB1 is less
than 2.5 volts.
No
Traction
STATUS CODE
Accelerator input voltage too high.
DESCRIPTION
-07
SYMPTOM
Forward or reverse contactor picks up but control will not operate
when accelerator pedal is depressed or status code -07 is displayed
then disappears when the vehicle starts to accelerate.
POSSIBLE CAUSE
Accelerator input mis-adjusted or defective.
Input voltage at TB1 should be less than 3.7 volts.Ad-
just or replace accelerator unit to insure that the
voltage at TB1 will vary from 3.5 volts to less than .5
volts when the pedal is depressed.
Open circuit between battery negative and TB1 in accelerator input
circuit.
Check for broken wires or loose connections or open
potentiometer / voltage supply in the circuit shown in
Figure 1.
Short circuit from battery positive to wiring in accelerator input
circuit.
Disconnect wire from TB1 and measure voltage at wire to
negative. Should be zero volts for potentiometer type and
less than 3.7 volts for solid state type accelerator input.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
No
Traction
This status code is displayed when the accelerator input voltage at TB1 is higher than 3.7 volts,
and a directional contactor is picked up.
31
Page 32
STATUS CODE
Accelerator input voltage too low on power up after
-08
Forward or reverse contactor does not pick up.
POSSIBLE CAUSE
Accelerator input mis-adjusted or defective.
Input voltage at TB1 should be more than 3.0 volts.
Adjust or replace accelerator unit to insure that the
voltage at TB1 is more than 3.0 volts before depressing pedal.
Short circuit between battery negative and TB1 in accelera-
tor input circuit.
Disconnect wire from TB1. Check for short circuit
from wire to battery negative. Resistance should be
greater than 4.7K ohms.
Defective Card
Disconnect wire from TB1. Measure voltage from
TB1 to negative. Voltage should be greater than 4.5
volts, if not, replace card.
initial key switch closure.
SYMPTOM
DESCRIPTION
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code will be displayed when the accelerator
input voltage at TB1 is less than 3.0 volts, and any of
the following connections are opened and closed,
battery plug or seat switch or key switch.
No
Traction
STATUS CODE
Both forward and reverse directional switches are closed
-09
Forward or reverse contactor will not pick up.
POSSIBLE CAUSE
Forward or reverse directional switch welded closed or misadjusted to be held closed.
Replace or adjust directional switches to insure that
they open when directional switch is returned to
neutral.
Short circuit between battery positive and TB5 and/or TB6.
Disconnect wires from TB5 and TB6 and check wires
for short circuit to positive side of directional switch.
Defective card
Disconnect wires and measure voltage at TB5 and
TB6 . Voltage should be less than 60% of battery
volts.
at the same time.
SYMPTOM
DESCRIPTION
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code will be displayed when TB5 and TB6
are greater than 60% of battery volts at the same time.
No
Traction
32
Page 33
STATUS CODE
Battery volts too low.
DESCRIPTION
-15
SYMPTOM
Forward or reverse contactor will not pick up.
POSSIBLE CAUSE
Discharged battery
Check battery for proper open circuit voltage as
outlined in figure 1 and charge battery if required.
Defective battery
Check each battery cell for proper voltage (greater
than 1.95 volts at cell). Replace or repair battery.
Incorrect control card adjustment.
Check function 15 for proper adjustment for
batterybeing used. See handset instruction
sheet for details. Adjust to proper settings.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the battery volts are
less than 1.95 volts per cell at initial start up. (See table
in figure 1).
No
Traction
STATUS CODE
Battery volts too high.
DESCRIPTION
-16
SYMPTOM
Forward and reverse contactor will not pick up.
POSSIBLE CAUSE
Incorrect control card adjustment
Check function 15 for proper adjustment for battery
being used. See handset instructions for details.
Adjust to proper setting.
Battery over charged or incorrect battery used.
Check battery for proper open circuit voltage per
table in figure 1. If voltage excessive-check battery
charger for proper output voltage.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the battery volts
are greater than 2.40 volts per cell at initial start up.
(See table in figure 1.)
No
Traction
33
Page 34
STATUS CODE
Invalid card type selection.
-17
SYMPTOM
Forward or reverse contactors will not close.
POSSIBLE CAUSE
Invalid card type selection.
Review function 17 in the Handset Instruction
sheets. Adjust and set card type value as instructed
by OEM service manual.
DESCRIPTION
This status code is displayed when the card type
selection value is set to an invalid number.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
No
Traction
STATUS CODE
Forward and reverse contactor coil current low.
DESCRIPTION
-23
SYMPTOM
Forward or reverse contactor will not pick up. Status code
may alternate between code 23 and code 24. Complete
check for code 23, if the problem is not found, perform
check for code 24.
POSSIBLE CAUSE
Defective F and R contactor coil circuit.
Check for open circuit or loose connection between
PB4 and positive side of F contactor coil and
between PB5 and positive side of R contactor coil.
Remove plug B. Check ohmic value from PB4 to
positive side of F coil. Value should be 10-14
ohms. Make same check for R coil.
Defective 1A, RB, SP,or FW contactor coil.
Remove plug B. Check ohmic value from positive
side of each coil to its respective plug connection.
Value should be 10-14 ohms.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the current draw in
the forward or reverse contactor coil circuit is less than
100 ma.
No
Traction
34
Page 35
STATUS CODE
T2 voltage low. (Less than 12% battery volts.)
DESCRIPTION
-24
SYMPTOM
SCR control does not operate. Status code may alternate between
code 23 and code 24. Complete checks for 24, if the problem is not
found, perform code 23 check.
POSSIBLE CAUSE
Defective F or R contactor.
F or R power tips fail to close because:
1) Welded normally closed power tips.
2) Binding contactor tip assembly.
3) Defective F or R contactor coil.
( See status code 23)
Defective RB contactor.
Check RB contactor power tips for closure and proper pick
up.
Check for open circuit or loose connections between
positive side of RB contactor coil and PB2.
Figure 1
MEMORY
RECALL
CONTROL
TYPE
No
Traction
Open motor circuit
Check for open circuit or loose connection in motor circuit
from the A1 connection to the A2 connection on the SCR
control panel.
Defective 1A,RB,SP or FW contactor
Perform checks as outlined in status 23.
STATUS CODE
1A contactor does not drop out or drops out slowly.
DESCRIPTION
-25
SYMPTOM
Short tip life on F and R or 1A contactor. Status code 46
displayed and no fault found.
POSSIBLE CAUSE
Note: This status code can only be found by using the
handset and looking at function 1. This status code is
furnished as a troubleshooting aid for status code 46.
Defective 1A contactor
Check 1A contactor for binding or slow operation
when dropping out.
STATUS INDICATION CRITERIA
This status code is displayed when T2 volts is greater
than 12% of battery volts and the F and R driver is
energized.
MEMORY
RECALL
CONTROL
TYPE
Yes
Traction
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when 1A contactor drop
out time exceeds .060 seconds.
35
Page 36
STATUS CODE
Shorted coil driver for SP or FW contactor.
DESCRIPTION
-26
SYMPTOM
SP or FW contactor picks up immediately when key switch
is closed.
POSSIBLE CAUSE
Defective coil driver internal to logic card.
Replace logic card.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when there is a shorted
RB,SP or FW coil driver.
No
Traction
STATUS CODE
Open thermal protector (TP) or control over temperature.
DESCRIPTION
-41
SYMPTOM
Reduced or no power to traction motor in SCR range.
POSSIBLE CAUSE
Open thermal protector circuit.
Check for loose connection or broken wire be-
tween:
Black wire-Thermal proctor and PZ1.
Gray wire-Thermal proctor and PZ5.
Defective thermal protector.
Disconnect wires from PZ1 and PZ5. At room
temperature (25oC or 75oF) measure resistance
between black and gray wire. Replace TP if ohmic
value is greater than 300 ohms.
SCR is in thermal cut-back.
Allow control to cool, status code should disap-
pear.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the voltage
between PZ1 and PZ5 is greater than 1.8 volts.
Traction
No
36
Page 37
STATUS CODE
Control motor current sensor input missing.
DESCRIPTION
-42
SYMPTOM
No power to traction motor in SCR range.
POSSIBLE CAUSE
Open sensor wire circuit to PZ4.
Check for loose connection or broken wire (green
wire) from current sensor to PZ4 on the logic card.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when voltage between
PY7 and negative is greater than 1.6 volts with no
current flowing in the motor circuit.
No
Traction
STATUS CODE
Control motor current sensor input missing.
DESCRIPTION
-43
SYMPTOM
Stall currents in SCR range higher than normal and
uncontrollable with C/L adjustment.
POSSIBLE CAUSE
Open sensor wire circuit to PZ3.
Check for loose connections or broken wire (yellow
wire) from current sensor to PZ3 on logic card.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when voltage between
PY7 and negative is less than .84 volts with no
current flowing in motor circuit.
No
Traction
37
Page 38
STATUS CODE
1REC did not turn off properly.
DESCRIPTION
-44
SYMPTOM
Forward or reverse contactors open and close, then can
only be closed by opening and closing the key switch.
POSSIBLE CAUSE
Defective 5 REC circuit.
Check for shorted 5 REC.
Check for shorted 5 REC snubber (25 REC).
Defective 2 REC circuit.
Check for shorted 2 REC.
Check for shorted 2 REC snubber (22 REC).
MEMORY
RECALL
CONTROL
TYPE
Yes
Traction
Open choke (1X).
Check for open circuit between T5 and T3. Ohm
meter should read zero ohms.
1 REC defective.
Turn off time for 1 REC out of specification. No
fieldtest is possible. Replace 1 REC
after above checks, show no problem found.
STATUS CODE
1 REC did not turn on properly.
DESCRIPTION
-45
SYMPTOM
Forward or reverse contactor will open and close, then open
and then can only be closed by opening and closing the
key switch.
POSSIBLE CAUSE
Defective 2 REC circuit.
Check for shorted 2 REC.
Check for shorted 2 REC snubber (22 REC).
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when, during SCR
operation, 1 REC fails to turn off.
MEMORY
RECALL
CONTROL
TYPE
Traction
Yes
Defective 1 REC circuit.
Check for open circuit or loose connections between
1REC and PZ8. (white/blue wire)
Check for open circuit or loose connection between
1REC (3 REC snubber) and PZ9. (blue wire)
Defective 1 REC.
Intermittent or open 1 REC gate. Field test may or
may not show defect. Replace 1 REC after above
checks, show no problem found.
38
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when 1 REC fails to gate
on.
Page 39
STATUS CODE
Look ahead test for T2 volts. ( Greater than 85% of
-46
SYMPTOM
Forward or reverse contactor will not pick up.
POSSIBLE CAUSE
Defective 1 REC.
Check for shorted 1 REC.
Check for defective 1 REC insulator (co-therm)
that may short 1 REC heat sink to base plate.
Defective 1A contactor.
Check for welded 1A contactor power tips.
battery volts)
DESCRIPTION
This status code is displayed when the voltage at T2 is
greater than 85% of battery volts.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
No
Traction
STATUS CODE
2REC does not turn properly
DESCRIPTION
-47
SYMPTOM
Forward or reverse contactor will open and close, then
open and then can only be closed by opening and closing
the key switch.
POSSIBLE CAUSE
Defective 2 REC circuit.
Check that 2 REC will gate on.
Check for open circuit or loose connection
between 2 REC gate and PZ10. (white/red wire)
Check for open circuit or loose connection 1 REC
and 1C through the 2 REC circuit.
F or R contactor or power tips bouncing open.
Check that power tips on F and R contactor power
tips do not bounce open during operation (ie:
travel over speed bumps or dock plates).
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the 2 REC fails to
turn on.
No
Traction
39
Page 40
STATUS CODE
Look ahead test for T2 volts. (Less than 12% of battery
-48
SYMPTOM
Forward or reverse contactor will not pick up.
POSSIBLE CAUSE
Defective forward or reverse contactor.
Check for welded forward or reverse contactor
power tips.
Check for sluggish operation of forward or reverse
contactor.
Defective 3 REC circuit.
Check for shorted 3 REC.
Check for shorted 3 REC snubber (23 REC).
volts)
DESCRIPTION
This status code is displayed when the voltage at T2
is less than 12% of battery volts.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
No
Traction
STATUS CODE
5 REC does not turn on properly
DESCRIPTION
-49
SYMPTOM
Forward or reverse contactor will open and close, then
open and then can only be closed by opening and closing
the key switch.
POSSIBLE CAUSE
Defective 5 REC circuit
Check for shorted 5 REC.
Check for shorted 5 REC snubber ( 25 REC ).
Check that 5 REC will gate on.
Check for open circuit or loose connection
between 5 REC gate and PZ12 ( white/violet wire
).
Shorted 2 REC circuit.
Check 2 REC and 2 REC snubber ( 22 REC ) for
short circuit.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the 5 REC circuit
fails to turn on.
No
Traction
Defective capacitor circuit.
Check for open capacitor.
Check for loose connections at capacitor terminals.
40
Page 41
STATUS CODE
Capacitor volts low .
DESCRIPTION
-50
SYMPTOM
Forward or reverse contactor picks up. Control does not
operate.
POSSIBLE CAUSE
Defective 2 REC circuit.
Open circuit or loose connection between spider
assembly and 5 REC (BUS A).
Open circuit or loose connection between 5 REC
and2 REC.
Open circuit or loose connection between 2 REC
and PZ11 (red wire) and between 2 REC gate and
PZ10(white/red wire).
Check 2 REC to insure that it will gate on.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when 2 REC circuit fails
to turn on at initial start up.
No
Traction
STATUS CODE
Excessive capacitor voltage when motor current is high.
DESCRIPTION
-51
SYMPTOM
Forward or reverse contactors open and close, then can
only be closed by opening and closing the key switch.
POSSIBLE CAUSE
Excessive source inductance.
Tag lines without filters are being used.
Battery cables are too long.
High peak current in motor.
Check for shorted field winding.
Check for shorted armature winding.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when capacitor volts
exceed 225 volts and motor current is greater than 300
amps.
No
Traction
41
Page 42
STATUS CODE
Excessive capacitor voltage when motor current is low.
DESCRIPTION
-52
SYMPTOM
Forward or reverse contactors open and close, then can
only be closed by opening and closing the key switch.
POSSIBLE CAUSE
Excessive source inductance.
Tag lines without filters are being used.
Battery cables are too long.
Defective 4 REC circuit.
Check for shorted 4 REC.
Check for open circuit or loose connection in 4
R E Ccircuit.
Figure 1
MEMORY
RECALL
CONTROL
TYPE
Yes
Traction
Defective 3 REC circuit.
Check for open circuit or loose connection in 3
R E Ccircuit.
STATUS CODE
1 REC fails to turn off during plug cycle.
DESCRIPTION
-53
Forward or reverse contactor opens and closes, then opens and can
only close by opening and closing the key switch.
1 REC turn off failure not related to plugging.
Stall vehicle in both directions and note any status codes
displayed that may more closely define the failure mode.
Troubleshoot per new status code.
1 REC turn off related to plugging.
Check 4 REC circuit for open 4 REC, loose or open cable/
bus connections.
SYMPTOM
POSSIBLE CAUSE
STATUS INDICATION CRITERIA
This status code is displayed when capacitor volts
exceed 225 volts and motor current is less than 200
amps.
MEMORY
RECALL
CONTROL
TYPE
Yes
Traction
Check current sensor for loose or open connection in power
circuit. Check yellow and green wire from sensor to logic
card for open and loose connection.
Defective motor circuit.
Check motor circuit for open or loose connections.
Check motor brushes for proper seating.
F or R contactor power bouncing open.
Insure that F and R contactor does not bounce open during
vehicle operation (ie: traveling over speed bumps and dock
plates).
42
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when any failure of 1
REC to turn off during plug cycle.
Page 43
STATUS CODE
-54
Control will not operate.
POSSIBLE CAUSE
Defective logic card.
Replace logic card.
Shorted F, R or 1A contactor coil driver.
SYMPTOM
DESCRIPTION
This status code is displayed when either the forward,
reverse or 1A contactor coil driver is shorted internal to
the logic card.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
No
Traction
STATUS CODE
Current sensor input voltage polarity check.
DESCRIPTION
-57
SYMPTOM
Forward or reverse contactors open and close, then can
only be closed by opening and closing the key switch.
POSSIBLE CAUSE
Reversed yellow and green current senors wires
Insure that the:-green wire connects to PZ4 with
no open circuits.
-yellow wire connects to PZ3 with
no open circuits or loose
connections.
Reversed power cable connection.
Insure that the battery negative cable connects to
SCR NEG and the motor A2 cable connects to SCR
A2.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the voltage input
to PZ4 and PZ3 is the wrong polarity.
No
Traction
43
Page 44
STATUS CODE
Regen current sensor input missing ( yellow wire ).
-70
SYMPTOM
Control does not operate.
POSSIBLE CAUSE
Defective regen sensor input circuit.
Check yellow sensor wire for open circuit or loose
connection between sensor (welded connection) and
PA4.
DESCRIPTION
This status code is displayed when input signal at PA4
is missing.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
Yes
Traction
STATUS CODE
Regen current sensor input missing ( green wire ).
-71
SYMPTOM
Control does not operate.
POSSIBLE CAUSE
Defective regen sensor input circuit.
Check green sensor wire for open circuit or loose
connection between sensor (welded connection) and
PA5.
DESCRIPTION
This status code is displayed when input signal at PA5
is missing.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
Yes
Traction
44
Page 45
STATUS CODE
Regen contactor does not pick up.
-72
SYMPTOM
Regen control does not operate.
POSSIBLE CAUSE
Open connection in the PA6 circuit.
Check for open circuit or loose connection between
PA6 and the A2 connection of the RB contactor.
Check for open circuit or loose connection between
7 REC and the A2 connection of the RB contactor.
DESCRIPTION
This status code is displayed when logic card is in run
mode and 2.5 volts or greater is present at PA6.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
Yes
Traction
STATUS CODE
Regen contactor does not drop out or drops out slowly.
DESCRIPTION
-73
SYMPTOM
Forward or reverse contactor opens and closes, then opens
and can only close by opening and closing the key
switch.
POSSIBLE CAUSE
Defective RB contactor.
Check RB contactor for smoothness of operation
and excessive wear on moving parts.
Intermittent PA6 input.
Check for loose connections in PA6 circuit from
PA6 to RB contactor A2 connection.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the RB contactor
power tips fail to open after 100 milliseconds after
power is removed from the RB contactor coil.
Yes
Traction
45
Page 46
STATUS CODE
Regen contactor picks up too slow.
DESCRIPTION
-74
SYMPTOM
Forward or reverse contactor opens and closes, then opens
and can only close by opening and closing the key switch.
POSSIBLE CAUSE
Defective RB contactor.
Check RB contactor for smoothness of operation
and excessive wear on moving parts.
Intermittent PA6 input.
Check for loose connections in PA6 circuit from
PA6 to RB contactor A2 connection.
Defective RB contactor coil circuit.
Check RB contactor coil for proper ohmic value. It
should be 10-14 ohms.
Figure 1
MEMORY
RECALL
CONTROL
TYPE
Yes
Traction
Check coil connection from PB2 to RB coil (-) for
loose connections.
Check coil connections from battery positive to RB
coil (+) for loose connections.
STATUS CODE
1 REC fails to turn off during Regen.
DESCRIPTION
-75
Forward or reverse contactor opens and closes, then opens and can
only close by opening and closing the key switch.
1 REC turn off failure not related to regen.
Stall vehicle in both directions and note any status codes
displayed that may more closely define the failure mode.
Trouble shoot per new status code.
1 REC turn off related to regen.
Check for loose connections on all regen power circuits from
battery positive to RB contactor A2 connection.
Check for loose connection on the following regen input
circuits.
Yellow wire from sensor 2 to PA4.
Green wire from sensor 2 to PA5.
Wire 17 from RB contactor to PA6.
Defective motor circuit.
Check motor circuit for open or loose connections.
Check motor brushes for proper seating.
F or R contactor power bouncing open.
Insure that F and R contactor does not bounce open during
vehicle operation (ie: traveling over speed bumps and dock
plates).
SYMPTOM
POSSIBLE CAUSE
STATUS INDICATION CRITERIA
This status code is displayed when the RB contactor
power tips do not close within 100 milliseconds after
power is applied to the RB contactor coil.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when any failure of 1
REC to turn off during regen cycle.
Yes
Traction
46
Page 47
STATUS CODE
Capacitor overvoltage during Regen.
DESCRIPTION
-76
SYMPTOM
Forward or reverse contactor opens and closes, then opens
and can only close by opening and closing the key switch
POSSIBLE CAUSE
Intermittent connection in battery power circuit.
Check battery power circuit, both positive and
negative for loose connections.
Check power fuse, battery connectors, line
contactors, and etc., for possible opening during
regen cycle.
Excessive source inductance.
Check for unfiltered tag lines.
Check for long battery cables.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when capacitor voltage is
greater than 225 volts during the regen cycle.
Yes
Traction
STATUS CODE
User defined status code - see OEM instructions manual.
DESCRIPTION
-90
SYMPTOM
Status code flashes on and off.
POSSIBLE CAUSE
User defined status code is displayed by switch closure or
motor brush sensor closure to negative.
See OEM instruction manual for corrective action
required.
Other Causes:
Terminal 1 shorted to negative.
Defective input switch (shorted).
Defective TMM card.
NOTE: When SCR pump control is used with internal
TMM function, input terminal is PA3 on pump logic
card.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the voltage at
terminal 1 of TMM is at zero volts.
No
TMM
47
Page 48
STATUS CODE
User defined status code - see OEM instructions manual.
DESCRIPTION
-91
SYMPTOM
Status code flashes on and off.
POSSIBLE CAUSE
User defined status code is displayed by switch closure or
motor brush sensor closure to negative.
See OEM instruction manual for corrective action
required.
Other Causes:
Terminal 3 shorted to negative.
Defective input switch (shorted).
Defective TMM card.
NOTE: When SCR pump control is used with internal
TMM function, input terminal is PA6 on pump logic
card.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the voltage at
terminal 3 of TMM is at zero volts.
No
TMM
STATUS CODE
User defined status code - see OEM instructions manual.
DESCRIPTION
-92
SYMPTOM
Status code flashes on and off.
POSSIBLE CAUSE
User defined status code is displayed by switch closure or
motor brush sensor closure to negative.
See OEM instruction manual for corrective action
required.
Other Causes:
Terminal 4 shorted to negative.
Defective input switch (shorted).
Defective TMM card.
NOTE: When SCR pump control is used with internal
TMM function, input terminal is PB6 on pump logic
card.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the voltage at
terminal 4 of TMM is at zero volts.
No
TMM
48
Page 49
STATUS CODE
User defined status code - see OEM instructions manual.
DESCRIPTION
-93
SYMPTOM
Status code flashes on and off.
POSSIBLE CAUSE
User defined status code is displayed by switch closure or
motor brush sensor closure to negative.
See OEM instruction manual for corrective action
required.
Other Causes:
Terminal 5 and 6 shorted to negative.
Defective input switch (shorted).
MEMORY
RECALL
CONTROL
TYPE
No
TMM
Defective TMM card.
NOTE: When SCR pump control is used with internal
TMM function, input terminal is PA1 and PA2 on pump
logic card.
STATUS CODE
User defined status code - see OEM instructions manual.
DESCRIPTION
-94
SYMPTOM
Status code flashes on and off.
POSSIBLE CAUSE
User defined status code is displayed by switch closure or
motor brush sensor closure to negative.
See OEM instruction manual for corrective action
required.
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the voltage at
terminal 5 and 6 of TMM is at zero volts.
MEMORY
RECALL
CONTROL
TYPE
No
TMM
Other Causes:
Terminal 8 and 10 shorted to negative.
Defective input switch (shorted).
Defective TMM1 card.
NOTE: When SCR pump control is used with internal
TMM function, input terminal is PA4 and PA5 on pump
logic card.
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the voltage at
terminal 8 and 10 of TMM is at zero volts.
49
Page 50
STATUS CODE
User defined status code - see OEM instructions manual.
DESCRIPTION
-95
SYMPTOM
Status code flashes on and off.
POSSIBLE CAUSE
User defined status code is displayed by switch closure or
motor brush sensor closure to negative.
See OEM instruction manual for corrective action
required.
Other Causes:
Terminal 11 and 12 shorted to negative.
Defective input switch (shorted).
MEMORY
RECALL
CONTROL
TYPE
No
TMM
Defective TMM card.
NOTE: When SCR pump control is used with internal
TMM function, input terminal is PB1 and PB2 on pump
logic card.
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the voltage at
terminal 11 and 12 of TMM is at zero volts.
50
Page 51
STATUS CODE
Invalid card type selection.
-117
SYMPTOM
Pump contactor will not close.
POSSIBLE CAUSE
Invalid card type selection.
Review function 17 in the Handset Instruction
sheets. Adjust and set card type value as instructed
by OEM service manual.
DESCRIPTION
This status code is displayed when the card type
selection value is set to an invalid number.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
No
Pump
STATUS CODE
Forward and reverse contactor coil current low.
DESCRIPTION
-123
SYMPTOM
Pump contactor will not pick up. Status code may alternate between code 23 and code 24. Complete check for
code 23, if the problem is not found, perform check for
code 24.
POSSIBLE CAUSE
Defective Pump contactor coil circuit.
Check for open circuit or loose connection between
PB4 and positive side of Pump contactor coil.
Remove plug A. Check ohmic value from PB4 to
positive side of F coil. Value should be 10-14
ohms.
Defective 1A contactor coil.
Remove plug A. Check ohmic value from positive
side of coil to its plug connection. Value should be
10-14 ohms.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the current draw in
the pump contactor coil circuit is less than 100 ma.
No
Pump
51
Page 52
STATUS CODE
T2 voltage low. (Greater than 12% battery volts.)
DESCRIPTION
-124
SYMPTOM
Control does not operate. Status code may alternate
between code 23 and code 24. Complete checks for 24, if
the problem is not found, perform code 23 check.
POSSIBLE CAUSE
Defective Pump contactor.
Pump power tips fail to close because:
1) Welded normally closed power tips.
2) Binding contactor tip assembly.
3) Defective Pump contactor coil.
( See status code 123)
Open motor circuit
Check for open circuit or loose connection in motor
circuit from the A1 connection to the A2 connection
on the control panel.
Defective 1A contactor.
Perform checks as outlined in status 123.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when T2 volts is greater
than 12% of battery volts and the pump driver is
energized.
No
Pump
STATUS CODE
1A contactor does not drop out or drops out slowly.
DESCRIPTION
-125
SYMPTOM
Short tip life on Pump or 1A contactor. Status code 46
displayed and no fault found.
POSSIBLE CAUSE
Note: This status code can only be found by using the
handset and looking at function 1. This status code is
furnished as a troubleshooting aid for status code 146.
Defective 1A contactor
Check 1A contactor for binding or slow operation
when dropping out.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when 1A contactor drop
out time exceeds .060 seconds.
No
Pump
52
Page 53
STATUS CODE
Open thermal protector (TP) or control over temperature.
DESCRIPTION
-141
SYMPTOM
Reduced or no power to pump motor in SCR range.
POSSIBLE CAUSE
Open thermal protector circuit.
Check for loose connection or broken wire be-
tween:
Black wire-Thermal proctor and PZ1.
Gray wire-Thermal proctor and PZ5.
Defective thermal protector.
Disconnect wires from PZ1 and PZ5. At room
temperature (25oC or 75oF) measure resistance
between black and gray wire. Replace TP if ohmic
value is greater than 300 ohms.
SCR is in thermal cut-back.
Allow control to cool, status code should disap-
pear.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the voltage
between PZ1 and PZ5 is greater than 1.8 volts.
No
Pump
STATUS CODE
Control motor current sensor input missing.
DESCRIPTION
-142
SYMPTOM
No power to pump motor in SCR range.
POSSIBLE CAUSE
Open sensor wire circuit to PZ4.
Check for loose connection or broken wire (green
wire) from current sensor to PZ4 on the logic card.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when voltage between
PY7 and negative is greater than 1.6 volts with no
current flowing in the motor circuit.
No
Pump
53
Page 54
STATUS CODE
Control motor current sensor input missing.
DESCRIPTION
-143
SYMPTOM
Stall currents in SCR range higher than normal and
uncontrollable with C/L adjustment.
POSSIBLE CAUSE
Open sensor wire circuit to PZ3.
Check for loose connections or broken wire (yellow
wire) from current sensor to PZ3 on logic card.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when voltage between
PY7 and negative is less than .84 volts with no
current flowing in motor circuit.
No
Traction
STATUS CODE
1REC did not turn off properly.
DESCRIPTION
-144
SYMPTOM
Forward or reverse contactors open and close, then can
only be closed by opening and closing the key switch.
POSSIBLE CAUSE
Defective 5 REC circuit.
Check for shorted 5 REC.
Check for shorted 5 REC snubber (25 REC).
Defective 2 REC circuit.
Check for shorted 2 REC.
Check for shorted 2 REC snubber (22 REC).
Open choke (1X).
Check for open circuit between T5 and T3. Ohm
meter should read zero ohms.
1 REC defective.
Turn off time for 1 REC out of specification. No
fieldtest is possible. Replace 1 REC
after above checks, show no problem found.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when, during SCR
operation, 1 REC fails to turn off.
Pump
Yes
54
Page 55
STATUS CODE
1 REC did not turn on properly.
DESCRIPTION
-145
SYMPTOM
Forward or reverse contactor will open and close, then open
and then can only be closed by opening and closing the
key switch.
POSSIBLE CAUSE
Defective 2 REC circuit.
Check for shorted 2 REC.
Check for shorted 2 REC snubber (22 REC).
Defective 1 REC circuit.
Check for open circuit or loose connections between
1REC and PZ8. (white/blue wire)
MEMORY
RECALL
CONTROL
TYPE
Yes
Pump
Check for open circuit or loose connection between
1REC (3 REC snubber) and PZ9. (blue wire)
Defective 1 REC.
Intermittent or open 1 REC gate. Field test may or
may not show defect. Replace 1 REC after above
checks, show no problem found.
STATUS CODE
Look ahead test for T2 volts. ( Greater than 85% of
-146
SYMPTOM
Pump contactor will not pick up.
POSSIBLE CAUSE
Defective 1 REC.
Check for shorted 1 REC.
battery volts)
This status code is displayed when 1 REC fails to gate
on.
DESCRIPTION
Figure 1
STATUS INDICATION CRITERIA
MEMORY
RECALL
CONTROL
TYPE
No
Pump
Check for defective 1 REC insulator (co-therm)
that may short 1 REC heat sink to base plate.
Defective 1A contactor.
Check for welded 1A contactor power tips.
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the voltage at T2 is
greater than 85% of battery volts.
55
Page 56
STATUS CODE
2REC does not turn properly
DESCRIPTION
-147
SYMPTOM
Pump contactor will open and close, then open and then
can only be closed by opening and closing the key
switch.
POSSIBLE CAUSE
Defective 2 REC circuit.
Check that 2 REC will gate on.
Check for open circuit or loose connection
between 2 REC gate and PZ10. (white/red wire)
MEMORY
RECALL
CONTROL
TYPE
No
Pump
Check for open circuit or loose connection 1 REC
and 1C through the 2 REC circuit.
F or R contactor or power tips bouncing open.
Check that power tips on F and R contactor power
tips do not bounce open during operation (ie:
travel over speed bumps or dock plates).
STATUS CODE
Look ahead test for T2 volts. (Less than 12% of battery
-148
SYMPTOM
Pump contactor will not pick up.
POSSIBLE CAUSE
Defective forward or reverse contactor.
Check for welded forward or reverse contactor
power tips.
volts)
This status code is displayed when the 2 REC fails to
turn on.
DESCRIPTION
Figure 1
STATUS INDICATION CRITERIA
MEMORY
RECALL
CONTROL
TYPE
No
Pump
Check for sluggish operation of forward or reverse
contactor.
Defective 3 REC circuit.
Check for shorted 3 REC.
Check for shorted 3 REC snubber (23 REC).
56
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the voltage at T2
is less than 12% of battery volts.
Page 57
STATUS CODE
5 REC does not turn on properly
DESCRIPTION
-149
SYMPTOM
Pump contactor will open and close, then open and then
can only be closed by opening and closing the key
switch.
POSSIBLE CAUSE
Defective 5 REC circuit
Check for shorted 5 REC.
Check for shorted 5 REC snubber ( 25 REC ).
Check that 5 REC will gate on.
Check for open circuit or loose connection
between 5 REC gate and PZ12 ( white/violet wire
).
Shorted 2 REC circuit.
Check 2 REC and 2 REC snubber ( 22 REC ) for
short circuit.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the 5 REC circuit
fails to turn on.
No
Pump
Defective capacitor circuit.
Check for open capacitor.
Check for loose connections at capacitor terminals.
STATUS CODE
Capacitor volts low .
DESCRIPTION
-150
SYMPTOM
Pump contactor picks up. Control does not operate.
POSSIBLE CAUSE
Defective 2 REC circuit.
Open circuit or loose connection between spider
assembly and 5 REC (BUS A).
Open circuit or loose connection between 5 REC
and2 REC.
Open circuit or loose connection between 2 REC
and PZ11 (red wire) and between 2 REC gate and
PZ10(white/red wire).
Check 2 REC to insure that it will gate on.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when 2 REC circuit fails
to turn on at initial start up.
No
Pump
57
Page 58
STATUS CODE
Excessive capacitor voltage when motor current is high.
DESCRIPTION
-151
SYMPTOM
Pump contactors open and close, then can only be closed
by opening and closing the key switch.
POSSIBLE CAUSE
Excessive source inductance.
Tag lines without filters are being used.
Battery cables are too long.
High peak current in motor.
Check for shorted field winding.
Check for shorted armature winding.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when capacitor volts
exceed 225 volts and motor current is greater than 300
amps.
No
Pump
STATUS CODE
Excessive capacitor voltage when motor current is low.
DESCRIPTION
-152
SYMPTOM
Pump contactors open and close, then can only be closed
by opening and closing the key switch.
POSSIBLE CAUSE
Excessive source inductance.
Tag lines without filters are being used.
Battery cables are too long.
Defective 4 REC circuit.
Check for shorted 4 REC.
Check for open circuit or loose connection in 4
R E Ccircuit.
Defective 3 REC circuit.
Check for open circuit or loose connection in 3
R E Ccircuit.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when capacitor volts
exceed 225 volts and motor current is less than 200
amps.
Yes
Pump
58
Page 59
STATUS CODE
-154
Control will not operate.
POSSIBLE CAUSE
Defective logic card.
Replace logic card.
Shorted F, R or 1A contactor coil driver.
SYMPTOM
DESCRIPTION
This status code is displayed when either the forward,
reverse or 1A contactor coil driver is shorted internal to
the logic card.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
No
Pump
STATUS CODE
Current sensor input voltage polarity check.
DESCRIPTION
-157
SYMPTOM
Pump contactors open and close, then can only be closed
by opening and closing the key switch.
POSSIBLE CAUSE
Reversed yellow and green current senors wires
Insure that the:-green wire connects to PZ4 with
no open circuits.
-yellow wire connects to PZ3 with
no open circuits or loose
connections.
Reversed power cable connection.
Insure that the battery negative cable connects to
SCR NEG and the motor A2 cable connects to SCR
A2.
MEMORY
RECALL
CONTROL
TYPE
Figure 1
STATUS INDICATION CRITERIA
This status code is displayed when the voltage input
to PZ4 and PZ3 is the wrong polarity.
No
Pump
59
Page 60
60
Page 61
TABLE 4 CHECKING COMPONENTS
Main Logic Card
All trouble-shooting is written to check all outside devices and eliminate them as the source of the
symptoms. The conclusion being then that the card is faulty.
1. Instructions for Removal of Control Card.
Remove control wires on the screw terminals 1 through 6 as required.
Unplug A, B, and Z plugs by pressing down on tab with wide blade screwdriver
and rotating 90 degrees.
Remove the two mounting screws and lift card box free.
NOTE: Do not attempt to remove circuit broad from card box.
Reverse procedures to install new control card.
MountingA and B PlugsTerminals 1 - 6Y PlugZ Plug
Screw
61
Page 62
Capacitor 1C
Disconnect the battery and discharge the capacitor. Measure ohms through the capacitor using the R x
10,000 scale. Meter should read zero and then swing slowly to above 100,000 ohms. Replace the
capacitor if above reading is not obtained.
Control is arranged so that the F and R contactors do not break current. Check to see that the
1A contactor drops out before the F or R contactor.
Most contactor coils are polarity sensitive. The left-hand terminal must be connected to
positive.
Potentiometer in Accelerator
To check operation of the potentiometer, disconnect the battery and disconnect the wire at
control card TB1. Connect a VOM to the wire that was removed from TB1 and to negative. Place the VOM on the R x 100 scale. With the accelerator in the creep speed position,
the ohms reading should be 4800 to 6000 ohms. With the accelerator in the top speed
position, the ohm reading should be 50 ohms or less. With the wire disconnected as above,
check for resistance of 1 megohm or higher from pot wire to the truck frame.
SCRs (1REC, 2REC,5REC)
These are silicon controlled rectifiers. Before checking, disconnect the battery and discharge capacitor 1C. Disconnect gate leads of SCRs at the SCR terminal.
To check an SCR, it is necessary to have a 6 volt battery and 2 A-14 diodes.
Connect the positive lead to the anode, connect the negative lead to the cathode as shown
below.
62
Page 63
(1). The lamp should not light. If the lamp does light, the SCR is shorted and must be
replaced.
(2). If check (1) was satisfactory, test the SCR for its ability to be turned on by the gate.
Connect positive through two diodes to the gate terminal. If the gate is operative, the lamp
will come on and remain on when the gate is removed. Some SCRs will operate correctly
even if the lamp does not remain on, particularly with a weak battery.
(3). If the lamp cannot be lit under step (2) the SCR is open and must be replaced.
NOTE:
If you do not have a test light to check the SCRs as described above, they may be checked
for shorts and opens by use of the VOM.
Measure resistance from anode to cathode (R x 100 scale). If SCR is shorted (zero
ohms), it must be replaced.
Measure resistance from the gate terminal to the cathode and then from the cathode to
the gate terminal (R x100 scale). If resistance reads either zero ohms (short) or infinity
ohms (open), replace the SCR. When reassembling SCRs, refer to TABLE 5.
Rectifiers (3REC, 4REC, Diode Blocks)
When checking diodes, disconnect battery and discharge capacitor 1C. When replacing
rectifiers, refer to TABLE 5. For 3REC and 4REC, disconnect one lead or flexible connection.
3REC and 4REC are diode with about 7 to 12 ohms in the conducting direction (anode to
cathode) measure on the R x 100 scale, and 10,000 ohms or higher, in the non-conducting
direction (cathode to anode) measured on the R x 10,000 scale.
Thermal Protector (TP)
Remove both the GRAY and BLACK wires from the Z plug that connects to the control
card. Read the resistance between these two wires with the VOM set on the R x 100 scale.
VOM should read 100 to 200 ohms if the 1REC heatsink is at room temperature (25C or
75F). Set the VOM to the highest ohm scale and read from each wires end to the 1REC
heatsink, reading should be infinity.
63
Page 64
Filter Block(23FIL,etc.)
To check, disconnect all wires from the filter block on remove from panel. With VOM on
the R x 10,000, touch the leads to the filter terminals to charge the filter. After a few seconds, reverse the meter leads and touch the filter terminal. The VOM needle will deflect and
return to infinity. If this capacitor action is not observed, replace the filter block.
Filter Block(23FIL,etc.)
Filter block test 4K is only to detect an open or shorted filter. If the control has symptoms as
in 1E, interchange 22REC and 25REC and try again. If the problem is corrected, the old
25REC is marginal and should be replaced. If the problem is not corrected, replace both
filters.
1X Choke and Reactor T3-T4
Refer to panel wiring diagram to locate windings. With VOM on R x 1 scale, measure
choke or reactor winding, reading should be less than 1 ohm.
64
Page 65
REPLACEMENT OF EV-100 COMPONENTS
When replacing stud semiconductors such as 3REC and 4REC it is not necessary to torque these
devices to a specific value.
The use of a heat-transfer grease (such as GE Versilube G-350-M or equivalent) is recommended.
When replacing module semiconductors such as 1REC, 2REC or 5REC
Remove all module connections. (As required)
Remove module by backing out the two screws at the device sides.
Clean the insulator surface with a clean rag and isopropyl alcohol.
Inspect the insulator surface for tears or cracks. If defective, replace. Wipe a light layer of
machine oil on the base and smooth the insulator into position.
NOTE: Insulator not required for 2REC and 5REC.
Coat insulator with a light coat of heat-transfer grease similar to GE-350.
Set new module on insulator and start screws back into base. Be sure to use the original
screws and washers. run screws in to base finger tight.
Check that the bottom of the module is flat against the insulator or base.
Alternately tighten the two screws by 1/4 turn until firm.
Replace all connections removed in step 1.
Capacitor
Remove nuts from capacitor connections and remove wires.
Remove hold down brackets and lift out.
Reverse procedure to replace capacitor.
22REC, 23REC and 25REC
Remove mounting screws and lift out.
NOTE: When replacing these devices, use the original hardware in the same holes, as the
inserts are used for electrical connections.
65
Page 66
Reactor/Choke
Disconnect all leads to the reactor.
Remove the two mounting bolts and lift out.
Set new reactor on SCR base and start screws back into base. Be sure to use the original
screws and washers. run screws in to base finger tight.
Check that the bottom of the reactor is flat against the base.
Alternately tighten the two screws by 1/4 turn until firm.
Replace all connections removed in step 1.
66
Page 67
GEH-5716
GE Electric Vehicle
Systems
GENERAL
The Handset is a multi-functional tool to be used with the
EV100/200 LX and LXT SCR controls. The Handset consist
of a Light Emitting Diode (LED) display and a keyboard for
data entry.
PURPOSE:
The purpose of the Handset is to allow authorized personnel
to perform the following functions:
Monitor existing system fault codes for both traction
and pump SCR systems
Monitor intermittent random status code
Monitor battery state of charge on LXT systems
Monitor hourmeter reading on traction and pump
SCR systems
Monitor or adjust the following control functions:
Creep speed
Controlled Acceleration and 1A time
Current Limit
Steer pump time delay and define signal input
( seat switch or directional switch )
Plugging distance (Current)
Pedal position plug range or disable
1A drop out current or disable
Field Weakening drop out
Field Weakening pick up
Regen braking current limit
Regen braking drop out
Speed limit points ( SL1,SL2, and SL3)
Truck Management fault speed limit
Internal resistance compensation for battery
state of charge indication
Battery voltage ( 36/48 volts is auto ranging )
Selection of card operation type:
Standard traction card selection:
Standard traction with Field Weakening
Standard traction with speed limits
Standard traction with Regen/Field Weaken-
ing
High or low current limit for all of the above.
OPERATION:
Warning : Before connecting or disconnecting the handset tool, jack up the drive wheels of the vehicle, turn off
the key switch, unplug the battery and discharge the
capacitors.
At the SCR control traction card, unplug the " Y plug " if the
dash display is in use and plug in the handset to the plug
September 1993
INSTRUCTIONS
EV100 HANDSET
location " Y " on the control card. After installing the handset
tool, plug in the battery and turn on the key switch. The
following is the start-up display sequence that will occur:
START-UP DISPLAY SEQUENCE
Key Switch on
Verify Display Segments for
one second
8888
BDI DisplayDiagnostics
oroverride
Blank Displaywith fault
( No BDI used )
Run Mode
BDI DisplayDiagnostics
oroverride
Blank Displaywith fault
( No BDI used )
Key Switch Off
Display traction
hourmeter for
four seconds
Display pump
hourmeter for
four seconds
or
Blank
( If no Pump SCR used )
NOTE: The vehicle can be operated with the handset
connected, however, the adjustment knob must be set
fully clockwise to insure the control operates at top
speed.
Page 68
0
0
0
0
FUNCTION SET-UP PROCEDURES:
Warning: Before making any adjustments to the control
you must consult the operating and maintenance instructions supplied by the vehicle manufacturer. Failure to
follow proper set up instructions could result in
misoperation or damage to the control system.
With the Handset connected , hold down the CONT key and
turn on the key switch. This will place you in the set up mode,
ready to monitor or adjust control function settings.
NOTE: The term push, means to depress key for approximately one second.
SET UP MODE
ActionDisplay showsRemarks
Hold down CONT,8888Segment check
turn on keydisplayed
Push functionU 005Selected
numberfunction number
is displayed
After one second085Stored value for
time delaythe function is
displayed
23456789
Push CONT085Displayed value
23456789
will blink
23456789
Change value with125Value changes
23456789
adjustment knobwhile blinking
DESCRIPTION AND LOCATION
Z PLUG
Y PLUG
B PLUG
A PLUG
EV100 LX/LXT
Push STORE125New value
stored and
blinking stops
Push ESC8888Segment check
displayed
At this point another function can be monitored/changed
by pushing another function number, or the vehicle can be
placed in the run mode by holding the ESC key down for
one second or longer. The display will return to either the
diagnostics mode or the BDI display or a blank display (
if BDI is not used and there are no fault codes). The
vehicle can now be operated with the handset connected
or the handset can be disconnected before operation.
NOTE: You can return to the segment check mode at any
time, by holding down the ESC key until 8888 appears in
the display.
68
Page 69
DESCRIPTION OF FUNCTION NUMBERS FOR:
Control CardsIC3645EVLXCD1TT AND
IC3645EVLXCD1TX
FUNCTION 1STORED FAULT CODE
( Push 1)
This function register contains the last fault that shut down
vehicle operation ( PMT type fault that is reset by cycling the
key switch ) . This fault code will be over written each time
a new fault occurs and can be cleared from memory by
adjusting the value to zero.
FUNCTION 2CREEP SPEED
( Push 2 )
Example:0 = min. current, 255 = max. current
FUNCTION 5PLUGGING DISTANCE (CURRENT)
( Push 5 )
This function allows for the adjustment of the plugging
distance of the vehicle. The larger the current setting, the
shorter the stopping distance.
Range200 to 1000 amps (EV100)
300 to 1500 amps (EV200)
Set0 to 255
Resolution3.14 amps per set unit (EV100)
4.7 amps per set unit (EV200)
Example:Setting of 20 = 263 amps (EV100)
This function allows for the adjustment of the creep speed of
the vehicle. A constant creep speed frequency will be maintained when an accelerator input voltage between 3.7 and 3.5
volts or an accelerator ohmic input between 6K and 4.7K
ohms is provided.
Range2% to 15% on time
Set0 to 255
Resolution.03% per set unit
Example:Setting of 20 = 2.6% on time
FUNCTION 3CONTROLLED ACCELERATION
AND 1A TIME
( Push 3 )
This function allows for the adjustment of the rate of time it
takes for the control to accelerate to 96% applied battery
voltage to the motor on hard acceleration. The 1A contactor
will automatically close .2 seconds after the controlled
acceleration stops and the accelerator input is less than .5
volts or less than 50 ohms.
Range.1 to 22.0 seconds
Set0 to 255
Resolution.084 seconds per set unit
Warning: Plug settings must be in accordance with
control operating instructions. An excessively high setting could cause damage to control system or traction
motor.
FUNCTION 61A DROP OUT CURRENT
( Push 6 )
This function allows for the adjustment of the 1A contactor
drop out current. The 1A contactor will be dropped out and
the vehicle motor torque will be limited to SCR current limit
when the set drop out current is reached.
Range450 to 1260 amps (EV100)
675 to 1890 amps (EV200)
Set0 to 250
Resolution3.24 amps per set unit (EV100)
4.86 amps per set unit (EV200)
Settings above 250 set units will disable 1A drop out function
( 1A will not drop out).
ExampleSetting of 20 = 515 amps (EV100)
FUNCTION 7FIELD WEAKENING PICK UP
( Push 7 )
Example:Setting of 20 = 1.8 seconds C/A
and 2.0 1A time.
FUNCTION 4CURRENT LIMIT
( Push 4 )
This function allows for the adjustment of the current limit
of the control. The rating of the control will determine the
range of adjustment for this function. Please refer to the
operating instructions for the control used in your vehicle.
RangeSee control C/L curves
Set0 to 255
This function allows the adjustment of field weakening
contactor pick up current. This setting allows the FW
contactor to pick up when the vehicle has returned to about
150% of its full load level running current after acceleration.
Range52 to 466 amps (EV100)
78 to 699 amps (EV200)
Set0 to 255
Resolution1.6 amps per set unit
2.4 amps per set unit
ExampleSetting of 20 = 84 amps
69
Page 70
FUNCTION 8FIELD WEAKENING DROP OUT
( Push 8 )
This function allows for the adjustment of the field weakening contactor drop out current. This setting allows the FW
contactor to drop out when the vehicle requires greater than
300% of the full load level running current for greater
torque.
allow top speed with no limit switch connected.
FUNCTION 12 SPEED LIMIT 2 (SL2)
( Push 12 )
Same as Function 11 except using SL2 limit switch for input.
FUNCTION 13 SPEED LIMIT 3 (SL3)
( Push 13 )
Range65 to 895 amps (EV100)
98 to 1343 amps (EV200)
Set0 to 255
Resolution3.25 amps per set unit (EV100)
4.88 amps per set unit (EV200)
ExampleSetting of 20 = 130 amps
FUNCTION 9REGEN BRAKING C/L
( Push 9 )
This function allows for the adjustment of the Regen braking
current limit. The higher the current the shorter the stopping
distance.
Range75 to 630 amps
Set0 to 255
Resolution2.2 amps per set unit
Example:Setting of 20 = 119 amps
FUNCTION 10 REGEN START
( Push 10 )
This function allows for the adjustment of the percent on
time at which the control will start to regen. Adjustment of
this function allows the OEM to set the regen start speed of
the vehicle to eliminate regen attempts when motor regen
current is low.
Range0 to 95% on time
Set0 to 255
Resolution.37% per set unit
Example:Setting of 20 = 7.4% on time
FUNCTION 11 SPEED LIMIT 1 (SL1)
( Push 11 )
This function allows for the adjustment of the speed limit (
maximum battery volts to the motor ) when the SL1 limit
switch input signal is received by the control card. SL1 limit
switch is a normally closed switch connected to battery
negative, the switch opening enables speed limit.
Range96% to 0% battery volts
Set0 to 180
Setting of 0 set units will disable speed limit function and
70
Same as Function 11 except using SL3 limit switch for input.
The SL3 set speed limit is also activated by the Truck
Management Module fault codes 90 and 93. See instructions
for IC3645TMM1A Truck Management Module for details.
FUNCTION 14 INTERNAL RESISTANCE
COMPENSATION
( Push 14 )
This function is used when the Battery Discharge Indicator
is present. Adjustment of this function will improve the
accuracy of the BDI. In order to made this setting the voltage
drop of the battery under load must first be determined by
following the steps listed below.
1. Load the traction motor to 100 amps in 1A and
record the voltage (VO) at the SCR positive and
negative power terminal.
2. Load the traction motor to 200 amps in 1A and
record the voltage (VL) at the SCR positive and
negative power terminal.
3. Calculate voltage drop (VD) as follows:
VD = VO - VL
4. Use the table below to determine the setting using
This function allows for the adjustment of voltage range for
controls equipped with the Battery Discharge Indication
function. In order for the BDI to operate properly, the setting
Page 71
as shown in the table must be entered .
Battery voltsSet units
24 voltsBetween 0 and 31
36 voltsBetween 32 and 44
48 voltsBetween 45 and 69
72 voltsBetween 70 and 80
80 voltsBetween 81 and 183
36/48 voltsBetween 184 and 250
No BDIBetween 251 and 255
The following functions have function numbers larger
than the numbers on the Handset keyboard. To access
these functions, push the CONT key and the number shown
in the following instructions at the same time.
FUNCTION 16 PEDAL POSITION PLUG
( Push CONT and 1 )
This function will allow the adjustment of the pedal position
plug range. Pedal position will reduce the plugging current
to the current value set by this function as the accelerator is
returned to the creep speed position. Maximum plug current
is obtained with the accelerator in the top speed position.
Range100 to 930 amps (EV100)
150 to 1425 amps (EV200)
Set0 to 255
Resolution3.2 amps per set unit (EV100)
5.0 amps per set unit (EV200)
ExampleSetting of 20 = 164 amps
To disable the pedal position plug function, adjust the
current value to the same current value as the plug distance
current.
(Auto plug)15 to 1935 to 3955 to 59
EV200StandardSpeed
Functionwith FWLimitRegen/FW
STD C/L64 to 6884 to 88104 to 108
STD C/L
(Auto plug)74 to 7894 to 98114 to 118
Settings for these function should be made in between the
values shown.
Warning: These settings must be changed by authorized
personnel only, following instructions supplied by the
manufacturer. Card type selection must be made within
the capabilities of the SCR control panel used and the
supporting electro-mechanical devices. Failure to comply with proper application standards could result in
misoperation or damage to the control and/or motors.
FUNCTION 18 STEER PUMP TIME DELAY
( Push CONT and 3 )
This function allows for the selection of steer pump contactor
pick up input, either seat switch or directional switch closing
and adjustment of the time delay for the contactor drop out.
Pick up on seat switch closure and time delay drop out on
seat switch opening.
Range1.5 to 65 seconds
SettingBetween 0 and 128
Resolution.5 seconds per set unit
Example:Setting of 20 = 10.5 seconds
Example: If plug distance current Function 5 is set at 500
amps, then set pedal plug current at 500 amps. With this
setting pedal position will have no effect on plugging
distance.
FUNCTION 17 CARD TYPE SELECTION
( Push CONT and 2 )
This function allows for the selection of the card type used for
your vehicle's application. The table below shows the setting
to select card application type depending on which control
card is used.
EV100Standard Speed
Functionwith FW LimitRegen/FW
STD C/L0 to 420 to 2440 to 44
High C/L5 to 925 to 2945 to 49
STD C/L
(Auto plug)10 to 1430 to 3450 to 54
High C/L
Pick up on directional switch closure and drop out time
delay on directional switch opening.
Range.5 to 63 seconds
Setting129 to 255
Resolution.5 seconds per set unit
Example:Setting of 149 = 10.5 seconds
Drop out will be 1.5 seconds after the seat switch opens.
71
Page 72
DESCRIPTION OF FUNCTION NUMBERS FOR:
Control CardsIC3645EVLXCD1MT AND
IC3645EVLXCD1MX
FUNCTION 1STORED FAULT CODE
( Push 1)
This function register contains the last fault that shut down
vehicle operation ( PMT type fault that is reset by cycling the
key switch ) . This fault code will be over written each time
a new fault occurs and can be cleared from memory by
adjusting the value to zero.
FUNCTION 2CREEP SPEED
( Push 2 )
Example:0 = min. current, 255 = max. current
FUNCTION 5PLUGGING DISTANCE (CURRENT)
( Push 5 )
This function allows for the adjustment of the plugging
distance of the vehicle. The larger the current setting, the
shorter the stopping distance.
Range200 to 1000 amps (EV100)
300 to 1500 amps (EV200)
Set0 to 255
Resolution3.14 amps per set unit (EV100)
4.7 amps per set unit (EV200)
Example:Setting of 20 = 263 amps (EV100)
This function allows for the adjustment of the creep speed of
the vehicle. A constant creep speed frequency will be maintained when an accelerator input voltage between 3.7 and 3.5
volts or an accelerator ohmic input between 6K and 4.7K
ohms is provided.
Range2% to 15% on time
Set0 to 255
Resolution.03% per set unit
Example:Setting of 20 = 2.6% on time
FUNCTION 3CONTROLLED ACCELERATION
AND 1A TIME
( Push 3 )
This function allows for the adjustment of the rate of time it
takes for the control to accelerate to 96% applied battery
voltage to the motor on hard acceleration. The 1A contactor
will automatically close .2 seconds after the controlled
acceleration stops and the accelerator input is less than .5
volts or less than 50 ohms.
Range.1 to 22.0 seconds
Set0 to 255
Resolution.084 seconds per set unit
Example:Setting of 20 = 1.8 seconds C/A
and 2.0 1A time.
FUNCTION 4CURRENT LIMIT
( Push 4 )
This function allows for the adjustment of the current limit
of the control. The rating of the control will determine the
range of adjustment for this function. Please refer to the
operating instructions for the control used in your vehicle.
RangeSee control C/L curves
Set0 to 255
Warning: Plug settings must be in accordance with
control operating instructions. An excessively high setting could cause damage to control system or traction
motor.
FUNCTION 61A DROP OUT CURRENT
( Push 6 )
This function allows for the adjustment of the 1A contactor
drop out current. The 1A contactor will be dropped out and
the vehicle motor torque will be limited to SCR current limit
when the set drop out current is reached.
Range450 to 1260 amps (EV100)
675 to 1890 amps (EV200)
Set0 to 250
Resolution3.24 amps per set unit (EV100)
4.86 amps per set unit (EV200)
Settings above 250 set units will disable 1A drop out function
( 1A will not drop out).
ExampleSetting of 20 = 515 amps (EV100)
FUNCTION 7PA4 INPUT SWITCH FUNCTION
SELECTION
(PUSH 7)
This function allows for the selection of PA4 input function.
The PA4 input can be adjusted to operate in either of the
following modes:
1) To activate a speed limit if a normally closed switch
is opened between PA4 and negative.
2) To reverse the direction of the in-board motor and
activate a speed limit if a normally open switch is
closed between PA4 and negative.
Set 128 or greater to select option 1 above.
72
Set 0-127 to select option 2 above.
Page 73
FUNCTION 11 SPEED LIMIT 1 (PA5 OR PA6)
( Push 11 )
This function allows for the adjustment of the speed limit (
maximum battery volts to the motor ) when the L1 or R1
limit switch input signal is received by the control card. L1
or R1 limit switch is a normally open switch connected to
battery negative, the switch closing enables speed limit.
Range96% to 0% battery volts
Set0 to 180
Setting of 0 set units will disable speed limit function and
allow top speed with no limit switch connected.
FUNCTION 12 SPEED LIMIT 2 (PA4)
( Push 12 )
Same as Function 11 except using L2 or R2 limit switch for
input. See function 7 for switch operation.
This function allows for the adjustment of voltage range for
controls equipped with the Battery Discharge Indication
function. In order for the BDI to operate properly, the setting
as shown in the table must be entered .
FUNCTION 13 SPEED LIMIT 3
( Push 13 )
This speed limit is activated by the Truck Management
Module fault codes 90 and 93. See instructions for
IC3645TMM1A Truck Management Module for details.
FUNCTION 14 INTERNAL RESISTANCE
COMPENSATION
( Push 14 )
This function is used when the Battery Discharge Indicator
is present. Adjustment of this function will improve the
accuracy of the BDI. In order to made this setting the voltage
drop of the battery under load must first be determined by
following the steps listed below.
1. Load the traction motor to 100 amps in 1A and
record the voltage (VO) at the SCR positive and
negative power terminal.
2. Load the traction motor to 200 amps in 1A and
record the voltage (VL) at the SCR positive and
negative power terminal.
3. Calculate voltage drop (VD) as follows:
VD = VO - VL
4. Use the table below to determine the setting using
the calculated VD as a reference.
Battery voltsSet units
24 voltsBetween 0 and 31
36 voltsBetween 32 and 44
48 voltsBetween 45 and 69
72 voltsBetween 70 and 80
80 voltsBetween 81 and 183
36/48 voltsBetween 184 and 250
No BDIBetween 251 and 255
The following functions have function numbers larger
than the numbers on the Handset keyboard. To access
these functions, push the CONT key and the number shown
in the following instructions at the same time.
FUNCTION 16 PEDAL POSITION PLUG
( Push CONT and 1 )
This function will allow the adjustment of the pedal position
plug range. Pedal position will reduce the plugging current
to the current value set by this function as the accelerator is
returned to the creep speed position. Maximum plug current
is obtained with the accelerator in the top speed position.
Range100 to 930 amps (EV100)
150 to 1425 amps (EV200)
Set0 to 255
Resolution3.2 amps per set unit (EV100)
5.0 amps per set unit (EV200)
ExampleSetting of 20 = 164 amps
To disable the pedal position plug function, adjust the
current value to the same current value as the plug distance
current.
73
Page 74
Example: If plug distance current Function 5 is set at 500
amps, then set pedal plug current at 500 amps. With this
setting pedal position will have no effect on plugging
distance.
Resolution.5 seconds per set unit
Example:Setting of 20 = 10.5 seconds
Pick up on directional switch closure and drop out time
delay on directional switch opening.
FUNCTION 17 CARD TYPE SELECTION
( Push CONT and 2 )
This function allows for the selection of the card type used for
your vehicle's application. The table below shows the setting
to select card application type depending on which control
card is used.
EV100Standard
Functionwith FW
STD C/L0 to 4
High C/L5 to 9
STD C/L
(Auto plug)10 to 14
High C/L
(Auto plug)15 to 19
EV200Standard
Functionwith FW
STD C/L20 to 24
STD C/L
(Auto plug)30 to 34
Range.5 to 63 seconds
Setting129 to 255
Resolution.5 seconds per set unit
Example:Setting of 149 = 10.5 seconds
Drop out will be 1.5 seconds after the seat switch opens.
Settings for these function should be made in between the
values shown.
Warning: These settings must be changed by authorized
personnel only, following instructions supplied by the
manufacturer. Card type selection must be made within
the capabilities of the SCR control panel used and the
supporting electro-mechanical devices. Failure to comply with proper application standards could result in
misoperation or damage to the control and/or motors.
FUNCTION 18 STEER PUMP TIME DELAY
( Push CONT and 3 )
This function allows for the selection of steer pump contactor
pick up input, either seat switch or directional switch closing
and adjustment of the time delay for the contactor drop out.
Pick up on seat switch closure and time delay drop out on
seat switch opening.
Range1.5 to 65 seconds
SettingBetween 0 and 128
74
Page 75
DESCRIPTION OF FUNCTION NUMBERS FOR:
Control CardIC3645EVLXCD1PX
FUNCTION 11 SPEED LIMIT 1 (SL1)
( Push 11 )
FUNCTION 1STORED FAULT CODE
( Push 1)
This function register contains the last status code that shut
down vehicle operation ( PMT type fault that is reset by
cycling the key switch ) . This status code will be over written
each time a new fault occurs and can be cleared from memory
by adjusting the value to zero.
FUNCTION 2INTERNAL RESISTANCE
COMPENSATION START
( Push 2 )
This function allows for the adjustment of the current level
at which the internal resistance compensation feature (Function 16) will take effect.
Range0 to 1325 amps
Set52 to 255
Resolution6.5 amps per set unit
Example:Setting of 72 = 130 amps
FUNCTION 3CONTROLLED ACCELERATION
AND 1A TIME
( Push 3 )
This function allows for the adjustment of the speed limit (
maximum battery volts to the motor ) when the SL1 limit
switch input signal is received by the control card. SL1 limit
switch is a normally open switch connected to battery
negative, the switch closing enables speed limit.
Range0% to 100% battery volts
Set0 to 255
Resolution.375 volts per set unit
ExampleSetting of 50=18.75 volts
FUNCTION 12 SPEED LIMIT 2 (SL2)
( Push 12 )
Same as Function 11 except using SL2 limit switch for input.
FUNCTION 13 SPEED LIMIT 3 (SL3)
( Push 13 )
Same as Function 11 except using SL3 limit switch for input.
FUNCTION 14 SPEED LIMIT 4 (SL4)
( Push 14 )
Same as Function 11 except using SL4 limit switch for input.
This function allows for the adjustment of the rate of time it
takes for the control to accelerate to 96% applied battery
voltage to the motor on hard acceleration. The 1A contactor
will automatically close .2 seconds after the controlled
acceleration stops and the accelerator input is less than .5
volts or less than 50 ohms.
Range.1 to 5.5 seconds
Set0 to 255
Resolution.021 seconds per set unit
Example:Setting of 20 = .52 seconds C/A
and .72 seconds 1A time.
FUNCTION 4CURRENT LIMIT
( Push 4 )
This function allows for the adjustment of the current limit
of the control. The rating of the control will determine the
range of adjustment for this function. Please refer to the
operating instructions for the control used in your vehicle.
RangeSee control C/L curves
Set0 to 255
Example:0 = min. current, 255 = max. current
The following functions have function numbers larger
than the numbers on the handset keyboard. To access these
functions, push the CONT key and the number shown in
the following instructions at the same time.
FUNCTION 16 SPEED / TORQUE
COMPENSATION
( Push CONT and 1 )
This function is used to stabilize pump speed at heavy loads.
This function is set using information obtained from the
speed torque curve of the motor used. See OEM service
manual for your vehicle for this setting.
This function allows for the selection of the card type used for
your vehicles application. The table below shows the setting
to select card application type depending on which control
card is used.
With PumpWithout Pump
FunctionCtr/PMTCtr/PMT
STD C/L0 to 836 to 44
High C/L9 to 17 45 to 53
STD C/L
BDI (Lockout)18 to 2654 to 62
High C/L
BDI (Lockout)27 to 3563 to 71
BDI Lockout means that the BDI signal from the traction
control must be present in order for the pump control to
operate. This control will stop operation when the battery
state of charge reaches 10%.
Settings for these functions should be made in between the
values shown.
Warning: These setting must be changed by authorized
personnel only, following instructions supplied by the
manufacturer. Card type selection must be made within
the capabilities of the SCR control panel used and the
supporting electro-mechanical devices. Failure to comply with proper application standards could result in
misoperation or damage to the control and/or motors.
76
Page 77
g GE Industrial Systems
EV200LX SUPPLEMENT
General:
The EV100LX instructions and operating information is applicable to the EV200LX. The only
difference in the two control types is that the EV200 has a high current rating than the EV100LX,
a larger mounting foot print and different component parts.