General Eastern General Eastern HUMI-DP-XR-D-N Manual

GE HumiTrac™ XR Transmitter Series
FR
ABS
2.37 (60.3)
2.37
(60.3)
3.30
(83.8)
3.79 (96.2)
4.69
(119.1)
**
Notes:
1.
Dimens
ions are in inches (millimeters).
2.
*To open the enclosure, squeeze the base
where indicated, and remove the cover.
1.50 (38.1)
1.75
(44.5)
3.79 (96.2)
4.69
(119.1)
*
Ø.188 (4.76)
mounting hole, 4 pl.
Ø.50
(12.7)
Notes:
1. Dimensions are in inches (millimeters).
2. Ensure the Duct Probe doesn't make any contact with the metal housing.
3.
*To open the enclosure, squeeze the base
where indicated, and remove the cover.
Sensing & Inspection Technologies Installation Guide
Warranty
GE Sensing & Inspection Technologies warrants equipment of its manufacture to the original buyer against defective materials or workmanship, for a period of one year for the sensor tip and two years for the rest of the product, from the date of shipment. The sensor element and calibration are not covered by this warranty.
Calibration
All GE Sensing & Inspection Technologies RH/Dewpoint and Temperature Products are fully tested and calibrated in accordance with the National Institute of Standards and Technology (NIST) prior to shipment. This is the highest quality calibration standard available.
Power Requirements
12–30 VDC power supply (furnished by the customer).
Specifications
Environmental Conditions
Operating Range: –40°F to 140°F (–40°C to 60°C)
0-99% RH non-condensing.
Storage Temperature: –67°F to +185°F (–55°C to +85°C)
Accuracy
Dew Point ±1.8°F (±1°C)
Enthalpy ±2 BTU/lb (±4.7 kJ/kg)
Wet Bulb ±3°F (±1.7°C)
Dry Bulb ±0.5°C (±0.9°F)
Certification
CE Marked
Complies with EMC Directive 89/336/EEC and LVD 73/23/EEC.
IP 42 rating for Duct Mount and Outside Air Transmitters.
Contact Information
99 Washington Street Melrose, MA 02176
Phone 781-665-1400 Toll Free 1-800-517-8431
Visit us at www.TestEquipmentDepot.com
Installation
For your convenience, the transmitters can be mounted using the base as a mounting template (see Figure 1 or 2).
Wall Mount
Locate the transmitter where it will be exposed to an unrestricted air circulation that is representative of the average humidity and/or temperature of the controlled space. Avoid locations where excessive moisture, corrosive fumes, vibration, or high ambient temperatures are present.
The wall mount transmitter is designed to install onto a standard electric switch box. Mount the transmitter on an indoor wall approximately 4 to 6 feet above the floor. The base assembly should be positioned with the letters FR/ABS located on the left side.
Duct Mount
The transmitter should be mounted away from fans, corners, heating and cooling coils, and other equipment that will affect the measurement of relative humidity. It should be mounted in a location that receives adequate air flow for proper operation.
The duct mount transmitter should be mounted so that the sensor probe is in the center of the duct.
Outside Air Mount
The transmitter should be mounted in a sheltered area that is protected from rain. Ideally , the transmitter should be located on the north side of the building (under an eave) to prevent sun-heated air from rising up the building's wall and affecting the relative humidity of the sensor.
The outside air mount transmitter should be mounted with the sensor pointing down to prevent water collection in the sensor cavity.
Sensing Element: Capacitive Sensor
Long Term Stability: Less than 1% drift per year, typical.
Temperature Effect:** Delta %RH =
(0.0014 x %RH + 0.1325) x T°C – (0.0317 x %RH + 3.0876)
**Not needed for Signal-Conditioned Temperature units.
Signal Outputs: 4-20 mA, 0-5V or 0-10V (user selectable)
Space (Wall Mount) Range
Dew Point 40° to 90°F (4.4 to 32.2°C)
Enthalpy 0-50 BTU/lb (0-116.3 kJ/kg)
Wet Bulb 40° to 90°F (4.4 to 32.2°C)
Dry Bulb 40° to 90°F (4.4 to 32.2°C)
Duct/Outside Air Mount Range
Dew Point -20° to 120°F (-28.8° to 49°C)
Enthalpy 0-50 BTU/lb (0-116.3 kJ/kg)
Wet Bulb 0° to 100°F (-17.8° to 37.8°C)
Dry Bulb -20° to 120°F (-28.8° to 49°C)
Figure 1: Wall Mount - Mounting Dimensions
Figure 2: Duct / Outside Air - Mounting Dimensions
A40254250,Rev. A (August 2009)
Page 1 of 2
GE HumiTrac™ XR Transmitter Series
J7
10V
SW2
5V
J8
Voltage
Current
SW3
SW1
VI
VI
JPR1
3K
10K
SW3
SW1
VI
VI
XR 0-5/0-10Vout
Switch Selectable 0-5 Volt or 0-10 Volt Output
I1XR/P+
I2XR/P–
V-XR
GND
V-TMP
J7
10V
SW2
5V
–GND, 0-5/0-10Vout +V
J8
TH
TH
I2-TMP
I2XR/P–
I1XR/P+
Thermistor Output*
Voltage
*To provide a connector for Thermistor
Output, divide the 5-pin terminal block into
a 3-pin and a 2-pin terminal block as shown.
XR REPRESENTS
Dew Point - DP Enthalpy - EN Wet Bulb - WB
Switch Selectable 0-5 Volt or 0-10 Volt Output
I1XR/P+
I2XR/P–
V-XR
GND
V-TMP
J7
10V
SW2
5V
+V
Voltage
–V
XR
GND
Temp
XR REPRESENTS
Dew Point - DP Enthalpy - EN Wet Bulb - WB
SW3
SW1
VI
VI
J8
TH
TH
I2-TMP
I2XR/P–
I1XR/P+
Current*
Vin
XR (4-20mA) out
Thermistor Output
*Shipped in 4-20mA output.
XR REPRESENTS
Dew Point - DP Enthalpy - EN Wet Bulb - WB
J8
TH
TH
I2-TMP
I2XR/P–
I1XR/P+
Current*
Vin
XR RTN
Temp RTN
*Shipped in 4-20mA output.
XR REPRESENTS
Dew Point - DP Enthalpy - EN Wet Bulb - WB
Hold the sides of
the sensor tip
the sintered filter.
near the base of
Caution: Remove power before replacing the sensor.
Sensing & Inspection Technologies Installation Guide
Wiring
Match your transmitter with the corresponding diagrams (Figure 4 through Figure 9), set the switches and wire accordingly. (See Figure 3 below for switch and terminal block locations.) Ensure that all the installation and wiring is in compliance with all national and local codes.
Note: All Voltage Outputs are measured with respect to the
POWER SUPPLY / CONTROLLER GROUND.
Wiring for the transmitter should be a shielded, twisted pair, 16-22 AWG. Use only copper conductors. Do not run transmitter wires and AC power wires together in the same conduit or wire bundle.
Caution!
Running transmitter wires and AC power wires,
including earth ground, in the same conduit or
wire bundle may cause malfunction due to
electrical noise.
Figure 4: Switch Positions for Voltage Mode
Figure 5: DP/EN/WB and Temp. (Direct Connection) -
Voltage
Wiring (cont.)
CE COMPLIANCE
1. Ensure that the probe earth ground wire (for Duct and
Outside Air units only), the shield wire and the PCB earth ground wire are connected to the mounting screw or the NEAREST (<1.5m) earth ground.
2. The other end of the shield wire MUST be connected to
the power supply /controller earth ground ONLY.
Figure 8: DP/EN/WB and Temp. (Direct Connection) -
Current
Figure 3: Connector/Switch Locations - Inside Cover
Figure 6: DP/EN/WB and Temp. (Signal Condition) -
Voltage
Figure 7: Switch Positions for Current Mode
Figure 9: DP/EN/WB and Temp. (Signal Condition) -
Current
Figure 10: Remove/Install the Sensor Tip
Table 1: HumiTrac XR Ordering Information
Model Product Information
Space (Wall)
Mount
Duct Mount
Air Mount
HUMI-DP-XR-S DEW POINT TRANSMITTER-SPACE MOUNT
HUMI-EN-XR-S ENTHALPY TRANSMITTER-SPACE MOUNT
HUMI-WB-XR-S WET BULB TRANSMIT TER-SPACE MOUNT
HUMI-DP-XR-D DEW POINT TRANSMITTER-DUCT MOUNT
HUMI-EN-XR-D ENTHALPY TRANSMITTER-DUCT MOUNT
HUMI-WB-XR-D WET BULB TRANSMITTER-DUCT MOUNT
HUMI-DP-XR-O DEW POINT TRANSMITTER-OPEN AIR
HUMI-EN-XR-O ENTHALPY TRANSMITTER-OPEN AIR
HUMI-WB-XR-O WET BULB TRANSMITTER-OPEN AIR
A40254250,Rev. A (August 2009)
P a g e 2 o f 2
Loading...