General Eastern Dew-10 Specifications

Page 1
Features
• Primary dew point measurement
• High accuracy
• Wide operating range
• No drift
• No hysteresis
• Direct dew point and temperature signals
GE
Dew-10
Dew-10 is a General Eastern product. General Eastern has joined other GE high-technology sensing businesses under a new name—GE Industrial, Sensing.
g
General Eastern Chilled Mirror Dew Point Transmitter
Applications
• Precision HVAC/BAS
• Clean rooms
• Museums
• Film storage
• Pharmaceutical
Page 2
Primary Dew Point Measurement with 4 to 20 mA or PRTD Output
The Dew-10 series is a family of cost effective chilled mirror dew point transmitters comprising of wall, duct and pipe mounted models. These instruments provide accurate and reliable dew point measurements over a wide range for building automation, mission critical environments and clean industrial applications.
Dew-10s provide accuracy of ±1ºF (±0.5ºC) over a range of
-40ºF to 136ºF (-40ºC to 58ºC) dew point. The range is dependent on the ambient temperature. At 77°F (25°C) the units provide approximately 72°F (40°C) depression. The wall mount version is also available with an air temperature measurement capability over the same range.
The Dew-10 measures dew point by utilizing a solid state heat pump to cool a metallic mirror. When the mirror temperature reaches the dew point of the surrounding air, a thin dew layer condenses on the mirror surface. The condensation is optically detected. A feedback loop keeps
the mirror at the exact dew point by continuously controlling the mirror temperature. A precision PRTD (Platinum Resistance Temperature Detector) is embedded just beneath the surface of the mirror, allowing the dew point temperature to be precisely measured.
Maintenance is straight-forward. Filter replacement and cleaning the mirror with a cotton swab restores the transmitter to its original condition. Since the wetted components are inert and the RTD is hermetically sealed, Dew-10s provides many years of drift-free measurement.
Each transmitter is calibrated to National Institute of Standards and Technology (NIST) traceable reference standards. A certificate of conformance with functional test data is supplied. Our manufacturing and quality system certified to ISO-9001 standards and Six-Sigma methodology is applied.
Contact our applications engineers to discuss your precision humidity measurement requirements.
GE
Page 3
Dew-10 Specifications
Wall Mounted Unit
Accuracy
±1.0ºF (±0.5ºC)
Repeatability
±0.1ºF (±0.05ºC)
Hysteresis
None
Dew Point Output
Platinum RTD, four-wire, 100 at 32ºF (0ºC) or 4 to 20 mA signal
Temperature Output
Platinum RTD, four-wire, 100 at 32ºF (0ºC) or 4 to 20 mA signal
Power Supply
24 VDC, 24 VAC, 115 VAC, 230 VAC, 10 watts maximum
Dew Point Range
-10ºF to 136ºF (-24ºC to 58ºC)
Operating Temperature
32ºF to 140ºF (0ºC to 60ºC)
Pressure
One atmosphere nominal
Weight
5.0 lb (2.5 kg)
Pipe/Duct Mounted Unit
Accuracy
±1.0ºF (±0.5ºC)
Repeatability
±0.1ºF (±0.05ºC)
Dew-10 dimensions
GE
4.75 in (120.65 mm)
Sample air outlet port
(1 in (25.4 mm) minimum
clearance required)
6.55 in
(166.37 mm)
2.6 in
(66.04 mm)
maximum
0.4 in (10.16 mm) minimum
Sample air intake port
Air thermometer and
shield (optional)
Plastic cover (fire retardant abs)
Ø 1 in
(25.4 mm)
1 in (25.4 mm)
high dimple on “B” holes
Metal base
4.1 in (104.14 mm) maximum
Ø 2.7 in (8.58 mm)
maximum
3.37 in
(88.8 mm)
typical
0.35 in
(8.8 mm)
typical
0.19 in
(4.83 mm)
typical
8.25 in
(109.55 mm)
maximum
4.25 in (107.05 mm) maximum
1 in (24.5 mm)
maximum
1 in (24.5 mm)
maximum
8 in (152.4 mm)
maximum
1 in (25.4 mm)
compression fittings
1 in NPT
2.5 in (89.5 mm) minimum 4 in (101.6 mm) maximum
Pipe Mount Sensor
Duct Mount Sensor
Sensor
Sponge
gasket
Duct
mounting
plate
3.4 in
(96.36 mm)
Page 4
g
©2006 GE. All rights reserved. 920-294A
All specifications are subject to change for product improvement without notice. GE® is a registered trademark of General Electric Co. Other company or product names mentioned in this document may be trademarks or registered trademarks of their respective companies, which are not affiliated with GE.
www.gesensing.com
GE
Dew-10 Specifications
Ordering Information
The code number to be ordered may be specified as follows: Dew-10
Code Power
0 24 VDC (standard) 1 24 VAC 2 115 VAC 3 230 VAC
Code Output Signal
A RPT direct; 100 W, 32°F (0°C) B 4 to 20 mA (15 VDC) 0°F to 100°F (-17°C to 37°C) C 4 to 20 mA (15 VDC) 32°F to 122°F (0°C to 50°C) D 4 to 20 mA (15 VDC) 40°F to 140°F (4°C to 60°C) X 4 to 20 mA (15 VDC) user specified
Code Mounting
0 Wall 0 Wall with temperature 1 Duct 2 Pipe
Dew-10 - ____ - ____ - ____ Typical model number
For wall mounted unit with temperature, select two output signals. Example: Dew-1-OCC0 is a wall mounted unit with 24 VDC power supply, dual 4 to 20 mA signals (dew point and temperature) scaled for 32°F to 122°F (0°C to 50°C).
Hysteresis
None
Output
Platinum RTD, four-wire, 100 at 32°F (0ºC) or 4 to 20 mA signal
Power Supply
24 VDC, 24 VAC, 115 VAC, 230 VAC 10 watts maximum
Dew Point Range
-40°F to 155ºF (-40°C to 68ºC)
Pressure
10 ft (3 m) water column
Duct Air Velocity
500 to 3,000 ft/min (50 to 900 m/min)
Operating Temperature
• Electronics: 32°F to 122ºF (0°C to 50ºC)
• Probe: -40°F to 155ºF (-40°C to 68ºC)
Weight
5.0 lb (2.5 kg)
Loading...