General Climate GC-S24HR, CU-S24HR, GC-S30HR, CU-S30HR, GC-S36HR user guide manual

...
Service manual Room Air Conditioner
Split Wall-Mounted Type
www.generalclimate.com Wall-Mounted Split Type
Content
1. Precaution 1
1.1 Safety Precaution 1
1.2 Warning 1
2. Function 3
3. Dimension 5
3.1 Indoor unit 5
3.2 Outdoor unit 6
4. Specification 7
5. Refrigerant cycle diagram 8
6. Operation limits 9
6.1 Cooling operation 9
6.2 Heating operation 9
7. Schematic diagram and Wiring diagram 9
7.1 Schematic diagram 10
7.2 Wiring diagram 11
8. Installation details 13
8.1 Wrench torque sheet for installation 13
8.2 Connecting the cables 13
8.3 Pipe length and the elevation 13
8.4 Air purging of the piping and indoor unit 14
8.5 Pumping down (Re-installation) 15
8.6 Re-air purging (Re-installation) 16
8.7 Balance refrigerant of the 2-way, 3-way valves 17
8.8 Evacuation 18
8.9 Gas charging 19
9. Capacity table 20
9.1 GC/GU-S24HR 20
9.2 GC/GU-S30HR 21
9.3 GC/GU-S36HR 22
10. Electronic function 23
10.1 Electronic control working environment 23
10.2 Proper symbols and their meaning 23
10.3 Function 24
10.4 Protection 24
10.5 Fan only mode 24
10.6 Cooling mode 24
10.7 Dehumidifying mode 25
10.8 Heating mode 25
10.9 Defrosting mode(available for heating mode) 27
10.10 Auto mode 28
10.11 Force cooling function 28
10.12 Sleep mode 28
www.generalclimate.com Wall-Mounted Split Type
10.13 Auto restart function 29
11. Model and Parameters 30
12. Troubleshooting 31
12.1 Display board 31
12.2 Troubleshooting 32
12.3 Diagnostic chart 33
12.4 Resetting phenomenon often occurs during operation. 34
12.5 Operation lamp flashes and Timer lamp off. 34
12.6 Operation lamp flashes and Timer lamp on. 34
12.7 Operation lamp off and Timer lamp flashes 35
12.8 Operation lamp on and Timer lamp flashes 35
12.9 Operation lamp flashes, Timer lamp flashes . 35
13. Characteristic of temperature sensor 36
www.generalclimate.com Wall-Mounted Split Type
1. Precaution
1.1 Safety Precaution
n To prevent injury to the user or other people and property damage, the following instructions must be followed. n Incorrect operation due to ignoring instruction will cause harm or damage. n Before service unit, be sure to read this service manual at first.
1.2 Warning
Ø Installation
n Do not use a defective or underrated circuit breaker.
Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
n For electrical work, contact the dealer, seller, a
qualified electrician, or an Authorized service center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
n Always ground the product.
There is risk of fire or electric shock.
n Install the panel and the cover of control box
securely.
There is risk of fire of electric shock.
n Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or electric shock.
n Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
n Do not modify or extend the power cable.
There is risk of fire or electric shock.
n Do not install, remove, or reinstall the unit by
yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
n Be caution when unpacking and installing the
product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and evaporator.
n For installation, always contact the dealer or an
Authorized service center.
There is risk of fire, electric shock, explosion, or injury.
n Do not install the product on a defective installation
stand.
It may cause injury, accident, or damage to the product.
n Be sure the installation area does not deteriorate
with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
n Do not let the air conditioner run for a long time
when the humidity is very high and a door or windows is left open.
Moisture may condense and wet or damage furniture.
n Take care to ensure that power cable could not be
pulled out or damaged during operation.
There is risk of fire or electric shock.
n Do not place anything on the power cable.
There is risk of fire or electric shock.
n Do not plug or unplug the power supply plug during
operation.
There is risk of fire or electric shock.
n Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
n Do not place a heater or other appliance near the
power cable.
There is risk of fire and electric shock.
n Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric shock.
n Do not store or use flammable gas or combustible
near the product.
There is risk of fire or failure of product.
n Do not use the product in a tightly closed space for a
long time.
Oxygen deficiency could occur.
n When flammable gas leaks, turn off the gas and
open a window for ventilation before turn the product on.
Do not use the telephone or turn switches on or off. There is risk of explosion or fire.
n If strange sounds, or small or smoke comes from
product. Turn the breaker off or disconnect the power supply cable.
There is risk of electric shock or fire.
n Stop operation and close the window in storm or
hurricane. If possible, remove the product from the window before the hurricane arrives.
www.generalclimate.com 1 Wall-Mounted Split Type
There is risk of property damage, failure of product, or electric shock.
n Do not open the inlet grill of the product during
operation. (Do not touch the electrostatic filter, if the unit is so equipped.)
There is risk of physical injury, electric shock, or product failure.
n When the product is soaked (flooded or submerged),
contact an Authorized service center.
There is risk of fire or electric shock.
n Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
n Ventilate the product from time to time when
operating it together with a stove, etc.
There is risk of fire or electric shock.
n Turn the main power off when cleaning or
maintaining the product.
There is risk of electric shock.
n When the product is not be used for a long time,
disconnect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or unintended operation.
n Take care to ensure that nobody could step on or fall
onto the outdoor unit.
This could result in personal injury and product damage.
Ø CAUTION
n Always check for gas (refrigerant) leakage after
installation or repair of product.
Low refrigerant levels may cause failure of product.
n Install the drain hose to ensure that water is drained
away properly.
A bad connection may cause water leakage.
n Keep level even when installing the product.
To avoid vibration of water leakage.
n Do not install the product where the noise or hot air
from the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
n Use two or more people to lift and transport the
product.
Avoid personal injury.
n Do not install the product where it will be exposed to
sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
www.generalclimate.com 2 Wall-Mounted Split Type
Ø Operational
n Do not expose the skin directly to cool air for long
periods of time. (Do not sit in the draft).
This could harm to your health.
n Do not use the product for special purposes, such
as preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
n Do not block the inlet or outlet of air flow.
It may cause product failure.
n Use a soft cloth to clean. Do not use harsh
detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
n Do not touch the metal parts of the product when
removing the air filter. They are very sharp.
There is risk of personal injury.
n Do not step on pr put anything on the product.
(outdoor units)
There is risk of personal injury and failure of product.
n Always insert the filter securely. Clean the filter
every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
n Do not insert hands or other object through air inlet
or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
n Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
n Use a firm stool or ladder when cleaning or
maintaining the product.
Be careful and avoid personal injury.
n Replace the all batteries in the remote control with
new ones of the same type. Do not mix old and mew batteries or different types of batteries.
There is risk of fire or explosion.
n Do not recharge or disassemble the batteries. Do not
dispose of batteries in a fire.
They may burn of explode.
n If the liquid from the batteries gets onto your skin or
clothes, wash it well with clean water. Do not use the remote of the batteries have leaked.
The chemical in batteries could cause burns or other health hazards.
2. Function
T
he function will be
Room temp
erature sensor.
Maintain the room temperature in accordance with the setting temperature.
Indoor fan is delayed for 5 sec at the starting.
Restarting is for approx.
3
minutes..
High
, med, low, breeze.
Light up in the LED (LCD) for each operation mode.
The unit will decide the louver direction according to operation mode.
The fan is turn to low speed
(cooling/heating).
The function is usually used in rainy days in
The louver can be
set at the desired position or swing up and
The unit can be change by the room temperature.
P
revent the cold wind at
Indoor unit
Operation ON/OFF by remote controller
Sensing by room temperature
Pipe temperature sensor.
Room temperature control
Starting temperature control
Time Delay Safety control
Indoor fan speed control
Operation indication Lamps (LED)
Two-direction air vane
Sleep mode auto control
The unit will be turn off after seven hours.
Independent dehumidification
springtime or damp areas.
Self-diag. function
operate in any operation
Air flow Direction control
down automatically
Anti-cold function
the beginning of unit start.
Temp. Compensation
Defrost mode
Auto-restart function
Flexible wiring connection
Easy clean panel
Auto mode
www.generalclimate.com 3 Wall-Mounted Split Type
T
he unit can operate in cooling mode at low
ambient
temperature conditions.
The unit has
3 mins delay between
continuously
ON/OFF
operations
.
Outdoor unit
B
ird tail propeller fan makes the outdoor unit run more quietly.
T
he hydrophilic fin can improve the heating efficiency at operation mode.
I
t is only operated in t
he heating operation mode except defrosting
operation
.
Made from electrolytic zinc steel shee
t and anti
-
rust coated components.
I
t protects the valves and prevents water from dripping.
Power relay control
Low ambient kit
Low noise air flow system
Hydrophilic aluminum fin
4 way valve control
Discharge pipe temperature protect
Anti-rust cabinet
Valve protection cover
www.generalclimate.com 4 Wall-Mounted Split Type
3. Dimension
3.1 Indoor unit
Dimension Mode
24K1080330222 30K1080330222 36K1250325230
WHL
www.generalclimate.com 5 Wall-Mounted Split Type
560
360
735
560
360
735
560
360
735
3.2 Outdoor unit
Dimension Mode
WHDL1L2L3
24K845695335 30K845695335 36K895860302
www.generalclimate.com 6 Wall-Mounted Split Type
μ
m3/h
Ф
Ф
Φ
m
4. Specification
Model
Power supply
Capacity Btu/h
Cooling
Input W Rated current A EER Btu/w.h Capacity Btu/h
Heating
Input W Rated current A
COP W/W Max. current Starting current
Model
Type
Brand
Capacity Btu/h Compressor
Input W
Rated current(RLA) A
Locked rotor Amp(LRA) A
Thermal protector
Capacitor uF
Refrigerant oil ml
Model Indoor
fan motor
Brand
Input W
Capacitor uF
Speed(hi/mi/lo) r/min Indoor air flow (Hi/Mi/Lo) Indoor noise level (Hi/Mi/Lo)
Model Outdoor
fan motor
Brand
Input W
Capacitor uF
Speed r/min Outdoor air flow Outdoor noise level Refrigerant type R410A Design pressure
Refrigerant piping
Liquid side/ Gas side mm
Max. refrigerant pipe length m
Max. difference in level m Operation temp Ambient temp
Application area
Ph-V-Hz
A A
m3/h
dB(A)
dB(A)
g
MPa
℃ ℃
2
GC/GU-S24HRGC/GU-S30HRGC/GU-S36HR
1, 220-240V~,50Hz1, 220-240V~,50Hz
2400028000
27503200
12,515
8.7, 2.68,8 2700030000
27503100
12,514,5
2,99,79,3
162032 5076150
QP407PT24CZR34KH-PFJ-522
RotaryScroll
LGCopeland
2340028800
23172520
10,112,1
5476
InternalInternal15HM1637
4550
65012421240
YDK36-4GYDK36-4GYDK50-4E
WellingWellingWelling
65/63/6068/65/62
2μF/450V3 1050/950/8501150/1050/9501260/1150/990 1050/950/8501150/1050/9501350/1200/1050
43/40/3747/44/41
YDK53-6KYDK53-6KYDK100-6
WellingWellingWelling
130140169
3,53,55
800800900
250025003000
56
R22/1900R22/24502450
2,62,62,6
9.53/Ф16.0 202025 101010
17-3017-3017-30
-7 - 45-7 - 45-7 - 45 40~5650~6860~78
F/450V3
58
9.53/Ф16.0
1, 220-240V~, 50Hz
35000
4120
18,6
8,5
38000
4100
18,5
ZR47K3-PFJ-522
SCROLL
COPELAND
39000
3510
19,3
114
60uF/≥400VAC
85/80/77
49/46/42
59
9.52/Φ16
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally somewhat different as a result of ambient condition. The above design and specifications are subject to change without prior notice for product improvement.
www.generalclimate.com 7 Wall-Mounted Split Type
5. Refrigerant cycle diagram
Ø Cooling only
Ø Heat pump mode
www.generalclimate.com 8 Wall-Mounted Split Type
6. Operation limits
6.1 Cooling operation
Outdoor unit air temp. DB
Indoor air temp. DB Note: The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage.
6.2 Heating operation
Indoor air temp. DB
Outdoor unit air temp. DB Note: The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage.
7. Schematic diagram and Wiring diagram
www.generalclimate.com 9 Wall-Mounted Split Type
7.1 Schematic diagram
www.generalclimate.com 10 Wall-Mounted Split Type
7.2 Wiring diagram
7.2.1 Heating mode
GC/GU-S24HR, GC/GU-S30HR
A2
A1
www.generalclimate.com 11 Wall-Mounted Split Type
GC/GU-S36HR
A1A2
www.generalclimate.com 12 Wall-Mounted Split Type
length
Btu/h
GAS
LIQUID
B (m)A
(m)
(g/m)
24K
5/8’’ (φ15.88)
3/8’’ (φ9.52)
51020655/8’’ (φ15.88)
3/8’’ (φ9.52)
51530653/4’’ (φ19.05)
3/8’’ (φ9.52)
51530
65
8. Installation details
8.1 Wrench torque sheet for installation
Outside diameter
Torque
mminchKg.m
φ6.351/41.8 φ9.523/84.2
φ12.71/25.5 φ15.885/86.6 φ19.053/46.6
8.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit24K30K36K
mm22,52,52,5
8.3 Pipe length and the elevation
Capacity
Standard
Pipe size
(m)ElevationElevationrefrigerant
Max.Max.Additional
30K~36K
In case that more than 5m.
Caution: Capacity is base on standard length and maximum allowance length is base of reliability. Oil trap should be install per 5-7 meters.
www.generalclimate.com 13 Wall-Mounted Split Type
8.4 Air purging of the piping and indoor unit
Required tools: Hexagonal wrench; adjustable wrench; torque wrenches, wrench to hold the joints and gas leak detector. Note: The air in the indoor unit and in the piping must be purged. If air remains in the refrigeration piping, it will affect the compressor, reduce the cooling capacity, and could lead to a malfunction of unit. Be sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gas leakage from the refrigeration cycle.
Procedure
1. Recheck the piping connections.
2. Open the valve stem of the 2-way valve counterclockwise approximately 90’, wait 10 seconds, and then set it to closed position.
§ Be sure to use a hexagonal wrench to operate the valve stem
3. Check for gas leakage.
§ Check the flare connection for gas leakage
4. Purge the air from the system.
§ Set the 2-way valve to the open position and remove the cap from the 3-way valve’s service port.
§ Using the hexagonal wrench to press the valve core pin, discharge for three seconds and then wait for one minute.
5. Use torque wrench to tighten the service port cap to a torque of 1.8 kg.m. (18n.m)
6. Set the 3-way valve to the opened position.
7. Mounted the valve stem nuts to the 2-way and 3-way valves.
8. Check for gas leakage.
§ At this time, especially check for gas leakage from the 2-way and 3-way stem nuts, and from the service port.
Caution: If gas leakage is discovered in step (3) above, take the following measures. If the leaks stop when the piping connections are tightened further, continue working from step (4). If the gas leaks do not stop when the connections are retightened, repair the location of the leak, discharge all of the gas through the service port, and then recharge with the specified amount of gas from a gas cylinder.
www.generalclimate.com 14 Wall-Mounted Split Type
8.5 Pumping down (Re-installation)
Procedure
1. Confirm that both the 2-way and 3-way valves are set to the opened position.
§ Remove the valve stem caps and confirm that the valve stems are in the opened position.
§ Be sure to use a hexagonal wrench to operate the valve stems.
2. Operate the unit for 10 to 15 minutes.
3. Stop operation and wait for 3 minutes, then connect the charge set to the service port of the 3-way valve.
§ Connect the charge hose with the push pin to the gas service port.
4. Air purging of the charge hose.
§ Open the low-pressure valve on the charge set slightly to purge air from the charge hose.
5. Set the 2-way valve to the close position.
6. Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
7. Immediately set the 3-way valve to the closed position.
§ Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
8. Disconnect the charge set, and amount the 2-way and 3-way valve’s stem nuts and service port caps.
§ Use a torque wrench to tighten the service port cap to a torque of 1.8 kg.m.
§ Be sure to check for gas leakage.
www.generalclimate.com 15 Wall-Mounted Split Type
8.6 Re-air purging (Re-installation)
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the closed position.
2. Connect the charge set and a charging cylinder to the service port of the 3-way valve.
§ Leave the valve on the charging cylinder closed.
3. Air purging.
§ Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on the 2-way valve approximately 45’ for 3 seconds then closing it for 1 minutes; repeat 3 times.
§ After purging the air, use a torque wrench to tighten the flare nut to on the 2-way valve.
4. Check the gas leakage.
§ Check the flare connections for gas leakage.
5. Discharge the refrigerant.
§ Close the valve on the charging cylinder and discharge the refrigerant until the gauge indicate 0.3 to 0.5 Mpa.
6. Disconnect the charge set and the charging cylinder, and set the 2-way and 3-way valves to the open position.
§ Be sure to use a hexagonal wrench to operate the valve stems.
7. Mount the valve stems nuts and the service port cap.
§ Be sure to use a torque wrench to tighten the service port cap to a torque 18N.m.
§ Be sure to check the gas leakage.
www.generalclimate.com 16 Wall-Mounted Split Type
8.7 Balance refrigerant of the 2-way, 3-way valves
Procedure:
1. Confirm that both the 2-way and 3-way valves are set to the open position.
2. Connect the charge set to the 3-way valve’s service port.
§ Leave the valve on the charge set closed.
§ Connect the charge hose with the push pin to the service port.
3. Open the valves (Low side) on the charge set and discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa.
§ If there is no air in the refrigeration cycle [the pressure when the air conditioner is not running is higher than 0.1Mpa, discharge the refrigerant until the gauge indicates 0.05 to 0.1 Mpa. If this is the case, it will not be necessary to apply a evacuation.
§ Discharge the refrigeration gradually; if it is discharged too suddenly, the refrigeration oil sill be discharged.
www.generalclimate.com 17 Wall-Mounted Split Type
8.8 Evacuation
Procedure:
1. Connect the vacuum pump to the charge set’s centre hose.
2. Evacuation for approximately one hour.
§ Confirm that the gauge needle has moved toward -0.1 Mpa (-76 cmHg) [vacuum of 4 mmHg or less].
3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
§ Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as needle.
www.generalclimate.com 18 Wall-Mounted Split Type
8.9 Gas charging
Procedure:
1. Connect the charge hose to the charging cylinder.
§ Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder.
2. Purge the air from the charge hose.
§ Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3. Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
§ If the system cannot be charge with the specified amount of refrigerant, if can be charged with a little at a time (approximately 150g each time0 while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure.(pumping down-pin).
4. Immediately disconnect the charge hose from the 3-way valve’s service port.
§ Stopping partway will allow the refrigerant to be discharged.
§ If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before
disconnecting the hose.
5. Mounted the valve stem caps and the service port
§ Use torque wrench to tighten the service port cap to a torque of 18N.m.
§ Be sure to check for gas leakage.
www.generalclimate.com 19 Wall-Mounted Split Type
Cooling mode
Conditions
21ºC D
Total capacity kW
6.76
6.35
5.88
5.41
5.05
4.69
15ºC W
Sensitive capacity kW
4.93
4.74
4.44
4.11
3.86
3.61
24ºC D
Total capacity kW
7.31
6.99
6.53
6.17
5.75
5.30
17ºC W
Sensitive capacity kW
5.38
5.21
4.96
4.72
4.43
4.11
27ºC D
Total capacity kW
7.79
7.44
6.64
6.19
5.71
19ºC W
Sensitive capacity kW
5.92
5.73
5.22
4.88
4.51
2.97
3.30
3.41
32ºC D
Total capacity kW
8.68
8.32
8.05
7.49
6.84
6.45
23ºC W
Sensitive capacity kW
6.68
6.49
6.32
5.91
5.47
5.22
-7ºC D
-8ºC W
7.91
2.75
9. Capacity table
9.1 GC/GU-S24HR
SUMMER
Indoor
Input kW.2.352.482.592.793.103.21
Input kW.2.432.562.672.883.203.31
Input kW.2.502.64
25ºC30ºC35ºC40ºC45ºC50ºC
OUTDOOR TEMPERATURE DRY
7.03
5.48
2.75
WINTER
Indoor
Conditions
15ºC
18ºC
20ºC
22ºC
Input kW.2.602.752.863.093.433.55
OUTDOOR CONDITIONS
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
12ºC D
11ºC W
9.338.197.506.585.674.98
2.952.682.502.312.011.83
9.168.047.316.355.384.66
3.032.732.532.372.071.85
9.08
3.11
9.007.827.126.105.014.15
3.222.782.652.512.272.03
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-4ºC D
-6ºC W
7.236.195.094.22
2.612.422.131.95
www.generalclimate.com 20 Wall-Mounted Split Type
Cooling mode
Conditions
21ºC D
Total capacity kW
7.88
7.40
6.86
6.31
5.90
5.47
15ºC W
Sensitive capacity kW
5.75
5.52
5.18
4.79
4.50
4.21
24ºC D
Total capacity kW
8.53
8.15
7.62
7.20
6.71
6.19
17ºC W
Sensitive capacity kW
6.27
6.07
5.79
5.51
5.17
4.79
27ºC D
Total capacity kW
9.09
8.68
7.75
7.22
6.66
19ºC W
Sensitive capacity kW
6.91
6.69
6.08
5.69
5.26
3.46
3.84
3.97
32ºC D
Total capacity kW
10.12
9.71
9.39
8.73
7.98
7.52
23ºC W
Sensitive capacity kW
7.79
7.57
7.37
6.90
6.38
6.09
-7ºC D
-8ºC W
8.79
3.10
9.2 GC/GU-S30HR
SUMMER
Indoor
Input kW.2.742.893.013.253.613.73
Input kW.2.822.983.103.353.723.85
Input kW.2.913.07
OUTDOOR TEMPERATURE DRY
25ºC30ºC35ºC40ºC45ºC50ºC
8.20
6.40
3.20
WINTER
Indoor
Conditions
15ºC
18ºC
20ºC
22ºC
Input kW.3.033.193.333.593.994.13
OUTDOOR CONDITIONS
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
12ºC D
11ºC W
10.379.108.337.316.305.53
3.333.032.812.602.272.06
10.188.938.137.065.985.18
3.413.072.862.672.332.09
10.09
3.51
10.008.697.916.785.564.61
3.633.132.992.832.552.29
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-4ºC D
-6ºC W
8.036.885.664.69
2.952.732.412.20
www.generalclimate.com 21 Wall-Mounted Split Type
Cooling mode
Conditions
21ºC D
Total capacity kW
9.87
9.27
8.59
7.90
7.38
6.85
15ºC W
Sensitive capacity kW
7.21
6.92
6.48
6.00
5.64
5.28
24ºC D
Total capacity kW
10.69
10.21
9.54
9.02
8.41
7.75
17ºC W
Sensitive capacity kW
7.85
7.61
7.25
6.90
6.47
6.00
27ºC D
Total capacity kW
11.38
10.88
9.71
9.05
8.34
19ºC W
Sensitive capacity kW
8.65
8.37
7.62
7.13
6.59
4.45
4.94
5.11
32ºC D
Total capacity kW
12.68
12.16
11.76
10.94
10.00
9.42
23ºC W
Sensitive capacity kW
9.76
9.48
9.23
8.64
8.00
7.63
-7ºC D
-8ºC W
11.14
4.12
9.3 GC/GU-S36HR
SUMMER
Indoor
Input kW.3.523.723.874.184.654.80
Input kW.3.643.844.004.324.804.96
Input kW.3.753.96
OUTDOOR TEMPERATURE DRY
25ºC30ºC35ºC40ºC45ºC50ºC
10.27
8.01
4.12
WINTER
Indoor
Conditions
15ºC
18ºC
20ºC
22ºC
Input kW.3.904.114.284.635.145.31
OUTDOOR CONDITIONS
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
Capacity kW
Input kW.
12ºC D
11ºC W
13.1411.5310.569.277.987.01
4.424.023.743.463.022.73
12.9011.3210.308.947.586.56
4.534.083.803.553.102.78
12.79
4.66
12.6711.0210.038.597.055.84
4.834.163.973.773.403.04
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-4ºC D
-6ºC W
10.188.727.175.95
3.913.633.202.93
www.generalclimate.com 22 Wall-Mounted Split Type
10. Electronic function
10.1 Electronic control working environment
Input voltage: 175~253V Input power frequency:50HZ Ambient temperature: -7°C+43°C Indoor fan normal working amp is less than 1A Outdoor fan normal working amp is less than 1.5A Four-way valve normal working amp is less than 1A Swing motor: DC12V Compressor: single-phase power supply. Its normal working amp is less than 15A
10.2 Proper symbols and their meaning
T1: Indoor ambient temperature T2: Indoor evaporator temperature T3: Outdoor condenser temperature. TS: Setting temperature through the remote controller I
: Self-protection amp of compressor, continue three seconds until turns off the compressor.
3sec
I
: Self-protection amp of compressor, continue five minutes until turns off the compressor.
5MIN
I
: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
FAN
I
: Amp self-protection return value
RESTORE
TE1: Anti-cold wind, from Fan Off to Breeze temperature TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature TE4: Anti-cold wind, from Breeze to Fan Off temperature TE5: Evaporator low temperature protection entering temperature TE6: Evaporator low temperature protection restoring temperature TE7: Evaporator high temperature protection, compressor off temperature TE8: Evaporator high temperature protection, fan off temperature TE9: Evaporator high temperature protection, restoring temperature TE10: Condenser high temperature protection, compressor off temperature. TE11: Condenser high temperature protection, restoring temperature. TE14: The indoor restoring temperature when the compressor is off on the heating mode. TE16: The indoor evaporator temperature after the defrost action, fan on temperature. TC1: Outdoor condenser sensor temperature for the defrost condition 1. TC2: Condenser sensor temperature after defrost. TC3: Outdoor condenser sensor temperature for the defrost condition 2.
www.generalclimate.com 23 Wall-Mounted Split Type
10.3 Function
Remote receiving Testing and forced running Position set for indoor unit wind vane LED displaying and alarm On or off Timer Protection for the compressor Current protection High temperature protection of indoor heat exchanger at heating mode Auto defrosting and heating recovery at heating mode Anti cold air at heating mode
10.4 Protection
10.4.1 3 minutes delay at restart for compressor.
10.4.2 Sensor protection at open circuit and breaking disconnection
10.4.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or too low(lower than 400RPM), the unit stops and LED displays failure information and can’t returns to normal operation automatically.
10.4.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED displays failure information and can’t returns to normal operation automatically.
10.4.5 The current protection of the compressor
10.5 Fan only mode
Fan speed is high/mid/low/ Auto
10.6 Cooling mode
The 4-way valve is closed at cooling mode. The action of the compressor and the outdoor fan:(T=indoor temperature)
www.generalclimate.com 24 Wall-Mounted Split Type
Auto fan at cooling mode:
Anti-freezing control to indoor evaporator at cooling mode ( T: evaporator temp. )
Condenser high temperature protection (only for heat pump)
10.7 Dehumidifying mode
Indoor fan speed at low speed. Protection is same as cooling mode.
10.8 Heating mode
10.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve must delay 2 minutes compared with compressor if the compressor changed into non-heating mode or turned off. 4-way valve doesn't delay in dehumidifying mode
www.generalclimate.com 25 Wall-Mounted Split Type
10.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except for the defrosting mode or the end of defrost
10.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes after starting and then judge temperature. Meanwhile other protections are still valid.
* This parameter can be changed from 0 to 3
10.8.4 Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind function prevails. Anti-cold wind control function at heating mode (T=indoor exchanger temp.)
10.8.5 Auto wind at heating mode (T=indoor temp.)
10.8.6 Indoor evaporator high-temperature protection at heating mode
(T=indoor exchanger temp.)
www.generalclimate.com 26 Wall-Mounted Split Type
10.8.7 The louver opens to Standard Angle ANGLHEAT when power is on for the first time
10.8.8
10.8.9
10.9 Defrosting mode(available for heating mode)
10.9.1 Defrosting condition:
Defrost starts when either of the following: T3 lower than 0’C, lasts for more than 40 minutes, provided that the time period then the temperature is lower than -3’C consecutively reaches 3 minutes. Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan with the compressor still running. Add up to 90 minutes.
10.9.2 Conditions of defrost ending:
Defrosting ends when either of the following: The time gets to 10 minutes. T3>20’C. The circulation is as following:
10.9.3 Defrosting Actions
Defrost 10 or 6 minutes
Compressor
5s
4-way valve
Outdoor fan
Indoor fan
10s
Remark: when the evaporator pipe temperature sensor more than TE16, the indoor fan start to run.
www.generalclimate.com 27 Wall-Mounted Split Type
25s
2s
10.10 Auto mode
10.10.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or fan only according to the temperature difference between room temperature (TA) and set temperature (TS).
10.10.2 The indoor fan blows automatically in corresponding selected mode
10.10.3 The motion of indoor fan’s blade should accord with the selected operation mode
10.10.4 One mode should be carried out for at least 15 minutes once selected. If the compressor cannot start for 15 minutes, reselect the operation mode according to the room temp. and set temp., or reselect when the set temp. varies
10.11 Force cooling function
10.11.1 Select forced cooling function with the forced cooling button or the switch
10.11.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode is set as low, the A/C operates at the DRY mode with a set temp. of 24
10.11.3 All protections of remote control cooling are available at forced cooling operation
10.11.4 Forced Auto function
Select forced auto function with the forced auto button or the switch. In forced auto status the A/C operates at remote control mode with a set temp. of 24 Manual operation is controlled by touching buttons and divided into force cooling and forced auto mode. It transfer between these two modes by pressing the buttons, the cycling order of the button press is as below graph show to you.
10.12 Sleep mode
10.12.1 The sleep function is available at cooling, heating or auto mode
10.12.2 Cooling:
The set temperature rise 1 per hour. Two hours later, the set temperature will maintain as a constant and the fan speed is kept at low speed.
www.generalclimate.com 28 Wall-Mounted Split Type
10.12.3 Heating:
The set temperature decrease 1 per hour. Two hours later, the set temperature will maintain as a constant and the air circulation is kept at low speed (Anti-cold function takes precedence over all).
10.12.4 Auto:
After an hour running under economic mode, the set temp will rise 1,if it is under cooling mode; the set temp will decrease 1,if it is under heating mode; the set temp will be changeless, if it is under fan-only mode; the condition will be the same after the air conditioner running under economic mode after 2 hours, and during the next time the set temp do not change. The total time is 7 hours, after 7 hours the unit stops.
10.13 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings before the power failure when power returns
www.generalclimate.com 29 Wall-Mounted Split Type
11. Model and Parameters
Model
I3SEC [A] I5MIN [A] IFAN [A] IDEFROST [A] TE1 ['C] TE2 ['C] TE3 ['C] TE4 ['C] TE5 ['C] TE6 ['C] TE7 ['C] TE8 ['C] TE9 ['C] TE10 ['C] TE11 ['C] TE14 ['C] TE16 ['C]
GC/GU-S24HRGC/GU-S30HRGC/GU-S36HR
222634 202432 162025 141822 252530 323237 303034 202024
222 121212 636363 545454 505050 656570 555565 323232 424234
www.generalclimate.com 30 Wall-Mounted Split Type
12. Troubleshooting
12.1 Display board
§ Operation
The indicator flashes once every second after power is on and illuminates when the air conditioner is in operation.
§ Timer indicator:
The indicator illuminates then TIMER is set ON.
§ PRE-DEF. indicator (For cooling & heating mode only) The air conditioner starts defrosting automatically if outdoor unit frosts in heating operating. At this time, PRE-DEF. indicator illuminates.
§ Auto indicator: This indicator flashes when the air conditioner is in AUTO operation.
§ ECON indicator This indicator illuminates while the air conditioner is in economic operation.
www.generalclimate.com 31 Wall-Mounted Split Type
lamp
lamp
Indoor fan speed has been out of control for over 1 minute
X
Indoor room temp. or evaporator sensor is open circuit or short circuit
On
Over current protection of the compressor occurs 4 times
X
EEROM error
On
No over-zero signal
Flash at 5Hz
lamp
lamp
lamp
Over current protection of the compressor occurs 4 times
X
Indoor fan speed has been out of control for over 1 minute
X
No over-zero signal
Temp. sensor on indoor evaporator is open circuit or short circuit
XXIndoor room temp. sensor is open circuit or short circuit
XXEEROM error
On
X
Flash at 5Hz
12.2 Troubleshooting
For cooling mode:
Failure phenomenon
r
Extinguish
For heat pump mode:
Failure phenomenon
r
Extinguish
Operation
Operation
Timer
Timer
Defrosting
www.generalclimate.com 32 Wall-Mounted Split Type
12.3 Diagnostic chart
After energizing, no indicator is lighted and the air conditioner can’t be operated.
www.generalclimate.com 33 Wall-Mounted Split Type
12.4 Resetting phenomenon often occurs during operation.
(That is automatically entering to the status when power is on.) The reason is that the instantaneous voltage of main chip is less than 4.5V. Check according to the following procedure:
Resetting phenomenon often occurs during operation.
Yes
After changing indoor PCB, check if the failure realease.
Yes
After changing indoor fan motor, check if the failure realease.
YES
Power supply circuit has problems.
Indoor PCB is defective.
12.5 Operation lamp flashes and Timer lamp off.
Yes
12.6 Operation lamp flashes and Timer lamp on.
www.generalclimate.com 34 Wall-Mounted Split Type
12.7 Operation lamp off and Timer lamp flashes
12.8 Operation lamp on and Timer lamp flashes
EEROM error, indoor PCB is defective.
12.9 Operation lamp flashes, Timer lamp flashes .
This is alarm signal when the main chip can’t detect over-zero signal. When such failure occurs, the main control board must have fault.
www.generalclimate.com 35 Wall-Mounted Split Type
13. Characteristic of temperature sensor
Temp.℃Resistance KΩ Temp.℃Resistance KΩ Temp.℃Resistance KΩ
-1062.27561714.6181444.3874
-958.70791813.918454.2126
-856.36941913.2631464.0459
-752.24382012.6431473.8867
-649.31612112.0561483.7348
-546.57252211.5493.5896
-4442310.9731503.451
-341.58782410.4736513.3185
-239.82392510523.1918
-137.1988269.5507533.0707
035.2024279.1245542.959
133.3269288.7198552.8442
231.5635298.3357562.7382
329.9058307.9708572.6368
428.3459317.6241582.5397
526.8778327.2946592.4468
625.4954336.9814602.3577
724.1932346.6835612.2725
822.5662356.4002622.1907
921.8094366.1306632.1124
1020.7184375.8736642.0373
1119.6891385.6296651.9653
1218.7177395.3969661.8963
1317.8005405.1752671.83
1416.9341414.9639681.7665
1516.1156424.7625691.7055
1615.3418434.5705701.6469
www.generalclimate.com 36 Wall-Mounted Split Type
Exploded View Parts for Model GC-S24HR 220-240V, 50Hz : Indoor Unit
No. Part Name Quantity Sale code
1 Front panel 1 10321121003
2 Air filter 2 10321111001
3 Air cleaner 1 10321111002
4 Screw cap 3 10321111003
5 Panel frame
6
7 1 10321121007
8 Big bush 2 10321121008
9 Small bush 4 10321121009
10 Air out frame 1 10321121010
Horizontal airflow grille 15 10321121005
Grille holder 3 10321121006
1
10321121004
11 Drain hose 1 10118121223
12 Left holder for evaporator 1 10321111004 13
14 Bearing holder 1 10321111008
15 Cross flow fan, assy 1 10321111009
www.generalclimate.com 37 Wall-Mounted Split Type
Evaporator 1 10924121003
16 Chassis 1 10321111010
17 Installation Plate 1 10321111011
18 Fan motor 1 10321111012
19 Fixing part for motor 1 10321111013
20 Protector for temp sensor 1 10112121224
21 Clamp for temp sensor 1 10109121231
22 Right holder for evaporator 1 10321111014
23 Indoor temp sensor 1 10118121242
24 Connecting pipe clamp 1 10321111015
25 Evaporator temp sensor 1 10109121242
26 Louver motor 1 10321111016
27 Vertical airflow louverdown 1 10321121011
28 Vertical airflow louverup 1 10321121012
29 Window cover for repairing 1 10321111017
30 Control assy 1 10321121013
31 E-part box cover 1 10321111018
32 Terminal block 1 10321121001
33 Terminal block 1 10121121227
34 Terminal block 1 10121121233
35 Fan motor capacitor 1 50309121808
36 Transformer 1 10118121232
37 E-Parts box 1 10321111019
38 Main control board 1 10321121002
39 Wire clamp for power cord 1 10121121234
40
41 Remote controller 1 10109121207
42 Holder for remote controller 1 10109121208
43 Connection pipe for drainage 1 11609121003
Display board 1 10321111021
Display board enclosure 1 10321111022
44 Sealing ring 1 31009321021
45 Copper nut, TLM-B02 1 10909121013
46 Copper nut, TLM-D04 1 11324113804
www.generalclimate.com 38 Wall-Mounted Split Type
Exploded View Parts for Model GU-S24HR 220--240V,50Hz : Outdoor Unit
No. Part Name Quantity Sale code
1 Front net 1 10118121801
2 Clamp for front net 8 10112121801
3 Front clapboard 1 10924121801
4 Propeller fan 1 10118121804
5 Fan Motor 1 10121121801
6 Holder for fan motor 1 10118121809
7 Foam over holder for motor 1 10118121807
8 Front right clapboard 1 10118121819
9 Chassis 1 10122113803
10 Compressor 1 10124111813
11 Separating board 1 10121121803
12 Little Handle 1 10830121811
13 Cover 1 10118121827
14 Condenser 1 11318123802
15 Left clapboard 1 10924121808
16 Rear Net 1 10924121809
www.generalclimate.com 39 Wall-Mounted Split Type
17 Rear right clapboard 1 10118113804
18 Big Handle 1 10118121817
19 Installation plate for valves 1 10118113805
20 Water collector 1 10118121832
21 Capacitor Clamp 1 10112121814
22 Compressor capacitor 1 10118121820
23 Fan motor capacitor 1 10109121819 24 Wire joint 1 10124121810
25 Washer for wire joint 1 10112121817
26 Clamp for wiring 1 10118121823
27 Installation board for E-parts 1 10424121802 28 Contactor 1 10121121806
29 Wire joint for multiplexer 1 10121121809
30 High Pressure Valve Ass'y 1 10124121815
31 Liquid pipe valve 1 10124121812
32 Low Pressure Valve Ass'y 1 10124121805 33 4-way valve 1 10312121852
34 Low Pressure Valve 1 10124121814 35 Copper nut, TLM-B02 36 Copper nut,TLM-D04 1 11324113804
37 Condenser temp sensor 1 10118121828
www.generalclimate.com 40 Wall-Mounted Split Type
1
10909121013
Exploded View Parts for Model GC-S30HR 220-240V, 50Hz : Indoor Unit
No. Part Name Quantity Sale code
1 Front panel 1 10321121003
2 Air filter 2 10321111001
3 Air cleaner 1 10321111002
4 Screw cap 3 10321111003
5 Panel frame
6
7 Stopple 1 10321121007
8 Big bush 2 10321121008
9 Small bush 4 10321121009
10 Air out frame 1 10321121010
11 Drain hose 1 10118121223
Horizontal airflow grille 15 10321121005
Grille holder 3 10321121006
1
10321121004
12 Left holder for evaporator 1 10321111004 13
14 Bearing holder 1 10321111008
15 Cross flow fan, assy 1 10321111009
16 Chassis 1 10321111010
www.generalclimate.com 41 Wall-Mounted Split Type
Evaporator 1 10924121003
17 Installation Plate 1 10321111011
18 Fan motor 1 10321111012
19 Fixing part for motor 1 10321111013
20 Protector for temp sensor 1 10112121224
21 Clamp for temp sensor 1 10109121231
22 Right holder for evaporator 1 10321111014
23 Indoor temp sensor 1 10118121242
24 Connecting pipe clamp 1 10321111015
25 Evaporator temp sensor 1 10109121242
26 Louver motor 1 10321111016
27 Vertical airflow louverdown 1 10321121011
28 Vertical airflow louverup 1 10321121012
29 Window cover for repairing 1 10321111017
30 Control assy 1 10321121013
31 E-part box cover 1 10321111018
32 Terminal block 1 10321121001
33 Terminal block 1 10121121227
34 Terminal block 1 10121121233
35 Fan motor capacitor 1 10109121819
36 Transformer 1 10118121232
37 E-Parts box 1 10321111019
38 Main control board 1 10324121001
39 Wire clamp for power cord 1 10121121234
40
41 Remote controller 1 10109121207
42 Holder for remote controller 1 10109121208
43 Connection pipe for drainage 1 11609121003
44 Sealing ring 1 31009321021
Display board 1 10321111021
Display board enclosure 1 10321111022
45 Copper nut, TLM-B02 1 10909121013
46 Copper nut, TLM-D04 1 11324113804
www.generalclimate.com 42 Wall-Mounted Split Type
Exploded View Parts for Model GU-S30HR 220-240V, 50Hz : Outdoor Unit
No. Part Name Quantity Sale code
1 Front net 1 10118121801
2 Clamp for front net 8 10112121801
3 Front clapboard 1 10924121801
4 Propeller fan 1 10118121804
5 Fan Motor 1 10121121801
6 Holder for fan motor 1 10118121809
7 Foam over holder for motor 1 10118121807
8 Front right clapboard 1 10118121803
9 Chassis 1 10124121801
10 Compressor 1 10124121809
11 Separating board 1 10124121803
12 Little Handle 1 10830121811
13 Cover 1 10118121827
14 Condenser 1 11318123802
15 Left clapboard 1 10924121808
16 Rear Net 1 10924121809
17 Rear right clapboard 1 10118113804
www.generalclimate.com 43 Wall-Mounted Split Type
18 Big Handle 1 10118121817
19 Installation plate for valves 1 10118113805
20 Water collector 1 10118121832
21 Capacitor Clamp 1 10112121814
22 Compressor capacitor 1 10118121820
23 Fan motor capacitor 1 10124121806 24 Wire joint 1 10124121810
25 Washer for wire joint 1 10112121817
26 Clamp for wiring 1 10118121823
27 Installation board for E-parts 1 10424121802 28 Contactor 1 10121121806
29 Wire joint for multiplexer 1 10121121809
30 High Pressure Valve Ass'y 1 15024121802
31 Liquid pipe valve 1 10124121812
32 Low Pressure Valve Ass'y 1 15024121803 33 4-way valve 1 10312121852
34 Low Pressure Valve 1 10124121814 35 Copper nut, TLM-B02 36 Copper nut,TLM-D04 1 11324113804
37 Condenser temp sensor 1 10121121816
1
10909121013
www.generalclimate.com 44 Wall-Mounted Split Type
Exploded View Parts for Model GC-S36HR 220-240V,50Hz : Indoor Unit
No Name Quanlity Sale code 1 Front panel 1 10336111001 2 Air filter 2 10336111002 3 Screw cap 3 10336111003 4 Down clap for panel frame 4 10336111004 5 Panel frame 1 10336111005 6 Up clap for panel frame 2 10336111006 7 Air out frame assy 1 10336111007 7,1 Horizontal louverdown 1 10336111008 7,2 Left bush for horizontal louver 1 10336111009 7,3 Horizontal louverup 1 10336111010 7,4 Louver connecter, middle-left 1 10336111011 7,5 Louver connecter, left 1 10336111012 7,6 Vertical louver, small size 2 10336111013 7,7 Vertical louver, large size 12 10336111014 7,8 Louver holder, left 1 10336111015 7,9 Air out frame 1 10336111016
www.generalclimate.com 45 Wall-Mounted Split Type
7.10 Louver holder, middle 1 10336111017
7.11 Stopple 1 10336111018
7.12 Vertical louver, middle size 2 10336111019
7.13 Bush 4 10336111020
7.14 Louver holder, right 1 10336111021
7.15 Louver connecter, right 1 10336111022
7.16 Swing bar for up horizontal louver 1 10336111023
7.17 Connecter for horizontal louver 1 10336111024
7.18 Swing bar for down horizontal louver 1 10336111025
7.19 Louver connecter, middle-right 1 10336111026 8 Evaporator assy 1 10336111027
Evaporator I 1 10336111028 Evaporator II 1 10336111029
8,1
8,2 Left holder for evaporator 1 10336111033
8,3
9 Cross flow fan, assy 1 10336111036 10 Bearing holder 1 10336111037 11 Chassis assy 1 10336111038 11,1 Chassis 1 10336111039 11,2 Left rear cover for chassis 1 10336111040 11,3 Right rear cover for chassis 1 10336111041 12 Installation plate 1 10336111042 13 Corner board for chassis 1 10336111043 14 Base for motor 1 10336111044 15 Fan motor 1 10336111045
Evaporator III 1 10336111030 Evaporator IV 1 10336111031 Right holder for evaporator 1 10336111032
Input pipe for evaporator 1 10336111034 Output pipe for evaporator 1 10336111035
16 Cover for motor 1 10336111046 17 Small cover for motor 1 10336111047 18 Waterproof board 1 10336111048 19 Drain hose 1 10336111049 20 Louver motor 1 10336111050 21 Air cleaner 1 10336111051 22 Air cleaner holder 1 10336111052 23 Remote controller 1 10109121207
www.generalclimate.com 46 Wall-Mounted Split Type
24 Holder for remote controller 1 10109121208 25 E-parts assy 1 10336121005 25,1 Display board 1 10336121002 25,2 Wire joint, 4p 1 10336111055 25,3 Wire clamp 1 10336111056 25,4 Main control board 1 10336121004 25,5 E-Parts box 1 10336111058 25,6 Transformer 1 50242122817 25,7 Indoor temp sensor 1 10118121242 25,8 Evaporator temp sensor 1 10109121242 26 E-part box cover 1 10336111059 27 Bottom cover for e-box 1 10336111060 28 Clamp for temp sensor 1 10109121231 29 Protector for temp sensor 1 10112121224
30 Copper nut, TLM-D04 1 11324113804 31
www.generalclimate.com 47 Wall-Mounted Split Type
Copper nut, TLM-B02 1 10909121013
Exploded View Parts for Model GU-S36HR 220-240V,50Hz : Outdoor Unit
No. Part Name Quantity Sale code
1 Front net 1 10118121801
2 Clamp for front net 8 10112121801
3 Front clapboard 1 11426432801
4 Propeller fan 1 10336111801
5 Fan motor 1 10336111802
6 Holder for fan motor 1 10224121803
7 Chassis 1 11426432808
8 Separating board 1 50224123803
9 Cover 1 10224121804
10 Condenser 1 11324123801
11 Underlay for rear net 4 10118121818
12 Rear net 1 10224121807
13 Left clapboard 1 10224121806
14 Rear right clapboard 1 11426432804
15 Big handle 1 10224121808
16 Installation plate for valves 1 11426432807
www.generalclimate.com 48 Wall-Mounted Split Type
17 Water collector 1 10336111804
18 Refrigerant container 1 10224121817
19 Small handle 1 10224121809
20 Front right clapboard
21 Condenser temp sensor 1 10121121816
22 Transformer 1 10336111806
23 Fan motor capacitor 1 10118121821
24 Main control board 1 10336121804
25 Contactor 1 10336111808
26 Wire joint for multiplexer 2 10121121809
27 Relay 1 10118121238
28 Wire joint 1 10336111809
29 Clamp for wiring 1 10118121823
30 Washer for wire joint 1 10112121817
1
10224121825
31 Capacitor clamp 2 10224121816
32 Compressor capacitor 2 10224121815
33 Installation board for E-parts 1 10336111805
34
35
36 Compressor 1 10336111810
37 Copper nut, TLM-D04 1 11324113804 38
Liquid pipe valve,assy 1 10336121807
Liquid pipe valve 1 11426432811
4-way valve,assy 1 10336121808
Gas pipe valve 1 11426432810
4-way valve 1 10312121852
Copper nut, TLM-B02 1 10909121013
Climatic Control Corpоration. LLP
29-30 Margaret Street, London W1R 6HH, UK
Tel./fax: +44 20 7016 9133
www.generalclimate.com 49 Wall-Mounted Split Type
Loading...