General Climate GC-S05CR, CU-S09HR, CU-S07HR, GC-S07HR, GC-S09HR Service Manual

...
Climatic Control Corporation Wall-Mounted Split Type
Service manual
Room air conditioner Split Wall-Mounted Type
GC/CU-S05CR GC/CU-S07HR GC/CU-S09HR GC/CU-S12HR GC/CU-S18HR
Downloaded from AC-Manual.com Manuals
www.generalclimate.com Wall-Mounted Split Type
Content
1. Precaution 1
1.1 Safety Precaution 1
1.2 Warning 1
2. Function 3
3. Dimension 5
3.1 Indoor unit 5
3.2 Outdoor unit 6
4. Specification 7
5. Refrigerant cycle diagram 9
6. Operation limits 10
6.1 Cooling operation 10
6.2 Heating operation 10
7. Schematic diagram and Wiring diagram 11
7.1 Schematic diagram 11
7.2 Wiring diagram 12
8. Installation details 15
8.1 Wrench torque sheet for installation 15
8.2 Connecting the cables 15
8.3 Pipe length and the elevation 15
8.4 Air purging of the piping and indoor unit 16
8.5 Pumping down (Re-installation) 17
8.6 Re-air purging (Re-installation) 18
8.7 Balance refrigerant of the 2-way, 3-way valves 19
8.8 Evacuation 20
8.9 Gas charging 21
9. Capacity table 22
9.1 GC/GU-S05CR 22
9.2 GC/GU-S07HR 22
9.3 GC/GU-S09HR 23
9.4 GC/GU-S12HR 23
9.5 GC/GU-S18HR 24
10. Electronic function 25
10.1 Electronic control working environment 25
10.2 Proper symbols and their meaning 25
10.3 Function 25
10.4 Protection 26
10.5 Fan-only mode 26
10.6 Cooling mode 26
10.7 Dehumidifying mode 27
10.8 Heating mode 28
10.9 Defrosting mode(available for heating mode) 29
Downloaded from AC-Manual.com Manuals
www.generalclimate.com Wall-Mounted Split Type
10.10 Auto mode 30
10.11 Force cooling function 30
10.12 Sleep mode 31
10.13 Auto restart function 31
10.14 Anion (optional) 31
11. Model and Parameters 33
12. Troubleshooting 34
12.1 Display board 34
12.2 Troubleshooting 34
12.3 Diagnostic chart 35
12.4 Resetting phenomenon often occurs during operation. 36
12.5 Operation lamp flashes and Timer lamp off. 36
12.6 Operation lamp flashes and Timer lamp on. 36
12.7 Operation lamp off and Timer lamp flashes 37
12.8 Operation lamp on and Timer lamp flashes 37
12.9 Operation lamp flashes, Timer lamp flashes . 37
13. Characteristic of temperature sensor 38
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 1 Wall-Mounted Split Type
1. Precaution
1.1 Safety Precaution
n To prevent injury to the user or other people and property damage, the following instructions must be followed. n Incorrect operation due to ignoring instruction will cause harm or damage. n Before service unit, be sure to read this service manual at first.
1.2 Warning
Ø Installation
n Do not use a defective or underrated circuit breaker. Use
this appliance on a dedicated circuit.
There is risk of fire or electric shock.
n For electrical work, contact the dealer, seller, a qualified
electrician, or an Authorized service center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
n Always ground the product.
There is risk of fire or electric shock.
n Install the panel and the cover of control box securely.
There is risk of fire of electric shock.
n Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or electric shock.
n Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
n Do not modify or extend the power cable.
There is risk of fire or electric shock.
n Do not install, remove, or reinstall the unit by yourself
(customer).
There is risk of fire, electric shock, explosion, or injury.
n Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and evaporator.
n For installation, always contact the dealer or an
Authorized service center.
There is risk of fire, electric shock, explosion, or injury.
n Do not install the product on a defective installation
stand.
It may cause injury, accident, or damage to the product.
n Be sure the installation area does not deteriorate with
age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
n Do not let the air conditioner run for a long time when the
humidity is very high and a door or a windows is left open.
Moisture may condense and wet or damage furniture.
n Take care to ensure that power cable could not be pulled
out or damaged during operation.
There is risk of fire or electric shock.
n Do not place anything on the power cable.
There is risk of fire or electric shock.
n Do not plug or unplug the power supply plug during
operation.
There is risk of fire or electric shock.
n Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
n Do not place a heater or other appliance near the power
cable.
There is risk of fire and electric shock.
n Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric shock.
n Do not store or use flammable gas or combustible near
the product.
There is risk of fire or failure of product.
n Do not use the product in a tightly closed space for a
long time.
Oxygen deficiency could occur.
n When flammable gas leaks, turn off the gas and open a
window for ventilation before turn the product on.
Do not use the telephone or turn switches on or off. There is risk of explosion or fire.
n If strange sounds, or small or smoke comes from
product. Turn the breaker off or disconnect the power supply cable.
There is risk of electric shock or fire.
n Stop operation and close the window in storm or
hurricane. If possible, remove the product from the window before the hurricane arrives.
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 2 Wall-Mounted Split Type
There is risk of property damage, failure of product, or electric shock.
n Do not open the inlet grill of the product during operation.
(Do not touch the electrostatic filter, if the unit is so equipped.)
There is risk of physical injury, electric shock, or product failure.
n When the product is soaked (flooded or submerged),
contact an Authorized service center.
There is risk of fire or electric shock.
n Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
n Ventilate the product from time to time when operating it
together with a stove, etc.
There is risk of fire or electric shock.
n Turn the main power off when cleaning or maintaining
the product.
There is risk of electric shock.
n When the product is not be used for a long time,
disconnect the power supply plug or turn off the breaker.
There is risk of product damage or failure, or unintended operation.
n Take care to ensure that nobody could step on or fall
onto the outdoor unit.
This could result in personal injury and product damage.
Ø CAUTION
n Always check for gas (refrigerant) leakage after
installation or repair of product.
Low refrigerant levels may cause failure of product.
n Install the drain hose to ensure that water is drained
away properly.
A bad connection may cause water leakage.
n Keep level even when installing the product.
To avoid vibration of water leakage.
n Do not install the product where the noise or hot air from
the outdoor unit could damage the neighborhoods.
It may cause a problem for your neighbors.
n Use two or more people to lift and transport the product.
Avoid personal injury.
n Do not install the product where it will be exposed to sea
wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Ø Operational
n Do not expose the skin directly to cool air for long
periods of time. (Do not sit in the draft).
This could harm to your health.
n Do not use the product for special purposes, such as
preserving foods, works of art, etc. It is a consumer air conditioner, not a precision refrigerant system.
There is risk of damage or loss of property.
n Do not block the inlet or outlet of air flow.
It may cause product failure.
n Use a soft cloth to clean. Do not use harsh detergents,
solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
n Do not touch the metal parts of the product when
removing the air filter. They are very sharp.
There is risk of personal injury.
n Do not step on pr put anything on the product. (outdoor
units)
There is risk of personal injury and failure of product.
n Always insert the filter securely. Clean the filter every
two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
n Do not insert hands or other object through air inlet or
outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
n Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
n Use a firm stool or ladder when cleaning or maintaining
the product.
Be careful and avoid personal injury.
n Replace the all batteries in the remote control with new
ones of the same type. Do not mix old and mew batteries or different types of batteries.
There is risk of fire or explosion.
n Do not recharge or disassemble the batteries. Do not
dispose of batteries in a fire.
They may burn of explode.
n If the liquid from the batteries gets onto your skin or
clothes, wash it well with clean water. Do not use the remote of the batteries have leaked.
The chemical in batteries could cause burns or other health hazards.
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 3 Wall-Mounted Split Type
2. Function
The function will be operate in any operation
Indoor unit
Operation ON/OFF by remote controller
Room temperature sensor. Pipe temperature sensor.
Sensing by room temperature
Maintain the room temperature in accordance with the setting temperature.
Room temperature control
Indoor fan is delayed for 5 sec at the
Starting temperature control
Restarting is for approx. 3 minutes..
Time Delay Safety control
High, med, low, breeze.
Indoor fan speed control
Light up in the LED (LCD) for each operation mode.
The unit will decide the louver direction according to operation mode.
Two-direction air vane
The fan is turn to low speed (cooling/heating). The unit will be turn off after seven hours.
Sleep mode auto control
The function is usually used in rainy days in springtime or damp areas.
Independent dehumidification
Operation indication Lamps (LED)
The louver can be set at the desired position or swing up and down automatically
Air flow Direction control
The unit can be change by the room temperature.
Auto mode
Easy clean panel
Flexible wiring connection
Defrost mode
Temp. Compensation
Prevent the cold wind at the beginning of unit
Anti-cold function
Auto-restart function
Self-diag. function
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 4 Wall-Mounted Split Type
The unit can operate in cooling mode at low ambient temperature conditions.
The unit has 3 mins delay between continuously ON/OFF operations.
Outdoor unit
Power relay control
Low ambient kit
Bird tail propeller fan makes the outdoor unit run more quietly.
Low noise air flow system
The hydrophilic fin can improve the heating efficiency at operation mode.
Hydrophilic aluminum fin
It is only operated in the heating operation mode except defrosting operation.
Discharge pipe temperature protect
Anti-rust cabinet
4 way valve control
Made from electrolytic zinc steel sheet and anti-rust coated components.
It protects the valves and prevents water from dripping.
Valve protection cover
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 5 Wall-Mounted Split Type
3. Dimension
3.1 Indoor unit
Dimension Mode
WHL
5K750250188 7K750250188
9K750250188 12K750250188 18K906286235
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 6 Wall-Mounted Split Type
3.2 Outdoor unit
Dimension Mode
WHDL1L2L3
5K700535235
458
280
540
7K700535235
458
280
540
9K700535235
458
280
540
12K780540250
530
315
590
18K760590285540335615
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 7 Wall-Mounted Split Type
4. Specification
GC/GU-S05CR
GC/GU-S07HR
Ph-V-Hz
1, 220-240V~,50Hz1, 220-240V~,50Hz
Capacity Btu/h
50007000 Input W560760 Rated current A2,63,6 EER Btu/w.h99,2 Capacity Btu/h
-----
7600
Input W
-----760
Rated current A
-----3,4
COP W/W
-----
10 A3,85 A
1618
Model
KH104VFHC
2P14C235ANA
Type
Rotary
Rotary
Brand
SHANGHAI SENLIN
GD Matsushita Capacity Btu/h57007500 Input W590725 Rated current(RLA) A2,73,4 Locked rotor Amp(LRA) A1315 Thermal protector BF540-KBMRA98854 Capacitor uF
15
25
Refrigerant oil ml
MS-56 270
ATOMOS M60 270
Model
RPG13HRPG13H Brand WELLINGWELLING Input W
36,536,5
Capacitor uF
1.2μF/450V1.2μF/450V
Speed(hi/mi/lo) r/min1020/ 960/ 9001020/ 960/ 900
m3/h
300/270/240380/350/320
dB(A)
32/30/2832/30/28 Model
YDK24-6TYDK24-6T Brand WELLINGWELLING Input W
7070
Capacitor uF
33
Speed r/min
850850
m3/h
14001400
dB(A)4949
g
480620
MPa
2,62,6
Liquid side/ Gas side mm
Ф
6.35/Ф9.53
Ф
6.35/Ф9.53 Max. refrigerant pipe length m1010 Max. difference in level m55
17-3017-30
18-45-7 - 45
m
2
8-1210-14
Operation temp Ambient temp Application area
Outdoor noise level Refrigerant type R22 Design pressure
Refrigerant piping
Indoor air flow (Hi/Mi/Lo) Indoor noise level (Hi/Mi/Lo)
Outdoor fan motor
Outdoor air flow
Max. current Starting current
Compressor
Indoor fan motor
Model
Power supply
Cooling
Heating
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally somewhat different as a result of ambient condition. The above design and specifications are subject to change without prior notice for product improvement.
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 8 Wall-Mounted Split Type
GC/GU-S09HR
GC/GU-S12HR
GC/GU-S18HR
Ph-V-Hz
1, 220-240V~,50Hz1, 220-240V~,50Hz1, 220-240V~,50Hz Capacity Btu/h90001200018000 Input W96012301920 Rated current A4,55,79 EER Btu/w.h9,49,89,4 Capacity Btu/h100001300020000 Input W98012901980 Rated current A4,469,2 COP W/W10,29,810,1
A79,110 A2526
36
Model 2P18S225ANKPH225X2C-4FT
SHY33MC2-U
Type RotaryRotary
rotary
Brand GD MatsushitaGD Toshiba
Hitachi Capacity Btu/h99201361017620 Input W97013051725 Rated current(RLA) A4,56,18,1 Locked rotor Amp(LRA) A242636 Thermal protector External(MRA98745
ExternalInternal
Capacitor uF3035
50
Refrigerant oil mlSUNISO 350430
600
Model
RPG13H
RPG13H
RPG25 Brand WELLINGWellingWELLING Input W
36,5
36,5
53
Capacitor uF
1.2μF/450V
1,2
1.5uF/450V
Speed(hi/mi/lo) r/min1100/1020/95013501180
m3/h
450/420/390
550/500/460
750/710/650
dB(A)
37/34/31
41/ 38 /34
41/38/35
Model
YDK24-6TYDK24-6YDK25-6H Brand WELLINGWELLINGWELLING Input W5572
96
Capacitor uF
2.5μF/450V2.5μF/450V2.5μF/450V
Speed r/min800850
900
m3/h
150018002000
dB(A)505254
g650820
1370
MPa
2,6
2,6
2,6
Liquid side/ Gas side mm
Ф
6.35/Ф9.53
Ф
6.35/Ф12.7
Ф
6.35/Ф12.7 Max. refrigerant pipe length m101015 Max. difference in level m558
17-30
17-30
17-30
-7 - 45-7 - 45-7 - 45
m
2
14-2118-2625-35
Operation temp Ambient temp Application area
Outdoor noise level Refrigerant type R410A Design pressure
Refrigerant piping
Indoor air flow (Hi/Mi/Lo) Indoor noise level (Hi/Mi/Lo)
Outdoor fan motor
Outdoor air flow
Max. current Starting current
Compressor
Indoor fan motor
Model
Power supply
Cooling
Heating
Note:
The noise date is base on hemi-anechoic chamber, during actual operation; these values are normally somewhat different as a result of ambient condition. The above design and specifications are subject to change without prior notice for product improvement.
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 9 Wall-Mounted Split Type
5. Refrigerant cycle diagram
Ø Cooling only
Ø Heat pump mode
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 10 Wall-Mounted Split Type
6. Operation limits
6.1 Cooling operation
Outdoor unit air temp. DB
Indoor air temp. DB Note: The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage.
6.2 Heating operation
Indoor air temp. DB
Outdoor unit air temp. DB Note: The chart is the result from the continuous operation under constant air temperature conditions. However, excludes the initial pull-down stage.
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 11 Wall-Mounted Split Type
7. Schematic diagram and Wiring diagram
7.1 Schematic diagram
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 12 Wall-Mounted Split Type
7.2 Wiring diagram
7.2.1 Cooling mode
GC/GU-S05CR
1 2︵N
COMPRESSOR CAPACITOR
RED
OUTDOOR UNIT
OVERLOAD
RELAY
YG
COMPRESSOR
S
C
BLUE
R
BLACK
RED
BLACK
INDOOR UNIT
FAN CAPACITOR
RED
YG
FAN
MOTOR
YG
BLUE
BLACK
RED
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 13 Wall-Mounted Split Type
7.2.2 GC/GU-S07HR, GC/GU-S09HR, GC/GU-S12HR
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 14 Wall-Mounted Split Type
MSG-18HR
Downloaded from AC-Manual.com Manuals
www.generalclimate.com 15 Wall-Mounted Split Type
8. Installation details
8.1 Wrench torque sheet for installation
Torque
mminchKg.m
φ6.351/41.8 φ9.523/84.2
φ12.71/25.5 φ15.885/86.6 φ19.053/46.6
Outside diameter
8.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Unit7K9K12K18K
mm21,01,01,52,5
Grade
8.3 Pipe length and the elevation
Standard
length
Max.Max.Additional
(m)ElevationElevationrefrigerant
Btu/h
GAS
LIQUID
B (m)A
(m)
(g/m)
3/8’’ (φ9.52)
1/4’’ (φ6.35)
5510301/2’’ (φ12.7)
1/4’’ (φ6.35)
55103018K1/2’’ (φ12.7)
1/4’’ (φ6.35)
5815
30
Pipe size
7k~12K
Capacity
Caution: Capacity is base on standard length and maximum allowance length is base of reliability. Oil trap should be install per 5-7 meters.
In case that more
than 5m.
Downloaded from AC-Manual.com Manuals
Loading...