GeneralAire Streamline SL-16 Installation Instructions Manual

GENERAI_A_ire
INSTALLER: PLEASE FILL OUT AND MAIL GUARANTEE CARD AFTER INSTALLATION
IS COMPLETE. LEAVE INSTALLATION INSTRUCTIONS WITH HOME OWNER
PRECAUTION: The installer should be an experienced service technician. Disconnect electrical power before beginning installation. Do not install where temperatures fall below 32 degrees F or where plenum temperatures exceed 200 degrees F. When wiring into a multi-speed blower circuit see Step 7D.
INSTALLATION: The humidifier may be mounted with the 6" outlet to the right or left by reversing the position of the Bypass Cover. The humidifier may be mounted on the warm or return air plenum with equal efficiency. See Typical Installations below.
ADDITIONAL MATERIALS THAT MAY BE NESSESARY:
2. 5/8" diameter drain tubing (G.F. #1099-16 suggested)
3. 3/4" O.D. drain tube clamp (G.F. #P-163 suggested)
4. 6" diameter galvanized by-pass pipe
5. 6" diameter galvanized elbow
6. 6" diameter galvanized damper
7. 6" diameter collar
8. wire, two-conductor #18 or heavier (G.F. #727-48 suggested)
9. transformer 120V, 60HZ primary 24V,
1OVA or greater secondary (G.F. #727-58 suggested)
10. air pressure switch (G.F. Model #12500 suggested)
HIGH BOY
',,,
", WARMAIR
' GENERALAIre"ACSERIES
HIGH EFFICIENCYAIRCLEANER
COUNTER-FLOW LOW BOY
WARM AIR
Cut 6" hole and install connecting collar, 6" elbow and by-pass pipe (not supplied). USE UNCRIMPED END IN HUMIDIFIER CABINET.
Connect by-pass pipe to collar and humidifier cabinet. Using holes at top and bottom of humidifier bypass opening drill 2---1/8" holes
through bypass pipe and screw by-pass pipe to humidifier cabinet. Install bypass cover by placing the tab of the bypass cover marked "TOP" behind the top flange of the humidifier cabinet, push up on the
bottom clip until it clears the opening of the humidifier cabinet then push in on the bottom of the bypass cover.
NOTE: If furnace is used for summer cooling, install inline damper in by-pass pipe.
COPPER
TUBING
PLASTIC
TUBING
Mount the self tapping saddle valve on either a cold or a hot water pipe. A side or top mount is best to avoid clogging from pipe sediment. Connect 1/4"
O.D. tubing to the saddle valve. Copper tubing requires a brass compression nut and brass sleeve. Plastic tubing requires a brass insert inside the tubing,
a plastic sleeve on the outside with a brass compression nut.
NOTE: DO NOT USE PLASTIC TUBING ON HOT WATER OR IN
CONTACT WITH ANY HOT PLENUM SURFACE OR DUCT. INSTALLATION OF THIS SADDLE VALVE MUST MEET OR EXCEED LOCAL CODES AND ORDINANCES.
DUCT HUMIDISTAT
TOP
MOUNTING TEMPLATE
1, REMOVE ADHESIVE BACKING AND APPLY TO
THE DUCT IN THE SELECTED LOCATION,
2, ACCU RATE|Y CENTER PUNCH ALL HOLES,
3. DRILl FOUR MOUNTING HOLES SIZE 3/32", DRILL NO, 42 OR 2 ram,
4. DRILl OTHER HOtES WITH 118"OR 3 mm DRILL,
5, BREAK METAL FROM GROUP OF HOLES AND
CUT OUT ON SOLID LINE WITH SHEARS.
+
+
OUTDOOR SUGC
TEMPERATURE SE
oF oC % R H
-20 29 IS°/o
0 -lS 2S_
+I0 -12 30_ *2O -7 3S%
+3O -I 40_
GENERALAire_
E ]
M _UMIDISTAT
\ /
+ +
Select location on vertical surface of warm or return air plenum for mounting humidifier and tape mounting template. Make sure the template is level. Do not install humidifier or 6" bypass pipe where the
blanked off ends of a cooling coil will restrict air flow to the humidifier. Extend horizontal centerline from template to the adjacent plenum. Scribe 6" circle 10" to 15"from side of humidifier, on cabinet centerline.
SADDLE VALVE INSTALLATION INSTRUCTIONS Copper Pipe
1. Retract piercing pin into valve body by turning handle counterclockwise.
2. Screw valve body into upper bracket and tighten.
3. Place rubber gasket over piercing pin.
4. Assemble saddle valve over copper pipe using enclosed screws, nuts and lower bracket.
5. Tighten screws evenly and firmly. Brackets should be parallel.
6. Complete compression connection to saddle valve outlet.
7. Turn handle clockwise to pierce tubing and close saddle valve.
8. Turn handle counterclockwise to open saddle valve, leave open for several seconds to flush dirt from pipe and tubing.
Steel, Brass or Hard Plastic Pipe
1. Shut off water supply and drain pipe.
2. Turn handle clockwise to expose piercing pin and close saddle valve.
3. Place rubber gasket over piercing pin.
4. Drill 1/8" hole in pipe using a hand crank drill to avoid shock hazard.
5. Assemble saddle valve over steel, brass or hard plastic pipe using enclosed screws, nuts and lower bracket.
6. Tighten screws evenly and firmly. Brackets should be parallel.
7. Complete compression connection to saddle valve outlet.
8. Turn handle counterclockwise to open saddle valve, leave open for several seconds to flush dirt from pipe and tubing.
Threaded Pipe Fittings
1. Turn handle clockwise to expose piercing pin and close saddle valve.
2. Seal valve body threads using pipe tape or sealant.
3. Install valve into 1/8" NPT fitting.
4. Complete compression connection to saddle valve outlet.
5. Turn handle counterclockwise to open saddle valve, leave open for
several seconds to flush dirt from pipe and tubing.
HUMIDIFIER
24v. SOLENOID VALVE
24v. HU I
60CY.
_1 ON-OFF HUMIDIFIER
ACC SWITCH TRANSFORMER VALVE EAC
727-58 24v. 24v. SOLENOID
GRD
50cv.11sv"(HOT)_ll
C
GRD
Center punch all 9 mounting holes on the template and drill with an
1/8" drill bit. Cut out center section of template and save humidistat
mounting template. Remove remaining template and start the three initial mounting screws. Mount humidifier cabinet in level position
and tighten screws. Install six additional screws at top and sides of cabinet.
COPPER TUBING PLASTIC TUBING
Attach solenoid valve into top of humidifier cover using 1/4 turn rotation.
If using copper tube, leave two coils of tube next to cabinet to allow
cover movement for changing pad. If using plastic tube, anchor tube 2
inches below humidifier and leave some slack. This will allow full cover movement.
Loosen the fitting nut on the solenoid valve 1/2 turn. Push the 1/4" O.D.
tubing straight into fitting until it bottoms on the fitting's shoulder. TIGHTEN NUT BY HAND. Additional tightening is not required.
DO NOT OVERTIGHTEN NUT AS THE THREADS WILL
STRIP AND THE FITTING WILL NOT FUNCTION PROPERLY.
DO NOT USE PLASTIC TUBING IN CONTACT WITH ANY HOT PLENUM SURFACE OR DUCT.
L1
115v. (HOT)
60CY.
O
115v. (HOT) 60CY.
L2
FAN CONTROL
BLOWER MOTOR
727_8 24v. HUMIDIFIER
ON-OFF 24v. SOLENOID VALVE
SWITCH _
ON-OFF
SWITCH PRESSURE 727-58 24v. 24v. SOLENOID
L1
12500 AIR HUMIDIFIER
SWITCH TRANSFORMER VALVE
TRANSFORMER
__ IIORD
GENERAI_Aire
INSTALLATEUR : VEUILLEZ REMPLIR ET POSTER LA CARTE DE GARANTIE UNE FOIS L'INSTALLATION
TERMINI_E. LAISSER LES DIRECTIVES D'INSTALLATION AU PROPRII_TAIRE DE LA MAISON.
PRE_CAUTION : L'installateur doit etre un technicien qualifie et experimente. Couper I'alimentation electrique avant de commencer I'installation. Ne pas installer
I'appareil dans un endroit o0 la temperature peut descendre sous 0 °C (32 °F) ou si la temperature du plenum depasse 93 °C (200 °F). Lors dIun branchement & un circuit de ventilateur & plusieurs vitesses, voir I'etape 7D.
INSTALLATION : LIhumidificateur peut etre installe avec la sortie de 15 cm (6 po) &droite ou & gauche en inversant le couvercle de derivation. L'humidificateur
fournit le meme rendement, quIil soit installe sur un plenum dIair chaud ou sur un plenum de reprise d'air. Voir rinstallation typique ci-dessous.
MATE_RIAUX ADDITIONNELS POUVANT I_TRE REQUIS :
1. Tuyau d'alimentation en cuivre ou en plastique de 6 mm (1/4 po) (G.F. n° 747-38 suggere)
2. Tube de drain de 1,6 cm (5/8 po) de diametre (G.F. n° 1099-16 suggere)
3. Collier de tube de drain de 1,9 cm (3/4 po) de diametre exterieur (G.F. n° P-163 suggere)
4. Tuyau de derivation galvanise de 15 cm (6 po)
5. Coude galvanise de 15 cm (6 po)
6. Registre galvanise de 15 cm (6 po)
7. Collier de 15 cm (6 po)
8. Fil, deux conducteurs n° 18 ou plus Iourd (G.F. n° 727-48 suggere)
9. Transformateur 120 V, 60 Hz primaire 24 V, 10 VA ou plus grand secondaire (G.F n° 727-58 suggere)
10. Commutateur de pression d'air (G.F. modele n° 12500 sugger6)
GENERALAIre'SERIES AC HAUT RENDEMENT FILTRE A AIR
DRAIN
AIR CHAUD
.>..-"
.J
. y....--''
z
.J
...--"
Couper un trou de 15 cm (6 po) et installer le collier de connexion, le coude et le tuyau de derivation de 15 cm (6 po) (ne sont par fournis). UTILISER
L'EXTR#MITE_ NON SERTIE DANS LE BO/TIER DE L'HUMIDIFICATEUR.
Connecter le tuyau de derivation au collier et au boitier de IIhumidificateur.
En utilisant les trous du haut et du bas de I'ouverture de derivation de
IIhumidificateur, percer 2 trous de 3 mm (1/8 po) & travers le tuyau de derivation et le visser au boTtier de I'humidificateur. Installer le couvercle de
derivation en pla?ant sa patte, marquee " TOP ,1derriere la bride superieure du boftier de IIhumidificateur, pousser sur le taquet du bas
jusqu'A ce qu'il d6gage I'ouverture du boTtier de I'humidificateur, puis pousser vers Ilinterieur sur le fond du couvercle de derivation.
REMARQUE : Si la fournaise sert b rafrafchir I'air durant I'_te, installer
le registre en ligne dans le tuyau de derivation.
TUYAUX EN
CUIVRE
TUYAUX EN
PLASTIQUE
Monter le robinet-vanne & etrier autotaraudeur sur un tuyau d'eau chaude ou dIeau froide. Un montage lateral ou sur le dessus est ideal pour eviter un
engorgement cause par les sediments du tuyau. Connecter un tuyau d'un diam. ext. de 6 mm (1/4 po) au robinet-vanne &etrier. Les tuyaux en cuivre
exigent un ecrou & compression et un manchon en laiton. Les tuyaux en plastique exigent un insert en laiton & I'interieur des tuyaux et un manchon en
plastique & Ilexterieur avec un ecrou & compression.
REMARQUE : NE PAS UTILISER DE TUYAUX EN PLASTIQUE AVEC DE L'EAU CHAUDE OU SUR UNE SURFACE DE CONTACT CHAUDE DE PLleNUM OU DE CONDUIT. L'INSTALLATION DE CE ROBINET-VANNE ,_,
I_TRIER DOlT RESPECTER OU DI_PASSER LES EXIGENCES DES CODES LOCAUX ET AUTRES ORDONNANCES.
GABARIT DE FIXATION
HAUT
DE L'HUMIDISTAT POUR CONDUITS
1. ENLEVEZ LE SUPPORT ADHESIF ET POSEZ SUR LE CONDUIT A L'ENDROIT CHOISI.
2, CENTREZ TOUS LES TROUS AU POINTEAU
AVEC PRECISION.
3. PERCEZ QUATRE TROUS DE MONTAGE DE 3/32 PO (MECHE N° 42 OU DE 2 ram),
4, PERCEZ LES AUTRES TROUS AVEC UNE
MECIIE DE 1/8 PO OU DE 3 ram,
5, DETACHEZ LE METAL DU GROUPE DE
) TROUS ET DECOUPEZ SUR LA LIGNE
._!,E......................
OUTDOOR SUGG
TEMPERATURE SE ¸
OF oC _ R H
-2O 29 15%
-10 -23 20_ 0 -18 25_
+_O -12 30_ *20 -_ 3S_
+_0 -1 40_
GENERALAir_
J
Loading...
+ 7 hidden pages