24-volt and 120-volt Current Sensing Relays
Installation Instructions
General Filters, Inc. 43800 Grand River Ave., Novi, Michigan 48375 • Phone: (248) 476-5100
Fax (248) 349-2366 • www.generalaire.com
Designed to interface with humidifiers and most heating and cooling systems.
It senses current rather than measuring voltage, making it more reliable. It is less expensive than using traditional flow switches,
pressure switches or other types of relays. The relay installs around the blower motor’s common lead and interface easily into the
circuitry.
The current sensing relay case is constructed from high-impact plastic. The lead wire bracket is protected by a soft sponge insert, in
order to prevent damage to the motor/blower wire and/or accidental contact with any metal.
Important:
The wire lead bracket needs to carry a minimum of 5.0 amps for proper operation. If the current draw is less than 5.0 amps,
wrap the lead wire around the bracket so that it passes between the bracket and relay housing two or more times.
Caution:
Turn off all power to the furnace motor circuit and cabinet.
GA50 24-volt and GA51120-volt Current Sensing Relay
General Installation Procedures
1. Follow the step-by-step instructions for
Common
Blower Lead
5 Amp. Min.
L
O
A
D
24 or 120 VAC.
mounting the General Filters humidifier,
found in the humidifier installation
manual. DO NOT connect the electrical,
water supply or drain at this time.
2. Please follow these wiring instructions:
A. Turn off electrical power to the
furnace. Attach the current sensing
relay around the common lead of
the furnace blower motor. The relay
must be located at least 3” from any
transformer. Make sure, the relay’s
metal bracket does not touch any
other metal. (See detail A)
Model X Wiring Diagrams
GeneralAire Model 1137 GeneralAire Model 1042 DME GeneralAire Models 1042 LH, 1099LH & SL16
B. Use a wire nut to connect one lead
wire. Use a wire nut to connect one
lead wire from the current sensing
relay to one of the 24V wires from
the humidifier. (X) (Additional wire
length may be needed.)
C. Use a second wire nut to connect
the remaining lead wire from
the current sensing relay to the
humidistat (Y).
D. To complete the circuit, use a third
wire nut to connect the humidistat’s
second lead wire to the 24V lead
from the humidifier (Z).
3. Follow the instructions supplied with the
humidifier to complete the installation.
COMMON LEAD
DETAIL A
120 V
GeneralAire Fan Powered Humidifier
CURRENT SENSING
RELAY
120 V 24 V
GeneralAire Bypass with Temperature
Compensating Auto Control
METAL BRACKET
CURRENT SENSING
RELAY
120 V 24 V
COMMON LEAD
FURNACE BLOWER
MOTOR
GeneralAire Bypass with manual control
24-volt and 120-volt Current Sensing Relays
Model Air Cleaner Installation
Installation Instructions
1. Install the air cleaner according to the
manufacturer’s instructions.
2. Install the GA51 on the common wire of the blower
motor as shown in the diagram.
3. Open the main power junction box on the side of
the furnace and run the leads of the GA51 relay
into the junction box.
120 VAC
2 x 4
Electrical
Box
EAC
4. Connect the leads of the
GA51 relay in series with
one of the electronic air
cleaner leads. Connect the
remaining lead and ground
wire. The 120 VAC source
must be independent of
the furnace blower motor.
Checkout Procedures
1. Replace all safety devices.
2. Reconnect power to furnace.
3. Activate furnace blower motor.
4. Check load for operation. It should now be working properly. Check
indicating lamp or other conditions showing that the load is receiving
power.
5. Switch off the blower unit. The power to the device should shut off.
6. If the device is activated properly and turns off when the power
through the common wire is removed, installation is complete.
5. Check all wire connections, close junction box
and restore furnace to working order. Test proper
functioning by observing that the air cleaner’s
indicator lamp turns on when the blower runs and
turns off when the blower stops.
GASI
EAC
120 VAC
7. If the device is not powered when the blower is turned on:
• Ensure the device’s power switch is in the “ON” position.
• Recheck all wiring.
• Check line fuses.
• Confirm that five or more amps is flowing through the control wire.
Wrap additional turns around the bracket if necessary.
Technical Specifications
24-volt and 120-volt Current Sensing Relay
Voltage Range 21-24 VAC, 50-60 Hz 100-125 VAC, 50-60 Hz
Sensing Current Minimum 5 amps Minimum 5 amps
Operating Ambient Temperature Range 40˚F - 104˚F 40˚F - 104˚F
Dimensions
Load Ratings Maximum (12 watts) 0.50 amps
GA50
24-volt Model
Minimum (3 watts) 0.12 amps
GA51
120-volt Model
Maximum (50 watts) 0.42 amps
Minimum (3 watts) 0.03 amps