GeneralAire EDMK4 User Manual

Elite Steam
Residential Steam Humidifiers
Revision 3.5
Warning
LATCH THE CYLINDER CLAMP
REMOVE BEFORE INSTALLING
REMOVE BEFORE INSTALLING
REMOVE BEFORE INSTALLING
REMOVE BEFORE INSTALLING REMOVE BEFORE INSTALLING
If present, remove the following items:
3
We wish to save you time and money! We can assure you that the thorough reading of this manual will guarantee correct installation and safe use of the product described.
IMPORTANT WARNINGS
BEFORE INSTALLING OR HANDLING THE HUMIDIFIER PLEASE CAREFULLY READ AND FOLLOW THE INSTRUCTIONS AND SAFETY STANDARDS DESCRIBED IN THIS MANUAL AND ON THE LABELS ATTACHED TO THE Elite Steam.
CAUTION: ALWAYS DISCONNECT THE MAIN POWER BEFORE OPENING OR SERVICING THE HUMIDIFIER!
Elite Steam produces non-pressurized steam by means of electrodes immersed in the water contained in the plastic steam generator cylinder. Electric current passes through the water between the electrodes, heating the water into steam, which is then used to humidify the air.
The quality of the water used affects the operation of this unit, so the Elite Steam may be supplied with untreated water, as long as this is drinkable and not softened or demineralized. The water converted into steam is automatically replaced through an electric fill valve. Periodically, based on the water quality, the unit will also drain some water to dilute the build-up of minerals in the steam generator. In cases of high water mineral content, an activated carbon filter is series with a particulate filter, no more than 5 microns is suggested.
This humidifier has been designed exclusively to directly humidify rooms or ducts, using a distribution system. The installation, use and maintenance operations must be carried out according to the instructions contained in this manual and on the labels applied internally and externally.
IMPORTANT: BEFORE beginning installation:
Check for shipping damage to cartons. Mark the shipping waybill accordingly.  Open cartons and check for any hidden damage. Mark the shipping waybill accordingly.  Check packing slip to ensure all items have been received. Notify GENERAL FILTERS, INC. of any shortages or damaged
parts. You must notify General Filters, Inc. within 5 working days of any shortages.
CAUTION: ELECTRIC SHOCK HAZARD! The humidifier has components under power inside! CAUTION: SCALDING HAZARD! The humidifier has hot parts (100°C/ 212°F) WARNING: Install the humidifier out of the reach of children. The humidifier must be installed in accordance with all local and national standards. All service and/or maintenance operations must be performed by qualified personnel who are aware of the necessary precautions and are capable of performing the operations correctly. Disconnect the humidifier from the main power supply before accessing any internal parts. The conditions of the environment and the power supply voltage must comply with the specified values listed on the data label in the humidifier. All other uses and modifications made to the humidifier that are not authorized by the manufacturer are considered incorrect, and the manufacturer assumes no liability for the consequences of any such unauthorized use.
Please note that the humidifier contains powered electrical devices and hot surfaces.
The humidifier is made of metallic and plastic parts. All parts must be disposed of according to the local and national standards for waste disposal.
WARNING: Your humidifier requires water to operate. Do NOT mount it above materials or machinery that could be damaged if a leak occurs. General Filters, Inc. assumes no responsibility for consequential or inconsequential damage as a result of any leaks.
Disposal of the parts of the humidifier: the humidifier is made up of metallic and plastic parts. All parts must be disposed
of according to the local standards on waste disposal.
Elite Steam +030222075 Rev. 3.5 – July 2012
4
Elite Steam +030222075 Rev. 3.5 – July 2012
5
CONTENTS
1. How The Elite Steam Works 6
1.1 Basic Operation 6
1.2 Cylinder Life 7
1.3 Calculating Humidity Load 7
2. Models 8
3. INSTALLATION 9
3.1 Positioning 9
3.2 Mounting 9
3.3 Plumbing 11
3.4 Steam distribution 12
3.5 Power wiring 15
3.6 Control wiring 15
3.7 Wiring Connections 17
4. START-UP 18
4.1 Startup Checklist 18
4.2 The Elite Steam Controller 18
4.3 Starting Elite Steam 18
4.4 Starting with a new cylinder 18
5. OPERATING ELITE STEAM 19
5.1 Displaying Information 19
5.2 Changing The Maximum Production 19
5.3 Activating Manual Drain 19
5.4 Resetting the hour counter 19
5.5 Using the E2 Humidistat 20
5.6 Alarms 20
6. TROUBLE SHOOTING 21
7. Maintenance 22
7.1 Periodic checks 22
7.2 Cylinder maintenance 22
7.3 Replacement Parts 23
8. TECHNICAL SPECIFICATIONS 24
9. LIMITED WARRANTY 25
Elite Steam +030222075 Rev. 3.5 – July 2012
6
No.
Description
A
Steam generator cylinder
B
Room blower/manifold (optional)
C
User interface/display
D
On/Off, SET buttons
E
Fill & tempering valves
F
Drain pump
Tab. 1.a
F
Fig. 1.a
HL
DP
DT
EVF
8 9
3
13
6
10
2
4
1
11
7
12
5
A
F
B
C
D
E
1. HOW THE ELITE STEAM WORKS
1.1 Basic Operation
Elite Steam is an electrode humidifier. It produces steam for humidification by
passing electric current through the water between metal electrodes in the plastic steam generator cylinder. There are no heating elements. Steam output is directly proportional to the conductivity of the water, and the amount of electrode immersed in the water.
On a call for humidity, the Elite Steam controller will open the water fill valve (1) and allow water to enter the cylinder. A flow restrictor (4) prevents the unit from filling too quickly or with too much pressure. The water flows up the fill tube (2) and into the fill cup (3). Water then flows over the dam in the fill cup (3), which creates a 1” air gap to prevent backflow of contaminated water into the feed lines, and through the fill tube (6) and into the bottom of the steam cylinder (5). Any backflow or overflow of water travels through the overflow hose (13) to the drain.
As the water fills the cylinder, it will reach the electrodes (7) and current will begin to flow. As the water continues to fill the cylinder, the current will increase, and this is monitored by an amperage transformer connected to one of the power wires and located on the electronic controller. When the desired current is reached, the fill valve will close (1) and the water will then begin to warm and produce steam. If the water reaches the cylinder full probes (9) or if current rises too much, the drain pump (11) will be activated to drain away some water and reduce the current flow to acceptable levels. Note that, any time the drain pump is activated, the tempering valve (10) will be opened for tempering the hot drained water down to 140 degrees F / 60 degrees C in accordance to local and national standards.
Periodically, based on the incoming water conductivity, the unit will run drain pump (11) and drain some water to reduce the mineral concentration. Every 120 hours the unit automatically drains to remove mineral sediment on the bottom of the cylinder. A strainer (12) in the cylinder helps to prevent mineral debris from jamming the drain pump (11). In case Elite Steam remains powered but idle, i.e. without producing steam, for more than 72 hours (3 days), the cylinder will be emptied to not have stagnant water inside.
If there is no water in the cylinder, there will be no current flow and no steam production. The electrodes do not burn out, but they will eventually become completely coated with mineral and the cylinder will then need to be replaced. Cleaning cylinders may cause electrode damage, therefore voiding its warranty. See 7.2.2 maintenance section on page 21.
Fig. 1.b
Elite Steam +030222075 Rev. 3.5 – July 2012
7
Table 1.2 Pounds of Moisture / Hour / Cubic Foot *
Indoor Air
Temp °F
35%
Indoor RH% 40%
45%
50%
68
0.00015
0.00018
0.00021
0.00024
70
0.00017
0.00020
0.00023
0.00026
72
0.00019
0.00022
0.00025
0.00028
* Based on .5 air charges per hour.
100%
20%
Cylinder Life
Fig. 1.c
1.2 Cylinder Life
1.2.1 Basics of the Steam Cylinder The Steam Cylinder is the engine of the humidifier. As the humidifier operates water is evaporated and minerals are left behind. Much of these minerals are removed through the cylinder drain. Some are deposited on the walls of the cylinder and the cylinder electrodes. When a lower section of the electrodes develop a thick coating, the water level is raised to expose clean electrode surface. Eventually minerals cover the electrodes’ entire length with a thick coating and little electrical current can pass between them resulting in poor steam output. The humidifier can sense the low amperage and will display the E6 Cylinder Exhausted error code. There are several factors that influence cylinder life.
1.2.2 Water Characteristics of water influence cylinder life and can vary greatly from place to place. Total mineral content of the water is important. Equally important is what minerals are present in the water. Most water conditions result in flaky scale that eventually fills the bottom of the cylinder until it can no longer function. Water with high silica content can result in a thin glass-like coating on the electrodes that is highly insulating resulting in shorter cylinder life. Only cold water is to be used. Water conductivity that is not matched to the correct cylinder will shorten cylinder life.
1.2.3 Water Filtration Typically additional filtration of the incoming water supply is not necessary. If, however, mineral content is known to reduce cylinder life excessively or if cylinder life proves insufficient then water filtration can be added. In most cases the addition of a two element water filter can improve cylinder life. The filter should contain an activated carbon element and a particulate filter element rated for 5 microns or less. Micron is a size measurement. The filter system should have a flow rate of at least 2 gpm. The activated carbon will absorb much of the mineral content while the particulate filter will catch any granular material or sediment. It is important to remember that the increase in cylinder life will be accompanied by the need to replace filter elements with each cylinder change.
1.2.4 Humidity Load and Cylinder Life Humidity load demands have an effect on cylinder life. Normal installations where humidity capacity is properly sized require only intermittent periods where full humidifier capacity is required. This allows the water level in the cylinder to be increased only as electrode segments become insulated. This tends to maximize cylinder life.
Extraordinary installations that require constant operation at full capacity reduce cylinder life. The water level in the cylinder is, on average, much higher, and the electrodes become completely insulated more quickly. Installations like this may result in cylinder life of less than 1000 hours.
The importance of providing adequate humidifier capacity should not be underestimated.
1.2.5 Maximum Production Another factor affecting cylinder life is the maximum production setting. A higher production rate will result in a shorter cylinder life. For this reason DS-25 and RS-25 units are preset from the factory at 70%. Further reductions in Maximum Production will extend cylinder life. See Figure 1.c.
1.2.6 Structures Under Construction In high end construction projects, humidification is often required while the structure is being finished. Humidification is necessary to protect and stabilize wood floors, trim and decoration. Humidification load, however, in an unfinished structure may be five to eight times higher than when finished. Elite Steam humidifiers may be operated while construction is underway but, reduced cylinder life is to be expected and budgeted for. Good practice dictates that the steam cylinders also be replaced once the project is complete.
1.3 Calculating Humidity Load
1.3.1 Steps to Determine Humidity Load
*Based on .5 air changes per hour.
Total Square Footage x Average Ceiling Height x Factor From Table 1.2 x 1.05 for each Fireplace Humidity Load in lbs./hour
x 2.88 convert to gallons/day Gallons per Day Humidity Load
Elite Steam +030222075 Rev. 3.5 – July 2012
8
PART NUMBER
DESCRIPTION
PARTS INCLUDED
RS 15P Fig. 2.b
Room steam dicharge, 15 gallons per day (5.5 Lbs per hour) 115-120v
Complete Humidifier. GFX3 humidistat, code valve, water fill connector, water supply tubing
RS 25 Fig. 2.b
Room steam dicharge, 35 gallons per day (12 Lbs per hour) 220-240v
Complete Humidifier. GFX3 humidistat, code valve, water fill connector, water supply tubing
DS 15P Fig. 2.a
Duct steam injection 15 gallons Humidifier only, Kit selection required per day (5.5 Lbs per hour) 115-120v
Humidifier only, Kit selection required DS 25 Fig. 2.a
Duct steam injection 35 gallons per day (12 Lbs per hour) 220-240v
Humidifier only, Kit selection required
DMNKIT (not shown)
Duct mount kit
8 ft. steam hose, nozzle, GFX3 humidistat, code valve, water fill connector, condensate hose, water supply tubing, air proving pressure switch.
RMB 15 (not shown)
Remote mount blower kit for DS 15
12 ft. steam hose, GFX3 humidistat, code valve, condensate hose, water fill connector, water supply tubing, and thru-the wall sleeve with 120v blower and grille pkg.
RMB 35 (not shown)
Remote mount blower kit for DS 25
12 ft. steam hose, GFX3 humidistat, code valve, condensate hose, water fill connector, water supply tubing, and thru-the wall sleeve with 240v blower and grille pkg.
EDMK4 (not shown)
Economy Duct mount kit
4 ft. steam hose, nozzle, 5 ft. condensate hose, fill connector, air proving pressure switch (Humidistat not included)
2. MODELS
There are two basic models available in two voltages. Duct models require selection of an additional kit.
Duct Steam Injection Room Steam Discharge
Fig. 2.a Fig. 2.b
Elite Steam +030222075 Rev. 3.5 – July 2012
MODEL LIST
9
3. INSTALLATION
Millimeters
Inch
A
(150 mm)
6”
B
(150 mm)
6”
C
(150mm)
6”
D
(150 mm)
6”
E
(600 mm)
24”
F
max. 0.2°
Tab. 3.a
Fig. 3.a
Duct Steam Injection
C
D
Fig. 3.b
Millimeters
Inch
A
150 mm
6”
B
1800 mm
72”
C
1800mm
72”
D
600 mm
24”
Tab. 3.b
Room Steam Discharge
Millimeters
Inch
A
341 mm
13.5“
B
204 mm
8.1“
C
600 mm
23.7“
Kilograms
Pounds
Weight empty
8kg
18 lbs
Weight packaged
10kg
22 lbs
Weight installed with water
12kg
26 lbs
Tab. 3.c
Unit Dimensions: Duct and Room Units
Fig. 3.c
3.1 Positioning
The Elite Steam has been designed for wall mounting and, since it is an atmospheric steam humidifier, should be placed close to the point where the steam will be used, to minimize the steam hose length (and the amount of condensate). Certain clearances must be maintained around the unit for safety and maintenance.
3.2 Mounting
3.2.1 Removing the front cover
The front cover is secured by four screws located at the four corners of the unit. Use a phillips head screwdriver to remove the four cover screws. Then simply pull the front cover away from the back part of the unit. Return it in reverse order.
Be careful not to over-tighten the screws.
Fig. 3.d
Fig. 3.e
Elite Steam +030222075 Rev. 3.5 – July 2012