E2 Humidistat
INTRODUCTION
Thank you for selecting the GENERALAire E2
Humidistat. A professional technician should install the
unit.
FRONT VIEW
1. Operation modes
2. Moisture is being added into the environment
3. Humidity / temperature reading
: Toggle between OFF, MANUAL and AUTO
4.
modes (if outdoor sensor is connected)
5.
: Toggle between indoor humidity and indoor /
outdoor temperature displays (if outdoor sensor is
connected)
6. °C / °F: Select temperature unit
7. Wall mount cover. Squeeze top-bottom to open.
8. Humidity index chart
9. Outdoor temperature reading is displayed
10. Temperature / humidity setting is displayed
11. Temperature / humidity offset is displayed
12. Indoor temperature / humidity reading i
/ : Increase / decrease setting; enter
13.
humidity / temperature offset setting
BACK VIEW
14.
TO MOUNT THE UNIT
NOTES
• To remove the humidistat from the base, squeeze
• To remove the humidistat from the wall, lift up on
• Before wall mounting, please remove the gasket.
• Before return air duct mounting, please remove the
• If return air duct mounting, route wires between
MOUNT THE OUTDOOR SENSOR
Mount the sensor outside the house:
• Do not mount on South side of the house or in
• Place at least 4 feet away from any exhaust vent.
• If in air intake, place 1 foot or closer to outside wall.
• Place at least 6” higher than possible snow.
• Do not route sensor wire near high voltage wires.
Removable terminal block for wire connections.
the louvered base at the top and bottom.
the humidistat and pivot top away from wall
breakout piece. Remove terminal block for wiring.
tat and base.
humidis
direct sunlight.
s dis
played
14.
WIRING
• If Outdoor Temperature is over 50°F or 10°C, a safety
stop will prevent calling for humidity. Test circuit by
removing one outdoor sensor wire.
• Confirm correct outdoor temperature reading. If
temperature reading is high, use Diagram for
GREATER THAN 20 FEET.
WIRING OUTDOOR SENSOR LESS THAN 20 FEET
SNSR
HUM
ACN
ACL
SNSR
COMMON GROUND
SNSR
SNSR
20 FEET MAX.
HUMIDIFIER CONTROL LEADS
(YELLOW WIRES)
(NOT USED IN MANUAL MODE)
FIELD
SUPPLIED
WIRING OUTDOOR SENSOR GREATER THAN 20 FEET
HUM
ACN
ACL
FIELD
SUPPLIED
COMMON GROUND examples:
Water pipe, metal duct, household electrical safety ground, conduit.
The wire from the unit and the wire from the sensor must both be
connected to the same common ground, for example both to water
pipe OR both to the household safety ground.
NOTE: Separate sensor and common ground by at least 4 inches.
Ex: Don’t lay the wire on the metal conduit or duct used for the ground.
WIRING TO 24V. BYPASS HUMIDIFIER
AC N
AC L
HUM
727-58 24 V. TRANSFORMER
OR 24 VAC POWER SUPPLY
SWITCHED WITH FURNACE OPERATION
WIRING TO 1137, 1000 POWER HUMIDIFIER
AC N
AC L
HUM
24V OUTPUT FROM HUMIDIFIER (RED WIRES) OR
727-58 24 V. TRANSFORMER SWITCHED WITH FURNACE OR
OR 24 VAC POWER SUPPLY SWITCHED WITH FURNACE.
WIRING TO DS-15, RS-15, CS-15, DS-35,
RS-35, CS-35 ELITE STEAM HUMIDIFIER
SNSR
AC N
AC L
HUM
SPLICES: NO MORE THAN
ONE PER LEAD.
300 FEET MAX.
JUMPER WIRE
OUTDOOR TEMP. SENSOR
(NOT USED IN MANUAL MODE)
OUTDOOR TEMP. SENSOR
(NOT USED IN MANUAL MODE)
OUTDOOR TEMP. SENSOR
OR 24V. DRUM MOTOR
SPLICES: NO
MORE THAN
ONE PER
LEAD.
HUMIDIFIER 24V.
SOLENOID VALVE
N2
GND
N1
AB
AB
GND
IN
NO
C
ALARM
NC
C
NO
EXT FAN
GND
24V
TO USE THE UNIT
Press to select OFF, MANUAL or AUTO mode (if
outdoor sensor is connected).
• OFF mode: The humidifier is turned off.
• MANUAL mode: The E2 will work to maintain the
single humidity selected. You can set your desired
humidity level by pressing
or . The humidifier
will turn ON or OFF according to your manual setting.
(The humidifier will operate when the measured
relative humidity falls more than 2% below the set
point.) Humidity will have to be lowered when weather
is colder or if condensation is suspected.
Suggested Setting Outdoor Temperatures
15% -20 -29
20% -10 -23
25% 0˚F -18˚C
30% +10 35% +20 - 7
40% +30 - 1
˚F ˚C
˚F ˚C
˚F ˚C
12
˚F ˚C
˚F ˚C
• AUTO mode: The E2 will automatically raise the
humidity as
the outdoor temperature increases. This
provides the highest possible humidity. The E2 will
automatically lower the humidity as temperatures
drop. This minimizes the risk of condensation on cold
surfaces like windows. You can adjust the Auto
Humidity Index Set Point from 0 (low) to 10 (high) by
p
ress
ing or . The Humidity Index is based on
the outdoor temperature and indoor humidity. The
humidifier will switch ON/OFF according to the
calculated auto humidity index set point. Lower Index
settings are for older homes with less insulation and
vapor barriers. Higher Index settings are for newer
homes with complete vapor barriers, triple pane
windows and high R-value insulation. If condensation
occurs
e Index setting by 2 points until
reduc
condensation stops.
NOTE If the outdoor temperature sensor fails,
flashes and the unit will default to MANUAL mode.
• To toggle between indoor / outdoor temperature
and indoor humidity: Press
.
• To change the temperature unit: Press °C / °F.
• To set the temperature / humidity offset in
MANUAL or AUTO mode:
1. Simultaneously press
and when viewing the
temperature or humidity reading.
2. Use
3. Press
or to change the setting (-3 to 3).
and simultaneously or wait 5
seconds to confirm and move onto the next setting.
• Lo or Hi will flash on the display when:
MEASUREMENT
Indoor temp.
Outdoor temp. Below -40oC
LO HI
Below 0oC
o
F)
(32
o
(-40
F)
Above
99
Above 50
(122
o
F(37oC)
o
F)
o
C
Humidity Below 10% Above 90%
• If power is lost, current settings are retained.
PRECAUTIONS
This product is engineered to give you years of
satisfactory service. Here are a few precautions:
• Do not allow excess humidification. Excess
humidity can cause condensation and enable mold
and mildew growth.
• Do not tamper with the unit’s internal components.
The unit contains no user-serviceable parts.
• The contents of this manual may not be reproduced
without the permission of the manufac
NOTE The technical specifications for this product and
turer.
the contents of the user manual are subject to change
without notice.
SPECIFICATIONS
TYPE DESCRIPTION
Dimensions
H x W x D
84 x 84 x 20 mm
(3.3 x 3.3 x 0.8 in.)
Weight 95.4 g (3.4 ounces)
Temperature unit °F / °C
Temperature operating
range
32°F to 99°F
-0°C to 37°C
Temperature resolution 2°F (1 °C)
Humidity range 10% to 60%
Humidity resolution 1%
Power 18-30 Volts, AC
TECHNICAL SUPPORT