GeneralAire DS50 User Manual

Page 1
DS 50 / DS 50 LC
Elite Steam Residential Humidifiers
Revision 1.2
Page 2
Warning
If present, remove the following items:
Page 3
IMPORTANT WARNINGS
We wish to save you time and money! We can assure you that the thorough reading of this manual will guarantee correct installation and safe use of the
described.
product
BEFORE INSTALLING OR HANDLING THE HUMIDIFIER PLEASE CAREFULLY READ AND FOLLOW THE INSTRUCTIONS AND SAFETY STANDARDS DESCRIBED IN THIS MANUAL AND ON THE LABELS ATTACHED TO THE DS 50 / DS 50 LC. THIS HUMIDIFIER MUST BE INSTALLED BY A QUALIFIE D HVAC, PLUMBING, OR ELECTRICAL
CONTRACTOR. ALL WARRANTIES ARE VOID IF INSTALLED BY A NON-TECHNICIAN.
CAUTION: ALWAYS DISCONNECT THE MAIN POWER BEFORE
OPENING OR SERVICING THE HUMIDIFIER!
The Elite Steam produces non-pressurized steam by means of electrodes immersed in the water contained in the plastic steam generator cylinder. Electric current passes through the water between the electrodes, heating the water into steam, which is then used to humidify the air.
The quality of the water used affects the operation of this unit, so the Elite Steam may be supplied with untreated water, as long as this is drinkable and not softened or demineralized. The water converted into steam is automatically replaced through an electric fill valve. Periodically, based on the water quality, the unit will also drain some water to dilute the build-up of minerals in the steam generator. In cases of high water mineral content, an activated carbon filter is series with a particulate filter, no more than 5 microns is suggested.
This humidifier has been designed exclusively to directly humidify rooms or ducts, using a distribution system. The installation, use and maintenance operations must be carried out according to the instructions contained in this manual and on the labels applied internally and externally.
IMPORTANT: BEFORE beginning installation:
Check for shipping damage to cartons. Mark the shipping waybill accordingly.
Open cartons and check for any hidden damage. Mark the shipping waybill accordingly.
Check packing slip to ensure all items have been received. Notify GENERAL FILTERS, INC. of any shortages or
damaged parts. You must notify General Filters, Inc. within 5 working days of any shortages.
CAUTION: ELECTRIC SHOCK HAZARD! The humidifier has components under power inside! CAUTION: SCALDING HAZARD! The humidifier has hot parts (100°C/ 212°F) WARNING: Install the humidifier out of the reach of children. The humidifier must be installed in accordance with all local and national standards. All service and/or maintenance operations must be performed by qualified personnel who are aware of the necessary precautions and are capable of performing the operations correctly. Disconnect the humidifier from the main power supply before accessing any internal parts. The conditions of the environment and the power supply voltage must comply with the specified values listed on the data label in the humidifier. All other uses and modifications made to the humidifier that are not authorized by the manufacturer are considered incorrect, and the manufacturer assumes no liability for the consequences of any such unauthorized use.
Please note that the humidifier contains powered electrical devices and hot surfaces.
WARNING: Your humidifier requires water to operate. Do NOT mount it above materials or machinery that could be damaged if a leak occurs. General Filters, Inc. assumes no responsibility for consequential or inconsequential damage as a result of any leaks.
Disposal of the parts of the humidifier:
the humidifier is made up of metallic and plastic parts. All parts must be
disposed of according to the local standards on waste disposal.
DS 50 / DS 50 LC +030222065 Rev. 1.2
3
Page 4
DS 50 / DS 50 LC +030222065 Rev. 1.2
4
Page 5
CONTENTS
1. HOW THE ELITE STEAM WORKS 6
1.1 B
1.2 C
1.3 C
2.
3.
3.1 P
3.2 M
3.3 P
3.4 S
3.5 P
3.6 C
3.7 W
4.
4.1 S
4.2 T
4.3 S
4.4 S
ASIC OPERATION 6 YLINDER LIFE 7 ALCULATING HUMIDITY LOAD 7
MODELS 8
INSTALLATION 9
OSITIONING 9
OUNTING 9 LUMBING 11 TEAM DISTRIBUTION 12 OWER WIRING 15 ONTROL WIRING 15
IRING CONNECTIONS: 17
START-UP 18
TARTUP CHECKLIST 18 HE ELITE STEAM CONTROLLER 18 TARTING THE ELITE STEAM 18 TARTING WITH A NEW CYLINDER 18
5.
OPERATING THE ELITE STEAM 19
5.1 D
5.2 C
5.3 A
5.4 R
5.5 H
5.6 A
6.
7.
7.1 P
7.2 C
7.3 R
8.
9.
ISPLAYING INFORMATION 19 HANGING THE MAXIMUM PRODUCTION 19 CTIVATING MANUAL DRAIN 19 ESETTING THE HOUR COUNTER 19 UMIDISTATS 20 LARMS 20
TROUBLE SHOOTING 21
MAINTENANCE 22
ERIODIC CHECKS 22 YLINDER MAINTENANCE 22 EPLACEMENT PARTS 23
TECHNICAL SPECIFICATIONS 24
LIMITED WARRANTY 25
DS 50 / DS 50 LC +030222065 Rev. 1.2
5
Page 6
1. HOW THE ELITE STEAM WORKS
1.1 Basic Operation
The Elite Steam is an electrode humidifier. It produces steam for humidification
by passing electric current through the water between metal electrodes in the plastic steam generator cylinder. There are no heating elements. Steam output
8 9
is directly proportional to the conductivity of the water, and the amount of electrode immersed in the water.
On a call for humidity, the Elite Steam controller will open the water fill valve (1) and allow water to enter the cylinder. A flow restrictor (4) prevents the unit from filling too quickly or with too much pressure. The water flows up the fill tube (2)
7
5
HL
and into the fill cup (3). Water then flows over the dam in the fill cup (3), which creates a 1” air gap to prevent backflow of contaminated water into the feed lines, and through the fill tube (6) and into the bottom of the steam cylinder (5). Any backflow or overflow of water travels through the overflow hose (13) to the
12
DP
drain. As the water fills the cylinder, it will reach the electrodes (7) and current will
begin to flow. As the water continues to fill the cylinder, the current will
Fig. 1.a
11
increase, and this is monitored by an amperage transformer connected to one of the power wires and located on the electronic controller. When the desired current is reached, the fill valve will close (1) and the water will then begin to warm and produce steam. If the water reaches the cylinder full probes (9) or if current rises too much, the drain pump (11) will be activated to drain away some water and reduce the current flow to acceptable levels. Note that, any time the drain pump is activated, the tempering valve (10) will be opened for tempering the hot drained water down to 140 degrees F / 60 degrees C in accordance to local and national standards.
Periodically, based on the incoming water conductivity, the unit will run drain pump (11) and drain some water to reduce the mineral concentration. Every 120 hours the unit automatically drains to remove mineral sediment on the bottom of the cylinder. A strainer (12) in the cylinder helps to prevent mineral debris from jamming the drain pump (11). In case DS 50 / DS 50 LC remains powered but idle, i.e. without producing steam, for more than 72 hours (3 days), the cylinder will be emptied to not have stagnant water inside.
If there is no water in the cylinder, there will be no current flow and no steam production. The electrodes do not burn out, but they will eventually become completely coated with mineral and the cylinder will then need to be replaced. Cleaning cylinders may cause electrode damage, therefore voiding its warranty. See 7.2.2 maintenance section on page 21.
3
EVF
DT
10
13
2
6
4
1
B
A
E
C
D
Fig. 1.b
DS 50 / DS 50 LC +030222065 Rev. 1.2
6
No. Description
A Steam generator cylinder B User interface/display C On/Off, SET buttons D Fill & tempering valves E Drain pump
Tab. 1.a
Page 7
1.2 Cylinder Life
1.2.1 Basics of the Steam Cylinder The Steam Cylinder is the engine of the humidifier. As the humidifier operates water is evaporated and minerals are left behind. Much of these minerals are removed through the cylinder drain. Some are deposited on the walls of the cylinder and the cylinder electrodes. When a lower section of the electrodes develop a thick coating, the water level is raised to expose clean electrode surface. Eventually minerals cover the electrodes’ entire length with a thick coating and little electrical current can pass between them resulting in poor steam output. The humidifier can sense the low amperage and will display the E6 Cylinder Exhausted error code. There are several factors that influence cylinder life.
1.2.2 Water Characteristics of water influence cylinder life and can vary greatly from place to place. Total mineral content of the water is important. Equally important is what minerals are present in the water. Most water conditions result in flaky scale that eventually fills the bottom of the cylinder until it can no longer function. Water with high silica content can result in a thin glass-like coating on the electrodes that is highly insulating resulting in shorter cylinder life. Only cold non-softened tap water is to be used. Water conductivity that is not matched to the correct cylinder will shorten cylinder life.
1.2.3 Water Filtration Typically additional filtration of the incoming water supply is not necessary. If, however, mineral content is known to reduce cylinder life excessively or if cylinder life proves insufficient then water filtration can be added. In most cases the addition of a two element water filter can improve cylinder life. The filter should contain an activated carbon element and a particulate filter element rated for 5 microns or less. Micron is a size measurement. The filter system should have a flow rate of at least 2 gpm. The activated carbon will absorb much of the mineral content while the particulate filter will catch any granular material or sediment. It is important to remember that the increase in cylinder life will be accompanied by the need to replace filter elements with each cylinder change.
1.2.4 Humidity Load and Cylinder Life Humidity load demands have an effect on cylinder life. Normal installations where humidity capacity is properly sized require only intermittent periods where full humidifier capacity is required. This allows the water level in the cylinder to be increased only as electrode segments become insulated. This tends to maximize cylinder life.
Extraordinary installations that require constant operation at full capacity reduce cylinder life. The water level in the cylinder is, on average, much higher, and the electrodes become completely insulated more quickly. Installations like this may result in cylinder life of less than 1000 hours.
The importance of providing adequate humidifier capacity should not be underestimated.
1.2.5 Maximum Production
Cylinder Life
Another factor affecting cylinder life is the maximum production setting. A higher production rate will result in a shorter cylinder life. For this reason DS50 or DS50LC units are preset from the factory at 70%. Further reductions in Maximum Production will extend cylinder life. See Figure 1.c.
Fig. 1.c
100%
20%
1.2.6 Structures Under Construction In high end construction projects, humidification is often required while the structure is being finished. Humidification is necessary to protect and stabilize wood floors, trim and decoration. Humidification load, however, in an unfinished structure may be five to eight times higher than when finished.
Elite Steam humidifiers may be operated while construction is underway
but, reduced cylinder life is to be expected and budgeted for. Good practice dictates that the steam cylinders also be replaced once the project is complete.
1.3 Calculating Humidity Load
1.3.1 Steps to Determine Humidity Load Total Square Footage
x Average Ceiling Height x Factor From Table 1.2 x 1.05 for each Fireplace Humidity Load in lbs./hour
x 2.88 convert to gallons/day Gallons per Day Humidity Load
*Based on .5 air changes per hour.
Table 1.2 Pounds of Moisture / Hour / Cubic Foot *
Indoor Air
Temp °F
35% Indoor RH%
40%
45%
50%
68 0.00015 0.00018 0.00021 0.00024 70 0.00017 0.00020 0.00023 0.00026 72 0.00019 0.00022 0.00025 0.00028
* Based on .5 air charges per hour.
DS 50 / DS 50 LC +030222065 Rev. 1.2
7
Page 8
Indoor Air Temp
2. MODELS
There are two basic models available for different water conditions. Duct Steam Injection
Fig. 2.a
MODEL LIST
PART NUMBER DESCRIPTION PARTS INCLUDED DS 50 Duct steam injections 58 gallons per day
(20 Lbs per hour) 220-240V
DS 50 LC Duct steam injections 58 gallons per day
(20 Lbs per hour) 220-240V
DS 50 / DS 50 LC +030222065 Rev. 1.2
Humidifier with Duct Mount Kit and Humidity GFX50 control. Humidifier for Low Conductivity water. Includes Duct Mount
Kit and GFX50 control.
8
Page 9
3. INSTALLATION
3.1 Positioning
The Elite Steam has been designed for wall mounting and, since it is an atmospheric steam humidifier, should be placed close to the point where the steam will be used, to minimize the steam hose length (and the amount of condensate). Do not mount on furnace, air handler or ductwork. Certain clearances must be maintained around the unit for safety and maintenance.
3.2 Mounting
3.2.1 Removing the front cover
The front cover is secured by two screws located in the bottom side of the unit. Use a phillips screwdriver to remove the screws. The front is clasped with 2 clips on the top of the back part. To remove the front cover, hold by the sides pivot the bottom out and lift cover. When installing the cover, be careful not to over-tighten the screws.
Clearance Dimensions
F
Fig. 3.a
Millimeters Inch A (150 mm) 6” B (150 mm) 6” C (150mm) 6” D (150 mm) 6” E (600 mm) 24” F max. 0.2°
Tab. 3.a
Unit Dimensions: Duct Units
screws M5x16
SCREWS M5x16
Fig. 3.c
Millimeters Inch A 445 mm 17.5“ B 290 mm 12“ C 790 mm 32“ Kilograms Pounds Weight empty 11kg 24 lbs Weight packaged 13kg 29 lbs Weight installed with water 23kg 51 lbs
Fig. 3.b
Tab. 3.c
Fig. 3.d
DS 50 / DS 50 LC +030222065 Rev. 1.2
9
Page 10
3.2.2 Fastening to the wall Drill the wall according to the drilling template supplied; then secure DS 50 / DS 50 LC firmly to the wall by the screws and anchors supplied. Do not mount on furnace, air handler or ductwork.
Dimensions are in millimeters and [inches]
Fig. 3.e
DS 50 / DS 50 LC +030222065 Rev. 1.2
10
Page 11
3.3 Plumbing
3.3.1 Water Characterisitc Requirements The humidifier must be supplied with water with the following characteristics:
• pressure between 20psi and 110psi or 0.1 and 0.8 MPa (1 and 8 bar)
• temperature between 33°F and 104°F or 1°C and 40°C
• flow-rate minimum of 0.83 L/min or 0.22gpm
• hardness no greater than 40°fH (equal to 400 ppm³ of CaCO), conductivity: from 125 to 1250 μS/cm
• absence of organic compounds
• the characteristics of the water of supply must fall within the following limits:
LIMIT VALUES FOR LOW SALT CONTENT WATER LIMIT VALUES FOR LOW NORMAL WATER
Units Min Max Units Min Max Hydrogen ions (pH) 7 8.5 Hydrogen ions (pH) 7 8.5 Specific conductivity (R,20°C) μS/cm 300 Specific conductivity (R,20°C) μS/cm 125 500 Total dissolved solids (c R) mg/l (*) (*) Total dissolved solids (c R) mg/l (*) (*) Dry residue at 180°C mg/l (*) (*) Dry residue at 180°C mg/l (*) (*) Total hardness mg/l CaC³O 150 400 Total hardness mg/l CaC³O 0 200 Temporary hardness mg/l CaC³O = 200 Temporary hardness mg/l CaC³O = 150 Iron + Manganese mg/l Fe + Mn = 0.2 Iron + Manganese mg/l Fe + Mn = 0.2 Chlorides ppm Cl = 30 Chlorides ppm Cl = 20 Chlorides mg/Si2O = 20 Chlorides mg/Si2O = 20 Chlorine residue mg/l Cl- = 0.2 Chlorine residue mg/l Cl- = 0.2 Calcium sulphate mg/l CaS4O = 100 Calcium sulphate mg/l CaS4O = 60
Tab.3.d Tab.3.e (*) Values dependent on the specific conductivity: in general: cR~=0.65*σR, 20°C; R180~=0.9*σR, 20°C Note: There is no relationship between the hardness and conductivity of water.
Water Conductivity must be matched by specifications of the steam cylinder. Check or know the water conductivity of the proposed site before installation. Replace the steam cylinder before startup if not correct. See Table 3.f right.
DS 50 / DS 50 LC models Conductivity μS/cm Steam Cylinder DS50 300-1250 50-14 DS50LC 125-500 50-15
Tab.3.f
The following water types are not acceptable:
1. Softened water as this will lead to foam, electrode corrosion and greatly shortened cylinder life.
2. Water containing disinfectants or corrosion inhibiters, as these are potential irritants.
3. Industrial water, boiler water or water from cooling circuits.
4. Any potentially chemically or bacteriologically contaminated water.
5. Heated water.
Water drain outlet
3.3.2 Water Supply Connection We recommend the connection between the fill valve and the water supply line by a soft poly hose capable of absorbing the water hammering in order to avoid damage to the fill valve itself. The water line may be routed through the back or through the bottom of the unit. With poly tubing, a tubing support must be used to prevent tubing collapse and leaks. The fitting then threads onto the fill valve inlet located on the bottom of the humidifier using a 3/4” G connection. Note
that there is a strainer built into the fill valve fitting underneath the unit, which will require periodic cleaning, so be sure to allow clearance for access. Length of 1/4” tube should be kept to less than 1M or 3 ft.
Fig. 3.g
Fig. 3.h
Extension tube
Fill valve and filter
Water drain
DS 50 / DS 50 LC +030222065 Rev. 1.2
11
Page 12
3.3.3 Water Drain The DS50 and DS50 LC requires a connection to a drain. The drain line may be routed out the back or bottom of the unit using the included angle fitting. The drain line can be 1-1/4” PVC, CPVC or polypropylene. The drain line is not glued or otherwise attached to the humidifier so it must be supported by itself. A coupling should be used. The DS 50 / DS 50 LC includes a drain tempering valve that runs whenever the drain pump runs and flushes cool water into the drain line to insure the drain water temperature never exceeds 60°C or 140°F. The drain water characteristics are:
• Drain Rate 26.8 liter per minute or 7.1 gallons per minute
• Connection 32mm or 1 1/4”
• Temperature 60°C or 140°F NOTE: Drain line must be trapped under the unit to prevent flash steam from condensing in the unit cabinet.
Fig. 3.i
3.3.4 Drain Connections When using a rear outlet drain passing through drywall, we suggest using a 1 1/4” extension tube type SJ (see Fig. 3.i). When using a bottom outlet drain, attach the included 90° fitting to the drain outlet. The drain outlet may be rotated. Then connect a 1 1/4” trap adaptor to connect to drain pipe.
IMPORTANT WARNING: The drain pipe must be free without back pressure. We recommend an external anti­flooding device not supplied to protect from faults of external hydraulic circuits.
3.4 Steam distribution
3.4.1 Duct steam injection
The maximum allowed duct static pressure is 2 in WC. The DS 50 / DS 50 LC duct injection models include a 12” Steam Distribution Manifold
Mounting screws
min. 5°
4
5
Steam Inlet
Condensate drain
Select an accessible location on the duct, allowing at least 36” of straight duct (no elbows or obstructions) after the point where the manifold will be installed and the clearances can be maintained as per the following drawings. See Fig. 3.j To mount the steam manifold, cut a 2 ½” hole in the duct. Install the supplied o-ring or apply caulk to the mounting plate of the nozzle. Attach the manifold to the duct using four sheet metal screws. Manifold must level or vertical to condensate outlet to the bottom. Connect the steam and condensate hoses using the clamps supplied. Note: End support bracket supplied only with 36” and longer manifold.
IMPORTANT: 1. Allow 3 feet (1m) of straight duct downstream of the manifold for absorption of the steam.
2. Alwa ys allow 2 feet (0.6m) of straight duct upstream of the manifold. Turbulent air flow may require more.
3. Duct must be kept warm. Ducts in unconditioned spaces or over faulted ceilings must be well insulated to prevent condensation.
DS 50 DS 50 LC
Steam distributor Steam inlet dia. mm (in) Max. capacity kg/h (lb/h) Length mm (in) 7599 (50-09 steam distributor) 30 (1.2”) 15 (33) 300 (11.8)
Flange gasket
Steam outlet dia. mm (in) 30 (1.2”) Max capacity kg/h (lb/h) 9 (20)
Fig. 3.j
DS 50 / DS 50 LC +030222065 Rev. 1.2
12
Page 13
Min 8”
Airflow
1000 cfm min.
8” min
24” min Upstream
36”min Downstream
Height >8”
Airflow
1000 cfm min.
=
=
1/3 Height
=
Fig. 3.k
Airflow
=
Airflow 1000 cfm min.
IMPORTANT: Allow 1 M ( 3 feet ) of straight duct downstream of the distributor pipes and nozzles for absorption of the steam. Always allow 0.6M (2 feet) of straight duct upstream of the distributor pipes for evaporation of the steam. Turbulent air flow may require longer lengths
.
3.4.2 Return Condensate Connection
The return condensate hose from the manifold must be trapped. Coil the hose into a vertical loop and secure it below the manifold. This water trap prevents steam from being released into the hose. Insert the barbed fitting into the end of the hose. Route the manifold drain hose through the top of the humidifier, into the top of the fill cup. This is just above and to the right of the steam cylinder. See. Fig. 3.l
Fig. 3.l
DS 50 / DS 50 LC +030222065 Rev. 1.2
13
Page 14
3.4.3 Steam Hoses
IMPORTANT WARNING: NINETY PERCENT (90%) OF ALL OPERATION PROBLEMS ARE CREATED BY IMPROPER STEAM PIPING FROM THE HUMIDIFIER UNIT TO THE DUCT DISTRIBUTOR PIPES.
To avoid these problems, remember one simple fact when running the steam hose: steam naturally flows up hill, and condensate naturally flows downhill. Run the steam hose or piping to avoid any kinks, sharp elbows, or low spots that could collect or restrict the flow of steam to the distributor pipe, or the flow of condensate back to the humidifier. Support the hose adequately to avoid sags. The following diagrams are to provide you with some guidelines. If you have a situation you are unsure of, please contact Technical Support for instructions. Contact information is printed on the back cover.
20%
IF NO TRAP
1,5 m (5 FT max.)
5%
WITH TRAP
1,5 m (5 FT max.)
IF NO SLOPE
20%
0,9 m (3 FT max.)
3 m (10 FT max.)
1,5 m (5 FT max.)
20% 20%
SUPPORTED STEAM HOSE
AND/OR COPPER PIPE
NOTES:
• SLOPE PIPING UP IN DIR ECTION OF STEAM FLOW AT 20% OR GREATER, WHICH MEANS 65,5mm x 305mm (2 1/2” PER FOOT);
• SLOPE PIPING DOWN IN THE DIRECTION OF STEAM FLOW AT 5% OR GREATER, WHICH MEANS 20mm x 305mm (3/4” P ER FOOT);
• MAX. LENGTH OF RUBBER STEAM HOSE IS 3 m (10 FT).
• HEIGHT OF P-TRAPS MUST BE GREATER THAN THE DUCT STATIC PRESSURE.
NO SLOPE
KINKED
GENTLE BEND
OBSTRUCTION
SAG
5%
NO TRAP
DRAINS
P - TRAP NOTE: HEIGHT OF TRAPS MUST BE GREATER THAN THE DUCT STATIC PRESSUR E
NO SLOPE
UNDRAINED
ELBOW
TYPICAL INSTALLATION WHEN UNIT IS ABOVE
THE DISTRIBUTOR PIPE
DRAINS
UNDRAINED
ELBOW
NO DISTRIBUTION
PIPE DRAIN
YES
NO
Fig. 3.m
IMPORTANT: Maximum length of rubber steam hose is 4m (12 feet.). Insulated copper tubing may be up to 6m(20feet) in length. In all cases, minimize sharp bends and elbows. Use 2 - 45° elbows instead o f 90°s.
Hose inner diameter = 1.18” ( 30 mm); Hose outer diameter = 1-1/2” (40 mm). Installation Items Included:
Steam hose, 8 feet Condansate hose, 9 feet. Hose Clamps, 4. Steam manifold 12-inch. Sheet Metal Screws, 4. Water supply tube kit. Fill Connector. Code Valve Ball valve. Pressure Switch. GFX50 Humidistat. Mounting Template.
DS 50 / DS 50 LC +030222065 Rev. 1.2
14
Page 15
3.5 Power wiring
Check that the power supply voltage to be connected matches the value indicated on the rating plate inside the electrical panel.
Insert the power and ground connection cables into the electrical panel compartment using the strain reliefs supplied, and connect to the terminals. An external fused disconnect must be installed. See Fig. 3.o
GROUND TERMINAL BLOCK
All wiring must be in accordance with local, state and national electric codes. NOTE: to avoid unwanted interference, the power cables should be kept separate from any
control wiring. NOTE: Tolerance allowed on main voltage =-15% to +10%.
Connect power wires to the power terminal. See Fig. 3.p
Model
DS50 230Vac 50/60Hz 20 - 58 9 6.9 30 AWG8 40 A / fast blow
DS50LC 230Vac 50/60Hz 20 - 58 9 6.9 30 AWG8 40 A / fast blow
Power supply
(single phase)
Steam Output
(lbs/hr – gal/day)
Fig. 3.m
Steam Output
(kg/h)
POWER
(kW)
CURRENT
(A)
EXTERNAL
POWER WIRES
EXTERNAL FUSE (A)
OR BRAKER
3.6 Control wiring
The Elite Steam allows connection of any simple or automa tic hu midista t, and safe ty devices such as high-limit humidistat, air flow proving switch, and remote on/off. Included with the humidifie r is the GFX50 Modulating Humidistat. The control will increase a steam output if the humidity and setpoint are far apart. It will reduce output as the humidity nears the setpoint. This allow s for the most pre cise humi dity control. For on-off operation the humidifier is opera ted by the closing of a me chani cal humidi stat H, or by the closing of a voltage-free remote contact, or alternatively by a combination of both. A pressure switch is always used to confirm blow er operation . The diagrams in th e figures show the connections to be made on the terminal block, in case of: Fig. 3.r Operation performed by an external mechanical humidistat or control contact and pressure switch; Fig. 3.s Operation controlled by the included GFX50 Humidistat and pressure switch.
Contact AB-AB:
• Closed: humidifier enabled to produce when humidistat closes closes or increases voltage;
• Open: steam production is immediately stopped.
Fig. 3.r
Fig. 3.n
Pressure switch
Fig. 3.o
• The remote on/off contact is usually the pres sure switch included with the humidifier. The pressure switch NO and C terminals are connected to the AB-AB terminals.
• The remote on/off may include safety s witches wired in series with the pressure switch. These may include a high-limit humidistat a relay that closes when fan is running or a downstream cooling coil contac t that closes when coil is off. Contact IN-GND: If on-off operation is enabled (see section 5.1.1):
• closed: steam production starts if contact AB-AB is closed
• open: steam production is stopped after 5 sec.
Pressure switch
MODULATING HUMIDISTAT
Fig. 3.s
DS 50 / DS 50 LC +030222065 Rev. 1.2
15
Page 16
3.6.1 Connect the GFX50 Humidistat for Modulating operation Connect Elite Steam terminals 24V and GND to GFX50 terminals GO5 and G6 respectively. Do not reverse these connections. Connect GFX50 terminal A OUT 6 to Elite Steam terminal IN. See fig. 3.t.
NOTE:
MODULATING OPERATION requires Elite Steam signal type be changed,
1.
Elite Steam
ON DIP
ON OFF OFF
1 2 3 4
ON
SEC. 5.1.1 page 19
2. The GFX50 is capable of ON-OFF operation. See the GFX50 manual.
3. The GFX50 is capable of Outdoor Temperature Compensation see the
GFX50 manual.
4. The GFX50 is designed to wall mount. It is not intended for duct
installation.
5. Reversing the 24V and GND leads will result in humidifier malfunction.
Fig. 3.t
3.6.2 Connect the E2 Humidistat ON-OFF Operation Connect Elite Steam terminals 24V and GND to E2 terminals ACL, ACN. Connect E2 terminals HUM to Elite Steam terminals GND and IN.
NOTE:
1. To remove humidistat from the base, squeeze the louvered base at the top and bottom. To remove from wall, lift up on the humidistat and pivot top away.
2. Terminal block may be pulled off humidistat for easy connecting.
3. The E2 is capab le of Outdoor Temperature Compensation see E2 manual.
4. The E2 may be wall or duct mounted.
AC L
AC N
HUM
SNSR
OUTDOOR TEMP. SENSOR (not used in manual mode)
N2 GND N1 AB AB
GND IN
NO C NC
C NO
Fig. 3.u
GND 24V
3.6.3 Air pressure, Safety and High Limit Switches
Remove the jumper between terminals AB-AB and connect 12500 pressure switch, High Limit Humidistat, safety switch or remote contact in series. If none are to be installed the jumper must remain in place. DO NOT apply any voltage to AB-AB.
3.6.4 Air Conditioner Relay Interlock
Auxiliary DPDT safety relay: Use this method in the following situations:
1. To prevent the air conditioner from running when there is a call from humidity. The DPDT relay will open the “Y” circuit and close the “G” circuit for operation while a call for humidity is present. Demand for humidity will override call for cooling.
2. In systems using a thermostat where G and Y are a single circuit. The DPDT relay will allow blower operation to occur without back-feeding the compressor. Do not use this method when simultaneous humidification and cooling will be desired. Use a high limit humidistat in to avoid condensation in ductwork. The humidistat should be set to OFF during the air conditioning season if
AIR CONDITIONER RELAY
Elite Steam
N2 GND N1 AB AB GND
IN
NO C NC
C NO
GND 24V
Furnace Control Circuit Board
W Y R G C
COIL 24V
NC1
DPDT RELAY
(FIELD SUPPLIED)
TO AIR
CONDITIONING
CONTAC TOR
NO2
NC2
C1
C2
humidification is not desired. For variable speed or DC systems, consult furnace manufacturer.
Fig. 3.v
Thread control wiring through the bottom of the unit and the strain relief (Fig. 3.m and 3.n) then up the side of the control module to the wiring terminal blocks.
DS 50 / DS 50 LC +030222065 Rev. 1.2
16
Page 17
3.7 Wiring Connections:
Terminals F unctions Electrical specifications L1-L2 -GROUND Power supply and Ground connections Power supply 230 VAC 1-phase 50-60Hz
6.9kW
KEY Programming port Connecting to Programming port or
supervisor N1-GND- N2 NTC air proving sensor Connection to NTC 2K and 10K to 20°C AB-AB Remote enabling input Imposes an external NO contact ;
Rmax=300 Ohm; Vmax=33 Vdc;
Imax=6mAdc; humidifier enabled =
contact closed IN-GND Control signal input
NC-C-NO NC alarm contact
Common alarm contact NO alarm contact
NO-C External fan relay 250V; 8Amp max with resistive load; 4 24GND Power for external humidistat Power supply for external humidistat 24 K Contactor
TAM Amperometric transformer Setting TAM 500 with pin strip
3.7.1 Wiring diagram of controller
If programmed 0...10V:
Input impedance 10 kOhm
If programmed ON-OFF:
Vmax 33Vdc
Imax = 5mA Rmax = 300 Ohm
250V; 8Amp max with resistive load; 4
Amp max with inductive load
Amp max with inductive load
Vac; 2 Watt
D
A
Fig. 3.w
DS 50 / DS 50 LC +030222065 Rev. 1.2
17
Page 18
4. START-UP
IMPORTANT WARNINGS:
1. Before starting, check that the humidifier is in perfect condition, that there are no water leaks and that the electrical parts
are dry;
2. Do not connect power if the humidifier is damaged or even partially wet!
When installation is completed, flush the supply pipe for around 10 minutes by piping water directly into the drain, without sending it into the humidifier; this will eliminate any scale or residues that may cause foam when boiling.
4.1 Startup Checklist
Before starting the humidifier, the following should be checked:
Water is connected (cold non-softened), the line has been flushed, and external valves are open.
Drain is connected, run to an open drain, and has a trap under the un it.
Electricity is connected in accordance with instructions, local codes and data labels in the unit.
The power fuses are installed and intact.
All control wiring is done and tested.
Airflow switch is wired to open on air flow loss.
Optional hi-limit humidistat is wired to open on humidity rise above set point.
Unit wires have been checked to make sure they and all connectors are tight from shipping.
The steam hose(s) are run correctly with no sags or kinks and sloped properly according to the manual.
Condensate hoses are run correctly with no sags or kinks and sloped properly according to the manual.
4.2 The Elite Steam Controller
The Elite Steam controller features a comprehensive information display that shows the operation of the system at a glance:
1. Display is % of nominal capacity
2. Maintenance
3. Display is amperage (default)
4. Steam is being produced
5. Cylinder filling
6. Foaming
7. Water presence inside the cylinder
8. Cylinder draining
9. LEDs indicate: power (yellow), operation (green) and alarms (red)
10. Drain button for manual draining of cylinder and confirming
parameter values
11. ON/OFF button
12. Reset button to reset alarms and access parameters
13. Level of output: 33%, 66%, 100%
14. Fan relay is activated The DS 50 / DS 50 LC is now ready to operate.
4.3 Starting the Elite Steam
Insure that the external power is turned on.
Push the top part of the On/Off button so that the I part is in. T he yellow Power LED will
be lit. The Elite Steam is now ready to operate.
When there is a call for humidity, DS 50 / DS 50 LC will close its power relays and send
power to the electrodes in the plastic steam generator. The green Operation LED will light, indicating that operation has begun.
4.4 Starting with a new cylinder
When starting with a new cylinder, you should activate the cylinder cleaning function a s follows:
1. Switch Elite Steam off.
2. Press and hold both buttons, “reset” and “drain”, and switch DS 50 / DS 50 LC back on.
When the wrench blinks
3. Press and hold “ reset” until the display shows 04.
WARNING: DO NOT confirm any value higher than 04. If 05 or higher is displayed,
press “reset” until the display goes back to the normal operating mode and restart from step
4. Press “drain” (minimum 1 second): the cleaning starts.
then release the two buttons.
14
13
1
2
3
4
5
6
7
8
9
1012
11
DS 50 / DS 50 LC +030222065 Rev. 1.2
18
Page 19
During the cleaning, the electrodes are powered and water is filled in until it touches the high-level sensor or the phase current equals 20A, whichever occurs first. After either of the events is detected, the boiler is fully discharged with the electrodes un­powered (the drain pump and the drain tempering valve are activated for 3 minutes). Warming the filling water helps washing out any mould release or dirt. General Filters, Inc. recommends to do two cleanings when starting a new boiler. After the cleaning ends, the humidifier starts the regular duty. When starting the unit with a new or empty cylinder, it ma y take a significant amount of time (hours) for the unit to build up enough mineral concentration to reach rated capacity. This time can be shortened b y the addition of Alka-Seltzer through the steam outlet on top of the cylinder.
5. OPERATING the Elite Steam
5.1 Displaying Information
By pressing the “reset” button for 2 seconds, the display will loop from amperage to production in % of the maximum production to the hour counter and back to amperage:
Fig. 5.a
1. Amperage: it is the value of the current that flows through the water making it boiling off (default display)
2. Production %: it is the current production expressed as a percentage of the humidifier ’s capacity
3. Hour counter, expressed in tens; for instance, when the dis pla y shows 13 the real hour value will be between 130 and 139
hours.
5.1.1 Select Signal Type
The DS50 is preset for the included E Series humidistat (signal type 0). If the ON-Off operation is used, this section may be omitted. If another humidistat is used, review this section to see if changes are needed.
1. Switch Elite Steam off.
2. Press and hold both buttons “reset” and “drain” and switch Elite Steam back on. When the wrench blinks, 2 buttons.
3. Press “Reset” until the displa y shows 02. WARNING: DO NOT confirm any value higher than 04. If 05 or higher is displayed, press “Reset” until the display goes back to the normal operating mode and restart from step 1.
4. Press “drain” (minimum 1 sec ond) to confirm: the display shows “P1” then the current signal type and “set”
5. Press “Reset” to change signal type between 0 and 1:
0 = On-Off humidistat such as the GeneralAire “M” or “E” series humidistat. 1 = external 0...10 Vdc modulating signal such as the GeneralAire ADCD series humidistat
6. Press “drain” (minimum 1 second) when done to confirm the new value of P1 and exit to the normal operating mode.
7. Switch Elite Steam off: you can now proceed with connecting the control wiring.
release the
5.2 Changing The Maximum Production
The maximum production can be adjusted between 20% to 100% of the nominal production in steps of 5% in order to suit the environment characteristics. DS50 and DS50L Maximum production is factor y set at 70%.
1. Switch Elite Steam off.
2. Press both and hold both buttons “Reset” and “Drain” , and switch Elite Steam back on. When the wrench blinks; release the 2 buttons.
3. Press “reset” until the display shows 01. WARNING: DO NOT confirm any value higher than 04. If 05 or higher is displayed, press "Reset" until the display goes back to the normal operating mode and restart from step 1.
4. Press “drain” (minimum 1 second) the display shows “P0” then the current Maximum Production Percent and “set”.
5. Press “reset” to change the Maximum Production in steps of 5% between 20% and 100%.
6. Press and hold “drain” (minimum 1 second) when done to confirm the new Maximum Production and exit to the normal operating mode.
5.3 Activating Manual Drain
Press and hold the “drain” button on the front of the unit until the cylinder is drained. Note: Water will continuate to flow from the tempering valve after the cylinder is empty.
5.4 Resetting the hour counter
The hour counter should be reset every time the cylinder is changed in order to reset and restart the internal maintenance timer:
1. Switch Elite Steam off.
2. Press and hold both buttons “Reset” and “Drain” and switch Elite Steam back on. When the branch buttons.
3. Press and hold “reset” until the display shows 03. WARNING: DO NOT confirm any value higher than 04. If 05 or higher is displayed, press “reset” until the display goes back to the normal operating mode a nd restart from step 1.
4. Press “drain” (minimum 1 second) to confirm: the hour counter will be reset at once and the humidifier will go back to the normal operating mode.
blinks; release
DS 50 / DS 50 LC +030222065 Rev. 1.2
19
Page 20
5.5 Humidistats
Several GeneralAire humidistats may be used with the Elite Steam Humidifier; GFX50 (included) Allows Modulating or On-Off operation. Is capable of Outdoor Temperature Compensation, and has other programmable functions. Backlit LCD display.
E2 (optional) On-Off operation only. Is capable of Outdoor Temperature Compensation. LCD display.
M3 and SCX3 (optional) Manual, On-Off operation only.
For detailed installation, programming and operating instructions, please see the Humidistat’s Operating Manual. WARNING: Do not allow excess humidification. Excess humidity can cause condensation and enable mold and mildew growth.
5.6 Alarms
In the event of an alarm, the red alarm LED will flash, the alarm relay will close, and the alarm code will flash in the display. Multiple alarms will flash in sequence, alternating with the main display. Pressing the sel button for 2 seconds will reset the alarms, although still active alarms will continue to display.
Dis
play
-- Remote on-off open Unit disabled Off Off Check Pressure Sw. circuit, AB-AB EE Internal memory error Unit disabled On On Contact Factory E0 Control board configuration not valid Unit disabled On On Contact Factory E1 High current alarm Unit disabled On On Turn off, check connections, check
E2 Low production, low supply water
conductivity or excessive foam/limescale in the cylinder
E4 Fill alarm, unable or slow fill
(current does not increase within timeout)
E5 Drain alarm, unable to drain
(current does not decrease within timeout)
E6 Cylinder exhausted
(critical performance detected)
E7 Foam detected Press reset/sel” key for 1 seconds to reset Off Off If it continues, do some cleaning cycles
E8 Cylinder lifetime expired (2000 hours) Reset the hour counter (read chap. Resetting the hour
E9 High controller temperature (above
176 °F / 80 °C)
Description Action Red
Unit disabled. Press “reset/sel” key for 1 seconds to reset.
Press “reset/sel” key for 1 seconds to reset, otherwise the warning will be reset automatically every 10 minutes until the supply water is available again.
Press “reset/sel” key for 1 seconds to reset On On Check drain pump and drain connection
The warning is automatically reset if DS 50 / DS 50 LC can produce the demand, otherwise turn off and then on.
counter”) The warning is automatically reset if the temperature
decreases below 176 °F / 80 °C.
Alarm
Led
Relay
cylinder (no limescale bridges between electrodes, no electrodes short-circuited)
On On Check supply water conductivity (too
On On Check water supply and fill valve; check
Off Off Change cylinder (urgent)
Off Off Change the cylinder.
Off Off Check the ambient temperature, replace
low?), replace the cylinder.
drain pump for leakage
(read chap. “Starting with a new cylinder”)
the controller.
Notes
DS 50 / DS 50 LC +030222065 Rev. 1.2
20
Page 21
6. TROUBLE SHOOTING
Problem Causes Solutions
The humidifier does not turn on 1. No electrical power
The humidifier does not start operation
The humidifier fills with water without producing steam
The humidifier wets the duct 1. The distributor is not installed correctly (too
The humidifier wets the floor below
Problem Causes Solutions Water in the cylinder turns black
Heavy arcing occurs within hours of startup
Humidifier continuously fills and drains without producing steam
2. On/off switch of the humidifier in position 0 (open)
3. Control connectors improperly connected
4. Blown fuses
5. Transformer failure
1. Remote ON/OFF contact open
2. The humidistat has not been connected correctly
3. Humidistat failure
4. Control signal not compatible with the type set
5. Value measured by the sensor/s higher than the corresponding set point
1. High steam back pressure
2. Fill valve strainer clogged
3. Mineral in the fill cup
4. Drain solenoid valve leaking
near the top of the duct or the condensate return is blocked)
2.Air flow rate is too low
3.Humidifier active when the fan in the duct is off
1. The humidifier drain is blocked
2. The supply water or overflow circuit has leaks
3. The condensate drain pipe does not bring the water back to the drain pan
4. The steam hose is not properly fastened to the cylinder
1. Minerals in the cylinder have overconcentrated and are deteriorating the electrodes.
1. The feed water contains large amounts of Iron, Copper or other conductive contaminants.
1. Mineral has bridged between the electrodes.
2. There is back pressure from the steam hoses or duct.
3. The flow regulator in the fill valve is broken or out of place.
4. Water conductivity is very high.
5. Water is foaming excessively.
1. Check the safety devices upstream from the humidifier and the presence of power
2. Close the switch on the panel: position I
3. Check that connectors are properly inserted in terminal block
4. Check the condition of fuses
5. Check that the proper voltage is connected and turned on
1. Close ON/OFF contacts
2. Check the external connection
3. Replace the humidistat
1. Check that the steam hose is not kinked or sagging, trapping condensate
2. Clean the fill valve strainer
3. Clean the fill cup
4. Check for voltage at the drain solenoid valve and/or drain solenoid replacement
1. Check that the steam distributor is installed correctly
2. Increase air flow in duct or decrease PO maximum steam production setting
3. Check the connection of the device (flow switch or differential pressure switch) controlling the humidifier to the ventilation in the duct
1. Clean the drain assembly and pan
2. Check the entire water circuit
3. Check the correct position of the condensate drain hose in the drain pan
4. Check the fastening of the hose clamps on the steam outlet
Tab. 6.a
1. Check for sags & kinks that could trap condensate in the steam hoses that could cause a back pressure on the cylinder.
2. Check the duct static pressure.
3. Check the fill valve and inlet strainer.
4. Check the drain pump operation.
5. Correct installation problems and replace cylinder.
1. If you are using a softener. Discontinue use.
2. Check the electrodes in the cylinder to be sure they were not damaged in shipping.
1. Clean or replace the cylinder.
2. Check the steam hoses for kinks or gullies that might be trapping condensate.
3. Replace the fill valve.
4. Consider using a mix of demineralized water with raw water.
5. Check cylinder - replace if exhausted. If feed water contains silica or nitrates, install a 1 micron water filter.
Tab. 6.b
DS 50 / DS 50 LC +030222065 Rev. 1.2
21
Page 22
7. MAINTENANCE
7.1 Periodic checks
After one hour of operation: Check that there are no significant water leaks.
Every fifteen days or no more than 300 operating hours: Check operation, that there are no significant water leaks and the
general condition of the cylinder. Check that during operation there is no arcing b etween the electrodes.
Every three months or no more than 1000 operating hours: Check operation, that there are no sig nificant water leaks and, if necessary, replace the cylinder. Check that there are no blackened parts of the cylinder. If there are blac kened parts of the cylinder, check the condition of the electrodes, and if necessary replace the cylinder.
Annually or no more than 1990 operating hours: Replace the cylinder.
CAUTION: ALWAYS DISCONNECT THE MAIN POWER BEFORE DOING MAINTENANCE! CAUTION: always disconnect the main power before touching the cylinder in the eve nt of leaks, as curre nt ma y flow through the water.
7.2 Cylinder maintenance
The life of the cylinder depends on a number of factors, including: the amount and type of mineral in the water, the correct use and sizing of the humidifier, and the output, as well as careful and regular maintenance. Another factor affecting cylinder life is Maximum Production, the higher the production rate the shorter the cylinder life; for this reason the DS-50 are preset from the factory at 70%. Further reductions in maximum production will extend cylinder life. See figure 7.a
IMPORTANT WARNINGS
The humidifier and its cylinder contain live electrical components and hot surfaces, and therefore all service and/or maintenance operations must be performed by expert and qualified personnel, who are aware of the necessary precautions. Before performing any operations on the cylinder, check that the humidifier is disconnected from the power supply. Remove the cylinder from the humidifier only after having drained it completely using the manual “drain” button or procedure. Check that the model and the power supply voltage of the new cylinder correspond to the data on the rating label.
7.2.1 Replacing the cylinder
IMPORTANT WARNING: the cylinder may be hot. Allow it to cool before touching it or use protective gloves. Fig. 7.a To replace the cylinder:
1. Completely dr ain the cylinder by pressing and holding the “drain” button until the cylinder is empty;
2. Turn the humidifier off and disconnect the main power;
3. Remove the cover;
4. DS Models:
o Remove the steam hose from the cylinder; o Flip up the cylinder holding belt and lift the cylinder out of the unit;
5. Disconnect the distributor from the cylinder and lift the c ylinder out of the unit;
6. Disconnect the electrical connections from the top of the cylinder;
7. Install the new cylinder in the humidifier by performing the previous operations in reverse
CAUTION: Do not tighten the 1-1/4”” hose clamp so tight that it crushes the cylinder outlet WARNING: connect the gray wire with the electrical connections “A” on the top of the cylinder and connect the black wire with the electrical connections “D” on the top of the cylinder.
7.2.2 Maintenance of the other plumbing components
IMPORTANT WARNINGS:
External power must always be disconnected when performing any maintenance on the humidifier.
When cleaning the plastic components do not use detergents or solvents;
Scale can be removed using a solution by using vinegar or a weak solution of acetic acid and a soft brush; then rinse the
cylinder thoroughly with fresh water.
Cleaning the fill valve:
After having disconnected the cables and the hoses, remove the valve and check the condition of the inlet filter; clean if necessary using the same cleaning solution as for the steam cylinder and a soft brush.
Cleaning the drain pump:
Remove the valve body, clean if necessary using the same cleaning solution as for the steam cylinder and a soft brush.
Cleaning the drain pan:
Clean the pan of any mineral deposits and check that the water flows freely from the pan to the drain at the drain pump.
Cleaning the supply, fill, overflow pipes: Check that these are clear and clean or replace if necessary. IMPORTANT WARNING: after having replaced or checked the plumbing, check that components have been reconnected correctly
with the proper seals. Re-start the humidifier and perform a number of cleaning cycles (from 2 to 4, read chap. “Starting with a new cylinder”), then check for any water leaks.
Cylinder life
Maximum Production
20%100%
DS 50 / DS 50 LC +030222065 Rev. 1.2
22
Page 23
7.3 Replacement Parts
ITEM PART NO. MODEL DESCRIPTION
1 7638 50-22 fill cup 2 7656 50-26 current sensor 3 7621 50-01 control module 230Vac 4 7551 35-18 on/off switch
5-6 7652 50-18 power terminal block kit w/cover
9 7626 50-25 cover screws kit 10 7542 35-21 90deg drain adapter 11 7623 50-04 drain pump assembly 12 7622 50-03 fill/tempering valve assembly 13 7624 50-14 cylinder 13 7635 50-15 cylinder low conductivity 14 7654 50-20 cylinder support strap
7637 50-17 internal wiring kit 7639 50-23 internal hose kit 7633 50-05 installation instructions 7501 20-04 fill connector 7636 50-16 internal filter and gasket kit ds50 7655 50-21 silent contactor 7657 50-10 hardware kit ds50
7 2 - Small cable clamp
4 - Screws for small cable clamp
8 1 - Large cable clamp
2 - Screws for large cable clamp
10 1 - 90 Deg drain adapter
1 - Kit of 4 Mounting screws and anchors
DS 50 / DS 50 LC +030222065 Rev. 1.2
23
Page 24
Steam flows, VAC, kW Outlet pressure limits Dimensions (mm ) Weight empty/packaged/installed
with water IP class
Electrode power cables Power contactor Ground connection Input water type Conductivity range
Water fill connection Water fill - instant flow
Drain connection Drain water temp Drain flow Serial communication
8. TECHNICAL SPECIFICATIONS
20 lbs/hr (9 kg/h): 230 VAC 1-phase 50-60 Hz, 6.9 kW
5.4 in WC / 1350 Pa
31” x 18” x 11.4” (790 x 460 x 290 mm)
24/29/51 lbs. (11/13/23 kg)
IP20
8 AWG
63 Amp
Terminal block
Potable water
125-1250 µS/cm
1/4” O.D. Compression
0.22 – 0.3 gpm
(0.825 – 1.1 l/min)
1.25” O.D. (32 mm)
< 140°F
(< 60°C)
Max 5.1 gpm
(max 21 l/min)
RS485
Notes For duct only (Height x Width x Depth)
no demin. or softened water Special cylinders for cond. < 350
µS/cm Adapter to ¾” FPS
Adjustable from horizontal to vertical. May be from back or bottom of unit. drain tempering device
DS 50 / DS 50 LC +030222065 Rev. 1.2
24
Page 25
9. LIMITED WARRANTY
DS Humidifiers, if properly registered by the return of the page 25 warranty registration to General Filters, Inc., are warranted to the consumer against defects in materials and workmanship for a period of two years from the date of installation, so long as the product has been installed by a qualified HVAC, Plumbing or Electrical Contractor and operated in accordance with all appropriate manuals and wiring diagrams in a residential structure.
Installation in commercial, industrial or office building will void all warranties. Installation to a water source that does not meet unit specification will void all warranties. Replacement of routinely replaceable parts such as steam cylinders and gaskets, are not covered by this limited warranty or any other warranties.
Any other defective parts will be repaired without charge except for removal, reinstallation and transportation costs. To obtain repair service under this limited warranty, the consumer must send the defective part to General Filters, Inc.
THERE ARE NO EXPRESS WARRANTIES COVERING THIS HUMIDIFIER OTHER THAN AS SET FORTH ABOVE. THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED. THE MANUFACTURER ASSUMES NO LIABILITY IN CONNECTION WITH THE INSTALLATION OR USE OF THIS PRODUCT, EXCEPT AS STATED IN THE LIMITED WARRANTY. THE MANUFACTURER WILL IN NO EVENT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES. This limited warranty gives you specific legal rights, and you may also have other rights which vary from state to state. Some states do not allow either limitations on implied warranties, or exclusions from incidental or consequential damages, so the above exclusion and limitation may not apply to you.
Any questions pertaining to this limited warranty should be addressed to General Filters, Inc. General Filters, Inc. has elected not to make available the informal dispute settlement mechanism which is specified in the Magnuso n-Moss Warranty Act.
General Filters, Inc. Canadian General Filters, Inc. 43800 Grand River 400 Midwst Road Novi, MI 48375-1115 Scarborough, ON M1P 3A9
www.generalfilters.com www.cgfproducts.com
DS 50 / DS 50 LC +030222065 Rev. 1.2
25
Page 26
NOTES
_____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________
Page 27
Page 28
GENERAL FILTERS, INC.
43800 GRAND RIVER AVE NOVI, MICHIGAN 43875-1115 248-476-5100
WWW.GENERALAIRE.COM
CANADIAN GENERAL FILTERS, INC.
400 MIDWEST POAD SCARBOROUGH, ONTARIO M1P3A9 416-757-3691
WWW.CGFPRODUCTS.COM
Agency:
Form 50-05 Rev. 1.2
DS 50 / DS 50 LC +030222065 REV 1.2
Loading...