Model 900 Humidier Installation Manual
Unit Location
• WARNING: Disconnect electrical power before beginning installation.
• Do not install where temperatures fall below 32°F / 0° C or where plenum temperatures exceed 200° F / 93° C.
For maximum evaporative capacity, install this humidier on the warm air supply plenum.
Additional Materials That May Be Necessary:
1. 1/4" Diameter plastic supply tubing for cold water applications, or 1/4" copper supply tubing for hot water
applications
2. 6" Diameter galvanized by-pass pipe, elbow, damper, collar
3. 24V Electrical wire and wire nuts
4. Current sensing relay (Model #GA50 - GFI #7026)
5. #8 Self-piercing sheet metal screws
6. 5/8" Drain tubing (990-16 - GFI #7046)
Specifications
• Model: 900 (A & M) Elite Flow Through Humidiers (GFI #5720 & 5725)
• Type: Flow Through
• GPD: 17 Based on 120° F / 49° C Plenum Temperature
• Warranty (Years): 10
• Replacement Vapor Pad®: GA19 (GFI#7919) (Replace 1-2 times per season)
• Dimensions (Inches): 15-1/4 W x 16-1/2 H x 10 D
• Weight (Pounds): 8
• Home Size (Square Feet): To 2,800
• Installation: Warm Air / Return Air Plenum / Right or Left Side
• Plenum Opening (Inches): 8-7/8 W X 12 H
• Bypass Opening (Inches): 6
• Pallet Qty: 32
• Cabinet Construction: UV-Stable Automotive Grade Plastic
• Humidistat (Incuded): “M” Models: MHX3C / “A” Models: GFX3
• Voltage: 24VAC
• In The Box: Humidier, Humidistat, Control Bypass Damper, 24V Transformer, Solenoid Valve, Vapor Pad®,
Saddle Valve, (GCV3412 Code Valve - A Models), Installation Instructions, Template, Parts.
!
15-1/4” W
16-1/2” H
10” D
Expected Humidity Performance Coverage in Square Feet Based on Construction Type
Model No. GPD
Loose
(0.75 AC/H)
Average
(0.50 AC/H)
Tight
(0.30 AC/H)
Elite 570 12 800 Sq. Ft. 1200 Sq. Ft. 2000 Sq. Ft.
Elite 900 17 1115 Sq. Ft. 1650 Sq. Ft. 2800 Sq. Ft.
Elite 1000 18 1175 Sq. Ft. 1770 Sq. Ft. 3000 Sq. Ft.
Outside Design Temperature 0° F / -18° C
Outside Design R.H. 70% R.H.
Inside Design Temperature 70° F / 21° C
Inside Design R.H. 30% R.H.
Air Changes/Hour (AC/H) 0.30
Ceiling Height (Feet) 8
Furnace Plenum Temperature 120° F / 49° C
Furnace Run Time For Calculating Sq. Ft. 8 Hour /1 Day
Humidifier Performance Baseline Criteria
Installation Options:
• Warm Air Plenum
• Return Air Plenum
• Right or Left Bypass
• Vertical or Horizontal
• Furnace or Air Handler