General AUHA12L, AUHA12LAL, AOHA12LACL, AUHA14L, AUHA14LAL Technical Manual

...
Page 1
R410A
INDOOR UNIT
1. CASSETTE
AU A12LAL AU F12LAL
AU A14LAL AU F14LAL
TYPE :
D2D_AU029E/03
2008.04.08
Page 2
1. FEATURE
MODEL :
CASSETTE TYPE
AU A12-14L
INDOOR UNIT
OUTDOOR UNIT
AU A12LAL AO A12LACL AO B12LACL AU F12LAL AO A12LALL AO B12LALL
AU A14LAL AO A14LACL AO B14LACL AU F14LAL AO A14LALL AO B14LALL
FEATURES
• ALL DC DESIGN
• Heat exchange efficiency increased and larger air flow by adoption of new type turbo fan
ADVANCEMENT IN COMFORT
• Quiet operation was realized by adoption of new type turbo fan
• Improvement of air stream
IMPROVEMENT IN AIRFLOW RANGE (14 TYPE)
Wind velocity at maximum point of airflow range is 0.5m/s
CASSETTE TYPE
AU A12-14L
Conventional type
New type
EXPANSION OF AIR OUTLET ADJUSTMENT RANGE (14 TYPE)
Auto airflow direction and auto swing Expanded air outlet range provides more comfortable space
2.5 m
3.7 m
IMPROVEMENT OF INSTALLATION & MAINTENANCE
• COMPACT DESIGN
Fits the European size ceiling.
590
590
18kg18kg
570
570
- (01 - 01) -
Page 3
CASSETTE TYPE
AU A12-14L
• EASY MAINTENANCE
Maintenance of fan motor and fan
Maintenance of fan motor and fan can be done easily after taking off the panel, since bell-mouth can be removed easily A : Fan motor B : 2 stage turbo fan C : Bell-mouth D : Panel
Long life filter Standard equipment
CASSETTE TYPE
AU A12-14L
A
B
C
D
Adaptation of transparent drainage parts
Easy check of operation of drain-up kit When you install
EASY INSTALLATION
Easy setting by wireless or wired remote controller.
FUNCTION SETTING
OTHER FUNCTIONS
• The number of air outlet can be selected.
4-way direction 3-way direction
Grille cover
• High ceiling mode
Air reaches sufficiently up to 3.5m height, even it is compact cassette type.
High ceiling
3.5m
• Setting the filter sign The indoor unit has sign to inform the user that it is time to clean the filter
• Setting the cooler room temperature correction
• Setting the heater room temperature correction
• Auto restart
- (01 - 02) -
Page 4
1 2
2. REMOTE CONTROLLER
WIRELESS REMOTE CONTROLLER
CASSETTE TYPE
AU A12-14L
FEATURES
Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible.
Four kinds of timers. Easy operation.
Easy to change transmission code (4 patterns) by button operation.
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
Built-in timers
Select from four different timer programs (On/Off/Program/Sleep).
CASSETTE TYPE
AU A12-14L
Program timer
The program timer operates the ON and OFF timer once within a 24 hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature automatically rises 1 °C every hour. The set temperature can rise up to a maximum of 2 °C.
Timer setting
60min.
1 °C
2 °C
Heating operation
When the sleep timer is set, the set temperature automatically drops 1 °C every 30 minutes. The set temperature can drop to a maximum of 4 °C.
1 °C
2 °C
3 °C
4 °C
30min.
60min.
90min.
Timer setting
Simultaneously operation
After code change
Mixed-up
• Code selector switch eliminates unit being wrongly switched. (Up to 4 codes can be set.)
A B C D
A B
C
1. Press the MODE button for more than five seconds to start the code change.
D
•Wide and precise transmitting range.
- (01 - 03) -
2. Press the or button to select the desired code.
A B C D
3. Press the MODE button again to end the code change.
Page 5
CASSETTE TYPE
AU A12-14L
FUNCTIONS
1
3
2
4
5
11
13
16
10
14
12
15
CASSETTE TYPE
1
MODE button
Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY). /Start / end R.C. custom code change. (Max 4 types)
2
Economy button
3
Set temp. button ( / )
AU A12-14L
Set remote controller custom code buttons
Sets the indoor temp./ Sets R.C. custom code.
4
Filter reset button
5
Sleep button
Pressed to select sleep timer.
6
6
7
8
9
Fan button
Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH).
7
START/STOP button
Pressed to start and stop operation.
8
Set button (Vertical)
Air flow direction vertical set button.
9
Set button (Horizontal)*
Air flow direction horizontal set button.
10
Swing button
Air flow direction swing button.
11
Timer mode button
Pressed to select the timer mode. (OFF TIMER, ON TIMER, PROGRAM TIMER, TIMER RESET)
Display panel
17
18
19
20
21
22
23
24
25
12
Timer set ( / ) button
Sets the current time and on-off time.
13
Clock adjust button
Sets the current time.
14
Reset button
Used when replacing batteries.
15
Test run button
Used when testing the air conditioner after installation.
16
Signal transmitter
17
Temperature set display
18
Economy display
19
Operating mode display
20
Sleep display
21
Transmit indicator
22
Fan speed display
23
Swing display
24
Timer mode display
25
Clock display
* These functions are not available.
SPECIFICATION
SIZE (H x W x D mm) 170 x 56 x 19
WEIGHT ( g ) 85 (w/o batteries)
ACCESSORY Holder
- (01 - 04) -
Page 6
3. SPECIFICATIONS
CASSETTE TYPE
AU A12-14L
Type
Model name
Power source
Available voltage range
European energy label
Cooling
Capacity
Heating
Input power
Current
EER 3.33 3.21
COP 3.69 3.71 Moisture removal
Fan
Sound pressure level
Heat exchanger type
Enclosure
Dimensions ( H×W×D)
Weight
Connection pipe
Operation range
Remote controller type
Drain pipe
Cooling
Heating
Cooling
Heating
Airflow rate
Type × Q'ty
Motor output W
Net
Gross
Net
Gross
Size mm
Method
Material Size
Rated
Min.-Max.
Rated
Min.-Max.
Rated
*Max.
Rated
*Max.
Rated
*Max.
Rated
*Max.
Cooling
Heating
Cooling
Heating
Cooling
Heating
Dimensions (H × W × D)
Fin pitch 1.20 1.20
Rows x Stages 2X10 2X10
Pipe type
Fin type
Material
Colour
Unit
Panel
Unit
Panel
Unit 15 (33) 15 (33)
Panel
Unit 18 (40) 18 (40)
Panel
Liquid
Gas 9.52( 3/8 in.) 12.70( 1/2 in.)
Cooling
Heating °C
Cooling A A
Heating A A
kW 3.50 4.30
BTU/h 11950 14650
kW 0.90 - 4.40 0.90 - 5.40
BTU/h 3100 - 15000 3100 - 18400
kW 4.10 5.00
BTU/h 14000 17050
kW 0.90 - 5.70 0.90 - 6.50
BTU/h 3100 - 19400 3100 - 22100
kW
A
kW/kW
l/h (pints/h) 1.2 ( 2.1 ) 1.5 ( 2.6 )
High 600 680
Med 530 580
Low 470 490
Quiet 410 410
High 600 800
Med 530 680
Low 470 580
Quiet 410 450
High 37 38 Med 34 34
Low 30 30
Quiet 27 27
High 37 43 Med 34 38
Low 31 34
Quiet 29 30
m3/h
dB(A)
mm
mm
kg(lb.)
°C
%RH
mm
AU A12LAL, AU F12LAL AU A14LAL, AU F14LAL
AO A12LACL, AO A12LALL AO A14LACL, AO A14LALL
1.05 1.33
1.73 2.07
1.11 1.34
2.30 2.88
4.6 5.8
7.5 9.0
4.9 5.9
10.0 12.5
210 × 1310 × 13.3 210 × 1250 × 13.3
Outer diameter : 25.4 / Inner diameter : 19.4
CASSETTE MODEL
INVERTER HEATPUMP
230V 50Hz
198-264V 50Hz
Turbo × 1
54
210 × 1310 × 13.3 210 × 1250 × 13.3
Copper tube
Aluminium
PS
WHITE
245 × 570 × 570
49 x 700 x 700
265 x 730 x 625
120 x 765 x 755
2.6 (5.7)
4.5 (10.0)
6.35 ( 1/4 in.)
Flare
18 to 32
80 or less
30 or less
WIRELESS
ABS
CASSETTE TYPE
AU A12-14L
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB. Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB. Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit) Ceiling mode : Standard *The maximum current and the maximum input value are the maximum values when operated within the operation range (temperature).
- (01 - 05) -
Page 7
CASSETTE TYPE
AU A12-14L
Type
Model name
Power source 230V 50Hz
Available voltage range 198-264V 50Hz
European energy label
Cooling
Capacity
Heating
Input power
Current
EER 3.15 3.05
COP 3.50 3.52 Moisture removal
Fan
Sound pressure level
Heat exchanger type
Enclosure
Dimensions ( H×W×D)
Weight
Connection pipe
Operation range
Remote controller type WIRELESS
Drain pipe
Cooling
Heating
Cooling
Heating
Airflow rate
Type × Q'ty
Motor output W
Net
Gross
Net
Gross
Size mm
Method
Material ABS Size Outer diameter : 25.4 / Inner diameter : 19.4
Rated
Min.-Max.
Rated
Min.-Max.
Rated
*Max.
Rated
*Max.
Rated
*Max.
Rated
*Max.
Cooling
Heating
Cooling
Heating
Cooling
Heating
Dimensions (H × W × D)
Fin pitch 1.20 1.20
Rows x Stages 2X10 2X10
Pipe type
Fin type
Material
Colour
Unit
Panel
Unit
Panel
Unit 15 (33) 15 (33)
Panel
Unit 18 (40) 18 (40)
Panel
Liquid
Gas 9.52( 3/8 in.) 12.70( 1/2 in.)
Cooling
Heating °C
Cooling B B
Heating B B
kW 3.50 4.30
BTU/h 11950 14650
kW 0.90 - 4.30 0.90 - 5.20
BTU/h 3100 - 14650 3100 - 17750
kW 4.10 5.00
BTU/h 14000 17050
kW 0.90 - 5.50 0.90 - 6.30
BTU/h 3100 - 18750 3100 - 21500
kW
A
kW/kW
l/h (pints/h) 1.2 ( 2.1 ) 1.5 ( 2.6 )
High 600 680
Med 530 580
Low 470 490
Quiet 410 410
High 600 800
Med 530 680
Low 470 580
Quiet 410 450
High 37 38
Med 34 34 Low 30 30
Quiet 27 27
High 37 43
Med 34 38 Low 31 34
Quiet 29 30
m3/h
dB(A)
mm
mm
kg(lb.)
°C
%RH
mm
AU A12LAL, AU F12LAL AU A14LAL, AU F14LAL
AO B12LACL, AO B12LALL AO B14LACL, AO B14LALL
1.11 1.41
1.73 2.07
1.17 1.42
2.30 2.88
4.9 6.2
7.5 9.0
5.1 6.2
10.0 12.5
210 × 1310 × 13.3 210 × 1250 × 13.3
CASSETTE MODEL
INVERTER HEATPUMP
Turbo × 1
54
210 × 1310 × 13.3 210 × 1250 × 13.3
Copper tube
Aluminium
PS
WHITE
245 × 570 × 570
49 x 700 x 700
265 x 730 x 625
120 x 765 x 755
2.6 (5.7)
4.5 (10.0)
6.35 ( 1/4 in.)
Flare
18 to 32
80 or less
30 or less
CASSETTE TYPE
AU A12-14L
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB. Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB. Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit) Ceiling mode : Standard *The maximum current and the maximum input value are the maximum values when operated within the operation range (temperature).
- (01 - 06) -
Page 8
4. DIMENSIONS
MODEL : AU A12L, AU F12L, AU A14L, AU F14L
CASSETTE TYPE
AU A12-14L
Top view
(Unit : mm)
Decoration panel mounting state
CASSETTE TYPE
AU A12-14L
Side view
MODEL : UTG-UF A-W, UTG-UF B-W
Bottom view (Panel)
Side view
- (01 - 07) -
Page 9
CASSETTE TYPE
Floor
AU A12-14L
MOUNTING POSITION
Strong and durable ceiling
(Unit : mm)
CASSETTE TYPE
AU A12-14L
Ceiling mode “Standard” : 2,500 - 3,000 Ceiling mode “High” : 3,000 - 3,500
3-Way Directions Setting
1,000 or more
Obstruction
1,000 or more
To set “3-way directions”, the air outlet shutter plate (UTR-YDZ ) sold separately must be installed and “outlet-direction” switched to “3-way” by remote controller.
- (01 - 08) -
Page 10
5. WIRING DIAGRAMS
MODEL : AU A12L, AU F12L, AU A14L, AU F14L
CASSETTE TYPE
AU A12-14L
CASSETTE TYPE
AU A12-14L
- (01 - 09) -
Page 11
6. CAPACITY TABLE
°CDB
°CWB
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3.47 3.22 0.29 3.87 3.24 0.30 4.00 3.52 0.30 4.26 3.53 0.30 4.40 3.81 0.30 4.66 3.80 0.31 4.92 4.05 0.31
3.29 3.07 0.49 3.67 3.09 0.50 3.79 3.36 0.50 4.05 3.37 0.51 4.17 3.64 0.51 4.42 3.63 0.51 4.67 3.86 0.52
3.30 3.07 0.47 3.67 3.09 0.48 3.80 3.36 0.48 4.05 3.37 0.49 4.17 3.64 0.49 4.42 3.63 0.50 4.67 3.86 0.50
3.30 3.07 0.44 3.67 3.09 0.45 3.80 3.36 0.45 4.05 3.37 0.45 4.17 3.64 0.46 4.42 3.63 0.46 4.67 3.86 0.46
3.19 2.99 0.53 3.56 3.01 0.54 3.68 3.27 0.54 3.92 3.28 0.55 4.04 3.54 0.55 4.28 3.53 0.56 4.53 3.76 0.56
4.12 3.76 1.23 4.59 3.78 1.25 4.74 4.11 1.26 5.05 4.12 1.27 5.21 4.45 1.28 5.52 4.43 1.29 5.84 4.72 1.31
3.95 3.62 1.37 4.40 3.64 1.40 4.55 3.96 1.40 4.85 3.97 1.42 5.00 4.29 1.42 5.30 4.27 1.44 5.60 4.55 1.45
3.78 3.47 1.52 4.21 3.49 1.54 4.35 3.80 1.55 4.64 3.81 1.57 4.78 4.12 1.57 5.07 4.10 1.59 5.36 4.37 1.61
3.48 3.22 1.54 3.87 3.24 1.56 4.00 3.52 1.57 4.27 3.54 1.59 4.40 3.82 1.60 4.66 3.80 1.61 4.93 4.05 1.63
2.96 2.80 1.31 3.29 2.81 1.33 3.40 3.06 1.34 3.63 3.07 1.35 3.74 3.31 1.36 3.97 3.30 1.37 4.19 3.51 1.39
2.19 2.17 1.00 2.44 2.18 1.02 2.52 2.38 1.03 2.68 2.38 1.04 2.77 2.57 1.04 2.93 2.56 1.05 3.10 2.73 1.06
30
35
40
Outdoor temperature
°CDB
-10
0
5
10
15
20
46
25
19212312151618
AFR
10.0
Indoor temperature
18212325272932
°CDB
°CWB
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
3.47 3.22 0.29 3.87 3.24 0.30 4.00 3.52 0.30 4.26 3.53 0.30 4.40 3.81 0.30 4.66 3.80 0.31 4.92 4.05 0.31
3.29 3.07 0.49 3.67 3.09 0.50 3.79 3.36 0.50 4.05 3.37 0.51 4.17 3.64 0.51 4.42 3.63 0.51 4.67 3.86 0.52
3.30 3.07 0.47 3.67 3.09 0.48 3.80 3.36 0.48 4.05 3.37 0.49 4.17 3.64 0.49 4.42 3.63 0.50 4.67 3.86 0.50
3.30 3.07 0.44 3.67 3.09 0.45 3.80 3.36 0.45 4.05 3.37 0.45 4.17 3.64 0.46 4.42 3.63 0.46 4.67 3.86 0.46
3.19 2.99 0.53 3.56 3.01 0.54 3.68 3.27 0.54 3.92 3.28 0.55 4.04 3.54 0.55 4.28 3.53 0.56 4.53 3.76 0.56
4.12 3.76 1.23 4.59 3.78 1.25 4.74 4.11 1.26 5.05 4.12 1.27 5.21 4.45 1.28 5.52 4.43 1.29 5.84 4.72 1.31
3.95 3.62 1.37 4.40 3.64 1.40 4.55 3.96 1.40 4.85 3.97 1.42 5.00 4.29 1.42 5.30 4.27 1.44 5.60 4.55 1.45
3.78 3.47 1.52 4.21 3.49 1.54 4.35 3.80 1.55 4.64 3.81 1.57 4.78 4.12 1.57 5.07 4.10 1.59 5.36 4.37 1.61
3.40 3.14 1.54 3.78 3.16 1.56 3.91 3.43 1.57 4.17 3.44 1.59 4.30 3.72 1.60 4.56 3.70 1.61 4.81 3.94 1.63
2.89 2.72 1.31 3.22 2.74 1.33 3.33 2.98 1.34 3.55 2.99 1.35 3.66 3.23 1.36 3.87 3.21 1.37 4.09 3.42 1.39
2.14 2.12 1.00 2.38 2.13 1.02 2.46 2.32 1.03 2.62 2.32 1.04 2.70 2.51 1.04 2.87 2.50 1.05 3.03 2.66 1.06
AFR
10.0
46
25
30
35
40
Indoor temperature
Outdoor temperature
12
18
21
5
20
10
15
15
°CDB
-10
0
16
18
2729232532
231921
6-1. COOLING CAPACITY
CASSETTE TYPE
AU A12-14L
This table is created using the maximum capacity.
MODEL : AU A12L, AU F12L / AO A12L
CASSETTE TYPE
AU A12-14L
MODEL : AU A12L, AU F12L / AO B12L
AFR : Air Flow Rate (m3/min) TC : Total Capacity (kW) SHC : Sensible Heat Capacity (kW) PI : Power Input (kW)
- (01 - 10) -
Page 12
CASSETTE TYPE
°CDB
°CWB
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
4.08 3.75 0.39 4.54 3.77 0.40 4.69 4.10 0.40 5.00 4.11 0.40 5.16 4.44 0.40 5.47 4.43 0.41 5.78 4.71 0.41
3.98 3.68 0.45 4.44 3.70 0.46 4.59 4.02 0.46 4.89 4.03 0.47 5.04 4.35 0.47 5.34 4.34 0.48 5.65 4.62 0.48
3.87 3.59 0.56 4.31 3.61 0.57 4.46 3.92 0.57 4.75 3.93 0.58 4.90 4.25 0.58 5.19 4.23 0.59 5.49 4.51 0.59
3.74 3.48 0.66 4.17 3.50 0.67 4.31 3.81 0.68 4.60 3.82 0.68 4.74 4.13 0.69 5.02 4.11 0.70 5.31 4.38 0.70
3.75 3.49 0.58 4.18 3.51 0.59 4.32 3.82 0.60 4.61 3.83 0.60 4.75 4.14 0.60 5.04 4.12 0.61 5.32 4.39 0.62
4.72 4.27 1.23 5.26 4.30 1.25 5.44 4.67 1.25 5.79 4.69 1.27 5.97 5.06 1.27 6.33 5.04 1.29 6.69 5.37 1.30
4.53 4.11 1.37 5.04 4.14 1.39 5.21 4.50 1.40 5.56 4.51 1.41 5.73 4.88 1.42 6.07 4.86 1.44 6.42 5.17 1.45
4.32 3.95 1.52 4.81 3.97 1.54 4.98 4.32 1.55 5.30 4.33 1.56 5.47 4.68 1.57 5.80 4.66 1.59 6.12 4.96 1.60
4.27 3.90 1.79 4.75 3.93 1.82 4.91 4.27 1.83 5.24 4.28 1.85 5.40 4.63 1.85 5.72 4.61 1.87 6.05 4.91 1.89
3.28 3.12 1.28 3.66 3.13 1.30 3.78 3.41 1.30 4.03 3.42 1.32 4.16 3.69 1.32 4.41 3.68 1.34 4.66 3.92 1.35
2.36 2.39 0.97 2.63 2.40 0.98 2.72 2.61 0.99 2.90 2.62 1.00 2.99 2.83 1.00 3.17 2.82 1.01 3.35 3.00 1.02
30
35
40
Outdoor temperature
°CDB
-10
0
5
10
15
20
46
25
AFR
11.3
Indoor temperature
18212325272932
12151618192123
°CDB
°CWB
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
4.08 3.75 0.39 4.54 3.77 0.40 4.69 4.10 0.40 5.00 4.11 0.40 5.16 4.44 0.40 5.47 4.43 0.41 5.78 4.71 0.41
3.98 3.68 0.45 4.44 3.70 0.46 4.59 4.02 0.46 4.89 4.03 0.47 5.04 4.35 0.47 5.34 4.34 0.48 5.65 4.62 0.48
3.87 3.59 0.56 4.31 3.61 0.57 4.46 3.92 0.57 4.75 3.93 0.58 4.90 4.25 0.58 5.19 4.23 0.59 5.49 4.51 0.59
3.74 3.48 0.66 4.17 3.50 0.67 4.31 3.81 0.68 4.60 3.82 0.68 4.74 4.13 0.69 5.02 4.11 0.70 5.31 4.38 0.70
3.75 3.49 0.58 4.18 3.51 0.59 4.32 3.82 0.60 4.61 3.83 0.60 4.75 4.14 0.60 5.04 4.12 0.61 5.32 4.39 0.62
4.72 4.27 1.23 5.26 4.30 1.25 5.44 4.67 1.25 5.79 4.69 1.27 5.97 5.06 1.27 6.33 5.04 1.29 6.69 5.37 1.30
4.53 4.11 1.37 5.04 4.14 1.39 5.21 4.50 1.40 5.56 4.51 1.41 5.73 4.88 1.42 6.07 4.86 1.44 6.42 5.17 1.45
4.32 3.95 1.52 4.81 3.97 1.54 4.98 4.32 1.55 5.30 4.33 1.56 5.47 4.68 1.57 5.80 4.66 1.59 6.12 4.96 1.60
4.11 3.74 1.79 4.58 3.76 1.82 4.73 4.09 1.83 5.04 4.10 1.85 5.20 4.43 1.85 5.51 4.41 1.87 5.82 4.70 1.89
3.16 2.99 1.28 3.52 3.00 1.30 3.64 3.27 1.30 3.88 3.28 1.32 4.00 3.54 1.32 4.24 3.52 1.34 4.48 3.75 1.35
2.27 2.30 0.97 2.53 2.31 0.98 2.62 2.51 0.99 2.79 2.52 1.00 2.88 2.72 1.00 3.05 2.71 1.01 3.22 2.89 1.02
AFR
11.3
46
25
30
35
40
Indoor temperature
Outdoor temperature
12
18
21
5
20
10
15
15
°CDB
-10
0
16
18
2729232532
231921
AU A12-14L
MODEL : AU A14L, AU F14L / AO A14L
MODEL : AU A14L, AU F14L / AO B14L
CASSETTE TYPE
AU A12-14L
AFR : Air Flow Rate (m3/min) TC : Total Capacity (kW) SHC : Sensible Heat Capacity (kW) PI : Power Input (kW)
- (01 - 11) -
Page 13
6-2. HEATING CAPACITY
TC PI TC PI TC PI TC PI TC PI
3.76 1.87 3.67 1.91 3.58 1.95 3.49 1.99 3.40 2.03
4.26 1.87 4.16 1.91 4.06 1.95 3.96 1.99 3.86 2.03
4.69 2.15 4.58 2.19 4.47 2.23 4.35 2.28 4.20 2.30
5.30 2.14 5.17 2.18 5.05 2.23 4.92 2.27 4.76 2.30
5.79 2.15 5.65 2.19 5.51 2.24 5.38 2.28 5.18 2.30
5.99 2.07 5.85 2.11 5.70 2.15 5.56 2.20 5.42 2.24
6.05 1.84 5.91 1.87 5.76 1.91 5.62 1.95 5.47 1.99
6.08 1.76 5.93 1.80 5.79 1.84 5.64 1.87 5.50 1.91
5.87 1.48 5.73 1.51 5.59 1.54 5.45 1.57 5.31 1.61
5.86 1.48 5.72 1.51 5.58 1.54 5.44 1.57 5.30 1.60
24
18
20
15
15
10
10
8
7
6
5
3
0
-2
-10
-11
-5
-7
Outdoor temperature
°CDB
°CWB
-15
-16
AFR
10.0
Indoor temperature
°CDB16182022
24
TC PI TC PI TC PI TC PI TC PI
3.76 1.87 3.67 1.91 3.58 1.95 3.49 1.99 3.40 2.03
4.26 1.87 4.16 1.91 4.06 1.95 3.96 1.99 3.86 2.03
4.53 2.15 4.42 2.19 4.31 2.23 4.20 2.28 4.20 2.30
5.12 2.14 4.99 2.18 4.87 2.23 4.75 2.27 4.76 2.30
5.59 2.15 5.45 2.19 5.32 2.24 5.19 2.28 5.18 2.30
5.78 2.07 5.64 2.11 5.50 2.15 5.37 2.20 5.23 2.24
5.84 1.84 5.70 1.87 5.56 1.91 5.42 1.95 5.28 1.99
5.87 1.76 5.73 1.80 5.59 1.84 5.45 1.87 5.31 1.91
5.67 1.48 5.53 1.51 5.40 1.54 5.26 1.57 5.13 1.61
5.65 1.48 5.52 1.51 5.38 1.54 5.25 1.57 5.11 1.60
Indoor temperature
-5
161820
22
18
20
7
3
15
10
6
0
-2
15
°CDB
°CWB
-15
24
-10
10
AFR
°CDB
10.0
24
-16
-11
-7
Outdoor temperature
8
5
CASSETTE TYPE
AU A12-14L
This table is created using the maximum capacity.
MODEL : AU A12L, AU F12L / AO A12L
CASSETTE TYPE
AU A12-14L
MODEL : AU A12L, AU F12L / AO B12L
AFR : Air Flow Rate (m3/min) TC : Total Capacity (kW) PI : Power Input (kW)
- (01 - 12) -
Page 14
CASSETTE TYPE
TC PI TC PI TC PI TC PI TC PI
4.24 2.16 4.14 2.21 4.04 2.25 3.94 2.30 3.84 2.34
4.88 2.16 4.76 2.21 4.65 2.25 4.53 2.30 4.41 2.34
5.49 2.40 5.36 2.45 5.23 2.50 5.10 2.55 4.97 2.60
6.37 2.73 6.22 2.79 6.07 2.84 5.87 2.88 5.61 2.88
6.97 2.71 6.80 2.77 6.64 2.83 6.47 2.88 6.18 2.88
6.82 2.36 6.66 2.40 6.50 2.45 6.34 2.50 6.17 2.55
7.03 2.37 6.86 2.42 6.70 2.47 6.53 2.52 6.36 2.56
6.75 2.07 6.59 2.12 6.43 2.16 6.27 2.20 6.11 2.25
6.22 1.59 6.07 1.63 5.92 1.66 5.77 1.69 5.62 1.73
6.40 1.60 6.25 1.64 6.10 1.67 5.94 1.70 5.79 1.74
24
18
15
10
20
15
7
6
10
8
-7
0
-2
5
3
Outdoor temperature
°CDB
°CWB
-15
-16
-10
-11
-5
AFR
14.7
Indoor temperature
°CDB16182022
24
TC PI TC PI TC PI TC PI TC PI
4.24 2.16 4.14 2.21 4.04 2.25 3.94 2.30 3.84 2.34
4.88 2.16 4.76 2.21 4.65 2.25 4.53 2.30 4.41 2.34
5.49 2.40 5.36 2.45 5.23 2.50 5.10 2.55 4.97 2.60
6.37 2.73 6.22 2.79 6.07 2.84 5.87 2.88 5.61 2.88
6.75 2.71 6.59 2.77 6.43 2.83 6.27 2.88 6.18 2.88
6.61 2.36 6.45 2.40 6.30 2.45 6.14 2.50 5.98 2.55
6.81 2.37 6.65 2.42 6.49 2.47 6.33 2.52 6.17 2.56
6.54 2.07 6.39 2.12 6.23 2.16 6.07 2.20 5.92 2.25
6.02 1.59 5.88 1.63 5.74 1.66 5.59 1.69 5.45 1.73
6.20 1.60 6.05 1.64 5.91 1.67 5.76 1.70 5.61 1.74
Indoor temperature
-5
161820
22
18
20
7
3
°CDB
°CWB
-15
24
15
Outdoor temperature
8510
15
10
6
0
-2
24
-16
-11-7-10
AFR
°CDB
14.7
AU A12-14L
MODEL : AU A14L, AU F14L / AO A14L
CASSETTE TYPE
AU A12-14L
MODEL : AU A14L, AU F14L / AO B14L
AFR : Air Flow Rate (m3/min) TC : Total Capacity (kW) PI : Power Input (kW)
- (01 - 13) -
Page 15
7. FAN PERFORMANCE
7-1. AIR VELOCITY DISTRIBUTION
CASSETTE TYPE
AU A12-14L
MODEL : AU A12L, AU F12L
4-WAY AIR OUTLET
(m)
4
0.25
3
0.5
2
1
Unit : m/s
Note :
Condition
Fan speed : High Operation mode : FAN Ceiling mode : Standard
CASSETTE TYPE
AU A12-14L
1
2
0
2
1
1
0.25
0.5
2
1
2
1
0.5
0.25
2
0.5
3
0.25
4
4 3 2 1 0 1 2 3 4
(m)
3
1
2
1
2
Unit : m/s
2
0.5
0.5
TOP VIEW HORIZONTAL LOUVER : Upward
(m)
1
0.25
0
4 3 2 1 0 1 2 3 4
(m)
3
2
2
Unit : m/s
2
1
1
0.25
0.5
1
0.5
0.25
0
4 3 2 1 0 1 2 3 4
- (01 - 14) -
0.25
SIDE VIEW HORIZONTAL LOUVER : Upward
(m)
SIDE VIEW HORIZONTAL LOUVER : Downward
(m)
Page 16
CASSETTE TYPE
AU A12-14L
3-WAY AIR OUTLET
(m)
4
3
2
1
0.25
0
0.5
1
CASSETTE TYPE
AU A12-14L
Unit : m/s
Note :
Condition
0.25
0.5
1
2
0.5
1
0.25
Fan speed : High Operation mode : FAN Ceiling mode : Standard
2
2
4 3 2 1 0 1 2 3 4
(m)
3
2
2
1
0.5
1
0.25
2
1
Unit : m/s
0.5
0.25
0
4 3 2 1 0 1 2 3 4
(m)
3
2
2
Unit : m/s
2
TOP VIEW HORIZONTAL LOUVER : Upward
(m)
SIDE VIEW HORIZONTAL LOUVER : Upward
(m)
1
1
1
0.25
0.5
0.5
0.25
0
4 3 2 1 0 1 2 3 4
- (01 - 15) -
SIDE VIEW HORIZONTAL LOUVER : Downward
(m)
Page 17
CASSETTE TYPE
AU A12-14L
MODEL : AU A14L, AU F14L
4-WAY AIR OUTLET
(m)
4
3
2
0.5
0.25
1
Unit : m/s
Note :
Condition
Fan speed : High Operation mode : FAN Ceiling mode : Standard
CASSETTE TYPE
AU A12-14L
1
2
0
1
0.25
0.5
1
2
2
2
1
0.5
1
0.25
2
0.5
3
0.25
4
4 3 2 1 0 1 2 3 4
(m)
3
1
2
2
1
Unit : m/s
2
0.5
0.5
TOP VIEW HORIZONTAL LOUVER : Upward
(m)
1
0.25
0
4 3 2 1 0 1 2 3 4
(m)
3
2
2
Unit : m/s
2
1
1
1
0.25
0.5
0.5
0.25
0
4 3 2 1 0 1 2 3 4
- (01 - 16) -
0.25
SIDE VIEW HORIZONTAL LOUVER : Upward
(m)
SIDE VIEW HORIZONTAL LOUVER : Downward
(m)
Page 18
CASSETTE TYPE
AU A12-14L
3-WAY AIR OUTLET
(m)
4
3
2
0.25
1
0.5
Unit : m/s
Note :
Condition
Fan speed : High Operation mode : FAN Ceiling mode : Standard
CASSETTE TYPE
AU A12-14L
1
0.25
0.5
1
2
2
2
1
0.5
0.25
0
4 3 2 1 0 1 2 3 4
(m)
3
2
2
1
0.5
1
0.25
2
1
0.25
Unit : m/s
0.5
0
4 3 2 1 0 1 2 3 4
TOP VIEW HORIZONTAL LOUVER : Upward
(m)
SIDE VIEW HORIZONTAL LOUVER : Upward
(m)
(m)
3
2
2
Unit : m/s
2
1
0.25
1
0.5
1
0.250.5
0
4 3 2 1 0 1 2 3 4
SIDE VIEW HORIZONTAL LOUVER : Downward
(m)
- (01 - 17) -
Page 19
7-2. AIR FLOW
650
580
520
460
MED
LOW
QUIET
MED
LOW
QUIET
650
580
520
460
Number of rotations
(r.p.m)
Air flow
7-2-1. STANDARD CEILING MODE
CASSETTE TYPE
AU A12-14L
MODEL : AU A12L, AU F12L
COOLING
Fan speed
CASSETTE TYPE
AU A12-14L
HIGH
HEATING
Fan speed
Number of rotations
(r.p.m)
m3/h
l/s 167
CFM 353
m3/h
l/s 147
CFM 312
m3/h
l/s 131
CFM 277
m3/h
l/s 114
CFM 241
Air flow
600
530
470
410
HIGH
m3/h
l/s 167
CFM 353
m3/h
l/s 147
CFM 312
m3/h
l/s 131
CFM 277
m3/h
l/s 114
CFM 241
600
530
470
410
- (01 - 18) -
Page 20
CASSETTE TYPE
630
LOW
540
QUIET
460
730
MED
HIGH
830
730
LOW
630
QUIET
500
AU A12-14L
MODEL : AU A14L, AU F14L
COOLING
Number of
Fan speed
rotations
(r.p.m)
Air flow
CASSETTE TYPE
AU A12-14L
HIGH
HEATING
Fan speed
Number of rotations
(r.p.m)
m3/h
680
l/s 189
CFM 400
m3/h
580
l/s 161
CFM 341
m3/h
490
l/s 136
CFM 288
m3/h
410
l/s 114
CFM 241
Air flow
MED
m3/h
800
l/s 222
CFM 471
m3/h
680
l/s 189
CFM 400
m3/h
580
l/s 161
CFM 341
m3/h
450
l/s 125
CFM 265
- (01 - 19) -
Page 21
7-2-2. HIGH CEILING MODE
QUIET
750
680
620
460
MED
LOW
750
MED
LOW
QUIET
680
620
460
CASSETTE TYPE
AU A12-14L
MODEL : AU A12L, AU F12L
COOLING
Number of
Fan speed
rotations
(r.p.m)
Air flow
CASSETTE TYPE
AU A12-14L
HIGH
HEATING
Fan speed
Number of rotations
(r.p.m)
m3/h
l/s 194
CFM 412
m3/h
l/s 175
CFM 371
m3/h
l/s 158
CFM 335
m3/h
l/s 114
CFM 241
Air flow
700
630
570
410
HIGH
m3/h
l/s 194
CFM 412
m3/h
l/s 175
CFM 371
m3/h
l/s 158
CFM 335
m3/h
l/s 114
CFM 241
700
630
570
410
- (01 - 20) -
Page 22
CASSETTE TYPE
HIGH
830
730
LOW
640
QUIET
460
LOW
730
QUIET
500
930
MED
830
AU A12-14L
MODEL : AU A14L, AU F14L
COOLING
Number of
Fan speed
rotations
(r.p.m)
Air flow
CASSETTE TYPE
AU A12-14L
MED
HEATING
Fan speed
Number of rotations
(r.p.m)
m3/h
800
l/s 222
CFM 471
m3/h
680
l/s 189
CFM 400
m3/h
590
l/s 164
CFM 347
m3/h
410
l/s 114
CFM 241
Air flow
HIGH
m3/h
900
l/s 250
CFM 530
m3/h
800
l/s 222
CFM 471
m3/h
680
l/s 189
CFM 400
m3/h
450
l/s 125
CFM 265
- (01 - 21) -
Page 23
8. OPERATION NOISE
HIGH
QUIET
HIGH
QUIET
HIGH
QUIET
HIGH
QUIET
8-1. NOISE LEVEL CURVE
CASSETTE TYPE
AU A12-14L
MODEL : AU A12L, AU F12L
CASSETTE TYPE
AU A12-14L
COOLING
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HEATING
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL : AU A14L, AU F14L
COOLING
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HEATING
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
- (01 - 22) -
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
Page 24
8-2. SOUND LEVEL CHECK POINT
CASSETTE TYPE
AU A12-14L
Microphone
CASSETTE TYPE
AU A12-14L
Microphone
- (01 - 23) -
Page 25
9. ELECTRIC CHARACTERISTICS
CASSETTE TYPE
AU A12-14L
Model name
AU A12L AU F12L
AU A14L AU F14L
CASSETTE TYPE
AU A12-14L
Voltage V
230
Power supply
Frequency Hz
50
Max. operating current (Indoor unit) A 0.2 0.3
Wiring spec. (Indoor unit to outdoor unit)
Connection cable
Limited wiring length m 26 26
mm
2
1.5-2.5 1.5-2.5
- (01 - 24) -
Page 26
10. SAFETY DEVICES
CASSETTE TYPE
AU A12-14L
Protection form
Model
AU A12L AU A14L AU F12L AU F14L
CASSETTE TYPE
AU A12-14L
Circuit protection Current fuse (PCB)
Fan motor protection Thermal protection program
3.15A 250V
140±20°C OFF
110±20°C ON
- (01 - 25) -
Page 27
11. OPTIONAL PARTS
CASSETTE TYPE
AU A12-14L
Exterior Summary
Parts name
Model No.
CASSETTE TYPE
AU A12-14L
Wired remote
controller
Decoration
panel
Air outlet
shutter plate
UTB- UD
UTG-UF A-F
UTR-YDZA
Unit control is performed by
wired remote controller
For AU A12L, AU A14L
Ceiling dirt by discharged wind was made difficult to cling by reviewing the shape of the
LOUVER.
For AU A12L, AU A14L
Air outlet shutter plate is installed at the air outlet when 3-way direction is performed.
Decoration
panel
Air outlet
shutter plate
UTG-UF B-F
UTR-YDZB
For AU F12L, AU F14L
Ceiling dirt by discharged wind was made difficult to cling by reviewing the shape of the
LOUVER.
For AU F12L, AU F14L
Air outlet shutter plate is installed at the air outlet when 3-way direction is performed.
- (01 - 26) -
Page 28
R410A
OUTDOOR UNIT
2.
SINGLE TYPE :
AO A12LACL
AO A12LALL
AO A14LACL
AO A14LALL
D2D_AO010E/03
2008.04.08
Page 29
1. SPECIFICATIONS
OUTDOOR UNIT
AO A12-14L
Type
Model name
Power source
Available voltage range
Starting current
Airflow
Fan
Sound pressure level
Heat exchanger type
Compressor
Refrigerant
Refrigerant oil
Enclosure
Dimensions (H × W × D)
Weight kg(lb.)
Connection pipe
rate
Type × Q'ty
Motor output
Type × Q'ty
Motor output
Net
Gross
Net
Gross
Size mm
Method
Max. length
Max. height difference
Cooling
Heating
Cooling
Heating
Dimensions (H × W × D)
Fin pitch
Rows x Stages
Pipe type
Fin type
Type
Charge
Type
Material
Colour
Liquid
Gas
Cooling
Heating
A 4.9 5.9
m3/h
W
dB(A)
mm
W
g 1150 1250
mm
m
°COperation range
INVERTER HEATPUMP
AO A12LACL AO A14LACL AO A12LALL AO A14LALL
230V 50Hz
198-264V 50Hz
1780 1910
1630 1740
Propeller × 1
54
47 49
48 49
546 × 876 × 18.2 546 × 842 × 18.2
1.30
2 × 26
Copper
Aluminium
Twin Rotary × 1
1100
R410A
POE
Steel sheet
Beige (10YR7.5/1.0NN)
578 × 790 × 300
648 × 910 × 380
40 (88) 40 (88)
44 (97) 44 (97)
Φ
6.35 (Φ 1/4 in.)
Φ
9.52 (Φ 3/8 in.)
Flare
25 (chargeless : 15)
-10 to 46
-15 to 24
15
Φ
12.70 (Φ 1/2 in.)
OUTDOOR UNIT
AO A12-14L
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27°CDB/19°CWB. and outdoor temperature of 35°CDB/24°CWB. Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB. Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
- (02 - 01) -
Page 30
2. DIMENSIONS
MODEL : AO A12L, AO A14L
OUTDOOR UNIT
AO A12-14L
Top view
(Unit : mm)
OUTDOOR UNIT
AO A12-14L
Front view
Bottom view
MOUNTING POSITION
When there are obstacles at the back or front sides.
Air flow
When there are obstacles at the back, side(s), and top.
Side view
When there are obstacles at the back, side with the installation of more than one unit.
600 - 1000
100 or more
600 or more
100 - 300
250 or more
(Service space)
300 or more
250 or more
250 or more
If the space is larger that is stated, the condition will be the same as that are no obstacles.
- (02 - 02) -
300 or more
Page 31
3. REFRIGERANT CIRCUIT
MODEL : AO A12L, AO A14L
OUTDOOR UNIT
AO A12-14L
OUTDOOR UNIT
AO A12-14L
- (02 - 03) -
Page 32
4. WIRING DIAGRAMS
MODEL : AO A12L, AO A14L
OUTDOOR UNIT
AO A12-14L
OUTDOOR UNIT
AO A12-14L
- (02 - 04) -
Page 33
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE
This table is created using the maximum capacity.
MODEL : AO A12L
OUTDOOR UNIT
AO A12-14L
Height
difference H
(m)
Height
difference H
(m)
COOLING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
HEATING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Pipe length (m)
5 7.5 10 15 20 25
15 - - -
10 - -
7.5 -
5
0 1.026 1.000 0.980 0.933 0.923 0.895
-5
-7.5 -
-10 - -
-15 - - -
15 - - -
10 - -
7.5 -
5
0 0.954 1.000 1.010 0.943 0.916 0.896
-5
-7.5 -
-10 - -
-15 - - -
1.018 0.992 0.972 0.925 0.916 0.888
1.026 1.000 0.980 0.933 0.923 0.895
5 7.5 10 15 20 25
0.954 1.000 1.010 0.943 0.916 0.896
0.949 0.995 1.005 0.939 0.912 0.892
0.988 0.968 0.922 0.912 0.885
1.000 0.980 0.933 0.923 0.895
1.000 1.010 0.943 0.916 0.896
0.993 1.002 0.936 0.909 0.890
0.964 0.918 0.909 0.881
0.980 0.933 0.923 0.895
Pipe length (m)
1.010 0.943 0.916 0.896
0.999 0.934 0.907 0.887
0.903 0.894 0.867
0.933 0.923 0.895
0.943 0.916 0.896
0.925 0.898 0.878
OUTDOOR UNIT
AO A12-14L
Indoor unit
H
Outdoor unit
Connection pipe
1
Indoor unit is upper than outdoor unit.
Height difference H
Outdoor unit
Connection pipe
2
Indoor unit is under than outdoor unit.
- (02 - 05) -
H
Indoor unit
Page 34
This table is created using the maximum capacity.
MODEL : AO A14L
OUTDOOR UNIT
AO A12-14L
Height
difference H
(m)
Height
difference H
(m)
COOLING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
HEATING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Pipe length (m)
5 7.5 10 15 20 25
15 - - -
10 - -
7.5 -
5
0.992 0.992 0.991 0.976 0.974 0.970
0.988 0.987 0.972 0.970 0.966
0.983 0.968 0.966 0.962
0.953 0.950 0.947
0 1.000 1.000 0.999 0.984 0.982 0.978
-5
-7.5 -
-10 - -
-15 - - -
1.000 1.000 0.999 0.984 0.982 0.978
1.000 0.999 0.984 0.982 0.978
0.999 0.984 0.982 0.978
0.984 0.982 0.978
Pipe length (m)
5 7.5 10 15 20 25
15 - - -
10 - -
7.5 -
5
0.994 1.000 0.981 0.918 0.891 0.862
1.000 0.981 0.918 0.891 0.862
0.981 0.918 0.891 0.862
0.918 0.891 0.862
0 0.994 1.000 0.981 0.918 0.891 0.862
-5
-7.5 -
-10 - -
-15 - - -
0.989 0.995 0.976 0.914 0.886 0.858
0.993 0.974 0.912 0.884 0.856
0.972 0.909 0.882 0.854
0.900 0.873 0.845
OUTDOOR UNIT
AO A12-14L
Height difference H
Indoor unit
H
Outdoor unit
Connection pipe
Indoor unit is upper than outdoor unit.1 Indoor unit is under than outdoor unit.2
Outdoor unit
H
Indoor unit
Connection pipe
- (02 - 06) -
Page 35
6. ADDITIONAL CHARGE CALCULATION
Refrigerant type
Refrigerant type
20g/m
1250
R410A
1150
20g/m
R410A
MODEL : AO A12L
Refrigerant amount g
OUTDOOR UNIT
AO A12-14L
REFRIGERANT CHARGE
Pipe length m 15 20 25
Additional charge g 0 (Chargeless) +100 +200
MODEL : AO A14L
Refrigerant amount g
REFRIGERANT CHARGE
Pipe length m 15 20 25
Additional charge g 0 (Chargeless) +100 +200
OUTDOOR UNIT
AO A12-14L
- (02 - 07) -
Page 36
7. AIR FLOW
750
820
700
770
Number of
rotations
(r.p.m)
(r.p.m)
(r.p.m)
(r.p.m)
Air flow
MODEL : AO A12L
COOLING
OUTDOOR UNIT
AO A12-14L
m3/h
l/s 494
CFM 1048
HEATING
Number of
rotations Air flow
m3/h
l/s 453
CFM 959
MODEL : AO A14L
COOLING
1780
1630
OUTDOOR UNIT
AO A12-14L
Number of
rotations Air flow
m3/h
l/s 531
CFM 1124
HEATING
Number of
rotations Air flow
m3/h
l/s 483
CFM 1024
1910
1740
- (02 - 08) -
Page 37
8. OPERATION NOISE
8-1. NOISE LEVEL CURVE
COOLING
OUTDOOR UNIT
AO A12-14L
MODEL : AO A12L
80
70
60
50
40
30
d pressure level, dB:(0dB=0.0002µbar) n
sou d
20
ave ban
t c
O
10
0
63 125 250 500 1,000 2,000 4 ,000 8,000
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL : AO A14L
80
70
60
50
40
30
d pressure level, dB:(0dB=0.0002µbar) n
sou d
20
ave ban
t c
O
10
0
63 125 250 500 1,000 2,000 4 ,000 8,000
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
OUTDOOR UNIT
AO A12-14L
HEATING
MODEL : AO A12L
80
70
60
) ar
µb 2
50
B:(0dB=0.000 d
40
30
20
Octave band sound pressure level,
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL : AO A14L
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63 125 250 500 1,000 2,000 4 ,000 8,000
Octave band center frequency,Hz
- (02 - 09) -
0
63 125 250 500 1,000 2,000 4 ,000 8,000
Octave band center frequency,Hz
Page 38
8-2. SOUND LEVEL CHECK POINT
OUTDOOR UNIT
AO A12-14L
OUTDOOR UNIT
AO A12-14L
- (02 - 10) -
Page 39
9. ELECTRIC CHARACTERISTICS
OUTDOOR UNIT
AO A12-14L
Model Name
Voltage V
AO A12L AO A14L
230
Power Supply
Frequency Hz
Max Operating Current
Starting Current
Main Fuse (Circuit breaker) Current
*1) Wiring Spec.
Power Cable
A 10.0 12.5
A 4.9 5.9
A 20 20
2
mm
50
4.0
*2) Limited wiring length m 36 28
*1) Wiring Spec. Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length This is the wiring length in case voltage descent is less than 2%. When the wiring length becomes long, please select the wiring of a more larger diameter.
OUTDOOR UNIT
AO A12-14L
- (02 - 11) -
Page 40
10. SAFETY DEVICES
AO A12L AO A14L
Thermal protection program (COMPRESSOR TEMP.)
Thermal protection program (DISCHARGE TEMP.)
15A 250V
3.15A 250V
Compressor protection
Circuit protection
OFF : 110°C
ON : After 40 minutes
OFF : 110°C
ON : After 7 minutes
Current fuse (NEAR THE TERMINAL)
Current fuse
(MAIN PRINTED CIRCUIT BOARD)
OFF : 100
+15
-10
°C
ON : 95
+15
-10
°C
Protection form
20A 250V
5A 250V
Model
OUTDOOR UNIT
AO A12-14L
Fan motor protection Thermal protection program
OUTDOOR UNIT
AO A12-14L
- (02 - 12) -
Page 41
R410A
OUTDOOR UNIT
2.
SINGLE TYPE :
AO B12LACL
AO B12LALL
AO B14LACL
AO B14LALL
D2D_AO020E/02
2008.04.08
Page 42
- (02 - 01) -
OUTDOOR UNIT
AOB12-14L
OUTDOOR UNIT
AOB12-14L
1. SPECIFICATIONS
Type
Model name
Power source
Available voltage range
Starting current
Fan
Sound pressure level
Heat exchanger type
Airflow rate
Type × Q'ty
Motor output W
Cooling 1780 1910
m3/h
Heating 1630 1740
Cooling 47 49
dB(A)
Heating 48 49
Dimensions (H × W × D)
mm
Fin pitch
Rows x Stages
Pipe type
Fin type
INVERTER HEATPUMP
AO B12LACL AO B14LACL
AO B12LALL AO B14LALL
230V ~50Hz
198-264V ~ 50Hz
A 4.9 5.9
Propeller × 1
54
546 × 876 × 18.2 546 × 842 × 18.2
1.30
2 × 26
Copper
Aluminium
Compressor
Refrigerant
Refrigerant oil Type
Enclosure
Dimensions ( H×W×D)
Weight kg(lb.)
Connection pipe
Type × Q'ty
Motor output W
Type
Charge g 1150 1250
Material
Colour
Net
mm
Gross
Net 40 ( 88 ) 40 ( 88 )
Gross 44 ( 97 ) 44 ( 97 )
Liquid
Size mm
Gas
Method
Max. length
m
Max. height difference
Cooling
°COperation range
Heating
Twin Rotary × 1
1100
R410A
POE
Steel sheet
Beige (10YR7.5/1.0NN)
578 × 790 × 300
648 × 910 × 380
Φ
6.35 (Φ 1/4 in.)
Φ 9.52 (Φ 3/8 in.) Φ
Flare
25(chargeless:15)
15
-10 to 46
-15 to 24
12.70 (Φ 1/2 in.)
Note : Specifications are based on the following conditions. Cooling : Indoor temperature of 27°CDB/19°CWB. and outdoor temperature of 35°CDB/24°CWB. Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB. Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)
Page 43
- (02 - 02) -
OUTDOOR UNIT
AOB12-14L
OUTDOOR UNIT
AOB12-14L
2. DIMENSIONS
MODEL : AO B12L, AO B14L
(Unit : mm)
Top view
Front view
Air flow
Side view
Bottom view
MOUNTING POSITION
When there are obstacles at the back or front sides.
100 or more
600 or more
100 - 300
If the space is larger that is stated, the condition will be the same as that are no obstacles.
When there are obstacles at the back, side(s), and top.
600 - 1000
250 or more
250 or more
(Service space)
300 or more
When there are obstacles at the back, side with the installation of more than one unit.
250 or more
300 or more
Page 44
- (02 - 03) -
OUTDOOR UNIT
AOB12-14L
OUTDOOR UNIT
AOB12-14L
3. REFRIGERANT CIRCUIT
MODEL : AO B12L, AO B14L
Page 45
- (02 - 04) -
OUTDOOR UNIT
AOB12-14L
OUTDOOR UNIT
AOB12-14L
4. WIRING DIAGRAMS
MODEL : AO B12L, AO B14L
Page 46
- (02 - 05) -
OUTDOOR UNIT
AOB12-14L
OUTDOOR UNIT
AOB12-14L
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DIFFERENCE
MODEL : AO B12L
Indoor unit
Height difference H
Connection pipe
H
Outdoor unit
Indoor unit
Connection pipe
H
Outdoor unit
Indoor unit is upper than outdoor unit.
1
Indoor unit is under than outdoor unit.
2
5 7.5 10 15 20 25
15 - - -
0.933 0.923 0.895
10 - -
0.980 0.933 0.923 0.895
7.5 -
1.000 0.980 0.933 0.923 0.895
5
1.026 1.000 0.980 0.933 0.923 0.895
0 1.026 1.000 0.980 0.933 0.923 0.895
-5
1.018 0.992 0.972 0.925 0.916 0.888
-7.5 -
0.988 0.968 0.922 0.912 0.885
-10 - -
0.964 0.918 0.909 0.881
-15 - - -
0.903 0.894 0.867
5 7.5 10 15 20 25
15 - - -
0.925 0.898 0.878
10 - -
0.999 0.934 0.907 0.887
7.5 -
0.993 1.002 0.936 0.909 0.890
5
0.949 0.995 1.005 0.939 0.912 0.892
0 0.954 1.000 1.010 0.943 0.916 0.896
-5
0.954 1.000 1.010 0.943 0.916 0.896
-7.5 -
1.000 1.010 0.943 0.916 0.896
-10 - -
1.010 0.943 0.916 0.896
-15 - - -
0.943 0.916 0.896
Height
difference H
(m)
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Pipe length (m)
Pipe length (m)
HEATING
COOLING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Height
difference H
(m)
Page 47
- (02 - 06) -
OUTDOOR UNIT
AOB12-14L
OUTDOOR UNIT
AOB12-14L
MODEL : AO B14L
Indoor unit
Height difference H
Connection pipe
H
Outdoor unit
Indoor unit
Connection pipe
H
Outdoor unit
Indoor unit is upper than outdoor unit.1 Indoor unit is under than outdoor unit.2
5 7.5 10 15 20 25
15 - - -
0.984 0.982 0.978
10 - -
0.999 0.984 0.982 0.978
7.5 -
1.000 0.999 0.984 0.982 0.978
5
1.000 1.000 0.999 0.984 0.982 0.978
0 1.000 1.000 0.999 0.984 0.982 0.978
-5
0.992 0.992 0.991 0.976 0.974 0.970
-7.5 -
0.988 0.987 0.972 0.970 0.966
-10 - -
0.983 0.968 0.966 0.962
-15 - - -
0.953 0.950 0.947
5 7.5 10 15 20 25
15 - - -
0.900 0.873 0.845
10 - -
0.972 0.909 0.882 0.854
7.5 -
0.993 0.974 0.912 0.884 0.856
5
0.989 0.995 0.976 0.914 0.886 0.858
0 0.994 1.000 0.981 0.918 0.891 0.862
-5
0.994 1.000 0.981 0.918 0.891 0.862
-7.5 -
1.000 0.981 0.918 0.891 0.862
-10 - -
0.981 0.918 0.891 0.862
-15 - - -
0.918 0.891 0.862
HEATING
COOLING
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Height
difference H
(m)
Pipe length (m)
Pipe length (m)
Height
difference H
(m)
1
Indoor unit is upper
than outdoor unit.
2
Indoor unit is under
than outdoor unit
Page 48
- (02 - 07) -
OUTDOOR UNIT
AOB12-14L
OUTDOOR UNIT
AOB12-14L
6. ADDITIONAL CHARGE CALCULATION
MODEL : AO B12L
REFRIGERANT CHARGE
MODEL : AO B14L
REFRIGERANT CHARGE
Refrigerant amount g
Pipe length m 15 20 25
Additional charge g 0 (Chargeless) +100 +200
Refrigerant amount g
Pipe length m 15 20 25
Additional charge g 0 (Chargeless) +100 +200
Refrigerant type
Refrigerant type
20g/m
1250
R410A
1150
20g/m
R410A
Page 49
- (02 - 08) -
OUTDOOR UNIT
AOB12-14L
OUTDOOR UNIT
AOB12-14L
7. AIR FLOW
750
820
700
770
Number of
rotations
(r.p.m)
(r.p.m)
(r.p.m)
(r.p.m)
Air flow
MODEL : AO B12L
COOLING
HEATING
MODEL : AO B14L
COOLING
m3/h
l/s 494
CFM 1048
Number of
rotations Air flow
m3/h
l/s 453
CFM 959
1780
1630
Number of
rotations Air flow
m3/h
l/s 531
CFM 1124
HEATING
Number of
rotations Air flow
m3/h
l/s 483
CFM 1024
1910
1740
Page 50
- (02 - 09) -
OUTDOOR UNIT
AOB12-14L
OUTDOOR UNIT
AOB12-14L
8. OPERATION NOISE
8-1. NOISE LEVEL CURVE
MODEL : AO B12L
COOLING
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
63 125 250 500 1,000 2,000 4 ,000 8,000
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HEATING
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
63 125 250 500 1,000 2,000 4 ,000 8,000
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL : AO B14L
COOLING HEATING
80
70
NC-65
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63 125 250 500 1,000 2,000 4,000 8,0 00
Octave band center frequency,Hz
0
63 125 250 500 1,000 2,000 4 ,000 8,000
Octave band center frequency,Hz
Page 51
- (02 - 10) -
OUTDOOR UNIT
AOB12-14L
OUTDOOR UNIT
AOB12-14L
8-2. SOUND LEVEL CHECK POINT
Page 52
- (02 - 11) -
OUTDOOR UNIT
AOB12-14L
OUTDOOR UNIT
AOB12-14L
9. ELECTRIC CHARACTERISTICS
*1) Wiring spec. Selected sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited wiring length This is the wiring length in case voltage descent is less than 2%. When the wiring length becomes long, please select the wiring of a more larger diameter.
Model name AO B12L AO B14L
Voltage V
Frequency Hz Max. operating current A 10.0 12.5 Starting current A 4.9 5.9
Main fuse (Circuit breaker)
current
A 20 20
Power cable mm
2
*2)Limited wiring length m 36 28
Power supply
*1) Wiring spec.
230
~
50
4.0
Page 53
- (02 - 12) -
OUTDOOR UNIT
AOB12-14L
OUTDOOR UNIT
AOB12-14L
10. SAFETY DEVICES
AO B12L AO B14L
Thermal protection program (COMPRESSOR TEMP.)
Thermal protection program (DISCHARGE TEMP.)
15A 250V
3.15A 250V
Compressor protection
Circuit protection
OFF : 110°C
ON : After 40 minutes
OFF : 110°C
ON : After 7 minutes
Current fuse (NEAR THE TERMINAL)
Current fuse
(MAIN PRINTED CIRCUIT BOARD)
OFF : 100
+15
-10
°C
ON : 95
+15
-10
°C
Protection form
20A 250V
5A 250V
Model
Fan motor protection Thermal protection program
Page 54
REMOTE CONTROLLER
3. WIRED REMOTE CONTROLLER
UTB - UD
:
D2D_RC001E/02
2007.09.03
Page 55
REMOTE CONTROLLER UTB- UD
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function. (2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Economy operation are possible.
Easy installation with a slim shape with no bulge in the back.
The room temperature can be controlled by being detected the temperature accurately with built-in thermo sensor.
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
High performance and compact size
REMOTE CONTROLLER UTB- UD
Three functions are combined in one unit.
Wired
remote
controller
Built-in timers
Possible to set ON/OFF time to operate twice each day of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example (Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
At "Weekly timer" + "Set back timer" setup
Easy-to-understand time bar display
SUMOTUWETH FR SA
7
3126 9
15 18 21
24°C
24°C 28°C 24°C
Weekly
timer
Setback
timer
Setback timerWeekly timer
Possible to set temperature for two time spans and for each day of the week.
SUMOTUWETH FR SA
Screen after setup
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
0 3 6 9 12 15 18 21 Time
24°C
0 3 6 9 12 15 18 21 Time
28°C
3126 9
15 18 21
28°C
Easy-to-understand operation Simple installation
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is needed.
Timer area
[
Variable timer control
]
The operation/display sections are zoned accord­ing to time and operation, enabling variable pro­gramming to match application.
Operation area
European switch box
- (03 - 01) -
JIS box
Page 56
REMOTE CONTROLLER UTB- UD
FUNCTIONS
2 6
7 8 9
10
11
Display panel
16
19
20
18
17
15
13
12
14
1
START/STOP button
Pressed to start and stop operation.
2
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
1 3
4
5
Fan control button
Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH).
5
Economy button
Turns the economy efficient mode on and off.
6
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER) Set the current time.
7
Day (DAY OFF) button
Temporarily cancels of one day timer.
8
Set back button
Pressed to select the set back timer.
9
Set time button
Pressed to set time.
10
Delete button
The schedule of a weekly timer is deleted.
11
Set button
Sets the date, hour, minute and on-off time.
12
Vertical airflow direction and swing button
Push for two seconds to change the swing mode.
13
Horizontal airflow direction and swing button
Push for two seconds to change the swing mode.
REMOTE CONTROLLER UTB- UD
DIMENSION
120
Front View
SPECIFICATION
21
[ Unit : mm ]
120
14
Filter button
15
Operation lamp
Lights during operation and when the timer is on.
16
Timer and clock display
17
17
Operation mode display
18
Fan speed display
19
Operation lock display
20
Temperature display
21
Function display
Defrost display
Thermo sensor display
Economy display
Vertical swing display
Horizontal swing display
Filter display
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT ( g ) 160
CABLE LENGTH ( m )
POWER ( V )
10
12
- (03 - 02) -