Cassette Type
SPLIT TYPE AIR CONDITIONER
INSTALLATION
INSTRUCTION SHEET
(PART NO. 9374318247)
For authorized service personnel only.
DANGER
WARNING
CAUTION
Never touch electrical components immediately after the power supply has been turned off. Electrical shock may occur. After
turning off the power, always wait 5 minutes or more before touching electrical components.
The basic installation work procedures are the same as conventional refrigerant models.
However, pay careful attention to the following points:
1 Since the working pressure is 1.6 times higher than that of conventional refrigerant models, some of the piping and
installation and service tools are special. (See the table below.)
Especially, when replacing a conventional refrigerant model with a new refrigerant R410A model, always replace the
conventional piping and flare nuts with the R410A piping and flare nuts.
2 Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous charging with
conventional refrigerant and for safety. Therefore, check beforehand. [The charging port thread diameter for R410A is
1/2 UNF 20 threads per inch.]
3 Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant models. Also, when
storing the piping, securely seal the openings by pinching, taping, etc.
4 When charging the refrigerant, take into account the slight change in the composition of the gas and liquid phases, and
always charge from the liquid phase side whose composition is stable.
Special tools for R410A
Tool name
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the
amount of residual oil is less than 40 mg/10 m. Do not use copper pipes
having a collapsed, deformed or discolored portion (especially on the interior
surface). Otherwise, the expansion valve or capillary tube may become
blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when
using conventional refrigerant, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in the table.
Never use copper pipes thinner than that in the table even when it is
available on the market.
This mark indicates procedures which, if improperly performed, are most likely to result in the death of or
serious injury to the user or service personnel.
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of
the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to
the user, or damage to property.
DANGER
This air conditioner uses new refrigerant HFC (R410A).
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of other
refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm
3.8 MPa (–76 cmHg to 38 kgf/cm
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
2
) for low pressure.
Contents of change
2
) for high pressure. –0.1 to
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Thickness
0.80 mm
0.80 mm
0.80 mm
1.00 mm
1.20 mm
For authorized service personnel only.
WARNING
1 For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
2 Connect the indoor unit and outdoor unit with the air conditioner piping and cords available from our standards parts. This instal-
lation instruction sheet describes the correct connections using the installation set available from our standard parts.
3 Installation work must be performed in accordance with national wiring standards by authorized personnel only.
4 Do not turn on the power until all installation work is complete.
CAUTION
This installation instruction sheet describes how to the indoor unit only.
To install the outdoor unit, refer to the installation instruction sheet included with the outdoor unit.
• Be careful not to scratch the air conditioner when handling it.
• After installation, explain correct operation to the customer, using the operating manual.
• Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
CONNECTION PIPE REQUIREMENT
CAUTION
Refer to the installation instruction sheet of the outdoor unit for description of the length of connecting pipe or for difference of
its elevation.
MODEL
Diameter
• Use pipe with water-resistant heat insulation.
Liquid
Gas
12,000 14,000/18,000 24,000
BTU/h model BTU/h model BTU/h model
6.35 mm (1/4 in.) 6.35 mm (1/4 in.) 6.35 mm (1/4 in.)
9.52 mm (3/8 in.) 12.70 mm (1/2 in.) 15.88 mm (5/8 in.)
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%, install heat
insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation that is 15 mm or thicker and
if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).
ELECTRICAL REQUIREMENT
Connection cord (mm2)
MAX.
2.5
• Use conformed cord with Type 245 IEC57.
• Install all electrical works in accordance to the standard.
• Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the units. (Both indoor unit and outdoor unit)
MIN.
1.5
INSTALLATION PROCEDURE
Install the air conditioner as follows:
1
INDOOR UNIT INSTALLATION
WARNING
1 Install the air conditioner in a location which can with-
stand a load do at least five times the weight of the
main unit and which will not amplify sound or vibration. If the installation location is not strong enough,
the indoor unit may fall and cause injuries.
2 If the job is done with the panel frame only, there is a
risk that the unit will come loose. Please take care.
1. INSTALLING BODY
Cealing openings and hanging bolt installation diagram
WARNING
When fastening the hangers, make the bolt positions uniform.
530 mm (Hanging bolt position)
570 mm (Indoor unit)
75 mm
135 mm 250 mm
114 mm
215 mm
Drain pipe (O.D. ø25.4)
Control box
Ceiling
40 mm 99 mm102 mm
Liquid pipe
Gas pipe
540 mm (Hanging bolt position)
30 mm
123 mm
58 mm
30 mm
(1) Install special nut A, then special nut B onto the hanging bolt.
(2) Raise the body and mount its hooks onto the hanging bolt between
the special nuts.
(3) Turn special nut B to adjust the height of the body.
Perform final tightening by tightening the double nut firmly.
2. LEVELING
Using a level, or vinyl hose filled with water, fine adjust so that the body is
level.
700 mm (Decoration Panel)
580 – 660 mm (Cealing openings)
262 mm
3. INSTALLING DRAIN PIPE
Note: Install the drain pipe.
• Install the drain pipe with downward gradient (1/50 to 1/100) and so
there are no rises or traps in the pipe.
• Use general hard polyvinyl chloride pipe (VP25) [outside diameter 32
mm (1-1/4”)] and connect it with adhesive (polyvinyl chloride) so that
there is no leakage.
• When the pipe is long, install supporters.
• Do not perform air bleeding.
• Always heat insulate the indoor side of the drain pipe.
• When desiring a high drain pipe height, raise it up to 700 mm or less
from the ceiling within a range of 150 mm from the body. A rise dimension over this range will cause leakage.
Air bleeding
Special nut B
Hanging bolt
Rise
19 mm
WARNING
Special nut A
Hook
Trap
150 mm or less
30 mm
or more
Ceiling
Supporter
After installing the
body, tighten the nuts.
Vinyl hose
1.5 to 2.0 m
Max. 700 mm
2
CONNECTING THE PIPE
CAUTION
1 Do not use mineral oil on flared part. Prevent mineral
oil from getting into the system as this would reduce
the lifetime of the units.
2 While welding the pipes, be sure to blow dry nitrogen
gas through them.
1. FLARING
(1) Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe and
remove the burrs.
(3) Insert the flare nut (always use the flare nut attached to the indoor
and outdoor units respectively) onto the pipe and perform the flare
processing with a flare tool.
Use the special R410A flare tool, or the conventional flare tool.
Check if [L] is flared uniformly
and is not cracked or scratched.
Die
A
Pipe
Pipe outside diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Pipe outside diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
When using conventional flare tools to flare R410A pipes, the dimension
A should be approximately 0.5 mm more than indicated in the table (for
flaring with R410A flare tools) to achieve the specified flaring. Use a thickness gauge to measure the dimension A.
Width across
flats
Pipe outside
diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Dimension A
Flare tool for R410A, clutch type
0 to 0.5
Dimension B
9.1
13.2
16.6
19.7
24.0
Width across flats
of Flare nut
17 mm
22 mm
26 mm
29 mm
36 mm
(mm)
0
(mm)
-0.4
B
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
Do not bend the pipes in an angle more than 90
When pipes are repeatedly bend or stretched, the material will harden,
making it difficult to bend or stretch them any more. Do not bend or
stretch the pipes more than three times.
°.
CAUTION
1 To prevent breaking of the pipe, avoid sharp bends.
Bend the pipe with a radius of curvature of 150 mm or
over.
2 If the pipe is bent repeatedly at the same place, it will
break.
3. CONNECTION PIPES
Indoor unit
(1) Detach the caps and plugs from the pipes.
CAUTION
1 Be sure to apply the pipe against the port on the in-
door unit correctly. If the centering is improper, the flare
nut cannot be tightened smoothly. If the flare nut is
forced to turn, the threads will be damaged.
2
Do not remove the flare nut from the indoor unit pipe
until immediately before connecting the connection pipe.
(2) Centering the pipe against port on the indoor unit, turn the flare nut
with your hand.
To prevent gas leakage, coat the flare
surface with alkylbenzene oil (HAB).
Do not use mineral oil.
Connection pipe
(Gas)
Connection pipe
(Liquid)
Indoor unit
(3) When the flare nut is tightened properly by your hand, use a torque
wrench to finally tighten it.
Holding spanner
Body side
Torque wrench
CAUTION
Hold the torque wrench at its grip, keeping it in the right
angle with the pipe, in order to tighten the flare nut
correctly.
Flare nut Tightening torque
6.35 mm (1/4 in.) dia.
9.52 mm (3/8 in.) dia.
12.70 mm (1/2 in.) dia.
15.88 mm (5/8 in.) dia.
19.05 mm (3/4 in.) dia.
16 to 18 N·m (160 to 180 kgf·cm)
30 to 42 N·m (300 to 420 kgf·cm)
49 to 61 N·m (490 to 610 kgf·cm)
63 to 75 N·m (630 to 750 kgf·cm)
90 to 110 N·m (900 to 1100 kgf·cm)
STANDARD PARTS
The following installation parts are furnished.
Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape
Coupler heat
insulation
Special nut A
(large flange)
Special nut B
(small flange)
Template
(Carton top)
Remote
control unit
Battery
Remote control unit holder
Tapping screw
DECORATION PANEL ACCESSORIES
Name and Shape
Connector cover
Screw
Screw
Q’ty
2
4
4
1
1
2
1
2
Q’ty
4
4
1
Application
For indoor side pipe joint
For installing indoor unit
For installing indoor unit
For cealing openings
cutting
Also used as packing
For air conditioner
operation
For remote controller unit
For installing the remote
controller unit holder
installation
For mounting the remote
control unit
Application
For covering connector
For mounting decoration
panel
For mounting connector
cover
SELECTING THE MOUNTING
POSITION
Decide the mounting position with the customer as follows:
WARNING
Select installation locations that can properly support the
weight of the indoor. Install the units securely so that they
do not topple or fall.
CAUTION
1 Do not install where there is the danger of combustible
gas leakage.
2 Do not install the unit near heat source of heat, steam,
or flammable gas.
3 If children under 10 years old may approach the unit,
take preventive measures so that they cannot reach
the unit.
(1) Install the indoor unit on a place having a sufficient strength so that it
withstands against the weight of the indoor unit.
(2) The inlet and outlet ports should not be obstructed; the air should be
able to blow all over the room.
(3) Leave the space required to service the air conditioner.
(4) The ceiling rear height as shown in the figure.
(5) A place from where the air can be distributed evenly throughout the
room by the unit.
(6) A place from where drainage can be extracted outdoors easily.
(7) Install the unit where noise and vibrations are not amplified.
Strong and durable ceiling
262 mm
or more
1,000 mm
1,000 mm
2,500 mm
Floor
This product can be installed at a height of up to 3.5 m. Perform the Function Setting on the remote control in accordance with the installed height.
Obstruction
or more
or more
or more
Discharge Direction Setting
• The discharge direction can be selected as shown below.
100 mm or more
(4 directions)
* For a 3-way outlet, make sure to perform the Function Setting on the
remote control. Also, make sure to use the optional shutter panel to
block the outlet.
* The ceiling height cannot be set in the 3-way outlet mode. Therefore,
do not change the setting in the “Setting the Ceiling Height” at 7 FUNCTION SETTING.
* When the outlet is shut, be sure to install the optional Air outlet
shutter plate kit.
For the details of installation, please refer to Installation Manual of kit.
(3 directions)
Piping position
3
INSTALLING THE COUPLER
HEAT INSULATION
After checking for gas leaks, insulate by wrapping insulation around the
two parts (gas and liquid) of the indoor unit coupling, using the coupler
heat insulation.
After installing the coupler heat insulation, wrap both ends with vinyl tape
so that there is no gap.
Coupler heat insulation
Body
Be sure to overlap the
insulation
CAUTION
Must fit tightly against body without any gap.
No gap
Coupler heat insulation
4
ELECTRICAL WIRING
WARNING
1 Before starting work, check that power is not being
supplied to the indoor unit and outdoor unit.
2 Match the terminal board numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric parts.
3 Connect the connection cords firmly to the terminal
board. Imperfect installation may cause a fire.
4 Always fasten the outside covering of the connection
cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.)
5 Always connect the ground wire.
6 Install the remote controller wires so as not to be di-
rect touched with your hand.
HOW TO CONNECT WIRING TO THE TERMINALS
For stand wiring
(1) Use crimp-type terminals with insulating sleeves as shown in the
figure below to connect to the terminal block.
(2) Securely crimp the crimp-type terminals to the wires using an ap-
propriate tool so that the wires do not come loose.
(3) Use the specified wires, connect them securely, and fasten them
so that there is no stress placed on the terminals.
(4)
Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads
may be damaged and prevent the screws from being properly tightened.
(5)
Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table below for the terminal screw tightening torques.
Crimp-type
Wire
terminal
Sleeve
Screw with
special washer
Crimp-type
terminal
Strip 10 mm
Screw with
special washer
Wire
M4 screw 1.2 to 1.8 N·m (12 to 18 kgf·cm)
Crimp-type terminal
Terminal
board
Terminal block
Tighting torque
WARNING
Use crimp-type terminals and tighten the terminal
screws to the specified torques, otherwise, abnormal overheating may be produced and possibly
cause heavy damage inside the unit.
1. CONNECTION DIAGRAMS
Connection cord (to outdoor unit)
Control line
Power line
2. CONNECTION CORD PREPARATION
Keep the earth wire longer than the other wires.
20 mm
Earth wire
30 mm or more
• Use a 4-core wire cord.
Power supply cord
or connection cord
3. CONNECTION OF WIRING
(1) Remove the control box cover and install each connection wire
Screw
Control box cover
(2) After wiring is complete, secure the remote controller cord, connec-
tion cord, and power cord with the cord clamps.
Connection cord
(to outdoor unit)
Wired remote controller
cord (option)
Wired remote controller cord
(option)
(3) Install control box cover.
Cord clamp
Cord clamp
Connection cord
(to outdoor unit)
CAUTION
Do not bundle the remote controller cord, or wire the remote controller cord in parallel, with the indoor unit connection wire (to the outdoor unit) and the power supply
cord. It may cause erroneous operation.
OPTIONAL PARTS
Exterior
Parts name
Wired remote
controller
Air outlet
shutter plate
Model No.
UTB
-
-
YDZA
UTR
Summary
Unit control is performed by
UD
wired remote controller
Install the plate at outlet
when carrying out 3-way
direction operation.
Indoor
unit side
Wired remote controller cord (option)
*
Black
White
Red
Indoor
unit side
Ground the remote controller ip it has a ground wire
*
(Continued to the next page)
5
DECORATION PANEL
INSTALLATION
1. REMOVE THE INTAKE GRILLE
(1) Slide the 2 grille hook
Grille hook
(2) Open the intake grille and remove.
2. INSTALL PANEL TO INDOOR UNIT
(1) Install the decoration panel on the indoor unit.
“DRAIN” mark
* Align the stamped marks on the decoration panel against the pipe and the drain
of the indoor unit.
Use only the supplied screws to install the decoration
panel.
Indoor unit
Sealant
Decoration panel
“PIPE” mark
CAUTION
5 ~ 7
Screw
Cealing
No gap between cealing and
decoration panel around entire
periphery
(2) Connect the connector.
Wire (louver): WHITE
• Arrange the wires as illustrated below.
(3) Attach the connector cover.
Wire (display): WHITE
Screw
Wire (louver): RED
Indoor unit side
Connector cover
3. ATTACH THE INTAKE GRILLE
The installation is the reverse of “REMOVING THE INTAKE GRILLE”.
The intake grille can be rotated and installed 4 ways to suit the user’s
preference.
CAUTION
1 The louver angle cannot be changed if the power is not
on, (If moved by hand, it may be damaged.)
2 The grille assembly is directional relative to the air con-
ditioner body.
3 Install so that there is no gap between the grille as-
sembly and the air conditioner body.
6
REMOTE CONTROLLER
SETTING
1. Load Batteries (R03/LR03 × 2)
1 Press and slide the battery compartment
lid on the reverse side to open it.
Slide in the direction of the arrow while
pressing the
2 Insert batteries.
Be sure to align the battery polarities
(
3 Close the battery compartment lid.
• Take care to prevent infants from accidentally swallowing batteries.
• When not using the Remote Control Unit for an extended
period, remove the batteries to avoid possible leakage
and damage to the unit.
• If leaking battery fluid comes in contact with your skin,
eyes, or mouth, immediately wash with copious amounts
of water, and consult your physician.
• Dead batteries should be removed immediately and disposed of properly, either in a battery collection receptacle or to the appropriate authority.
• Do not attempt to recharge dry batteries.
NOTES
• Never mix new and used batteries, or batteries of different types.
• Batteries should last about one year under normal use. If the
Remote Control Unit’s operating range becomes appreciably
reduced, replace the batteries and press the RESET button
with the tip of a ballpoint pen or other small object.
2.
REMOTE CONTROL UNIT HOLDER INSTALLATION
• Check that the indoor unit correctly receives the signal
from the remote control unit, then install the remote
control unit holder.
• Select the remote control unit holder selection site by
paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat from
a stove, etc.
• Install the remote control unit with a distance of 7 m between the
remote control unit and the photocell as the criteria. However, when
installing the remote control unit, check that it operates positively.
• Install the remote control unit holder to a wall, pillar, etc. with the tap-
ping screw.
Screws
1 Mount the Holder.
Slide up
Pull out
3 To remove the Remote Control Unit
(when use at hand).
mark.
) correctly.
CAUTION
CAUTION
Insert
Press in
2 Set the Remote Control Unit.
7
• This procedure changes to the function settings used to control the
indoor unit accoding to the installation conditions. Incorrect settings
can cause the indoor unit malfunction.
• After the power is turned on, perform the "FUNCTION SETTING"
according to the installation conditions using the remote controller.
• The settings may be selected between the following two: Function
Number or Setting Value.
• Settings will not be changed if invalid numbers or setting values are
selected.
FUNCTION SETTING
Entering the Function Setting Mode
• While pressing the FAN button and SET TEMP. ( ) simultaneously,
press the RESET button to enter the function setting mode.
STEP 1
Selecting the Remote Control Unit Signal Code
Use the following steps to select the signal code of
the remote control unit. (Note that the air conditioner
cannot receive a signal code if the air conditioner
has not been set for the signal code.)
The signal codes that are set through this process
are applicable only to the signals in the FUNCTION
SETTING. For details on how to set the signal codes
through the normal process, refer to 8 SELECTING
THE REMOTE CONTROL SIGNAL CODE.
1 Press SET TEMP. ( ) ( ) button to change
the signal code between
Match the code on the display to the air
conditioner signal code. (initially set to
(If the signal code does not need to be selected,
press the MODE button and proceed to STEP 2.)
2 Press the TIMER MODE button and check that
the indoor unit can receive signals at the
displayed signal code.
3 Press the MODE button to accept the signal
code, and proceed to STEP 2.
The air conditioner signal code is set to A prior to shipment. Contact
your retailer to change the signal code.
The remote control unit resets to signal code A when the batteries
in the remote control unit are replaced. If you use a signal code
other than signal code A, reset the signal code after replacing the
batteries.
If you do not know the air conditioner signal code setting, try each
of the signal codes (
operates the air conditioner.
) until you find the code which
.
)
STEP 2
SELECTING THE FUNCTION NUMBER AND SETTING VALUE
Refer to the indoor unit installation instruction sheet for details on the
function numbers and setting values.
Selecting the Function Number and Setting Value
1 Press the SET TEMP. ( ) ( ) buttons to select the function number.
(Press the MODE button to switch between the left and right digits.)
2 Press the FAN button to proceed to setting the value.
(Press the FAN button again to return to the function number selection.)
3 Press the SET TEMP. ( ) ( ) buttons to select the setting value.
(Press the MODE button to switch between the left and right digits.)
4 Press the TIMER MODE
button, and START/STOP
button, in the order listed
to confirm the settings.
5 Press the RESET button
to cancel the function
setting mode.
6 After completing the
FUNCTION SETTING,
be sure to turn off the
power and turn it on
again.
Function
number
Setting
value
CAUTION
After turning off the power, wait 10 seconds or more before
turning on it again.
The FUNCTION SETTING doesn't become effective if it
doesn't do so.
Setting the Ceiling Height
• Select the setting values in the table below according to the height of the
ceiling. (The unit is factory-set to “00”.)
Setting Description
Standard
(2.5 m to 3.0 m)
High ceiling
(3.0 m to 3.5 m)
The ceiling height values are for the 4-way outlet.
Do not change this setting in the 3-way outlet mode.
Function Number
20
Setting Value
00
01
Setting the Outlet Directions
• Select the setting values in the table below for using a 3-way outlet.
(The unit is factory-set to “00”.)
Setting Description
4-way
3-way
Function Number
22
Setting Value
00
01
Setting the Filter Sign
• The indoor unit has a sign to inform the user that it is time to clean the
filter.
• Select the time setting for the filter sign display interval in the table
below according to the amount of dust or debris in the room. (The unit
is factory-set to “00”)
• If you do not wish the filter sign to be displayed, select the setting value
for “No indication”.
Setting Description
Standard
(2,500 hours)
Long interval
(4,400 hours)
Short interval
(1,250 hours)
No indication
Function Number
11
Setting Value
00
01
02
03
Setting the Cooler Room Temperature Correction
• Depending on the installed environment, the room temperature sensor
may require a correction. The settings may be selected as shown in the
table below. (The unit is factory-set to “00”.)
Setting Description
Standard
Lower control
Function Number
30
Setting Value
00
01
Setting the Heater Room Temperature Correction
• Depending on the installed environment, the room temperature sensor
may require a correction. The settings may be changed as shown in the
table below. (The unit is factory-set to “00”.)
Setting Description
Standard
Lower control
Slightly warmer control
Warmer control
Function Number
31
Setting Value
00
01
02
03
Setting Other Functions
• The following settings are also possible, depending on the operating
conditions. (The unit is factory-set to “00”.)
Auto Restart
Setting Description
Yes
No
Indoor Room Temperature Sensor Switching Function (Wired remote controller only)
Setting Description
No
Yes
• If setting value is “00”, room temperature is controlled by the indoor unit
temperature sensor.
• If setting value is “01”, room temperature is controlled by either indoor
unit temperature sensor or remote control unit sensor.
Function Number
40
Function Number
42
Setting Value
00
01
Setting Value
00
01
Setting record
• Record any changes to the settings in the following table.
Setting
Ceiling height
Outlet direction
Filter sign
Cooler room temperature
correction
Heater room temperature
correction
Auto restart
Indoor room temperature
sensor switching function
After completing the FUNCTION SETTING, be sure to turn off the power
and turn it on again.
Setting Value
8
SWLECTING THE REMOTE
CONTROL UNIT SIGNAL CODE
When two or more air conditioners are installed in a room and the remote
control unit is operating an air conditioner other than the one you wish to
set, change the signal code of the remote control unit to operate only the
air conditioner you wish to set (four selections possible).
When two or more air conditioners are installed in a room, please contact
your retailer to set the individual air conditioner signal codes.
• Confirm the setting of the remote control unit signal
code and the printed circuit board setting.
If these are not confirmed, the remote control unit cannot
be used to operate for the air conditioner.
Selecting the Remote Control Unit Signal Code
Use the following steps to select the signal code
of the remote control unit. (Note that the air conditioner cannot receive a signal code if the air
conditioner has not been set for the signal code.)
1 Press the START/STOP button until only the
clock is displayed on the remote control unit
display.
2 Press the MODE button for at least five sec-
onds to display the current signal code (initially set to
3 Press the (
signal code between
the code on the display to the air conditioner
signal code.
4 Press the MODE button again to return to
the clock display. The signal code will be
changed.
If no buttons are pressed within 30 seconds after the signal code
is displayed, the system returns to the original clock display. In
this case, start again from step 1.
The air conditioner signal code is set to A prior to shipment. Contact
your retailer to change the signal code.
The remote control unit resets to signal code A when the batteries
in the remote control unit are replaced. If you use a signal code
other than signal code A, reset the signal code after replacing the
batteries.
If you do not know the air conditioner signal code setting, try each
of the signal codes (
operates the air conditioner.
Indoor unit setting
JM1
Connect
Disconnect
Connect
Disconnect
).
) ( ) buttons to change the
Jumper wire
JM2
Connect
Connect
Disconnect
Disconnect
. Match
) until you find the code which
Remote control unit
signal code
A (Primary setting)
TROUBLESHOOTING
[Troubleshooting with the indoor display]
Troubleshooting at the display is possible either on the wired or wireless
remote control.
FILTER LAMP
(ORANGE)
TIMER LAMP
(GREEN)
OPERATION LAMP
(RED)
Indoor unit
Printed circuit board
9
TEST RUN
CHECK ITEMS
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do not air flow direction louvers operate normally?
(4) Is the drain normal?
(5) Is there any abnormal noise and vibration during operation?
• Do not operate the air conditioner in the running state for a long time.
CHECKING DRAINAGE
To check the drain, remove the water cover and fill with 1rof water as
shown in the figure.
The drain pump operates when operating in the cooling mode.
Drain pipe
Watering pot
• Test running
When the air conditioner is run by pressing the remote control unit test
run button, the OPERATION and TIMER lamps flash slowly at the same
time.
[OPERATION METHOD]
• For the operation method, refer to the operating manual.
• The outdoor unit may not operate depending on the room temperature.
In this case, press the test run button on the remote control unit while
the air conditioner is running. (Point the transmitter section of the remote control unit toward the air conditioner and press the test run button with the tip of a ball-point pen, etc.)
Transmitter section
Test run button
•
To end test operation, press the remote control unit START/STOP button.
(When the air conditioner is run by pressing the test run button, the
OPERATION indicator lamp and TIMER indicator lamp and TIMER indicator lamp will simultaneously flash slowly.)
[Using the wired remote control] (Option)
b
c
d
• For the operation method, refer to the operating manual.
(1) Stop the air conditioner operation.
(2) Press the master control button and the fan control button simultane-
ously for 2 seconds or more to start the test run.
(3) Press the start/stop button to stop the test run.
Wire cover
Test run display
Screw
The OPERATION, TIMER and FILTER lamp operate as follows table according to the error contents.
Error contents
Indoor signal error
Wired remote controller abnormal
Indoor room temperature sensor error
Indoor heat exchanger temperature
sensor (middle) error
Indoor heat exchanger temperature
sensor (inlet) error
Float switch operated
Outdoor discharge pipe temperature
sensor error
Outdoor heat exchanger temperature
sensor (outlet) error
Outdoor temperature sensor error
Compressor temperature sensor error
2-way valve temperature sensor error
3-way valve temperature sensor error
Outdoor heat exchanger temperature
sensor (middle) error
Indoor manual auto switch abnormal
Power supply frequency detection error
IPM protection
CT error
Compressor location error
Outdoor fan error
Connected indoor unit abnormal
Outdoor unit computer communication
error
Indoor fan abnormal
Discharge temperature error
Exessive high pressure protection on
cooling
4-way valve abnormal
Pressure switch abnormal
Compressor temperature error
Active filter abnormal
PFC circuit error
: 0.5s ON/0.5s OFF (Flash) : OFF
MANUAL AUTO
OPERATION
lamp (RED)
(2 times)
(2 times)
(2 times)
(2 times)
(3 times)
(3 times)
(3 times)
(3 times)
(3 times)
(3 times)
(3 times)
(4 times)
(4 times)
(5 times)
(5 times)
(5 times)
(5 times)
(5 times)
(5 times)
(6 times)
(7 times)
(7 times)
(7 times)
(7 times)
(7 times)
(8 times)
(8 times)
TIMER lamp
(8 times)
(2 times)
(3 times)
(4 times)
(6 times)
(2 times)
(3 times)
(4 times)
(8 times)
(2 times)
(4 times)
(2 times)
(3 times)
(5 times)
(6 times)
(7 times)
(8 times)
(2 or 3 times)
(2 times)
(3 times)
(4 times)
(5 times)
(6 times)
(2 or 3 times)
(4 times)
FILTER lamp
(GREEN)
(2 times)
(3 times)
(4 times)
(ORANGE)
[Troubleshooting at the remote control LCD]
This is possible only on the wired remote control. (Option)
[SELF-DIAGNOSIS]
This possible only on the wired remote control. (Option)
If an error occurs, the following display will be shown.
(“EE” will appear in the set room temperature display.)
Unit number
Error code
Ex. Self-diagnosis
Error code Error contents
01
13
26
27
00
02
04
28
09
0C
06
0A
15
1d
1E
29
20
2A
17
18
1A
1b
1F
1c
12
0F
24
2c
16
2b
19
25
If “CO” appears in the unit number display, there is a remote controller
error.
Unit number
Indoor signal error
Wired remote controller abnormal
Indoor room temperature sensor error
Indoor heat exchanger temperature sensor (middle)
error
Indoor heat exchanger temperature sensor (inlet)
error
Float switch operated
Outdoor discharge pipe temperature sensor error
Outdoor heat exchanger temperature sensor (outlet)
error
Outdoor temperature sensor error
Compressor temperature sensor error
2-way valve temperature sensor error
3-way valve temperature sensor error
Outdoor heat exchanger temperature sensor (middle)
error
Indoor manual auto switch abnormal
Power supply frequency detection error
IPM protection
CT error
Compressor location error
Outdoor fan error
Connected indoor unit abnormal
Outdoor unit computer communication error
Indoor fan abnormal
Discharge temperature error
Exessive high pressure protection on cooling
4-way valve abnormal
Pressure switch abnormal
Compressor temperature error
Active filter abnormal
PFC circuit error
Error code
C0
C0
1d
1c
Incompatible indoor unit is
connected
Indoor unit ↔ remote controller
communication error
Content
10
SPECIAL INSTALLATION
METHODS
CAUTION
1 When setting DIP switches, do not touch any other parts
on the circuit board directly with your bare hands.
2 Be sure to turn off the main power.
1. GROUP CONTROL SYSTEM
A number of indoor units can be operated at the same time using a
single remote controller.
(1) Wiring method (indoor unit to remote controller)
Indoor unit 2Indoor unit 1Indoor unit 0 Indoor unit 3
Remote
controller cord
Remote controller
When ground wire is necessary
(2) DIP switch setting (indoor unit)
Set the unit number of each indoor unit using DIP switch on the indoor
unit circuit board. (see following table and figure.)
DIP switch is normally set to make unit number No. 0.
Indoor unit
Unit number DIP SWITCH No.
2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Example : No. 3
1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Bus wire
3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
11
Explain the following to the customer in accordance with the operating
manual:
(1) Starting and stopping method, operation switching, temperature ad-
justment, timer, air flow switching, and other remote control unit op-
erations.
(2) Air filter removal and cleaning, and how to use the air louvers.
(3) Give the operating and installation manuals to the customer.
(4) If the signal code is changed, explain to the customer how it changed
(the system returns to signal code A when the batteries in the remote
control unit are replaced).
*(4) is applicable to using wireless remote control.
CUSTOMER GUIDANCE
PART NO. 9374318247