General AUH30L, AUH30LUAS, AOH30LMAWL, AUH36L, AUH36LUAS Technical Manual

...
Page 1
R410A
4 . CASSETTE TYPE :  AU 30LUAS, AU 36LUAS
D2D_AU003E/02
2006.01.10
Page 2
4-1. FEATURE
FEATURES
Easy maintenance
The control box is easily accessible for maintenance work Wide opening for easy access.
Detachable,washable filter and intake grille.
Wide opening and long-life filter.
Long-life filter High efficiency, long-life filter extends the cleaning cycle.
CASSETTE TYPE
AU30-AU36
Long-life filter
CASSETTE TYPE
AU30-AU36
Slim intake grille
Slim type intake grille can fit the ceiling after installation.
20
(unit: mm)
Group controller
One remote controller can control up to 16 air conditioners. All of the air conditioners will be operated with the same settings.
Connectable quantity : Maximum 16 indoor units for 1 remote controller.
- (04 - 01) -
Page 3
Duct connection hole opening
Fresh air can be introduced through this opening.
Distribution duct
Fresh air
Distribution duct
CASSETTE TYPE
CASSETTE TYPE
AU30-AU36
AU30-AU36
Conditioned air can be distributed by means of a distribution duct.
Two-way
One-way
- (04 - 02) -
Page 4
4-2. REMOTE CONTROLLER
4-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
SUMOTUWETH FR SA
7
3126 9
15 18 21
High performance and compact size
Equipped with weekly timer as standard function. (2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible.
Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature accurately with built-in thermo sensor.
CASSETTE TYPE
Three functions are combined in
AU30-AU36
one unit.
Wired
remote
controller
Weekly
timer
Setback
timer
CASSETTE TYPE
AU30-AU36
Built-in timers
Setback timerWeekly timer
Possible to set ON/OFF time to operate twice each day of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example (Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 18 21
Screen after setup
At "Weekly timer" + "Set back timer" setup
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
Possible to set temperature for two time spans and for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
24°C
28°C
Easy-to-understand operation Simple installation
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is needed.
Timer area
[
Variable timer control
]
The operation/display sections are zoned accord­ing to time and operation, enabling variable pro­gramming to match application.
Operation area
European switch box
- (04 - 03) -
JIS box
Page 5
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
2
Display
SUMOTUWETH FR
SA
369
11
12
10
12 15 18 21
2 7 8 9
CLOCK ADJUST
SET BACK
DELETE SET
DAY
DAY OFF
ENERGY
SAVE
THERMO SENSOR
14
1 3
4
5
6
13
Display panel
CASSETTE TYPE
AU30-AU36
15
16
1718 19
Set Temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Thermo sensor button
6
Energy save button
Turns the energy efficient mode on and off.
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER) Set the current time.
8
Day (DAY OFF) button
Temporarily cancels of one day timer.
9
Set back button
pressed select the set back timer.
CASSETTE TYPE
AU30-AU36
SUMOTUWETH FR
369
DIMENSION
120
SUMOTUWETH FR
CLOCK ADJUST
SET BACK
DELETE SET
SA
369
12 15 18 21
DAY
DAY OFF
Front View
12 15 18 21
ENERGY
SAVE
SA
THERMO SENSOR
202122
[ Unit : mm ]
120
10
Set time button
Pessed to select the set back timer.
11
Delete button
The schedule of a weekly timer is deleted.
12
Set button
Sets the date, hour, minute and on-off time.
13
Vertical air flow direction and swing button
Push for two seconds to change the swing mode
14
17
Operation lamp
Lights during operation and when the timer is on.
15
Timer and clock display
16
Operation mode display
17
Fan speed display
18
Central control display
19
Temperature display
20
Stand by display Indicates during the oil recovery and defrosting operation.
21
Vertical swing display
22
Energy save display
SPECIFICATION
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT ( g ) 160
CABLE LENGTH ( m )
POWER ( V )
10
12
- (04 - 04) -
Page 6
4-3. SPECIFICATIONS
AU 30LUAS AU 36LUAS
AO 30LMAWL AO 36LMAWL
230V 50Hz 230V 50Hz
Fin Pitch
Fin Pitch
600/600
490/490
420/420
-/-
CASSETTE MODELS
INVERTER HEAT PUMP TYPE
INVERTER
Turbo × 1
Propeller × 1
100
103
DC TWIN ROTARY(INVERTER)
1300
850/900
Copper tube
Aluminium
2 × 12
252 × 970 × 26.6
1.30
Copper tube
Aluminium
798 × 900 × 36.38
2 × 38
1.30
White(5Y9/0.5NN)
Beige(10YR7.5/1.0NN)
296 × 830 × 830
830 × 900 × 330
455 × 1060 × 1025
970 × 1050 × 445
37/52(82/115)
FLARE
9.52(3/8 inc.)
15.88(5/8 inc.)
64/70(141/154)
50(chargeless:15)
WIRED
ABS
30
R410A
2200
POE
Outer diameter 37.0 / Inner diameter 32.0
1550/1550
1300/1300
1100/1100
3600/3800
48.0/48.0
44.0/44.0
41.0/41.0
-10 to 43
-10 to 24
FAN MOTOR OUTPUT
W
OUTDOOR
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
Fin
Coil
INDOOR
HEAT EXCHANGER TYPE
OUTDOOR
TYPE
HEATING
CAPACITY
RATED/MAX
TYPE
MODEL NAME
OUTDOOR
POWER SOURCE
INDOOR
FAN TYPE x Q'ty
A
FAN SPEED COOL/HEAT INDOOR
MOISTURE REMOVAL
STARTING CURRENT
INDOOR
EER
COP
r.p.m
REMOTE CONTROLLER
DRAIN PIPE MATERIAL
REFRIGERANT
SIZE
TYPE
OPERATION(OUTDOOR)
°C
TYPE
INDOOR
MAX LENGTH
Rows × Stages
mm
Rows × Stages
mm
OUTPUT
NET
CASING COLOR STARTING METHOD
COMPRESSOR
REFRIGERANT OIL
mm
kg(lbs)
DIMENSIONS H × W × D WEIGHT
NET / GROSS
PIPE
MAX HEIGHT
mm
CONNECTION METHOD
SIZE AVAILABLE VOLTAGE RANGE
GROSS
Coil
dB(A)
INDOOR
OUTDOOR
Fin
198-264V 50Hz
EUROPEAN ENERGY LABEL
m3/h
kW
AIR CIRCULATION COOL/HEAT
CURRENT
kW/kW
RATED/MAX
INPUT POWER
COOLING
COOLING RATED/MAX 2.86/3.46 4.01/4.08
HEATING RATED/MAX 2.84/3.37 3.49/4.15
COOLING RATED/MAX 12.5/15.2 17.6/17.9
HEATING RATED/MAX 12.4/14.8 15.2/18.2
COOLING 2.97 2.49
HEATING 3.52 3.21
High
Med
Low
OUTDOOR High
High
Med
CASSETTE TYPE
AU30-AU36
OUTDOOR High
Low
Quiet
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High
Med
Low
C E
kW 8.50/10.00 10.00/11.20
BTU/h 29000/34100 34100/38200
kW 10.00/11.20 11.20/12.77
BTU/h 34100/38200 38200/43600
A 15 15
l/h (pints/h) 3.0(6.3) 4.0(8.4)
53.0/55.0 54.0/55.0
CASSETTE TYPE
AU30-AU36
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
W
Coil Dimensions
Coil Dimensions
LIQUID
GAS
m
m
CHARGE g
COOLING
HEATING
Note: Specifications are based on the following conditions. Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB. Heating: Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB. Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
mm
- (04 - 05) -
Page 7
4-4. DIMENSIONS
4-4-1. OUTDOOR UNIT
MODELS : AO 30L, AO 36L
(Unit : mm)
Top view
900
830
CASSETTE TYPE
AU30-AU36
21
9
Front view
77
31 330
400
12
CASSETTE TYPE
AU30-AU36
Side view
650
Air flow
370
MOUNTING POSITION
When there are obstacles at the back or front sides.
100 mm or more
600 mm
or more
100 mm or more
603
Bottom view
When there are obstacles at the back, side(s), and top.
600 mm or more
300 mm or more
(
250 S
er
mm or
v
i
c
e s
pac
more
e)
196
99
147
170
When there are obstacles at the back, side with the installation of more than one unit.
250 mm or more
250 mm or more
300 mm or more
- (04 - 06) -
Page 8
4-4-2. INDOOR UNIT
MODELS : AU 30L, AU 36L
30
(Unit : mm)
296
Side view
940
CASSETTE TYPE
CASSETTE TYPE
AU30-AU36
750
830
AU30-AU36
940
Bottom view (Panel)
Drain Inside Dia. 32
Dia. 37Outside
Side view (Standard setting)
750
830
Bottom view
298.5
305.5
285
60
(Drain pipe)
248.5
120
(Small pipe)
(Large pipe)
150
250
Side view (Slender setting)
- (04 - 07) -
Page 9
MOUNTING POSITION
Floor
Strong and durable ceiling
2,300 mm or more
1,200 mm or more
1,000 mm or more
Obstruction
CASSETTE TYPE
CASSETTE TYPE
AU30-AU36
You can select 2-way setting
(A) Standard setting (B) Slender setting
265 mm
300 mm
or more
100 or more 100 or more
or more
100 or more
AU30-AU36
(4 directions) (3 directions)
Piping position
(2 directions) (2 directions)
100 or more
- (04 - 08) -
Page 10
4-5. REFRIGERANT CIRCUIT
MODELS : AU 30L / AO 30L, AU 36L / AO 36L
CASSETTE TYPE
CASSETTE TYPE
AU30-AU36
AU30-AU36
- (04 - 09) -
Page 11
4-6. WIRING DIAGRAMS
4-6-1. OUTDOOR UNIT
MODELS : AO 30L, AO 36L
CASSETTE TYPE
CASSETTE TYPE
AU30-AU36
AU30-AU36
- (04 - 10) -
TO POWER SUPPLY
TO INDOOR UNIT
Page 12
4-6-2. INDOOR UNIT
MODELS : AU 30L, AU 36L
CASSETTE TYPE
AU30-AU36
CASSETTE TYPE
AU30-AU36
- (04 - 11) -
Page 13
4-7. CAPACITY TABLE
(°CDB)
Indoor temperature
26°CDB
27°CDB
29°CDB
18°CWB
19°CWB
21°CDB
23°CDB
Outdoor temperature
15°CWB
16°CWB
21°CWB
22°CWB
23°CWB
32°CDB
30°CDB
(°CWB)
23°CDB
25°CDB
27°CDB
30°CDB
Outdoor temperature
Indoor temperature
16°CDB
18°CDB
20°CDB
MODELS : AU 30L / AO 30L
COOLING
AFR 26
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
-10 7.59 5.79 1.97 7.73 6.18 1.99 7.99 6.48 2.01 8.12 6.40 2.02 8.36 6.28 2.04 8.48 6.13 2.05 8.58 6.49 2.05
0 8.73 6.49 1.73 8.96 7.16 1.74 9.40 7.63 1.75 9.62 7.59 1.75 10.05 7.48 1.76 10.27 7.44 1.77 10.47 7.93 1.77
10 7.58 5.71 2.05 7.77 6.15 2.06 8.15 6.63 2.07 8.34 6.53 2.08 8.71 6.46 2.09 8.88 6.35 2.09 9.05 6.78 2.10
20 10.04 7.13 2.31 10.40 7.82 2.31 11.14 8.47 2.30 11.52 8.45 2.29 12.28 8.39 2.28 12.67 8.36 2.27 13.05 8.98 2.26
30 8.74 6.60 2.78 9.07 7.29 2.78 9.73 7.95 2.79 10.07 7.93 2.79 10.77 7.88 2.78 11.11 7.85 2.78 11.46 8.48 2.78
35 8.66 6.57 3.41 8.99 7.26 3.43 9.66 7.92 3.45 10.00 7.90 3.46 10.61 7.83 3.41 10.96 7.80 3.41 11.30 8.43 3.42
40 7.09 4.90 3.30 7.37 5.49 3.30 7.95 6.08 3.30 8.25 6.15 3.30 8.86 6.22 3.30 9.08 6.16 3.30 9.38 6.71 3.30
43 6.53 4.74 3.30 6.79 5.25 3.30 7.25 5.75 3.30 7.53 5.79 3.30 8.08 5.83 3.30 8.36 5.82 3.30 8.64 6.34 3.30
HEATING
AFR 26
CASSETTE TYPE
AU30-AU36
CASSETTE TYPE
AU30-AU36
(°CDB)
-10 -11 7.73 2.79 7.56 2.85 7.49 3.00 7.22 3.08 6.99 3.09 6.76 3.10 6.38 3.10
-4 -6 8.87 3.02 8.69 3.08 8.44 3.09 8.02 3.09 7.77 3.11 7.52 3.12 7.11 3.11
1 -1 10.21 3.10 9.95 3.11 9.58 3.09 9.11 3.09 8.83 3.10 8.54 3.12 8.04 3.11
7 6 11.77 3.37 11.50 3.37 11.20 3.37 10.57 3.37 10.22 3.37 9.79 3.37 9.20 3.37
12 10 13.83 3.37 13.35 3.37 13.12 3.37 12.35 3.37 11.92 3.37 11.48 3.37 10.77 3.37
18 13 13.32 3.13 13.15 3.22 12.95 3.30 12.61 3.41 12.30 3.48 11.92 3.55 11.34 3.68
24 17 12.77 3.02 12.62 3.10 12.45 3.18 11.95 3.18 11.56 3.19 11.21 3.21 10.52 3.22
AFR: Air flow rate (m3/min)
TC : Total capacity (kW)
SHC: Sensible Heat capacity (kW)
PI : Power Input (kW)
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
- (04 - 12) -
Page 14
MODELS : AU 36L / AO 36L
(°CDB)
Outdoor temperature
Indoor temperature
21°CDB
23°CDB
26°CDB
23°CWB
21°CWB
22°CWB
15°CWB
16°CWB
18°CWB
19°CWB
27°CDB
29°CDB
30°CDB
32°CDB
(°CWB)
Outdoor temperature
Indoor temperature
16°CDB
18°CDB
20°CDB
23°CDB
25°CDB
27°CDB
30°CDB
COOLING
AFR 26
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
-10 10.91 7.80 1.88 11.18 8.45 1.89 11.72 9.02 1.93 12.01 8.96 1.95 12.58 8.82 1.98 12.87 8.75 2.00 13.14 9.36 2.01
0 9.83 7.13 2.24 10.07 7.79 2.26 10.54 8.37 2.29 10.78 8.30 2.30 11.23 8.16 2.33 11.46 8.08 2.34 11.66 8.68 2.34
10 9.73 7.09 2.06 10.01 7.77 2.06 10.57 8.38 2.07 10.85 8.33 2.07 11.40 8.21 2.07 11.67 8.15 2.07 11.93 8.76 2.07
20 10.77 7.52 2.51 11.15 8.22 2.51 11.93 8.89 2.50 12.33 8.87 2.50 13.14 8.80 2.49 13.55 8.77 2.48 13.95 9.40 2.47
30 10.04 7.44 3.38 10.40 8.19 3.39 11.15 8.91 3.40 11.54 8.89 3.41 12.31 8.83 3.41 12.71 8.80 3.41 13.09 9.48 3.41
35 9.73 7.09 4.07 10.11 7.81 4.09 10.80 8.47 4.07 11.20 8.45 4.08 11.93 8.39 4.05 12.33 8.37 4.06 12.73 9.02 4.07
40 7.31 5.59 3.40 7.60 6.27 3.40 8.20 6.94 3.40 8.51 7.02 3.40 9.13 7.10 3.40 9.36 7.04 3.40 9.67 7.66 3.40
43 6.73 5.41 3.40 7.00 5.99 3.40 7.48 6.56 3.40 7.76 6.61 3.40 8.33 6.65 3.40 8.62 6.64 3.40 8.91 7.24 3.40
HEATING
AFR 26
CASSETTE TYPE
CASSETTE TYPE
AU30-AU36
AU30-AU36
(°CDB)
-10 -11 7.73 2.85 7.56 2.90 7.49 3.07 7.22 3.14 7.05 3.20 6.87 3.25 6.60 3.33
-4 -6 8.87 3.09 8.69 3.14 8.51 3.20 8.22 3.29 8.03 3.34 7.84 3.40 7.53 3.49
1 -1 10.29 3.20 10.10 3.27 9.88 3.33 9.55 3.43 9.32 3.49 9.09 3.56 8.72 3.66
7 6 13.27 3.98 13.05 4.06 12.77 4.15 12.30 4.28 11.99 4.36 11.65 4.45 10.97 4.46
12 10 13.95 3.79 13.74 3.88 13.51 3.96 13.03 4.09 12.67 4.18 12.29 4.26 11.68 4.40
18 13 13.32 3.20 13.15 3.28 12.95 3.37 12.61 3.48 12.30 3.55 11.92 3.63 11.34 3.76
24 17 12.77 3.08 12.62 3.17 12.45 3.25 11.95 3.25 11.56 3.25 11.21 3.27 10.52 3.28
AFR: Air flow rate (m3/min)
TC : Total capacity (kW)
SHC: Sensible Heat capacity (kW)
PI : Power Input (kW)
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
- (04 - 13) -
Page 15
4-8. CAPACITY COMPENSATION FOR PIPE LENGTH
HEIGHT DIFFERENCE (m)
HEATING
Outdoor unit
is up-side
Outdoor unit
is bottom-side
Outdoor unit
is bottom-side
Outdoor unit
is up-side
PIPE LENGTH (m)
COOLING
PIPE LENGTH (m)
HEIGHT DIFFERENCE (m)
AND HEIGHT DIFFERENCE
5 7.5 15 20 30 40 50
30 - - - - 0.960 0.935 0.913
20 - - - 0.983 0.960 0.935 0.913
10 - - 0.989 0.983 0.960 0.935 0.913
7.5 - 1.000 0.989 0.983 0.960 0.935 0.913
5 0.994 1.000 0.989 0.983 0.960 0.935 0.913
0 0.994 1.000 0.989 0.983 0.960 0.935 0.913
-5 0.986 0.992 0.981 0.975 0.952 0.927 0.906
-7.5 - 0.988 0.977 0.971 0.948 0.924 0.903
CASSETTE TYPE
AU30-AU36
-10 - - 0.973 0.967 0.945 0.920 0.899
CASSETTE TYPE
AU30-AU36
-20 - - - 0.951 0.929 0.905 0.884
-30 - - - - 0.914 0.890 0.870
5 7.5 15 20 30 40 50
30 - - - - 0.906 0.885 0.872
20 - - - 0.938 0.916 0.894 0.881
10 - - 0.959 0.947 0.925 0.903 0.890
7.5 - 0.993 0.962 0.950 0.927 0.905 0.893
5 0.995 0.995 0.964 0.952 0.930 0.907 0.895
0 1.000 1.000 0.969 0.957 0.934 0.912 0.899
-5 1.000 1.000 0.969 0.957 0.934 0.912 0.899
-7.5 - 1.000 0.969 0.957 0.934 0.912 0.899
-10 - - 0.969 0.957 0.934 0.912 0.899
-20 - - - 0.957 0.934 0.912 0.899
-30 - - - - 0.934 0.912 0.899
- (04 - 14) -
Page 16
4-9. ADDITIONAL CHARGE CALCULATION
REFRIGERANT TYPE
REFRIGERANT AMOUNT g
R410A
2200
15 20 30 40 50 (MAX)
0 (Charge less)
40g/m
REFRIGERANT CHARGE
PIPE LENGTH m
ADDITIONAL CHARGE g
CASSETTE TYPE
AU30-AU36
+200 +600 +1000 +1400
CASSETTE TYPE
AU30-AU36
- (04 - 15) -
Page 17
4-10. OPERATION RANGE
Indoor unit Outdoor unit Indoor temperature Indoor humidity Outdoor temperature
Cooling
Dry
18 to 32 °C About 80% or less -10 to 43 °C
Heating 16 to 30 °C - -10 to 24 °C
Operation Range
AU 30L AU 36L
AO 30L
36L
AO
Model
Mode
CASSETTE TYPE
CASSETTE TYPE
AU30-AU36
AU30-AU36
- (04 - 16) -
Page 18
4-11. FAN PERFORMANCE AND AIR FLOW
4-11-1. AIR VELOCITY DISTRIBUTION
MODELS : AU 30L, AU 36L
4-WAY AIR OUTLET
(m)
3
2
1
0.5
0.25
1
2
Unit : m/s
Note :
Condition
Fan speed : High Operation mode :FAN
0.25
0
1
10.5
2
2
2 1 0.5 0.25
2
3
8765432
CASSETTE TYPE
(m)
AU30-AU36
2
1
0
0.25
87
(m)
2
0.5
654321012345678
Unit : m/s
2
1
2
1
2
1
1
0.5
0
0.25
21012
0.5
0.25
1
0.25
0.5
1012345678
Unit : m/s
2
1
0.5
SIDE VIEW HORIZONTAL LOUVER  : Downward
0.25
(m)
TOP VIEW HORIZONTAL LOUVER  : Upward
(m)
SIDE VIEW HORIZONTAL LOUVER  : Upward
(m)
CASSETTE TYPE
AU30-AU36
2-WAY AIR OUTLET
(m)
1
0
1
87654321012345678
(m)
2
1
0.25
0
87654321012345678
0.5
1
210.50.25 2 1 0.5
2
2
1
- (04 - 17) -
0.5
Unit : m/s
0.25
Unit : m/s
0.25
TOP VIEW HORIZONTAL LOUVER  : Upward
(m)
SIDE VIEW HORIZONTAL LOUVER  : Upward
(m)
Page 19
4-11-2. AIR FLOW
m3/h
1550
l/s 431
CFM 912
m3/h
1300
l/s 361
CFM 765
m3/h
1100
l/s 306
CFM 647
m3/h
3600
600
490
420
850
Indoor unit
Outdoor unit
HIGH
MED
LOW
HIGH
NUMBER OF
ROTATIONS
(r.p.m)
AIR FLOW
FAN SPEED
MODELS : AU 30L / AO 30L, AU 36L / AO 36L
CASSETTE TYPE
AU30-AU36
CASSETTE TYPE
AU30-AU36
l/s 1000
CFM 2119
- (04 - 18) -
Page 20
4-11-3. DUCT CONNECTION
MODELS : AU 30L, AU 36L
OUTLET AIR
(mmAq)
Duct (Inside Dia. ø100mm)
L
(Pa)
DUCT STATIC PRESSURE
98
49
L=5m
L=3m
L=1m
10
8
6
4
2
0
01234
(m
3
/min)
(Pa)
CASSETTE TYPE
AU30-AU36
Duct (Inside Dia. ø100mm)
L
DUCT STATIC PRESSURE
98
49
L=5m
0
5
(mmAq)
10
L=3m
8
L=1m
6
4
CASSETTE TYPE
AU30-AU36
2
FRESH AIR
Duct (Inside Dia. ø70mm)
P
Static pressure required to take in fresh air
Duct Fan
(Pa)
DUCT STATIC PRESSURE
0
0 1234
(m3/min)
(mmAq)
7
58.8
6
5
39.2
4
3
19.6
2
1
0
0
0.1 0.2 0.3 0.4 0.5 0.6
0
(m3/min)
0
5
- (04 - 19) -
Page 21
4-12. NOISE LEVEL CURVE
4-12-1. OUTDOOR UNIT
COOLING
MODEL : AO 30L
80
70
NC-65
60
50
40
30
CASSETTE TYPE
20
AU30-AU36
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
63 125 250 500 1,0 00 2,000 4,000 8,000
Octave band center frequency,Hz
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL : AO 36L
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
63 125 250 500 1,0 00 2,000 4,000 8,000
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
CASSETTE TYPE
AU30-AU36
HEATING
MODEL : AO 30L MODEL : AO 36L
80
70
NC-65
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63 125 250 500 1,0 00 2,000 4,000 8,000 63 125 250 500 1,000 2,000 4, 000 8,000
Octave band center frequency,Hz Octave band center frequency,Hz
0
- (04 - 20) -
Page 22
SOUND LEVEL CHECK POINT
CASSETTE TYPE
CASSETTE TYPE
AU30-AU36
AU30-AU36
- (04 - 21) -
Page 23
4-12-2. INDOOR UNIT
HIGH
LOW
HIGH
LOW
HIGH
LOW
COOLING
MODEL : AU 30L
80
70
NC-65
60
50
40
30
CASSETTE TYPE
20
AU30-AU36
LOW
HIGH
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
63 125 250 500 1,0 00 2,000 4,000 8,000
Octave band center frequency,Hz
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
MODEL : AU 36L
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
63 125 250 500 1,0 00 2,000 4,000 8,000
Octave band center frequency,Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
CASSETTE TYPE
AU30-AU36
HEATING
MODEL : AU 30L MODEL : AU 36L
80
70
NC-65
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
0
63 125 250 500 1,0 00 2,000 4,000 8,000 63 125 250 500 1,000 2,000 4, 000 8,000
0
Octave band center frequency,Hz Octave band center frequency,Hz
- (04 - 22) -
Page 24
SOUND LEVEL CHECK POINT
MIC
// //
CENTER
CASSETTE TYPE
CASSETTE TYPE
AU30-AU36
AU30-AU36
1.5m
MIC
// //
CENTER
- (04 - 23) -
Page 25
4-13. ELECTRIC CHARACTERISTICS
Main Fuse (Circuit breaker) Current
Model Name
AU 30L
AU 36L
AO 30L
AO 36L
Power Supply
230
2305050
Rated Value
Mode
*1) Wiring Spec
302730
4.0
4.0
21
Indoor Fan Motor
0.19
0.19
1.00
1.00
0.42
0.42
Outdoor Fan Motor
0.13
0.13
Indoor unit
Outdoor unit
Voltage V
Frequency Hz
Current A 12.5 12.4 17.6 15.2
Input kW 2.86 2.84 4.01 3.49
Max Operating Current A 15.2 14.8 17.9 18.2
Starting Current A 15 15 15 15
A
Cooling Heating Cooling Heating
CASSETTE TYPE
AU30-AU36
*1) Wiring Spec : Selected Sample
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
Power Cable
*2)Limited wiring length m
Input kW
Full Load Amp. A
Input kW
Full Load Amp. A
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
When the wiring length becomes long, please select the wiring of a more larger diameter.
mm
2
CASSETTE TYPE
AU30-AU36
- (04 - 24) -
Page 26
4-14. SAFETY DEVICE
PROTECTION FORM AO 30L AO 36L
FUSE (SIDE OF POWER SUPPLY TERMINAL) - 25A 250V 25A 250V
FUSE (SIDE OF INDOOR UNIT) - 10A 250V 10A 250V
- 3.15A 250V 3.15A 250V
- 5A 250V 5A 250V
FAN MOTOR PROTECTOR THERMAL PROTECTOR 150±5°C OFF 150±5°C OFF
HIGH PRESSURE PROTECTION PRESSURE SWITCH
OFF:4.2±0.1MPa
ON:3.2±0.15MPa
OFF:4.2±0.1MPa
ON:3.2±0.15MPa
DISCHARGE THERMOSTAT THERMAL PROTECTOR
OFF:120±5°C
ON:80±5°C
OFF:120±5°C
ON:80±5°C
COMPRESSOR THERMISTOR THERMAL PROTECTOR
OFF:130±5°C
ON:80±5°C
OFF:130±5°C
ON:80±5°C
FUSE ON MAIN PCB
PROTECTION FORM AU 30L AU 36L
PCB FUSE - 3.15A 250V 3.15A 250V
FAN MOTOR PROTECTION THERMAL PROTECTOR 130±5°C OFF 130±5°C OFF
TERMINAL FUSE THERMAL FUSE 102±2°C OFF 102±2°C OFF
OUTDOOR UNIT
CASSETTE TYPE
CASSETTE TYPE
AU30-AU36
AU30-AU36
INDOOR UNIT
- (04 - 25) -
Page 27
Change current capacity No use (OFF)
1
OUTDOOR UNIT
2
3
DIP SW 1
PUSH SW
4-15. FUNCTION SETTING
4-15-1. OUTDOOR UNIT
Pump down switch
SWITCH POSITION
Outdoor unit control circuit board
CASSETTE TYPE
CASSETTE TYPE
AU30-AU36
DIP SW 1
OFF ON
1
2
3
PUSH SW
AU30-AU36
- (04 - 26) -
Page 28
4-15-2.
13.5A
12.0A
DIP-SW1
CURRENT
(MAX.)
18.0A *1
15.0A *2
OFF
OFF
OFFONON
OFF
ON
OFF
1
OFFON23OFF
OFF
SWITCH FUNCTION (OUTDOOR UNIT)
DIP SWITCH SETTING
Current capacity setting
*1=36000BTU model's factory setting *2=30000BTU model's factory setting
PUSH SWITCH SETTING
CASSETTE TYPE
SW2 setting
AU30-AU36
Press the push-button switch, and "PUMP DOWN OPERATION" is starting.
CASSETTE TYPE
AU30-AU36
- (04 - 27) -
Page 29
4-15-3. INDOOR UNIT
Auto restart validity/invalidity
Room temperature correct coefficient
Room temperature correct coefficient
Forbidden
Indoor unit number setting
Forbidden
Forbidden
Forbidden
SW 1
SW 4
1
2
Jumper Wire
2
3
JM1
JM2
Rotary SW
SW 2
INDOOR UNIT
DIP SW
3
1
JM3
Ceiling height setting
SWITCH POSITION
CASSETTE TYPE
AU30-AU36
Indoor unit control circuit board
CASSETTE TYPE
AU30-AU36
ON
OFF
3 2 1
ON OFF 3 2 1
JM1
JM2
JM3
- (04 - 28) -
Page 30
SW 1-1
SW state
OFF
Invalidity
ON
Validity
0 deg
0 deg
0 deg
cooling
-2 deg
SW 1-2
SW 1-3
0 deg
heating
dry
-2 deg
-2 degONONONOFF
OFF
+2 deg
-2 deg
OFF
SW state
-2 deg
OFF
ON
0 deg
+4 deg
SW 4-1
OFF
3
OFF
-
ON
Less than 2.5
Normal
High ceiling 1
High ceiling 2
Low ceiling
-ONON
3.0-3.5
More than 3.5
-
OFF
-
ON
OFF
2.5-3.0
OFF
Ceiling height(m)
DIP - SW4
1
2
4-15-4.
DIP SWITCH SETTING
SW1-1. Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTO RESTART SETTING
SW1-2, 1-3. Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
TEMPERATURE CORRECTION
CASSETTE TYPE
AU30-AU36
SWITCH FUNCTION (
( Factory setting)
( Factory setting)
INDOOR UNIT)
CASSETTE TYPE
AU30-AU36
SW4-1. Dip SW 4-1setting forbidden
( Factory setting)
SW4-2, 4-3. Ceiling height setting
( Factory setting)
If the setting for a low ceiling is selected, the capacity of the air conditioner decreases slightly.
- (04 - 29) -
Page 31
ROTARY SWITCH SETTING (SW2)
0
Single
1 - 15
Indoor unit address
SW 2
SW state
SW state
JM 1, 2, 3
Connect
Disconnect
Forbidden
This switch can be used when group control system. Set the indoor unit address in the 0,1,-,15 order.
( Factory setting)
JUMPER WIRE SETTING
JM 1, 2, 3 setting forbidden
( Factory setting)
CASSETTE TYPE
CASSETTE TYPE
AU30-AU36
AU30-AU36
- (04 - 30) -
Page 32
4-15-5. WIRED REMOTE CONTROLLER CIRCUIT BOARD
Wired remote controller
1
Dual remote controller setting
2
Group control setting
DIP SW
SWITCH POSITION
Wired remote controller
Front case (back side)
CASSETTE TYPE
AU30-AU36
3
4
Model setting
Auto changeover setting
5
6
Memory backup setting
CASSETTE TYPE
AU30-AU36
DIP Switch
OFF
ON
1 2 3 4 5 6
ON
- (04 - 31) -
Page 33
4-15-6. WIRED REMOTE CONTROLLER
DIP SWITCH SETTING
1. SW setting
1-1 Dual remote controller setting
Set the remote controller DIP switch No.1 and 2 according to the following table.
( Factory setting)
Number of remote controller
1 (Normal)
2 (Dual)
1-2 Group control setting
Number of indoor unit connection (One/Multiple) This is switched according to the number of connected indoor units.
CASSETTE TYPE
AU30-AU36
DIP-SW No.3
OFF
Master unit Slave unit
DIP-SW No.1
DIP-SW No.2
ON
OFF
( Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW No.1
ON ON
DIP-SW No.2
CASSETTE TYPE
AU30-AU36
ON Multiple unit connection
1-3 Model setting
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
( Factory setting)
DIP-SW No.4
OFF
ON Cooling only model
Heat Pump model
Model
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
( Factory setting)
DIP-SW No.5
OFF
ON Validity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used, all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
( Factory setting)
DIP-SW No.6
OFF
ON Validity
Memory backup
Invalidity
- (04 - 32) -
Page 34
4-16. OPTIONAL PARTS
ADDITIONAL GRILLE UTG-AGEA-W
The additional grille hides the gap between the ceiling hole and the outlet grille.
Additional grille (optional parts)
Additonal grille
CASSETTE TYPE
AU30-AU36
The ceiling hole
Indoor Unit(grille)
CASSETTE TYPE
AU30-AU36
- (04 - 33) -