General AUH18L, AUH18LBAB, AOH18LMAKL Technical Manual

Page 1
R410A
2 . CASSETTE TYPE :  AU 18LBAB
D2D_AU001E/01
2005.12.12
Page 2
2-1. FEATURE
MODELS : AU 18LBAB / AO 18LMAKL
CASSETTE TYPE
AU18
FEATURES
Compact size
Compact grille fits European ceiling panel (650 x 650 mm).
Punch Hall grille
CASSETTE TYPE
AU18
650
650
(unit: mm)
Slim intake grille
Slim type intake grille can fit the ceiling after installation.
20
(unit: mm)
Detachable,washable filter and intake grille.
Intake grille and air filter can be removed easily and cleaned.
Long-life filter
Page 3
Duct connection hole opening
Fresh air can be introduced through this opening.
Fresh air
CASSETTE TYPE
AU18
CASSETTE TYPE
AU18
Distribution duct
Distribution duct
Conditioned air can be distributed by means of a distribution duct.
One-way
Two-way
Page 4
2-2.
REMOTE CONTROLLER
2-2-1. WIRELESS REMOTE CONTROLLER
FEATURES
Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible.
Four kinds of timers. Easy operation.
CASSETTE TYPE
AU18
CASSETTE TYPE
AU18
Built-in timers
Easy to change transmission code (4 patterns) by button operation.
Select from four different timer programs (On/Off/Program/Sleep).
Program timer
The program timer operates the ON and OFF timer once within a 24 hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature automatically rises 1 °C every hour. The set temperature can rise up to a maximum of 2 °C.
Heating operation
When the sleep timer is set, the set temperature automatically drops 1 °C every 30 minutes. The set temperature can drop to a maximum of 4 °C.
Timer setting
60min.
1 °C
Simultaneously operation
After code change
Mixed-up
• Code selector switch eliminates unit being wrongly switched. (Up to 4 codes can be set.)
A B C D
A B
C
2 °C
D
•Wide and precise transmitting range.
1 °C
2 °C
3 °C
4 °C
30min.
60min.
90min.
Timer setting
1. Press the MASTER CONTROL button for more than five seconds to start the code change.
2. Press the (+) or (-) button to select the desired code.
A B C D
3. Press the MASTER CONTROL button again to end the code change.
- (02 - 03) -
Page 5
FUNCTIONS
1
5
START/STOP button
Pressed to start and stop operation
64
Display
2
Set temp./Set time/ Set remote controller custom code buttons
Sets the indoor temp./ Sets the current time and on-off time. /Sets R.C. custom code.
CASSETTE TYPE
AU18
3
2
9
10
1
7
11
12
8
3
Master control / Code change buttons
Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY). /Start / end R.C. custom code change. (Max 4 types)
4
Sleep timer button
Pressed to select sleep timer.
5
Signal transmitter
6
Timer button
CASSETTE TYPE
AU18
Pressed to select the timer mode. (OFF TIMER, ON TIMER, PROGRAM TIMER, TIMER RESET)
7
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
8
Battery compartment lid
9
Air flow direction set button
TEST
RUN
13
10
Time adjust button
Sets the current time.
Display panel
14
15
16
17
18
19
20
21
11
Air flow direction swing button
12
ACL button
Used when replacing batteries or change the code.
13
Test run button
Used when testing the air conditioner after installation.
14
Transmit indicator
15
Clock display
16
Master control display
17
Timer mode display
18
Fan speed display
19
Set temperature display
20
Timer set indicator
21
Temperature set indicator
SPECIFICATION
SIZE (H x W x D mm) 160 x 56 x 20
WEIGHT ( g ) 120
ACCESSORY Holder
- (02 - 04) -
Page 6
2-3. SPECIFICATIONS
Rows x Stages
Fin Pitch
Rows x Stages
Fin Pitch
70 × 720 × 720
743 × 984 × 413
1.40
1.45
235 × 580 × 580 + 70
650 × 830 × 320
280 × 710 × 750
Beige(10YR7.5/1.0NN)
35 × 650 × 650
2.2/4.3
NET / GROSS
kg(lbs)
18/23 (40/51)
54/58 (119/128)
Inverter
White(5Y9/0.5NN)
Hermetic type, 4 poles, DC motor, TWIN ROTARY
1300
630 × 901 × 36.38
2 × 10
210 × 1000 × 26.6
Copper tube
Aluminium
520/520
450/450
2800/2800
400/400
1.65/1.74
1.71/1.95
7.2/7.6
7.5/8.5
4.70/4.90
16000/16700
4.80/5.20
16400/17800
REMOTE CONTROLLER
wireless
PP
DRAIN PIPE MATERIAL
SIZE
Outer diameter 37.0/Inner diameter 32.0
POE
15
TYPE
REFRIGERANT OIL
1500
6.35
REFRIGERANT TYPE
MAX HEIGHT
MAX LENGTH
PIPE
SIZE
R410A
12.7
25(chargeless 10)
mm
CASING COLOR
DIMENSIONS H × W × D
GROSS
NET
mm
WEIGHT
CONNECTION METHOD
kW
INPUT POWER
COOLING
HEATING
HEAT PUMP TYPE
CASSETTE INVERTER MODELS
TYPE
230V 50Hz
RATED / MAX
INDOOR
OUTDOOR
POWER SOURCE
MODEL NAME
CAPACITY
RATED / MAX
AU 18LBAB
AO 18LMAKL
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
INDOOR FAN MOTOR OUTPUT
W
HEAT EXCHANGER TYPE
INDOOR
COMPRESSOR
Coil
Fin
mm
mm
FAN TYPE x Qty
dB(A)
38/38
FLARE
OUTDOOR
TYPE
STARTING METHOD
OUTDOOR
Coil
Fin
Aluminium
2 × 30
Turbo x 1
Propeller x 1
50/521465
44/45
41/41
Copper tube
A
r.p.m m3/h
INDOOR
INDOOR
700/700
600/600
STARTING CURRENT
MOISTURE REMOVAL
kW/kW
10
2.85
2.81
2.0
620/620
780/780
198-264V 50Hz
C
FAN SPEED COOL/HEAT
OUTDOOR AVAILABLE VOLTAGE RANGE
EUROPEAN ENERGY LABEL
AIR CIRCULATION COOL/HEAT
CURRENT
800/800
CASSETTE TYPE
AU18
COOLING RATED / MAX
HEATING RATED / MAX
COOLING RATED / MAX
HEATING RATED / MAX
EER COOLING
COP HEATING
High
Med
Low
OUTDOOR High
High
Med
Low
High
Low
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High
Med
Low
kW
BTU/h
kW
BTU/h
A
l/h
CASSETTE TYPE
AU18
OUTPUT W
Coil Dimensions
Coil Dimensions
INDOOR
OUTDOOR
INDOOR
OUTDOOR
GRILLE
INDOOR
OUTDOOR
GRILLE
INDOOR
OUTDOOR
GRILLE
LIQUID
GAS
m
m
Note: Specifications are based on the following conditions. Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB. Heating: Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CW B. Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
CHARGE g
mm
- (02 - 05) -
Page 7
2-4. DIMENSIONS
2-4-1. OUTDOOR UNIT
MODEL : AO 18L
CASSETTE TYPE
AU18
Top view
(Unit : mm)
CASSETTE TYPE
AU18
830
650
12
Front view
Bottom
Air flow
343
350
320
Side view
154
101
58
90
MOUNTING POSITION
When there are obstacles at the back or front sides.
100 mm or more
600 mm or more
Bottom view
100 mm or more
603
When there are obstacles at the back, side(s), and top.
600 mm or more
300 mm
25
(
S
0 mm o
er
v
i
c
r
more
e s
p
ac
e)
or more
When there are obstacles at the back, side with the installation of more than one unit.
250 mm or more
250 mm or more
300 mm or more
- (02 - 06) -
Page 8
2-4-2. INDOOR UNIT
MODEL : AU 18L
(Unit : mm)
20
CASSETTE TYPE
AU18
650
Bottom view (Panel)
35
440
650
580
Bottom view
235
66
580
CASSETTE TYPE
AU18
245
Side view
(Grille measurement) 650
(Hanging bolt position) 400
60
47
111
131
440
(Hanging bolt position)
606
Top view
66
46 86
(Ceiling opening measurement)
Drain pipe(I.D. 32)
600
245
54
- (02 - 07) -
Page 9
MOUNTING POSITION
Floor
Strong and durable ceiling
250 mm
CASSETTE TYPE
AU18
or more
CASSETTE TYPE
AU18
1,000 mm
2,300 mm or more
(4 directions) (3 directions)
Piping position
or more
Obstruction
100 or more 100 or more
1,000 mm or more
100 or more
(2 directions) (2 directions)
100 or more
- (02 - 08) -
Page 10
2-5. REFRIGERANT CIRCUIT
MODELS : AU 18L / AO 18L
CASSETTE TYPE
AU18
CASSETTE TYPE
AU18
Page 11
2-6. WIRING DIAGRAMS
2-6-1. OUTDOOR UNIT
MODEL : AO 18L
CASSETTE TYPE
AU18
CASSETTE TYPE
AU18
Page 12
2-6-2. INDOOR UNIT
MODEL : AU 18L
CASSETTE TYPE
AU18
CASSETTE TYPE
AU18
- (02 - 11) -
Page 13
2-7. CAPACITY TABLE
Indoor temperature
18°CDB
21°CDB
23°CDB
26°CDB
27°CDB
29°CDB
30°CDB
32°CDB
23°CWB
12°CWB
15°CWB
16°CWB
18°CWB
19°CWB
21°CWB
22°CWB
Outdoor temperature
30°CDB
Outdoor temperature
Indoor temperature
16°CDB
18°CDB
20°CDB
23°CDB
25°CDB
27°CDB
MODELS : AU 18L / AO 18L
COOLING
AFR 10.3
(°CDB) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
CASSETTE TYPE
AU18
HEATING
AFR 10.3
0 2.63 2.05 0.30 2.70 1.88 0.31 2.77 2.05 0.31 2.88 2.17 0.32 2.93 2.15 0.32 3.01 2.09 0.32 3.05 2.06 0.32 3.09 2.19 0.33
5 2.73 2.12 0.38 2.82 1.96 0.39 2.91 2.15 0.39 3.05 2.31 0.40 3.10 2.29 0.40 3.20 2.24 0.41 3.25 2.22 0.41 3.29 2.36 0.42
10 3.42 2.70 0.35 3.53 2.51 0.37 3.64 2.74 0.37 3.83 2.95 0.39 3.91 2.93 0.39 4.04 2.89 0.40 4.10 2.86 0. 41 4.15 3.04 0.41
15 3.16 2.46 0.42 3.26 2.27 0.43 3.37 2.51 0.44 3.55 2.71 0.45 3.62 2.70 0.46 3.75 2.67 0.47 3.81 2.65 0. 48 3.87 2.82 0.48
20 3.08 2.38 0.51 3.17 2.20 0.52 3.27 2.42 0.53 3.43 2.62 0.54 3.50 2.61 0.55 3.63 2.58 0.56 3.70 2.56 0. 57 3.75 2.74 0.57
25 4.28 3.40 0.99 4.41 2.17 1.00 4.53 3.44 1.01 4.74 3.69 1.03 4.83 3.67 1.04 4.99 3.62 1.05 5.06 3.60 1. 06 5.13 3.82 1.07
30 4.04 3.18 1.14 4.19 2.98 1.15 4.31 3.25 1.16 4.50 3.50 1.19 4.59 3.49 1.20 4.76 3.45 1.22 4.84 3.43 1. 22 4.91 3.65 1.23
35 4.35 3.41 1.67 4.45 3.16 1.68 4.59 3.47 1.70 4.80 3.74 1.73 4.90 3.73 1.74 5.09 3.70 1.77 5.18 3.68 1. 78 5.27 3.94 1.79
40 4.04 3.15 1.89 4.11 2.89 1.90 4.23 3.18 1.91 4.44 3.45 1.94 4.55 3.45 1.96 4.74 3.43 1.99 4.83 3.42 2. 01 4.93 3.68 2.03
43 3.79 2.92 1.96 3.87 2.69 1.97 3.99 2.98 1.98 4.20 3.26 2.01 4.31 3.26 2.03 4.50 3.24 2.07 4.61 3.24 2. 08 4.71 3.51 2.09
(°CDB) (°CWB) TC PI TC PI TC PI TC PI TC PI TC PI TC PI SHC: Sensible Heat capacity (kW)
-10 -11 3.47 2.00 3.38 2.08 3.20 2.15 3. 02 2.23 2.93 2.27 2.76 2.35 2.58 2.39 PI : Power Input (kW)
-5 -6 3.37 2.01 3.29 2.08 3.13 2.15 2.97 2.22 2.89 2.26 2.73 2.33 2.57 2.37
0 -1 3.61 1.97 3.53 2.04 3.39 2.10 3.24 2.16 3.16 2.19 3.02 2.26 2.87 2.29
2 1 3.79 2.06 3.73 2.11 3.60 2.17 3.48 2.22 3.42 2.25 3.29 2.30 3.17 2.33
7 6 5.43 1.85 5.35 1.90 5.20 1.95 5.05 2.00 4.98 2.02 4.83 2.07 4.68 2.09
10 8 5.73 1.91 5.66 1.96 5.51 2.00 5.37 2.05 5.29 2.07 5.15 2.12 5.00 2.14
15 12 5.93 1.95 5.85 2.00 5.71 2.04 5.56 2.09 5.48 2.11 5.33 2.16 5.19 2.18
20 15 6.09 1.90 6.00 1.95 5.84 2.00 5.68 2.04 5.60 2.07 5.44 2.12 5.27 2.14
24 18 6.21 1.85 6.13 1.90 5.95 1.95 5.78 2.00 5.69 2.03 5.51 2.08 5.34 2.10
AFR: Air flow rate (m3/min)
TC : Total capacity (kW)
CASSETTE TYPE
AU18
Page 14
2-8. CAPACITY COMPENSATION FOR PIPE LENGTH
PIPE LENGTH (m)
PIPE LENGTH (m)
Outdoor unit
is up-side
COOLING
Height diference(m)
Height diference(m)
HEATING
Outdoor unit
is up-side
Outdoor unit
AND HEIGHT DIFFERENCE
MODELS : AU 18L / AO 18L
5 7.5 10 15 20 25
15 - - - 0.982 0.974 0.966
CASSETTE TYPE
AU18
10 - - 0.988 0.982 0.974 0.966
7.5 - 1.000 0.988 0.982 0.974 0.966
CASSETTE TYPE
AU18
is bottom side
Outdoor unit
is bottom side
5 1.010 1.000 0.988 0.982 0.974 0.966
0 1.010 1.000 0.988 0.982 0.974 0.966
-5 1.002 0.992 0.980 0.974 0.966 0.958
-7.5 - 0.988 0.976 0.970 0.962 0.954
-10 - - 0.972 0.966 0.958 0.950
-15 - - - 0.958 0.951 0.943
5 7.5 10 15 20 25
15 - - - 0.987 0.985 0.983
10 - - 0.993 0.992 0.990 0.988
7.5 - 0.993 0.996 0.994 0.992 0.991
5 0.979 0.995 0.998 0.997 0.995 0.993
0 0.984 1.000 1.003 1.002 1.000 0.998
-5 0.984 1.000 1.003 1.002 1.000 0.998
-7.5 - 1.000 1.003 1.002 1.000 0.998
-10 - - 1.003 1.002 1.000 0.998
-15 - - - 1.002 1.000 0.998
Page 15
2-9. ADDITIONAL CHARGE CALCULATION
10 15 20 25(MAX)
(Charge less)
20g/m
R410A
1500
MODELS : AU 18L / AO 18L
REFRIGERANT TYPE
REFRIGERANT AMOUNT g
CASSETTE TYPE
AU18
REFRIGERANT CHARGE
PIPE LENGTH m
CASSETTE TYPE
AU18
ADDITIONAL CHARGE g
+100 +200 +350
Page 16
2-10. OPERATION RANGE
Mode
Indoor unit Outdoor unit Indoor temperature Indoor humidity Outdoor temperature
Cooling
Dry
18 to 32 °C About 80% or less 0 to 43 °C
Heating 16 to 30 °C - -10 to 24 °C
Operation Range
Model
AO 18L
AU 18L
CASSETTE TYPE
AU18
CASSETTE TYPE
AU18
Page 17
2-11. FAN PERFORMANCE AND AIR FLOW
2-11-1. AIR VELOCITY DISTRIBUTION
MODEL : AU 18L
4-WAY AIR OUTLET
0.5
11
Unit : m/s
0.25
(m)
4
3
CASSETTE TYPE
AU18
2
1
0
0.25
0.5
0.25
0.5
1
2
22
Note :
Condition
Fan speed : High Operation mode :FAN
CASSETTE TYPE
AU18
1
2
3
2
1
0.5
0.25
4
4 3 2 1 0 1 2 3 4
(m)
3
2
1
0.25
2
1
0.5
0
4 3 2 1 0 1 2 3 4 5 6 77 6 5
(m)
3
2
1
0
2
1
0.5
0.25 0.25
3 2 1 0 1 2 3
Unit : m/s
2
1
0.5
SIDE VIEW HORIZONTAL LOUVER  : Downward
(m)
TOP VIEW HORIZONTAL LOUVER  : Upward
(m)
2
1
0.5
0.25
Unit : m/s
(m)
AIR DISCHARGE ANGLE
SIDE VIEW HORIZONTAL LOUVER  : Upward
Upward
2
3
Downward
2-WAY AIR OUTLET
(m)
2
1
0
0.5
0
0.25
2
1
2 1
0.5
1
2
7 6 5 4 3 2 1 0 1 2 3 4 5 6 7
(m)
3
2
1
0
0.25
1
0.5
3
2
2
1
0.5
0.25
7 6 5 4 3 2 1 0 1 2 3 4 5 6 7
Unit : m/s
0.25
Unit : m/s
TOP VIEW HORIZONTAL LOUVER  : Upward
(m)
SIDE VIEW HORIZONTAL LOUVER  : Upward
(m)
Page 18
2-11-2. AIR FLOW
m3/h 620
l/s 172
CFM 365
m3/h 520
l/s 144
CFM 306
m3/h 450
l/s 125
CFM 265
m3/h 2800
l/s 778
CFM 1648
Outdoor unit
Indoor unit
FAN SPEED
NUMBER OF
ROTATIONS
(r.p.m)
780
HI
MED
LOW
-
800
700
600
AIR FLOW
MODELS : AU 18L / AO 18L
CASSETTE TYPE
AU18
CASSETTE TYPE
AU18
Page 19
2-11-3. DUCT CONNECTION
MODEL : AU 18L
OUTLET AIR
Duct (inside dia.ø150mm)
CASSETTE TYPE
AU18
L
8
240V Hi
L=5m
7
220V Hi
6
240V Lo
5
220V Lo
4
(mmAq)
CASSETTE TYPE
AU18
3 2 1 0
0 2 4 6 8
3
(m
/min)
Duct (Inside Dia. ø150mm)
8
240V Hi
L=5m
(mmAq)
7
220V Hi
6
L
240V Lo
5
220V Lo
4 3 2 1 0
0 2 4 6 8 10
3
(m
/min)
FRESH AIR
P
Duct (inside dia.ø150mm)
Duct Fan
Static pressure required to take in fresh air
7
(mmAq)
6
5
4
3
2
1
0
0 0.1 0.2 0.3 0.4
3
(m
/min)
Page 20
2-12. NOISE LEVEL CURVE
2-12-1. OUTDOOR UNIT
COOLING
MODEL : AO 18L
80
CASSETTE TYPE
70
AU18
µbar)
60
50
40
30
Octave-band sound-pressure level dB : (0dB=0.0002
20
10
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
HEATING
MODEL : AO 18L
80
70
µbar)
60
50
40
30
Octave-band sound-pressure level dB : (0dB=0.0002
20
10
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
CASSETTE TYPE
AU18
0
63 125 250 500 1000 2000 4000 8000
Octave-band limiting frequency, Hz
0
63 125 250 500 1000 2000 4000 8000
Octave-band limiting frequency, Hz
- (02 - 19) -
Page 21
SOUND LEVEL CHECK POINT
CASSETTE TYPE
AU18
CASSETTE TYPE
AU18
Page 22
2-12-2. INDOOR UNIT
LOW
HIGH
LOW
COOLING
MODEL : AU 18L
80
CASSETTE TYPE
70
AU18
µbar)
60
50
40
30
Octave-band sound-pressure level dB : (0dB=0.0002
20
10
HIGH
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
HEATING
MODEL : AU 18L
80
70
µbar)
60
50
40
30
Octave-band sound-pressure level dB : (0dB=0.0002
20
10
NC-70
NC-60
NC-50
NC-40
NC-30
NC-20
CASSETTE TYPE
AU18
0
63 125 250 500 1000 2000 4000 8000
Octave-band limiting frequency, Hz
0
63 125 250 500 1000 2000 4000 8000
Octave-band limiting frequency, Hz
- (02 - 21) -
Page 23
SOUND LEVEL CHECK POINT
MIC
CASSETTE TYPE
AU18
CENTER
// //
1.5m
CASSETTE TYPE
AU18
MIC
// //
CENTER
Page 24
2-13. ELECTRIC CHARACTERISTICS
Main Fuse (Circuit breaker) Current
Model Name
Outdoor Fan Motor
0.15
Rated Value
Mode
10
0.73
Indoor Fan Motor
0.042
0.19
*1) Wiring Spec
34
3.5
20
Power Supply
230
50
AU 18L
AO 18L
MODELS : AU 18L / AO 18L
Indoor unit
Outdoor unit
Voltage V
CASSETTE TYPE
AU18
Frequency Hz
CASSETTE TYPE
AU18
Cooling Heating
Current A 7.2 7.5
Input kW 1.65 1.71
Max Operating Current A 10.5 10.5
Starting Current A
A
Power Cable
mm
2
*2)Limited wiring length m
Input kW
Full Load Amp. A
Input kW
Full Load Amp. A
*1) Wiring Spec : Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
Page 25
2-14. SAFETY DEVICE
PROTECTION FORM
AO 18L
FUSE (SIDE OF POWER SUPPLY TERMINAL)
OFF 120±5°C
ON 85±7°C
PROTECTION FORM
AU 18L
OUTDOOR UNIT
CASSETTE TYPE
AU18
FUSE ON MAIN PCB CURRENT FUSE 3.15A 250V
FAN MOTOR PROTECTOR THERMAL PROTECTOR 150±5°C OFF
COMPRESSOR THERMAL PROTECTOR
HIGH PRESSURE PROTECTION PRESSURE SWITCH 4.2MPa
INDOOR UNIT
CURRENT FUSE 25A 250V
CASSETTE TYPE
AU18
PCB FUSE CURRENT FUSE 3.15A 250V
FAN MOTOR PROTECTOR THERMAL PROTECTOR 140±5°C OFF
Page 26
2-15. FUNCTION SETTING
Auto restart validity/invalidity
Room temperature correct coefficient
Room temperature correct coefficient
Forbidden
Remote control unit single code
Remote control unit single code
INDOOR UNIT
DIP SW
3
JM3
SW 1
Jumper Wire
JM1
JM212
2-15-1. INDOOR UNIT
CASSETTE TYPE
AU18
SWITCH POSITION
Indoor unit control circuit board
CASSETTE TYPE
AU18
JM1
JM3
JM2
CN10
Page 27
SW 1-1
SW state
OFF
Invalidity
ON
Validity
-2 deg
0 deg
0 deg
-2 deg
-2 deg
0 deg
0 deg
-2 deg
cooling
SW state
ON
OFF
-2 deg
SW 1-2
SW 1-3
heating
dry
ON
ON
ON
0 deg
+4 deg
OFF
OFF
OFF
+2 deg
Jumper wire
JM3
Remote control unit signal code
connect
connect
A
JM2
Disconnect
Disconnect
Disconnect
connect
connectBC
D
Disconnect
2-15-2. SWITCH FUNCTION (INDOOR UNIT)
DIP SWITCH SETTING
SW1-1. Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTO RESTART SETTING
CASSETTE TYPE
AU18
SW1-2, 1-3. Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
TEMPERATURE CORRECTION
( Factory setting)
( Factory setting)
CASSETTE TYPE
AU18
JUMPER WIRE SETTING
JM 1, 2, 3 setting
( Factory setting)
Page 28
2-16. OPTIONAL PARTS
ADDITIONAL GRILLE UTG-AGDA-W
The additional grille hides the gap between the ceiling hole and the outlet grille.
Additional grille (optional parts)
CASSETTE TYPE
AU18
Additonal grille
The ceiling hole
CASSETTE TYPE
AU18
Indoor Unit(grille)