Various timer setup (ON / OFF / WEEKLY) are possible.
SUMOTUWETH FR SA
7
3126 9
15 18 21
High performance and compact size
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible.
Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature
accurately with built-in thermo sensor.
Three functions are combined in
one unit.
Wired
remote
controller
Weekly
timer
Setback
timer
Built-in timers
Setback timerWeekly timer
CASSETTE TYPE
AU45 - AU54
Possible to set ON/OFF time to operate twice each day
of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 18 21
Screen
after setup
Possible to set temperature for two time spans and
for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example
(Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
At "Weekly timer" + "Set back timer" setup
24°C
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
28°C
CASSETTE TYPE
AU45 - AU54
Easy-to-understand operationSimple installation
Components are compatible with standard
switch boxes. Flat back construction allows
equipment to be installed wherever it is
needed.
Timer
area
[
Variable timer control
]
The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
Operation
area
European
switch box
- (05 - 03) -
JIS box
Page 5
FUNCTIONS
Display
2
7
8
9
10
11
12
Display panel
15
CLOCK ADJUST
SET BACK
SUMOTUWETH FR
369
12 15 18 21
DAY OFF
DELETESET
1
START/STOP button
Pressed to start and stop operation.
2
Set Temperature button
SA
14
DAY
ENERGY
THERMO
SAVE
SENSOR
1
3
4
5
6
13
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Thermo sensor button
6
Energy save button
Turns the energy efficient mode on and off.
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER,
WEEKLY TIMER) Set the current time.
8
Day (DAY OFF) button
Temporarily cancels of one day timer.
9
16
1718 19
Set back button
pressed select the set back timer.
10
SUMOTUWETH FR
SA
Set time button
Pessed to select the set back timer.
11
369
12 15 18 21
CASSETTE TYPE
AU45 - AU54
202122
Delete button
The schedule of a weekly timer is deleted.
12
Set button
CASSETTE TYPE
AU45 - AU54
Sets the date, hour, minute and on-off time.
13
Vertical air flow direction and swing button
DIMENSION
120
SUMOTUWETH FR
CLOCK ADJUST
SET BACK
DELETESET
369
SA
12 15 18 21
DAY
DAY OFF
ENERGY
SAVE
THERMO
SENSOR
[ Unit : mm ]
17
120
Push for two seconds to change the swing mode
14
Operation lamp
Lights during operation and when the timer is on.
15
Timer and clock display
16
Operation mode display
17
Fan speed display
18
Central control display
19
Temperature display
20
Stand by display
Indicates during the oil recovery and defrosting operation.
21
Front View
Vertical swing display
22
Energy save display
SPECIFICATION
SIZE (H x W x D mm)120 x 120 x 17
WEIGHT( g )160
CABLE LENGTH( m )
POWER( V )
Note:Specifications are based on the following conditions.
Cooling:Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB.
Heating:Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Note:Specifications are based on the following conditions.
Cooling:Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB.
Heating:Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
mm
- (05 - 06) -
Page 8
5-4. DIMENSIONS
5-4-1. OUTDOOR UNIT
MODELS : AO 45F, AO 54F, AO 45U, AO 54U
Top view
AO 45 : 1165
AO 54 : 1290
21
317790033012
(Unit : mm)
CASSETTE TYPE
AU45 - AU54
Front view
370
Bottom view
9
650
Air Flow
4-Ø12mm hole
400
Side view
CASSETTE TYPE
AU45 - AU54
196
99
151
170
MOUNTING POSITION
When there are
obstacles at the
back or front side.
When there are obstacles
at the back and front sides.
When there are obstacles at
the back, side(s), and top.
When there are obstacles
at the back side with the
installation of more than
one unit.
100 mm
or more
600 mm
or more
100 mm
or more
100 to 300 mm *
- (05 - 07) -
600 to 1000 mm
250 mm
or more
250
(
mm
Ser
v
ic
e
* If the space is larger than that is stated, the
condition will be the same as that there are no
obstacles.
Power Cable
*2)Limited wiring length m
InputkW
Full Load AmpA
InputkW
Full Load AmpA
W
*1) Wiring Spec :Selected Sample (Selected based on Japan Electrotechnical Standard and Codes
Committee E0005)
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger
diameter.
CASSETTE TYPE
AU45 - AU54
CASSETTE TYPE
AU45 - AU54
- (05 - 32) -
Page 34
5-14. SAFETY DEVICE
PROTECTION FORMAO 45FAO 45UAO 54FAO 54U
FUSE
(SIDE OF POWER SUPPLY TERMINAL)
-
--6.3A 250V-6.3A 250V
OFF:130±5°C
ON:100±15°C
-
OFF:130±5°C
ON:100±15°C
-
5A 250V
150±5°C OFF
OFF:4.2±0.1MPa
ON:3.2±0.15MPa
OFF : 50°C(27A) 165°C(0A)
ON : 80±10°C
OFF : 50°C(29A) 165°C(0A)
ON : 80±10°C
PROTECTION FORMAU 45FAU 45UAU 54FAU 54U
PCB FUSE
-
FAN MOTOR PROTECTORTHERMAL PROTECTOR
TERMINAL FUSE
-
150±5°C OFF
102±2°C OFF
3.15A 250V
OUTDOOR UNIT
FUSE ON PCB
FAN MOTOR PROTECTORTHERMAL PROTECTOR
COMPRESSOR THERMAL PROTECTOR
HIGH PRESSURE PROTECTION PRESSURE SWITCH
DISCHARGE THERMOSTATTHERMAL PROTECTOR
INDOOR UNIT
CASSETTE TYPE
AU45 - AU54
CASSETTE TYPE
AU45 - AU54
- (05 - 33) -
Page 35
5-15. FUNCTION SETTING
Auto restart validity/invalidity
Room temperature correct coefficient
Room temperature correct coefficient
Forbidden
Indoor unit number setting
Forbidden
Forbidden
Forbidden
SW 1
SW 4
1
2
Jumper Wire
2
3
JM1
JM2
Rotary SW
SW 2
INDOOR UNIT
DIP SW
31JM3
Ceiling height setting
5-15-1. INDOOR UNIT
SWITCH POSITION
Indoor unit control circuit board
CASSETTE TYPE
AU45 - AU54
CASSETTE TYPE
AU45 - AU54
- (05 - 34) -
Page 36
5-15-2. SWITCH FUNCTION (INDOOR UNIT)
SW 1-1
SW state
OFF
Invalidity
ON
Validity
0 deg
0 deg
0 deg
cooling
-2 deg
SW 1-2
SW 1-3
0 deg
heating
dry
-2 deg
-2 degONONONOFF
OFF
+2 deg
-2 deg
OFF
SW state
-2 deg
OFF
ON
0 deg
+4 deg
SW 4-1
OFF
3
OFF
-
ON
Less than 2.5
Normal
High ceiling 1
High ceiling 2
Low ceiling
-ONON
3.0-3.5
More than 3.5
-
OFF-ON
OFF
2.5-3.0
OFF
Ceiling height(m)
DIP - SW4
1
2
DIP SWITCH SETTING
SW1-1. Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTO RESTART SETTING
(Factory setting)
SW1-2, 1-3. Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
TEMPERATURE CORRECTION
(Factory setting)
CASSETTE TYPE
AU45 - AU54
CASSETTE TYPE
AU45 - AU54
SW4-1. Dip SW 4-1setting forbidden
(Factory setting)
SW4-2, 4-3. Ceiling height setting
(Factory setting)
If the setting for a low ceiling is selected, the capacity of the air
conditioner decreases slightly.
- (05 - 35) -
Page 37
ROTARY SWITCH SETTING
0
Single
1 - 15
Indoor unit address
SW 2
SW state
SW state
JM 1, 2, 3
Connect
Disconnect
Forbidden
This switch can be used when group control system.
Set the indoor unit address in the 0,1,-,15 order.
(Factory setting)
JUMPER WIRE SETTING
JM 1, 2, 3 setting forbidden
(Factory setting)
CASSETTE TYPE
AU45 - AU54
CASSETTE TYPE
AU45 - AU54
- (05 - 36) -
Page 38
5-15-3. WIRED REMOTE CONTROLLER CIRCUIT BOARD
Wired remote controller
1
Dual remote controller setting
2
Group control setting
DIP SW
SWITCH POSITION
Wired remote controller
Front case (back side)
3
4
Model setting
Auto changeover setting
5
6
Memory backup setting
OFF
CASSETTE TYPE
AU45 - AU54
ON
1
2
3
4
CASSETTE TYPE
5
6
AU45 - AU54
ON
DIP Switch
- (05 - 37) -
Page 39
5-15-4. WIRED REMOTE CONTROLLER
DIP SWITCH SETTING
1. SW setting
1-1 Dual remote controller setting
Set the remote controller DIP switch No.1 and 2 according to the following table.
(Factory setting)
Number of
remote
controller
1 (Normal)
2 (Dual)
1-2 Group control setting
Number of indoor unit connection (One/Multiple)
This is switched according to the number of connected indoor units.
DIP-SW
No.3
OFF
Master unitSlave unit
DIP-SW
No.1
DIP-SW
No.2
ON
OFF
(Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW
No.1
ONON
DIP-SW
No.2
ONMultiple unit connection
CASSETTE TYPE
AU45 - AU54
1-3 Model setting
CASSETTE TYPE
AU45 - AU54
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
( )
( )
(
DIP-SW
No.4
OFF
ONCooling only model
Heat Pump model
Factory setting)
Model
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
(Factory setting)
DIP-SW
No.5
OFF
ONValidity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used,
all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
(Factory setting)
DIP-SW
No.6
OFF
ONValidity
Memory backup
Invalidity
- (05 - 38) -
Page 40
5-16. OPTIONAL PARTS
ADDITIONAL GRILLE
UTG-AGEA-W
The additional grille hides the gap between the ceiling hole
and the outlet grille.
Additional grille (optional parts)
Additonal grille
CASSETTE TYPE
AU45 - AU54
The ceiling hole
Indoor Unit(grille)
CASSETTE TYPE
AU45 - AU54
- (05 - 39) -